| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.8 LAccepted-AOC SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | L1 | Accepted-AOC ACCEPTANCE | |
| 2 | L2₹21.5 L+₹2.5 L (13.3%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | Rejected-Technical | - | Rejected-Technical Not Recommended as same work of last year is still not completed, thus not capable of handling more load |
Tender Value
₹30.0 L
EMD Value
₹60,000
Closing Date
11 Nov 2024, 6:00 pmClosed
COL SAIKAT DE CWE NAVY VASCO
CWE NAVY VASCO VASCO DA GAMA GOA 403802
REPAIR MAINT OF CENTRAL PACKAGE AC PLANTS AND CONNECTED WORKS FOR SOUTH SIDE AND HANSA VIHAR UNDER GE (NW) VASCO
2024_MES_676683_2
85835/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
CWE NAVY VASCO
AS PER TENDER DOC
9 documents required · 9 mandatory
₹500
GE (NW) VASCO
₹60,000
Yes
7 Jan 2025
21 Oct 2024
13 Nov 2024
21 Oct 2024
11 Nov 2024
28 Oct 2024
Amount
M&L for cleaning of shell and tube water cooled condensers of the A/C plants of following capacities after dismantling the water lines and headers and cleaning with suitable wire brush and washing soda to remove the dirt and water scaling and refixing the water lines and headers including provision of new gaskets, etc for following AC plants complete all as directed by Engr-in-Charge.
(a) 3x49.5 TR capacity at ATC AC plant
(b) 3x49.5 TR capacity at ADR AC plant
(c) 03x75 TR capacity at Sh Harrier Simulator AC Plant
(d) 02X12.5 TR capacity at AL/AR AC plant
(e) 03 X 25 TR Capacity at NTS AC Plant
(f) 03X5.5 TR Package unit EW wksp AC plant
Note : Cleaning of all units of an AC Plant will be treated as One Time only. Hence, All units of AC plant will be cleaned with interval of 6 months.
Supply and charging compressor oil Servo manufactured by Indian Oil Corporation or Equivalvent approved make including flushing/cleaning of oil chamber etc complete all as directed by Engr-in-Charge.
Supply and filling Refrigerant gas R-22 /Mafron -22 for AC plant compressor
Supply and filling Refrigerant gas R-407 for AC plant compressor Note :- If required the gas charging of any areas, compressor & capacity of same days otherwise panal recovery as per PS clause
Supply and fix in repairs ball / roller bearing for pumps and motors of following capacity including taking down old bearing and re installation at site including testing on completion.
(a) Upto 10 HP capacity
(b) 12.5 to 15 HP capacity
M&L for servicing monoblock pumps including dismantling and opening the pump, repair/replacement of defective impeller,replace the worn out bearing impeller, stuffing box, back plates, gland packing mechincal seal and rusted nut, bolts etc assembling property , greasing all movable parts, fixing in position, testing and commissioning all as directed for the following HP pumps.
(a) 3 HP to 5 HP Pump
(b) 7.5 HP to 10 HP Pump
Supply and fixing in repair power assembly expansion valve for 75 TR capacity at Sh Harrier Simulator and TU hanger AC plant as per sample and all as directed by Engineer-in-Charge.
Supply and fixing in repair power assembly expansion valve for 49.5 TR capacity at ATC and ADR AC plant as per sample and all as directed by Engineer-in-Charge.
Supply and fixing in repair power assembly expansion valve for 12.5 TR capacity at AL/AR AC plant as per sample and all as directed by Engineer-in-Charge.
Suuply and fix of V-belt of size B-101 .
All as per item No- 10 as above but of size B- 85.
All as per item No- 10 as above but of size B- 99.
All as per item No- 10 as above but of size A- 53
All as per item No- 10 as above but of size B- 75.
Supply and fix in replacement of High pressure control switch as per existing make and type at site all as specified and directed by Engr-in-charge
Supply and fix in replacement oil pressure control switch as per existing make and type at site all as specified and directed by Engr-in-charge
Supply and fix in replacement low pressure control switch as per existing make and type at site all as specified and directed by Engr-in-charge
Supply and fixing in replacement of power contactor assembly complete 63 Amp , 50 KA, 415 V, as per existing
Supply and fixing power contactor assembly complete Lc -1 E 01 as per existing.
Supply and fixing power contractor assembly complete NO and NC as per existing.
Supply and fixing power contactor assembly complete 32A as per existing.
Disconnecting wiring carefully and removing defective auxillary power contactor assembly complete and replacing by new one of same make and model , reconneting wiring and testing on completion 400/415 volts.
Disconnecting wiring carefully and removing defective auxillary power contactor assembly complete and replacing by new one of same make and model , reconneting wiring and testing on completion 400/415 volts.
All as per item No - 23 but same make and model 12.5 to 20 amps type 3 NA with 1 NO+NC.
Supply & fixing digital type ammeter panel mounting three phase LED type 96 x 96 mm square including taking down old meter.
Supply & fixing digital typer voltmeter panel mounting three phase LED 96 x 96 mm square including taking down old meter.
Supply and fixing current transformer secondary current 5 Amps and primery current up to 60 Amps including taking down old current transformer.
Supply and fixing in repair themometer suitable for condenser water line with suitable housing to mount in pipe line 0 – 100 deg C including taking down old themostat.
Supply and fixing indicator lamp assembly complete LED type suitable for the existing system supply voltage for the existing system supply voltage 230V / 440 V AC including taking down old lamp assembly.
Supply and fixing in repair of MCCB 3 pole 415 volts AC , 100 Amps breaking capcity 16 KA.
Supply and fixing in repair of MCCB 3 pole 415 volts AC , 125 Amps breaking capcity 25 KA.
Supply and fixing in repair of MCCB 3 pole 415 volts AC , 200 Amps breaking capcity 25 KA.
Supply and fixing in repair of MCCB 3 pole 415 volts AC , 250 Amps breaking capcity 25 KA.
Supply and fixing in repair of MCB TP 40 to 63 Amps 10 KA.
Supply and fixing in repair of MCB SP 06 to 32 Amps 10 KA.
Dismantling the unserviceable electric motor any type (for pump or CT) of capacity upto 10 HP and transporting to reputed workshop, taking out old and burnt winding wire and rewinding with super enameled copper winding wire of existing gauge and size with insulating materials, varnishing and baking etc, re-fixing the same at site and re-alignment, testing and commissioning complete all as directed by Engr-in-Charge
Taking out old and unserviceable PVC fins of cooling tower of any capacity AC plant and replacing with new one including setting complete.
Supply and fixing in repair fabricated micro filter upto 90 micron made out of GI channel frame overall size 610 mm x 610 mm x 50 mm including nylon micro filter and wire mesh covered front and back all as per sample given including taking down old micro filter
All as per item No 38 above but overall size 610 mms x 305 mms x 50 mm .
All as per item No 38 above but overall size 305 mms x 305 mms x 50 mm .
Supply and fix in repair DOL starter suitable for upto 10 HP motor capacity 9 to 23 Amp complete with over load relay , single phasing preventer under volt release in existing enclosure etc.
Nitrogen testing for the following capacity of compressors including condensing unit and gas piping complete as per the manufacturer instructiions and entire satisfaction of the Engineer in Charge.
Note :- (i) Nitrozen pressure should be held with out any drop in pressure inside the unit continue for 24 hours.
(a) 3x49.5 TR capacity at ATC AC plant
(b) 3x49.5 TR capacity at ADR AC plant
(c) 03x75 TR capacity at Sh Harrier Simulator AC Plant
(d) 02X12.5 TR capacity at AL/AR AC plant
(e) 03 X 25 TR Capacity at NTS AC Plant
(f) 03X5.5 TR Package unit EW wksp AC plant
M & L Preparation of old painted surfaces by removing dust, rust etc and, applying two coats of synthetic enamel paint with spray gun of approved make and colour for cooling tower, condensing pipe line, condenser water pumps including all pipe line valves etc. of 5.5 TR to 25 TR Capacity Plant.
M & L preparation of old painted surfaces by removing dust, rust etc and, applying two coats of synthetic enamel paint with spray gun of approved make and colour for cooling tower, condensing pipe line condenser water pumps including all pipe line valves etc. of 25 TR to 75 TR Capacity Plant.
Supply and fix CT fan (with hub and fan blade) of capacity 25 to 75 TR cooling tower all as specified and directed by Engr-in-Charge
Supply and fix CT fan (with hub and fan blade) of capacity upto 5.5 to 25 TR cooling tower all as specified and directed by Engr-in-Charge
Supply and fixing of union 40 mm of water tower all as specified.
Supply and fixing of union 32/25 mm of cooling tower all as specified.
Supply and fixing of gate valve 40 mm of cooling tower all as specified.
Supply and fixing of gate valve 32/25 mm of cooling tower all as specified.
Supply and fixing of Float valve 32/25 mm of cooling tower all as specified.
Supply and fixing of FRP Plate of suitable size for covering of cooling tower all as specified.
S & F in repair chilled water sensor for AC Plants of various capacity
S & F loading/unloading switch assembly for compressor of capacity upto 15 TR.
S & F loading/unloading switch assembly for compressor of capacity from 20 TR upto 30 TR.
S & F loading/unloading switch assembly for compressor of capacity from 45 TR upto 75 TR.
S & F pressure gauge for neon gases 0 to 25 kg .
S & F pressure gauge for freon gases 0 to 16 kg .
S & F microprocessor for compressor of capacity from 10 TR to 25 TR
S & F microprocessor for compressor of capacity from 45 TR to 75 TR
S & F cooling tower nozzles 1/4'' and 1/2" size
S & F block bearing for air handling unit of any size
S&F in replacement of strip heater 2 KW capacity including making electrical connections with main supply complete all as specified and as directed.
S&F in replacement of strip heater 3 KW capacity including making electrical connections with main supply complete all as specified and as directed.
M&L for oil diffrential pressure control high pressure and low pressure switch, rewiring of the control and connecting to starter panel complete all as specified and directed by Engr-in-Charge
S&F in replacement of HDPE make up water tank of 1000 litre capacity with air vent, drain, overflow and make up connection with PVC High Pressure float valve complete all as specified and directed by Engr-in-charge.
M & L for taking out old worn out cladding and supply and rapping glass wool and aluminium cladding to cover the GI tubing 100/80/65 mm bore to avoid heat condution.
S & F in repairs liquid line drier 5/8" x 5/8" all as directed
Supply only cooling tower fan blade assy for Capacity upto 25 TR AC plant all as directed.
Supply only cooling tower fan blade assy for Capacity 25 to 75 TR AC plant all as directed.
S & F in repairs water line strainer 2 1/2" dia size with GI flange including necessary joint arrangement complete at NDT Ejection Bay AC plants all as directed
S & F in repairs condensor monoblock water pump set 3 HP 3 phase capacity with suitable head and discharge ammunator store including necessary PCC foundation work and electric/ water connection complete all as directed.
Supply only Pressure Gauge upto 300psi (100mm) all as directed
M & L for replacement of tarpaulim canvas cloth connecting the air outlet and main duct of AHU as per existing size and thickness inclusing provision of chain with Zip for taking Wet/ Dry Bulb reading, angle iron complete, including taking out unserviceable as directed
S & F in repairs Thermal over load relay 2.5 to 9 Amp.
Dismantling carefully and removing of old U/S compressor's sealed unit of upto 12.5 Ton capacity from any type Air conditioner and supply anf fix new sealed unit of same capacity complete with all standard accessories as per exisiting AC plant. Note:- Sealed unit shall be purchased from authorised dealers/agents
Rewiring of all electrical controls inclsuing Micro- processor, electric contractor, supply and fix in replacement of auxiliay contractor for one of central AC plantlpackage type AC plant of any capacity all as directed
S & F in repiars of Thermostatic Expansion Valve assembly complete Model : MVE series suitable for gas R-22 or R-407 of all as directed
Dismanting of damaged cooling coil of 5TR to 20 TR AC plantcapacity and repairing of coling coil to distributor and nrow paralleled 5/16 size and from distributor to expansion valve and room expansion value to compressor suction line with 11/8" size of coopwer pipe including following items :- (a) Expansion valve 5 TR- 02 Nos (b) Distributor - 02 Nos (c) Filter drier 5/8x5/8-02 Nos (d) Hand shut off value 5/8"-02Nos
All as per item No 79 above but 20 TR to 75 TR AC plant .
S & F in reapairs DOL starter suitable for 5HP TO 10HP motor MK-1 complete with over load relay, single phasing preventer under volt release etc all as directed.
Charges for attending break down of AC plant of 5 TR to 25 TR capacity by only auth OEM rep / team for fault finding incl attending repairs as and when required such as No start condition of AC plant and repairing, starting the AC plant till smooth running and setting up the alighnment/required paramenters of all major parts such as fan belt, compressor, gas charge, cooling tower, power contactor, starter, MCCBs, Micro processor based control panel, pumps etc as required in ground/as ordered by EIC all as directed. (The payment for the above shall be made to Contractors after submitting the original invoice only)
Ditto all as per item No 82 here in before but of AC plant capacity 25 TR to 75 TR.
BUTTERFLY VALVE: Suply, installation, testing and commissioning of wafer type PN 1.6 rated short pattern CI butterfly valve having Gr. FG-200 CI body conforming to IS 210: 2009, seat having EPDM rubber lining, CF 8 stainless steel disc, AISI- 410 stainless steel stem, 2.4 MPa body test pressure & 1.6 MPa seat test pressure and standard flange end conforming to BS 10 Table D/E & ANSI B 16.1 CI- 125 with necessary accessories including dismantling of existing old one complete all as specified and directed.
(a) 80 to 100 mm NB
(b) 100 to 150 mm NB
star freeze service (BID ID -3155758)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .