GE E/M RR HOSP DELHI CANTT-10
GE E/M RR HOSP DELHI CANTT-10
GE/H/ T-32/ 2026-27 REPAIR / MAINT OF AHU PANELS AC PLANT LT PANEL ALONG WITH ALLIED WORKS AT AHRR UNDER GE E/M RR HOSP DELHI CANTT-10
2026_MES_777891_1
GE/H/T-32/2026-27
Open Tender
Electrical and Maintenance Works
180 days
GE E/M RR HOSP DELHI CANTT-10
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE E/M RR HOSP DELHI CANTT-10
₹90,000
Yes
11 Jul 2026
11 Jul 2026
3 Aug 2026
11 Jul 2026
1 Aug 2026
25 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing & commissioning in replacement LT panel board In door type, wall mounted of suitable size for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of CRCA sheet outer box thickness 2.0 mm, side covers with hinged doors & proper locking arrangement, rubber gasket on front and back door to make it dust and vermin proof, powder coated , The cubicle shall have control wiring with minimum size: 1.5 SQmm of copper cable including M&L for fixing / grouting the panel to wall and required cable connection with necessary double compression brass gland and cable end sockets, complete comprising of following accessories all as specified and any other items required for smooth functioning of VFD starter Panel is deemed to be included in the rate quoted for the items and as directed by the Engr-in-charge.
Note:-All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job.) also having built in single phase preventer for 5 HP capacity fan motor complete with following specifications:- | 5 | Each Job | - | - |
| 1.1 | INCOMING:-
(i) MCB 25A 10kA (incoming)-01 No.
(ii) Ammeter, Voltmeter and CTs- 01 set
(iii) RYB indicating lamps LED type- 03 Nos
(iv) MCB SP 6A -03 Nos
OUTGOING:-
(i) FASD Starter 5 HP -01 No.
(ii) Contactor 3P 12 A -03 No.
(iii) O/L relay 6-10A -01 No.
(iv) ON-TRIP indicator - 02 No.
(v) Start/stop push button - 02 No.
(vi) MCB SP 6A,10kA- 01 No
(vii) Add on Aux Block 1 NO + 1 NC - 02 set
(viii) Single Phase Preventer - 01 No
(ix) Auto manual selector switch - 01 No.
(x) Star Delta Timer - 01 No.
(xi) Variable Frequency Drive suitable for 5 HP motor -01 No.Make:- Danfoss
(xii) Glass relay 5 A, 11 PIN -01 No.
(xiii) Control Wiring, busbar,nut, bolts, washers , auxillary contacts etc alongwith all misc connected items are deemed to be included in quoted rate.
Note:- Contractor need to submit drawing of panel alongwith bill of quantities for approval before starting execution of work | - | - | - | - |
| 2 | Supply, installation, testing & commissioning in replacement LT panel board In door type, wall mounted of suitable size for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of CRCA sheet outer box thickness 2.0 mm, side covers with hinged doors & proper locking arrangement, rubber gasket on front and back door to make it dust and vermin proof, powder coated , The cubicle shall have control wiring with minimum size: 1.5 SQmm of copper cable including M&L for fixing / grouting the panel to wall and required cable connection with necessary double compression brass gland and cable end sockets, complete comprising of following accessories all as specified and any other items required for smooth functioning of VFD starter Panel is deemed to be included in the rate quoted for the items and as directed by the Engr-in-charge.
Note:-All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job.) also having built in single phase preventer for 7.5 HP capacity fan motor complete with following specifications:- | 5 | Each Job | - | - |
| 2.1 | INCOMING:-
(i) MCB 32A 10kA (incoming)-01 No.
(ii) Ammeter, Voltmeter and CTs- 01 set
(iii) RYB indicating lamps LED type- 03 Nos
(iv) MCB SP 6A -03 Nos
OUTGOING:-
(i) FASD Starter 7.5 HP -01 No.
(ii) Contactor 3P 18 A -03 No.
(iii) O/L relay 9-15A -01 No.
(iv) ON-TRIP indicator - 02 No.
(v) Start/stop push button - 02 No.
(vi) MCB SP 6A,10kA- 01 No
(vii) Add on Aux Block 1 NO + 1 NC - 02 set
(viii) Single Phase Preventer - 01 No
(ix) Auto manual selector switch - 01 No.
(x) Star Delta Timer - 01 No.
(xi) Variable Frequency Drive suitable for 7.5 HP motor -01 No.Make:- Danfoss
(xii) Glass relay 5 A, 11 PIN -01 No.
(xiii) Control Wiring, busbar,nut, bolts, washers , auxillary contacts etc alongwith all misc connected items are deemed to be included in quoted rate.
Note:- Contractor need to submit drawing of panel alongwith bill of quantities for approval before starting execution of work | - | - | - | - |
| 3 | Supply, installation, testing & commissioning in replacement LT panel board In door type, wall mounted of suitable size for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of CRCA sheet outer box thickness 2.0 mm, side covers with hinged doors & proper locking arrangement, rubber gasket on front and back door to make it dust and vermin proof, powder coated , The cubicle shall have control wiring with minimum size: 1.5 SQmm of copper cable including M&L for fixing / grouting the panel to wall and required cable connection with necessary double compression brass gland and cable end sockets, complete comprising of following accessories all as specified and any other items required for smooth functioning of VFD starter Panel is deemed to be included in the rate quoted for the items and as directed by the Engr-in-charge.
Note:-All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job.) also having built in single phase preventer for 7.5 HP capacity fan motor complete with following specifications:- | 6 | Each Job | - | - |
| 3.1 | INCOMING:-
(i) MCB 32A 10kA (incoming)-01 No.
(ii) Ammeter, Voltmeter and CTs- 01 set
(iii) RYB indicating lamps LED type- 03 Nos
(iv) MCB SP 6A -03 Nos
OUTGOING:-
(i) FASD Starter 10 HP -01 No.
(ii) Contactor 3P 22 A -03 No.
(iii) O/L relay 9-15A -01 No.
(iv) ON-TRIP indicator - 02 No.
(v) Start/stop push button - 02 No.
(vi) MCB SP 6A,10kA- 01 No
(vii) Add on Aux Block 1 NO + 1 NC - 02 set
(viii) Single Phase Preventer - 01 No
(ix) Auto manual selector switch - 01 No.
(x) Star Delta Timer - 01 No.
(xi) Variable Frequency Drive suitable for 10 HP motor -01 No.Make:- Danfoss
(xii) Glass relay 5 A, 11 PIN -01 No.
(xiii) Control Wiring, busbar,nut, bolts, washers , auxillary contacts etc alongwith all misc connected items are deemed to be included in quoted rate.
Note:- Contractor need to submit drawing of panel alongwith bill of quantities for approval before starting execution of work | - | - | - | - |
| 4 | Supply, installation, testing & commissioning in replacement LT panel board In door type, wall mounted of suitable size for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of CRCA sheet outer box thickness 2.0 mm, side covers with hinged doors & proper locking arrangement, rubber gasket on front and back door to make it dust and vermin proof, powder coated , The cubicle shall have control wiring with minimum size: 1.5 SQmm of copper cable including M&L for fixing / grouting the panel to wall and required cable connection with necessary double compression brass gland and cable end sockets, complete comprising of following accessories all as specified and any other items required for smooth functioning of VFD starter Panel is deemed to be included in the rate quoted for the items and as directed by the Engr-in-charge.
Note:-All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job.) also having built in single phase preventer for 10 HP capacity fan motor complete with following specifications:- | 1 | Each Job | - | - |
| 4.1 | INCOMING:-
(i) MCB 63A 10kA (incoming)-01 No.
(ii) Ammeter, Voltmeter and CTs- 01 set
(iii) RYB indicating lamps LED type- 03 Nos
(iv) MCB SP 6A -03 Nos
OUTGOING:-
(i) FASD Starter 30 HP -01 No.
(ii) Contactor 3P 50 A -03 No.
(iii) O/L relay 30-60 A -01 No.
(iv) ON-TRIP indicator - 02 No.
(v) Start/stop push button - 02 No.
(vi) MCB SP 6A,10kA- 01 No
(vii) Add on Aux Block 1 NO + 1 NC - 02 set
(viii) Single Phase Preventer - 01 No
(ix) Auto manual selector switch - 01 No.
(x) Star Delta Timer - 01 No.
(xi) Variable Frequency Drive suitable for 30 HP motor -01 No.Make:- Danfoss
(xii) Glass relay 5 A, 11 PIN -01 No.
(xiii) Control Wiring, busbar,nut, bolts, washers , auxillary contacts etc alongwith all misc connected items are deemed to be included in quoted rate.
Note:- Contractor need to submit drawing of panel alongwith bill of quantities for approval before starting execution of work | - | - | - | - |
| 5 | Supply, installation, testing & commissioning in replacement LT panel board In door type, wall mounted of suitable size for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of CRCA sheet outer box thickness 2.0 mm, side covers with hinged doors & proper locking arrangement, rubber gasket on front and back door to make it dust and vermin proof, powder coated , The cubicle shall have control wiring with minimum size: 1.5 SQmm of copper cable including M&L for fixing / grouting the panel to wall and required cable connection with necessary double compression brass gland and cable end sockets, complete comprising of following accessories all as specified and any other items required for smooth functioning of VFD starter Panel is deemed to be included in the rate quoted for the items and as directed by the Engr-in-charge.
Note:-All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job.) also having built in single phase preventer for 30 HP capacity fan motor complete with following specifications:- | 4 | Each Job | - | - |
| 5.1 | INCOMING:-
(i) MCB 40A 10kA (incoming)-01 No.
(ii) Ammeter, Voltmeter and CTs- 01 set
(iii) RYB indicating lamps LED type- 03 Nos
(iv) MCB SP 6A -03 Nos
OUTGOING:-
(i) FASD Starter 15 HP -01 No.
(ii) Contactor 3P 25 A -03 No.
(iii) O/L relay 14-23 A -01 No.
(iv) ON-TRIP indicator - 02 No.
(v) Start/stop push button - 02 No.
(vi) MCB SP 6A,10kA- 01 No
(vii) Add on Aux Block 1 NO + 1 NC - 02 set
(viii) Single Phase Preventer - 01 No
(ix) Auto manual selector switch - 01 No.
(x) Star Delta Timer - 01 No.
(xi) Variable Frequency Drive suitable for 15 HP motor -01 No.Make:- Danfoss
(xii) Glass relay 5 A, 11 PIN -01 No.
(xiii) Control Wiring, busbar,nut, bolts, washers , auxillary contacts etc alongwith all misc connected items are deemed to be included in quoted rate.
Note:- Contractor need to submit drawing of panel alongwith bill of quantities for approval before starting execution of work | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
TenderT32.pdf
Tender Documents • 1.16 MB
T32SoC.pdf
Additional Documents • 0.43 MB
BOQ_871214.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid