| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹1.0 CrAccepted-AOC PLOT NO D 25 INDUSTRIAL GROWTH CENTRE MANSA ROAD BATHINDA PB 151001 | BATHINDA | BATHINDA | PUNJAB | 151001 | ₹1.0 Cr | L-1 | Accepted-AOC Being lowest and reasonable. |
| 2 | L-2₹1.2 Cr+₹16.1 L (16.0%)Rejected-Finance HOUSE NO 8 589 BEHIND PHC HOSPITAL OLD BUS STAND KORBA KORBA CHHATTISGARH 495678 | 495678 | ₹1.2 Cr+₹16.1 L (16.0%) | L-2 | Rejected-Finance Not being lowest bidder. |
| 3 | L-3₹1.3 Cr+₹27.3 L (27.1%)Rejected-Finance | ₹1.3 Cr+₹27.3 L (27.1%) | L-3 | Rejected-Finance Not being lowest bidder. |
Tender Value
₹1.0 Cr
EMD Value
₹1.8 L
Closing Date
22 Jun 2024, 6:00 pmClosed
CWE Bathinda
HQ CWE Bathinda Bathinda Mil Stn
PROVN OF ACCN AT BATHINDA MIL.STN. JOB NO.81/BTD/AMWP-01/2022-2023
2024_MES_652929_1
CWE BTD/TOKEN-72/2023-24
Open Tender
Civil Works
Lump-sum
360 days
Bathinda Mil Stn
As per NIT
7 documents required · 7 mandatory
₹1,000
GE (P) Bathinda
₹1.8 L
HQ CWE Bathinda
18 Sept 2024
8 May 2024
24 Jun 2024
8 May 2024
22 Jun 2024
7 Jun 2024
15 May 2024
Amount
Note:-Please refer schedule 'A' notes before quoting the tender.
GENERAL SUMMARY
Lump sum price worked out by the contractor for BUILDING WORKS as listed in Schedule ‘A’ Part- I (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for INTERNAL WATER SUPPLY WORKS as listed in Schedule ‘A’ Part- II (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for INTERNAL ELECTRIFICATION WORKS as listed in Schedule ‘A’ Part- III (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY WORKS as listed in Schedule ‘A’ Part- IV (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for EXTERNAL ELETRIC SUPPLY WORKS as listed in Schedule ‘A’ Part- V (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for ROAD ,PATH , HARDSTANDING AND CULVERT WORKS as listed in Schedule ‘A’ Part- VI (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for STEEL GATE & COMPOUND WALL WORKS as listed in Schedule ‘A’ Part- VII (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for SEWAGE DISPOSAL WORKS as listed in Schedule ‘A’ Part- VIII (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for AREA DRAINAGE WORKS as listed in Schedule ‘A’ Part-IX(Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for HOT WATER APPLIANCES WORKS as listed in Schedule ‘A’ Part-X (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for SUMMER APPLIANCES WORKS as listed in Schedule ‘A’ Part-XI (Ref prepriced schedule attached seperately)
Lump sum price worked out by the contractor for EXCAVATION, EARTH WORK AND SITE DEVELOPMENT WORKS as listed in Schedule ‘A’ Part-XII (Ref prepriced schedule attached seperately)
SCH 'A' Pt - XIII (MISCELLANEOUS ITEMS) (Contains Ser item No 3.01 to Ser item No 11.04)
INTERNAL WATER SUPPLY NOTE:- For items of internal water supply notes given at the beginning of Sch ‘A’ Part-II (Internal Water Supply) shall also be applicable.
Supply and Fixing 15mm bore angle valve / cock fancy type, cast copper alloy chromium plated screwed down high pressure, screwed both ends for iron pipe or unions and fixed, complete all as specified & as directed.
Supply & Fixing 2 way Bib tap 15mm bore , fancy type cast copper alloy chromium plated with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified and directed.
INTERNAL ELETRIFICATION NOTE:- For items of internal Electrifications notes given at the beginning of Sch ‘A’ Part-III (internal Electrification) shall also be applicable.
Material and Labour concealed Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with 1.5 Sqmm nominal cross sectional area PVC insulated unsheathed multi-stranded FRLSH copper conductor 1100 volts grade, drawn in and including medium grade, rigid PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked with valid CML No.(IS-9537-1983 for conduits and IS:3419:1976 for conduit accessories), and including modular metal flush boxes concealed with modular natural / white finish front plate with base plate for the mounting of modular switches, sockets and fan regulators etc. etc including 1.5 Sqmm nominal cross sectional area PVC insulated unsheathed multi-stranded FRLSH copper conductor cable as earth continuity conductor to common earth dolly complete all as specified and directed for the following:- NOTE:- The quoted unit rate is deemed to be inclusive of cost of metal flush boxes, modular white cover plates, modular frame plates, etc.However modular switches,modular sockets and regulators shall be measured and paid seperately under respective items of Schedule'A' BoQ.
One light point /Fan Point / Bell Point controlled by one 6 amps one way modular switch.
One light point controlled by two 6 amps two way modular switch.
One modular Socket outlet, 6 Amp, 2/3 Pin controlled by one 6 amps one way modular switch or modular switch/ socket combination 6 Amps, 2/ 3 Pin on the same board.
One modular Socket outlet, 6 Amp, 2/3 Pin controlled by one 6 amps one way modular switch or modular switch/ socket combination 6 Amps, 2/ 3 Pin on independent board and not below the any other switch board.
Material and Labour Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with 2.5 sq mm nominal cross sectional area PVC insulated unsheathed multi-stranded FRLSH copper conductor 1100 volts grade, drawn in and including 20mm dia medium grade, rigid PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked with valid CML No.(IS-9537-1983 for conduits and IS:3419:1976 for conduit accessories), and including modular metal flush boxes concealed with modular natural / white finish front plate with base plate for the mounting of modular switches, and modular sockets etc. etc including 2.5 Sq mm nominal cross sectional area PVC insulated unsheathed multi-stranded FRLSH copper conductor cable as earth continuity conductor to common earth dolly NOTE:- The quoted unit rate is deemed to be inclusive of cost of metal flush boxes, modular white cover plates, modular frame plates, etc.However modular switches and modular sockets shall be measured and paid seperately under respective items of Schedule'A' BoQ.
Material and Labour for Sub main wiring concealed PVC conduit with two single core of size 10 Sqmm FRLS PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade drawn in and including non metallic rigid PVC conduit medium quality of size 25 mm dia conforming to 3537 Part-I ISI marked including one single core of size 10 Sqmm FRLS PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade as in contineous earth conductor cable connected to earth dolly complete all as directed. (Colour code phase-Red, Nuetral-black and Earth as Green) complete all as specified & directed.Notes:-(a) Cost of PVC conduit , conduit accessories i.e. PVC Clamp, rawl plug, screws, PVC junction box, Tee, bend etc. and earth wire included in sub main wiring and nothing shall be paid extra on this account. (b) Three single core 10 Sqmm cable including non metallic rigid PVC conduit of size 25 mm dia shall be measured as one length.
Supply and Fixing MCB SPN 16 amps 10 KA , 240, 'B' Curve including connection with suitable size copper lugs complete all as specified and directed
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 250 Amp rated bus bar) VTPN, 4 Way 415V, suitable for mounting MCCB/MCB, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge.
Supply and fixing energy efficient LED security light fitting of 25W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street luminaire, with driver, including electric connection with using 3 core flexible copper conductor cable 1.5Sqmm from ceiling rose to light fitting, fixing the light fitting with new bracket made out of GI tubing light grade 25mm dia, 1.2 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron size 25x3 mm with suitable nuts and bolts for fixing of bracket including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP66. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : Minimum 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing LED lamp minimum 3 star rated 12 W LED B-22 base complete all as specified and directed by Engr-in-Charge with following specifications (a) Lumen system efficacy of lamp should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 45°C
Supply and fixing LED tube light fitting polycarbonate housing 1 x 20 Watt, appx 4 feet long, with decorative box linear, housing environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts. (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) LED Driver of the same make as of the luminaire. (h) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (j) Surge protection minimum 2.5 kV. (k) CCT : Minimum 6000K (l) CRI : Minimum 80 (m) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing LED light fitting 1 x 10 Watt, appx 2 feet long with decorative ultra ceiling square profile linear LED lighting fixture with extruded polycarbonate environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to light fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) CRCA pre coated housing with plastic end cap. (h) LED Driver of the same make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection minimum 2.5 kV. (l) CCT : Minimum 6000K (m) CRI : Minimum 80 (n) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing LED Luminaire 600 mm x 600 mm, 35/36 watt, 220V AC surface type with high efficiency PMMA diffuser soft free light complete with driver, holders LED Lamp suitable for roof ceiling including connecting up with dirver three core flexible copper conductor with complete point wiring of size 1.5 sqmm and switch board including earth wire 1.5 Sqmm copper conductor complete all as specified and directed by Engineer-in-Charge.
EXTERNAL WATER SUPPLY NOTE:- For items of EXTERNAL WATER SUPPLY notes given at the beginning of Sch ‘A’ Part-IV ( EXTERNAL WATER SUPPLY ) shall also be applicable.
Material and Labour for for drilling / cutting of existing CI/ DI/ GI pipe line up to 150 mm bore for taking branch connection, inserting with and including one No. tapping saddles, PN16, of size 150mm x 40mm ductile iron with fusion bonded expoxy coating in compliance with DIN 3476 Part 1 and EN 14901. Main gasket of drinking water approved EPDM rubber, including necessary jointing materials, i.e nuts bolts, washers etc. complete all as specified and directed.
Material and Labour Construction of brick masonary valve pit chamber of internal size 750mm x 750mm x 750mm , PCC 1:4:8 type D2 using ( 40mm graded stone aggregate ) lean concrete in foundation , providing old size well burnt clay brick masonary wall of 230mm thick built in Cement Mortar 1:4 , Rendering 15mm thick in cement mortar 1:4 finished even and fair internally , supply and fix 3.15 mm thick MS sheet steel cover fixed on 50mm x 50mm x 6mm thick angle iron frame , embeded in PCC coping with PCC 1:2:4 type-B1 using 20mm graded stone aggregates , with locking arrangement and 1 No. 50mm size 4 levers lock with key in duplicate Standard size and MS hold fast and handle made out of 25mm x 6mm flat iron and applying two coats of synthetic enamel paint of approved shade over a coat of primer (Red Oxide zinc chromate primer ) to all exposed surface including earth work i.e. excavation, returing filling and removal of soil complete all as specified and as directed and all as shown on drawings No.BTD-811 sheet 1/2 to 2/2 Note:- The rate of earth work i.e. excavation, returing filling and removal of soil is included in this item and nothing shall be paid extra on this account.
EXTERNAL ELETRIC SUPPLY NOTE:- For items of EXTERNAL ELECTRIC SUPPLY notes given at the beginning of Sch ‘A’ Part-V ( EXTERNAL ELETRIC SUPPLY ) shall also be applicable.
Supply, installation, commissioning and testing of LT Feeder Pillar Type Panel of suitable size suitable to accomdate mentioned accessories , factory made (CPRI approved) outdoor cubical type , double door both side openable with hinged doors & locking arrangement made out of not less than 3.15 mm thick mild steel CRCA sheet supported and fixed on structural frame of angle iron of size 50mm x 50mm x 6mm angle iron frame with and including legs, legs shall be made of angle iron of size 50mm x 50mm x 6mm,750mm long,300mm shall be grouted in block of PCC 1:2:4 Type B-1 using 20mm graded stone aggregates with 450mm ground clearance , angle iron frame and legs shall be painted with of two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer including earthing stud labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 stage process)( colour as approved by GE), duly fixed in ground with PCC foundation (1:2:4) type B1 with danger notice plate of 1.6mm thick mild steel sheet, vitrious enamelled (white) with letters figures and conventional skull and bones in signal red colour complete all as specified and directed. comprising of the following accessories :-
Contd/- serial item No.6.01 Incoming:- (a)Copper bus bar 100 Amps rated capacity suitable for 4 wire 415 volt,50Hz AC system with insulated sleaves and making connections with single core copper multistranded conductor PVC insulated of size 10.00Sq mm wires in color code (b) MCCB 63 Amp, 4 Pole, 25 KA (Icu=100%Ics) with adjustable thermal release 0.8 to 1.0 and fixed magnetic type-01 No.(Incomer) (c) MCCB 40 Amp, 4 Pole, 16 KA (Icu=100%Ics) with adjustable thermal release 0.8 to 1.0 and fixed magnetic type-01 No.(Admn Block) (d) MCB DP,6 Amp to 20 Amp,240 Volt ,'C' curve ,,10KA-03 Nos.(Out goint: Garrage, street light and Gate light) (e) Digital voltmetre -01 No. (f) Digital Ammetre with CT -01 Set (g) Neon indicator lamp with holder (Yellow, Blue,Red)- 01 set (Set of three) Note: MCCB spreader terminals shall be used for cable connections in the LT panel.
Supply & Fixing Energy Efficient LED Street Light fittings 45 Watt , 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protectioncapacity of lumen system efficacy of luminarie should be minimum 100 lumen per watt complete all as per manufacturer's instructions and complete all as specified and directed by Engineer-in-charge.Note :- 1.The cable for connection shall be measured and paid seperately under respective item of Schedule 'A' BoQ.
Supply & Fixing Decorative LED Post Top Lantern Luminior with IP-65 protection die cast aluminium spigot, spun aluminium powder coated, top cover clear/opal acralic, difusser LED Light fitting of 15 watt including LED lamp complete all as per manufacturer's instructions and complete all as specified and as directed . Note :- 1.The cable for connection shall be measured and paid seperately under respective item of Schedule 'A' BoQ.
Supply & Fixing Three core cord flexible wire, copper conductor multistranded,PVC insulated and overall PVC sheathed of size 1.5 Sqmm 1100 volt complete all as specified and as directed
Supply & Fixing Thermoplastic (Polystreen) Junction Box having IP 66 protection of size 130mm x 180mm x 77 mm in size, fixed to pole / wall with MS clamps of size 25mm x 3mm , nuts, bolts, washers etc. , terminal of same company having provision of 3 phase aluminium bus bar with and including one no. MCB 6 Amp SPN 'C' Curve , clamps of size 25mm x 3mm complete all as specified and as directed.Note: The rate of one no. MCB 6 Amp SPN 'C' Curve and clamps of size 25mm x 3mm is included in this item and nothing shall be paid extra on this account.
Material and Labour for Making the hole under road / pavement / hardstanding for laying of GI tube light grade 50mm bore as required at site by mechanical drill system or Auger system and making the surface good as per existing surface complete all as specified and directed. Note : The GI tube light grade 50mm bore shall be measured and paid as material and labour seperately under respective item of Schedule 'A' Part-V EXTERNAL ELECTRIC SUPPLY WORKS
Material and Labour sand cushioning, with dry and clean sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified. (Note:- Punned thickness shall be considered for payment purpose)
Supply and fixing Single Swan Neck steel tubular swaged pole type 410 SP-31 (09 meter long) complete with cast iron base plate, finial, taper plug, bolts nuts & screws complete all as specified including internal surface of steel tubular pole through out and external surface up to planting depth shall be painted with bituminous paint and remaining external surface shall be treated with two coats of aluminium paint over a coat of red oxide zinc chromate primer complete and painting upto 1.5 mtr with alternate layer of yellow & black including marking Sr No of the poles all as specified. Note:- Necessary earthwork and cement concrete work shall be measured and paid seperately in respective items of respective schedules. (Note:- Excavation, earthwork and PCC shall be measured and paid separately under respective item of Sch.)
ROAD ,PATH , HARDSTANDING AND CULVERT WORKS NOTE:- For items of ROAD ,PATH , HARDSTANDING AND CULVERT WORKS notes given at the beginning of Sch ‘A’ Part-VI ( ROAD ,PATH , HARDSTANDING AND CULVERT WORKS ) shall also be applicable.
Material and Labour 100mm thick Cement Concrete (1:2:4) Type- B-1 , using 20mm graded stone aggregate as in edging for stoping the end of interlocking tiles complete all as specified & directed.
STEEL GATE & COMOUND WALL WORKS NOTE:- For items of STEEL GATE & COMOUND WALL WORKS notes given at the beginning of Sch ‘A’ Part-VII ( STEEL GATE & COMOUND WALL WORKS ) shall also be applicable.
Material and Labour for Steel Gate 5.5 mtr wide and 2.7mtr height complete all as shown on drawing No. BTD-79 complete all as specified and directed.
SEWAGE DISPOSAL WORKS NOTE:- For items of SEWAGE DISPOSAL WORKS notes given at the beginning of Sch ‘A’ Part-VIII ( SEWAGE DISPOSAL WORKS ) shall also be applicable.
Supply and laying DWCPE (SN-8) drain pipes 150 mm nominal dia as per IS-16098 (Part-II), laid in trenches on and including bed 100 mm thick bedding comprising of well compacted clean poorly graded grave, gravel/sand mixture with little or no fines to required slope, and as directed by Engineer-in-Charge. Note: Excavation, earth work and pedestal/ anchorage if required shall be measured and paid separately under appropriate items of BOQ/ Sch ‘A’.
HOT WATER APPLIANCES NOTE:- For items of HOT WATER APPLIANCES notes given at the beginning of Sch ‘A’ Part-X ( HOT WATER APPLIANCES ) shall also be applicable.
Material and Labour for Sub main wiring concealed PVC conduit with two single core of size 2.5 Sqmm FRLS PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade drawn in and including non metallic rigid PVC conduit medium quality of size 20 mm dia conforming to 3537 Part-I ISI marked including one single core of size 2.5 Sqmm FRLS PVC insulated unsheathed with multistranded copper conductor cable 1100 volts grade as in contineous earth conductor cable connected to earth dolly complete all as directed. (Colour code phase-Red, Nuetral-black and Earth as Green) complete all as specified & directed.Notes:-(a) Cost of PVC conduit , conduit accessories i.e. PVC Clamp, rawl plug, screws, PVC junction box, Tee, bend etc. and earth wire included in sub main wiring and nothing shall be paid extra on this account. (b) Three single core 2.5 Sqmm cable including non metallic rigid PVC conduit of size 20 mm dia shall be measured as one length.
Supply and Fixing SITC of electric water heater (Geyser) storage type ABS body of capacity 25 litre, BEE approved 5 star rating, 230V, single phase, AC supply, inner tank made out of heavy duty stainless steel sheet (Designed with single weld line, factory tested with hydraulic pressure as per latest IS code), with glass lined coating complete with all accessories such as safety valve, thermo state, NRV, connection piece etc, 04 Nos suitable size mild steel L-hook fastener with washer using for hanging the Geyser and making good the disturbed surface complete all as specified and directed by Engineer-in-Charge.
SUMMER APPLIANCES NOTE:- For items of SUMMER APPLIANCES notes given at the beginning of Sch ‘A’ PART-XI SUMMER APPLIANCES shall also be applicable.
Supply , Fixing , Testing and commissioning Water cooler fully stainless steel, Electric Driven, Single Phase , having storage capacity 40 Liters and nominal cooling capacity 40 Litres per hour with anti corrosive pre coated body with float valve, energy efficient compressor, Eco friendly refrigerant, including electric connection through voltage stabilizer complete
Supply , Fixing , Testing and commissioning Voltage stabilizer for automatic operation , single phase, copper wound, of capacity 2 KVA, naturally air cooled , indoor type , and designed for input variation between 170 volt to 250 volt with out put voltage stablized 230 volt , with accuracy of +/- 2.5% , mounting bracket complete with time delay relay complete all as per manufacturer's instructions and complete all as specified and as directed.
Supply , Fixing , Testing and commissioning Desert cooler of size 26" x 26" x 33" or next available higher size having nominal air flow capacity 3000 cubic metre per hour single phase 240 volts 50Hz made out of plain GI Sheet of 18SWG and side panels of 22 SWG, water sump capacity not less than 40 ltrs, with and including water pump submersible type of suitable capacity ISI marked complete all as specified and as directed. Notes :(i) Contractor shall submit original purchase voucher and warranty card as recommended by manufacturer. (ii) Srl No. as issued by Engineer-in-Charge of desert cooler and GE Office name shall also be written on cooler with red colour permanent marker or paint. The rate of this aspect is included in this item and nothing shall be paid extra on this account.
Supply , Fixing Rotational moulded double lavyer polyethylene water storage tanks (cylindrical vertical with closed top) of capacity 500 Liters ISI Marked, hoisted and fixed in position all as specified in SSR Part I complete all as specified and as directed.
M/S BHAGWATI CONSTRUCTION COMPANY (BID ID -3029840)
M/s Kataria Construction Company (BID ID -3029841)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .