Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.9 LAccepted-Finance | L1 | Accepted-Finance OK | |
| 2 | L2₹42.9 L+₹5.1 L (13.4%)Accepted-Finance | L2 | Accepted-Finance OK | |
| 3 | L3₹43.1 L+₹5.2 L (13.8%)Accepted-Finance | L3 | Accepted-Finance OK | |
| 4 | L4₹44.2 L+₹6.3 L (16.7%)Accepted-Finance FLAT NO 101 2ND FLOOR RAGHAVENDRA RESIDENCY PLOT NO 1 2 3 SURVEY NO 27 PICKET SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | L4 | Accepted-Finance OK | |
| 5 | L5₹45.4 L+₹7.6 L (20.1%)Accepted-Finance | L5 | Accepted-Finance OK |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
26 Jul 2023, 6:00 pmClosed
GE (UTILITY) SECUNDERABAD
GE UTILITY SECUNDERABAD MUDFORT SECUNDERABAD-500003
REPAIRS/RENEWAL OF OH LINE, LT UG CABLE, LT POLE, RE-STRINGING OF OH LINE, CUTTING OF TREE BRANCHES AND ALLIED WORKS AT ZONE IIA AND ADJOINING AREA UNDER AGE E/M NO II OF GE (U) SECUNDERABAD
2023_MES_607037_1
GE (U)/SEC/TOKEN/26 OF 2023-2024
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
SECUNDERABAD
AS PER NIT
8 documents required · 8 mandatory
₹500
GE (UTILITY) SECUNDERABAD
₹96,000
Yes
11 Aug 2023
30 Jun 2023
2 Aug 2023
30 Jun 2023
26 Jul 2023
14 Jul 2023
Amount
M&L for attending, repair and rectification of external LT electric supply complaints on up to 1100 Volts grade, over head/underground system alongwith necessary T&P, safety devices as per site requirement for the following type of complaints complete all as specified and directed:-
Replacement of worn out jumpers, jointing and tightening with new ACSR conductor. Note:- Single phase/two wire or 3 phase/4 wire system will be considered as one job for payment purpose.
Disconnecting from over head conductor, cutting worn out portion of LT cables of any type and size, carry out repairs including taking out cables from under ground loop line and rejoining the same to restore electric supply. Note :- (i) LT Jointing Kits, Cable protection Pipe if required at site will be measured and paid separately. (ii) Quoted rate is deemed to be inclusive of cutting and removing the pole coping and inserting the cable alongwith protection pipes.
Notes for Item Nos 1.01 to 1.02 :- (a) The contractor will be allotted complaints at MES complaint cell on daily basis on all working days and sufficient resources will be deployed by him/her for completion of day to day complaint within 24 Hrs from the time of reporting. Any delay beyond above mentioned time limit without intimation of sufficient cause, penalties will be recovered twice of the quoted rate for each un-attended complaint. (b) A detailed log of complaints with completion/non-completion remarks from users/MES will be maintained by the contractor and the same will be updated on daily basis in consultation with Engr-in-Charge or JE E&M as detailed. (c) The contractor will make suitable arrangement for emergency complaints and will notify auth rep/Engr-in-Charge about extraordinary circumstances for probable non-completion or delay in rectification of complaints beyond stated time limit set for disposal of complaint. In case of any dispute the decision of accepting officer will be final and binding in this regard. (d) The contractor will intimate MES authority well in advance if electric shutdown is required during rectification of complaints. (e) The quoted rate is deemed to be inclusive of transportation and other expenses required for the resource deployment at the complaint site around scattered Military station at Secunderabad. (f) The contractor will maintain location wise record of each spare utilized as per inventory format given by AGE E/M, Secunderabd and the same shall be submitted to E/M No II store on daily basis.
M&L for ACSR conductor, steel reinforced for LT over head lines on poles including streching tightining of poles insulator with binding wire of suitable size with insulator/streching of ACSR conductor including disconnecting/taking out old existing unsv ACSR conductors complete all as specified and directed.
M&L for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade, including disconnecting/taking out old existing unsv insulators complete all as specified and directed.
M&L for Shackle type, Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts of size 100 mm height, 115 mm dia for 1100 Volt grade, section of straps 31x5 mm, including disconnecting/taking out old existing unsv insulators complete all as specified and directed.
S&F Stay assembly comprising of 7/10 SWG galvanised MS stranded stay wire of required length, minimum tensile strength 70 Kg/mm (grade-2 quality) fixed to pole with and including FI clamps, bolts, nuts, washers, galvanised steel stay rod 16mm dia 180 cm long bow 400 x 14 mm nuts/bolts, washers, loop type insulator of size 65 x 90 mm vitreous, clearance dia of hole 16mm, stay plate of size 230 x 230 x 6 mm including necessary excavation and earth work PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate in foundation and disposal of surplus soil, upto 50m including disconnecting/taking out old existing unsv stay assembly complete all as specified and directed.
S&F of Galvanised steel wire (GI) 4mm dia including disconnecting/taking out old existing unsv GI wire complete all as specified and directed.
M/L for cross arms, bracing, supports clamps and back plates fabricated from structural steel section incl nuts, bolts washers, welding, bending cold or hot drilling holes for bolts in any shapes or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including disconnecting/taking out old existing unsv cross arms complete all as specified and directed.
Supply & Replace MCCB along with both side spreader link and nut bolts of appropriate size (Conforms to IEC:60947-II/IS:13947-II) in exisitng LT Panel box/Feeder Pillar boxes (KIOSK),in MCCB DBs of capacity 315-400 Amps, 4 Pole, 35 KA, 415 Volt including disconnecting/taking out existing old unsv/burned MCCB complete all as specified and directed.
All as per item No-8 here in before but of capacity 250 Amps, 4 pole, 25 KA
All as per item No-8 here in before but of capacity 200 Amps, 4 pole, 25 KA
All as per item No-8 here in before but of capacity 160 Amps, 4 pole, 16KA
All as per item No-8 here in before but of capacity 125 Amps, 4 pole, 16 KA
All as per item No-8 here in before but of capacity 100 Amps, 4 pole, 16 KA
All as per item No-8 here in before but of capacity 63 Amps, 4 pole, 16 KA
S&F MCCB, 63 Amps, 3 pole, 415 Volts with breaking capacity 16KA, including disconnecting/taking out existing old unsv/burned MCB complete all as specified and directed.
All as per item No-9 here in before but of capacity 100 Amps, 3 pole, 415 Volts with breaking capacity 16KA
All as per item No-9 here in befor but of capacity 160 Amps, 3 pole, 415 Volts with breaking capacity 16KA
S&F MCB, SP 10-32 Amps, 'C' Curve with breaking capacity 6KA, including disconnecting/taking out existing old unsv/burned Isolator complete all as specified and directed.
Supply, lay, commissioning and testing of cable jointing Kit Heat shrinkable type for 1100 V grade cable for straight through joint with jointing material and accessories suitable for LTUG cable of size 16 to 50 Sqmm, 3.5 Core complete all as specified and directed.
All as per item No 13 above but suitable for aluminium conductor cable of size from 70 sqmm, 3.5 Core to 95 Sqmm, 3.5 Core
All as per item No 13 above but suitable for aluminium conductor cable of size from 120 sqmm, 3.5 Core to 185 Sqmm, 3.5 Core
All as per item No 13 above but suitable for aluminium conductor cable of size from 240 sqmm, 3.5 Core to 240 Sqmm, 3.5 Core
Supply and lay in trenches/fixed to walls/poles etc connecting buy using lugs, testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor 4 Core 10 Sqmm complete all, as specified and directed Note :- Earth work excavation, sand cushioning and brick protection shall be measured and paid separately.
All as per item no:17 above but 4 Core 16 Sqmm
All as per item no:17 above but 4.0 Core 25 Sqmm
All as per item no:17 above but 3.5 Core 35 Sqmm
All as per item no:17 above but 3.5 Core 50 Sqmm
All as per item no:17 above but 3.5 Core 70 Sqmm
All as per item no:17 above but 3.5 Core 95 Sqmm
All as per item no:17 above but 3.5 Core 120 Sqmm
All as per item no:17 above but 3.5 Core 150 Sqmm
All as per item no:17 above but 3.5 Core 185 Sqmm
All as per item no:17 above but 3.5 Core 240 Sqmm
Taking out and Relaying of LT cable of size 10sq mm to 50 Sqmm 2/3.5 core after carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugs all as specified and directed by ingr in charge. Note: ( Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item)
Taking out and Relaying of LT cable of size 70 sq mm to 150 Sqmm 3.5 core after carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugs all as specified and directed by ingr in charge. Note: ( Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item)
Taking out and Relaying of LT cable of size 185 sq mm to 300 Sqmm 3.5 core after carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugs all as specified and directed by ingr in charge. Note: ( Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item)
Supplying, erecting and fixing steel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 mtrs long) including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide including taking down old unserviceable PCC poles of any type complete all as specified and directed. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
Restreching/Restringing, tightening and repair to overhead line ACSR conductor of any size on LT poles including necessary Aluminium binding wire connectors PVC sleeves for jumper, fixing of insulators and prunning of tree complete all as specified and directed. Notes: (i) The distance between pole to pole in one span (contains 2/4/6 runs) i.e one span will only be considered for payment purpose. (ii) No Extra conductor will be measured for binding to insulators / jumpering etc.
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in Hard / Dense soil complete all as specified and directed.
All as per item No 23.00 above but depth exc 1.5 mtr but not exc 3 mtr.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
Spreading riddled earth ( after preparation of excavated earth) in Cable duct with sand cushioning of cable laid in trenches complete all as directed by Engineer-in-Charge Note:- Punned thickness 18 CM( 6.25 Cm below cale and 11.75 cm above cable) will be measured for payment purpose. Quoted rate inclusive of all arrangement as mentioned.
Supply and Lay reinforced precast concrete cable cover LV, Type I,flat, size 250x150x40 mm complete all as specified and directed.
Supply and Laying bricks, common burnt clay building bricks, sub class 'B' of size 230 x 115 x 75 mm laid across in trenches for cable protection complete all as specified and directed.
M&L PCC 1:4:8 type D2 using 40 mm graded stone aggregate for filling & foundation of pole & mass complete all as directed
M&L PCC 1:3:6 type C2 using 40 mm graded stone aggregate for filling & foundation of pole & stay complete all as directed
M&L PCC 1:2:4 type B1 using 20 mm graded stone aggregate for coping of pole complete all as directed
Cutting the existing road/PCC surface straight by manual, depth and width not less than 1 mtr below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 (using 20 mm graded aggregate stone complete all as specified and directed.
M&L for road crossing/drain crossing by adopting trench less tunneling work through specified pipe jacking method by erecting the equipment to true to the allignment and gradient by haidrolic pipe jacking technique complete including tunneling, excavation in any type of soils including hard rock, HDPE pipe medium duty duty of size 100 mm dia in any length including jointing materials to carry LT UG cables of size upto 240 Sqmm and necessary conveyance charges of machinery and other required materials in co-ordination with the concerned authorites complete all as specified and as directed.
M&L for replacement of broken earth pit made out of PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, 20 mm thick and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia MS deformed bars @ 100 mm centre to centre both ways with hook made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers etc as required at site complete all as specified and directed.
M&L repair/maintenance of stay by tightening of stay wire after untying the conductor spans from the poles to make correct tensions and maintain verticality of poles, including re-jointing the conductors in position with new binding wire complete all as specified and directed.
M&L for painting the existing LT steel poles of 9.0 Mtr long including cross arms, clamps, street light junction boxes etc with 1 coats of aluminium paint including throughly cleaning the existing surface, writing of pole numbers in yellow circle 15 cm with black paint on poles. Painting the poles up to 1.5 Mtr height with alternate bands 30 cm height (3 Nos black and 2 Nos Yellow) from ground level, complete all as specified and directed.
M&L for Painting the existing LT PCC poles with 1 coats of synthetic enamole base paint including painting of cross arms, clamps, etc with one coat of aluminium paint and providing alternative band of 30 cm width (3 black and 2 yellow) from bottom of pole to 1.5 metres height , writing of pole numbers in yellow circle15 cm with black paint on poles complete all as specified and directed.
Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia( THICKNESS NOT LESS THAN -2.5MM) and two meter length, The electrode should be of galvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m . The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg BackFill compound to provide maximum contact between the electrode and Back Fill Compound. .The earting pit should be cover with pcc(1:2:4 , B1) cover ,of 450 x 450 mm complete all as specified and directed
Trimming/pruning and removing of tree branches or any other foreign objects from HT/LT over head conductor and clearing the OH Line of any type and size for one span of any length in 2 way /4 way/6 way conductor system. Notes: (i) Insulators of any type, connectors and ACSR conductor of any size required at site will be measured and paid separately under relevant item of this schedule. (ii) The contractor is responsible for provision of Necessary T & P and safety equipments to complete the job.
Cutting unaxious green growth and grass by manual labour or by machine at all 11 KV Electric Installation premisses/around 2/4 Pole structure/along the boundary fencing and removing rubbish from the site of work complete all as specified and directed.
Supply and fixing steel light bracket made out of 40 mm bore mild steel GI light grade tubing over all length 1.5 mtr bend to shape as directed including providing two Nos MS flat iron 40x6 mm clamp of appropriate size with nut bolts and washer duly painted with two coat of synthetic enamel paint over a coat of primer (GI surface shall not be painted) complete all as specified.
S&F PVC insulated unsheathed/sheathed cable with stranded Aluminium conductor 1100 Volts grade, flat twin core service cable of size 4 Sqmm conforming to IS:694/1990 with latest amendments ISI including disconnecting/taking out existing unsv/damaged old service cable complete all as specified and directed.
All as per item No-43 above but of size 6 Sqmm complete all as specified and directed.
All as per item No-43 above but of size 10 Sqmm complete all as specified and directed.
S&F hot press moulded SMC junction/terminal box of size with internal diamensions of 200 x 140 x 95 mm with hinged door, incl provision of 2 way connector 415 Volts made out of polycarbonate or bakelite and 1 No MCB of 6 Amps with DIN bar, drilling holes for cable connections, connecting incoming and or out going cables by providing suitable of size of cable lugs/glands, fixed on pole by means of clamps made out of MS flat iron of size 25mm x 3 mm 2 Set including dismantling of old unserviceable all as specified and as directed.
Supply and laying GI tubing light grade of size 40 mm for cable protection on road/drain/floor/pole including necessary clamps 40x4mm.
Supply and laying GI tubing light grade of size 50 mm for cable protection on road/drain/floor/pole including necessary clamps 40x4mm.
Supply and laying GI tubing light grade of size 80 mm for cable protection on road/drain/floor/pole including necessary clamps 40x4mm.
S&F LT line rigid PVC Spacers spiral type, two lines, Phase to phase distance 300 mm, spacer rod dia 13 mm, spiral hole dia 5-6 mm and spiral length 250 mm.
S&F LT line rigid PVC Spacers spiral type, three lines, Phase to phase distance 600 mm, spacer rod dia 13 mm, spiral hole dia 5-6 mm and spiral length 250 mm.
S&F LT line rigid PVC Spacers spiral type, four lines, Phase to phase distance 900 mm, spacer rod dia 13 mm, spiral hole dia 5-6 mm and spiral length 250 mm.
S&F On-Load changeover switch , 4 pole of capacity 400 Amps, 415 Volts, 50 Hz, complete all as specified and directed.
S&F On-Load changeover switch , 4 pole of capacity 200 Amps, 415 Volts, 50 Hz, complete all as specified and directed.
S&F On-Load changeover switch , 4 pole of capacity 100 Amps, 415 Volts, 50 Hz, complete all as specified and directed.
Supply only of aluminium cable lugs of following sizes :-
16 to 25 Sqmm Size
35 to 50 Sqmm Size
70 to 95 Sqmm Size
120 to 150 Sqmm Size
185 to 240 Sqmm Size.
S&F MCCB factory made enclosure box with neutral link for TPN System made of sheet metal Powder coated Suitable for fixing at Pole including two set of clamps comprising with the following i) MCCB 63 Amps 16 KA TP .
S&F MCCB factory made enclosure box with neutral link for TPN System made of sheet metal Powder coated Suitable for fixing at Pole including two set of clamps comprising with the following i) MCCB 100 Amps 16 KA TP .
Dismentling of damage / broken coping of PCC/steel pole of any size and and removing the debries from site complete all as specified and directed
Supply and fix on wall with necessary arrangements busbar chamber 100 amps 4 way 4 pole wall mounted IP -31 , made out of 1.6 mm thick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Second including necessary cable connections complete all as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber.
Supply and fix on wall with necessary arrangements busbar chamber 200 amps 4 way 4 pole wall mounted IP -31 , made out of 1.6 mm thick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Second including necessary cable connections complete all as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber.
Material and Labour for drawing two runs of PVC insulated unsheathed single core multi stranded copper conductor FRLS cable of size 1.50 sq mm with one run of PVC insulated unsheathed single core multi stranded copper conductor FRLS cable of size 1.50 sq mm including 20mm dia PVC conduit of dia 20 mm medium gradeexclusive of boxes but inclusive of all tees, bends, elbow, reducers etc and fixing accessories such as couples, lock nuts, saddles, pipe hooks, clamps etc complete all as specified
M&L for repairing of automatic operation of highmast lantren including all arrangements required including crane and replacement of all unserviceable spares of highmast lighting system of height 12 m to 16 meter . Quoted rates deemed to be inclusive of the following:- (i) crane as required for taking down of high mast pole including light without any damage to the mast, lantern and lights etc and refixing the same after repairing of the all problem on the same position (ii) Necessary disconnection and reconnection of electrical connection. (iii) Replacement of all unserviceable spare like High mast head, high mast ring , stainless steel wire, clamp, winch, transition plate, service door , Hook ring, nose plate, cabinet, gear, reel, transmission belt etc including servicing of gear box , filling of gear oil, greasing etc complete (quoted rates deemed to be inclusive of all spares required for proper functioning of lantern system except stainless steel wire, High mast head, high mast ring etc.
Supply only steel wire rope 6mm dia (7/19 construction) suitable for highmast system including u bolt complete all as directed
Taking down, transport to workshop , Re-winding of electric motor 3 phase installed at highmast pole of capacity upto 2.2/3 HP and refixing of the same including necessary arrangement complete all as directed
Repair/maintenance, excluding major spares but including regualr maintenance of the Automatic Power factor correction panel capacity up to 100 KVARs and up 8 stages installed at various locations at CDM area including carrying out complete maintenance/repairs as required of all the sub systems viz. based control panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT, MCBs/MCCBs for isolation (with all the accessoires) any breakdown maintenance and replacement of unserviceable parts, refixing of old serviceable parts/new parts if any project completion and trouble shooting responsibility also lies with contractor including following provisions complete all as specified and directed. Notes:- (i) Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, repavement of defective control wiring, small part such as Push button, lugs any auxilary contatct,auto selctor switch etc and necessary servicing repair by expert technician and register will be maintaned for the same. (ii) The scope of work includes the labour charges required for removing, repairing, refixing, carrying out electrical termination, capacitors bank, APFC relay, power contactor, contol CT, MCBs/MCCB and fixing/installing/testing and commissioning the complete system. (iii) capacitors bank, APFC relay, power contactor, control CT, MCBs/MCCB shall be measured and paid separately
Supply only power factor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old unserviceable capacitor complete all as specified and directed.
All as per item No 67 above but 10 KVAR Capacitor Bank
All as per item No 67 here-in-before but 20 KVAR Capacitor Bank
S&F APFC relay etaCON M series with auto-set functiont 7/8 stage APFC relay
Supply and fix Power contactor coil of Power contactor of having capacity 360/400 Amps 4 pole 2NO +2NC complete all as specified and directed. Make:- L&T Cat part No. CS94195 or equivalent as approved by GE
Supply and fix Power contactor of having capacity 400 Amps 4 pole 2NO +2NC complete all as specified and directed. Make:- L&T Cat part No. CS97025 or equivalent as approved by GE
Supply and fix Power contactor of having capacity 360 Amps 4 pole 2NO +2NC complete all as specified and directed. Make:- L&T Cat part No. CS97024 or equivalent as approved by GE
Disconnecting electrical connection and overhauling the mechanical parts incl Greasing Oiling and re-assembling the same as required and ,made the Crane serviceable including making all electrical Connection and Testing complete all spd and directed for following capacity Note : All Spares parts of Crane measured and paid separately under relevent Item.
Capacity 05 ton
Capacity 10 ton
Supply , fixing, testing and commissioning of three phase AC drive VFD 7.5 HP of IP20 with Inbuilt PLC & EMC filter braking chopper,air temperature -10 to 50 degree C of having Output Frequency 0.1 to 600 HZ incl taking down old Unsv one complete all as specified and directed. Make : Model No: VFD 055E43A or equivalent as approved by GE
Supply and fixing of 3P power contractor rating 26-40 Amps incl taking down unserviceable one complete all as specified and directed
Supply only Over load relay Magnetic type of range 26 - 40 Amps Make :- L & T / BCH / Seiemens or equivalent as approved by GE
Testing (full load test , deflection test , capacity test , speed test , and break test) and serviceablility checking of each cranes by authorised Engineer in presence of Engr-in-charge ,JE (E/M) and user representative and generating & submission of the test certificate with list of defects if any to be produced in duplicate. The capacities of cranes to be tested are as under :-
Electrically operated over head travelling (EOT) cranes of capacity from 05 ton to 10 ton - 02 Nos.
Supply only crane gear oil for filling/topping up of Type EP-320 thick level complete all as directed. Make :- Mobil / HP / Castrol
M&L for preparation of old painted surfaces for outdoor/indoor Amf panel/LT Panel of any size with applying two coat of synthetic enamelled grey paint after removing all dust & rust and paint shall confirm to IS 2032 complete all as specified .
S&F cable route indicator for LT UG cable of 1100 volts bolted with 25x5 mm flate iron member of height 0.60 mtrs and 80 mm CI plate embeded in PCC 1:3:6 type C2 of size 15x15x20 cm block complete all as specified
Supply, Install, testing and commissioning of APFC Power Panel of 50 KVAR 6 stage, outdoor type, factory made, , cubical feeder pillar box panel board IP 54 free standing suitable for working on 440 volts, 3 phase 50 Hz A C supply, floor mounted made out of 3.15mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots incl taking down old unsv one complete of suitable size comprising of following items:-
(a) MCCB, 3 pole, 125 Amp with ultimate breaking capacty Icu-25 kA at 415 Volts and microprocessor release conforming to IEC 60947 Part?I/IS-13947-Part-I with breaking capacity Ics=Icu at 415 Volts of 25 KA, overload setting 70% to 100%, short circuit setting 5 to 10 times - 01 No ( As Incomer) (b) Metallised polypropylene MPP-H capacitor bank heavy duty of rating 50 KVAR ( 4 No x 10 KVAR + 2 No x 5 KVAR) confirming to IS-2834, IS-13340, 3341 & IEC 931. (c) Capacitor duty contactors of appropriate rating for capacitor switching confirming to IEC-947-4-1 and IS 13947.
Supply, Installation, test and Commissioning factory fabricated, out door type,LT FEEDER PILLAR BOX made out of 3.15 mm thick CRCA Sheet of size 1MX.75mX.35M with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeded with 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level comp -lete with internal connection with suitable size of cable ,cable lugs,and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Test-ing after Installation complete all as specified and comprising of the following :–
(a) Aluminium bas bar 200amps - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 100 amps ,415 volt ,16 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar As IN COMING - 01 Nos Make Legrand model no: 420015 or equivalent from Schinder/L&T/Hagar as approved by GE.
Supply and fixing lantren of dia 60 CM for fixing of flood light, cap type to be fixed on the top of 9 m SP-31 Steel pole , made of MS pip medium grade dia greater than the top dia of the pole of length 0.35 M supported by MS flat iron of size 50X6 mm 8 nos including two coat of aliminium painting over a coat of redoxide primer complete all as directed
Dismantling LT steel tubuler pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed by Engineer-in-Charge.
sree venkateswara enterprises
SUN LIGHT HOUSE
L and S ENTERPRISES
Sri venkateswara Electricals
srisaienterprises
DPS sales and services india
vvcenterprises
Srinivasa Consructions
Universal refrigeration and Engineering Company
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .