HOS ENGINEERING
IPM SECTION, IIT GUWAHATI
Provision of sub-main wiring for installation UPS input/output connection along with power plug point in the various location in the SART Building and Installation of 40KVA UPS along with suitable distribution system at entire old block of HSS Dept.
2025_IITG_856148_1
IITG/IPM/NIT/C/2024-25/75
Open Tender
Electrical Works
Works
60 days
IIT GUWAHATI
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹20,000
Yes
27 May 2025
9 Apr 2025
22 Apr 2025
9 Apr 2025
21 Apr 2025
9 Apr 2025
Amount
SART Department
Supply and drawing following sizes of FR PVC insulated copper conductor,single core cable in the existing surface/recess/pVC conduit as required make Havells/Finolex/RR Kabel or equvalent
i) 2 x 4 sqmm + 1x 4sqmm earth wire
i) 2 x 6 sqmm + 1x 6sqmm earth wire
Supplying and fixing following modular type switch/socket on the existing swith box/cover including connection etc.as required make legrand or equivalent
(a) 15 Amp Switch
(b)15 Amp socket
Supplying and fixing of following modules GI boxes along with modular base & cover plate for modular switch in recess etc as required make havels crabtree
i) 4module
Supplying and fixing following way single phase and neutral sheet steel MCB distribution board 240V on surface/recess complete with tinned copper busbar neutral bus bar earth bar din bar inetrconnection power painted including earthing as required ( But without MCB/RCCB/Isolator)
i) 8 waydouble door
Supply and fixing DP sheet steel enclosure on surface/recess along with 25/32 A 240V c urve DP MCB complete with connection testing and commissioing etc as required
Supply and fixing 5amps to 32amp 240/415V 10KA C curve miniatutre ckt braker suitable for inductive load of following poles in the existing MCB DB complete with connection testing and commissioing etc as required
i) Single pole
ii) Double pole
Supply and fixing of following sizes of medium class PVC conduit along with accessories in the surface/recess including cutting the wall amking good the same in case of recess conduit required
i) 25mm dia
HSS Department
Suplly and drawing following sizes of FR PVC insulated copper conductor,single core cable in the existing surface/recess/pVC conduit as required make Havells/Finolex/RR Kabel or equvalent
iii) 4 x 10 sqmm + 2x 6 sqmm earth wire
Proding and fixing following rating and breaking capacity and pole MCCB with thermo magnetic release and thermal spreader in exiting cubicles panel board including drilling holes in cubicles panel, making connection etc as required
i) 125A ,36KA FP MCCB
Earthing with copper earth plate 600mmX600mmX3mm thick including accessories and providng masonary enclosure with cover having locking arragement and waterring pipeof 2.7 meter long etc with Charcoal/coke and salt as rquired
Providing and fixing 25mm X 5mm copper strip in 40mm dia GI pipe from earth electrode including connection with brass nut, bolt, spring, washer excation and re-filling etc. as required
Providing, laying and fixing following dia G.I pipe(medium class) in ground complete with G.I fittings including trenching (75cm deep) and re-filling etc as required
50mm dia
Supply delivery and fixing of metal one way enclosure for 4 pole MCCB as required
i) 4 pole metal enclosure
Supply and fixing of of 1.1KV Grade PVC/XLPE insulated unarmored power/control solid copper cable of following sizes (Make KEI/Havells/RR Kabel/Polycab)
i) 25 sqmm 4 core
Supply and installation of 200A copper busbar distribution board make Havell or equivalent
Supply and fixing of 63A 240/240 10KA C curve TPN minitature Ckt breaker suitable for inductive load of following connection in the exting MCB DB complete with connection testing and commissioing etc as required make Havells/Legrand/Scheider
i) 63A TPN MCB
Supply and drawing following sizes of FR PVC insulated copper conductor,single core cable in the existing surface/recess/pVC conduit as required make Havells/Finolex/RR Kabel or equvalent
i) 5X35sqmm sqmm
Rupam Das (BID ID -3202802)
Sankardev Enterprise (BID ID -3204027)
M/S ANUSHREE CONSTRUCTIONS & ASSOCIATES (BID ID -3204550)
Delta Engineers (BID ID -3204276)
Swastika Teleservices (BID ID -3204753)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .