Executive Engineer (E)
O/o EE (E), PWD NES/ M-251, LM Bund Road, Ramesh Park, Delhi-92
(1) RMO E and M Services at UTCS Bldg. Vishwas Nagar, Shahdara Delhi. (2) RMO E and M Services in KKD Court (Court Block) ACI, B and JKL at Distt. Court KKD Delhi. (SH- Servicing and Calibration, Testing of 11 KV HT/ LT Panel and transformer etc.)
2021_PWD_208028_2
DB-5/PWD NES ED/M-251/2021/1219
Open Tender
Electrical Works
Item Rate
30 days
KKD Court Complex
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹5,000
Yes
22 Sept 2021
13 Sept 2021
18 Sept 2021
13 Sept 2021
18 Sept 2021
13 Sept 2021
Amount
Servicing of 630/1000 Amps capacity 3ph 415/500 Volt withdrawal type LT ACB (L&T/ C&S make) complete with removal from panel board opening/ dismantling the required parts for servicing, checking, cleaning, testing & rectification of defects, oiling greasing moving gear assembly and arc contacts with CR-2 spray and cadmium solution, and testing of micrology with testing kit for actual working of earth fault over load short circuits etc i/c re- assembling, re-commissioning in the LT panel etc. complete as required.
Servicing of 630 Amps 3 ph 11 KV HT VCB (Cromton Greaves make) opening the required parts for servicing checking cleaning testing & rectification of defects oiling greasing moving gear assembly and arc contacts with CR-2 spray and cadmium solution i/c reassembling, re-commissioning in the HT panel etc. complete as required.
Testing and calibration of IDMT relay set having 2 Nos. O/L and one No. earth fault relay installed in the existing HT panel by secondary injection method cleaning the contacts resetting with required accuracy complete checking & setting of control wiring i/c refixing of the relay unit etc complete as required.
Servicing, checking & cleaning of 11 KV HT panel board in respect of each HT breaker by opening of HT panel & CT’s chamber removing the dust with vacuum cleaner checking, cleaning & decarbonizing the HT panel, fixed contacts of switchgear & CT’s with CTC/ CRC tightening of contacts & joints of bus-bar CT & PT connections, checking actual working of CT's, tightening of cable end termination replacement of burnt/ heated thimbles, nuts, bolts, HT tapping and monoplast compound etc wherever required i/c testing complete as required.
Servicing of 11 KV/110 Volts PT Complete i/c removal of PT from HT panel board, cleaning of dirt particles tightening connection i/c checking of wiring, replacement of gaskets of top cover reassembly, testing and commissioning etc. complete as required.
FOR COURT COMPLEX (ACI, B, JKL, D & F Block)
Performing of High pot testing of 11 KV HT CTR Cables and Busbar by DC high pot equipment, and checking in all respect etc as required.
Servicing of 400 Amp. HT OCB i/c cleaning removal of dust and dirt of the male and female contacts and checking of spring pressure , oiling, greasing of the mechanical system for its smooth trouble free functioning i/c testing and re commissioning etc. complete as required.
Dehydration & filtration of Transformer oil / OCB Oil with filter machine i/c the cost of transformation of filter machine providing oil checking at site and increasing dielectric strength upto 50 KV/cm etc as required at site.
Topping up the existing transformer with new Transformer oil to fill the oil upto the desired level etc complete as required. (Make:- Savita)
Checking and calibration of safety relay installed in HT panel with secondary injection set i/c checking, overhauling, removal of minor defects and coordination of relay settings of following relays etc as required at site. (a) IDMT Over current Relay-2Nos (b) Earth Fault Relay-1No
Servicing of 630 Amps 3 ph 11 KV HT VCB (Cromton Greaves make) opening the required parts for servicing checking cleaning testing & rectification of defects oiling greasing moving gear assembly and arc contacts with CR-2 spray and cadmium solution i/c reassembling, re-commissioning in the HT panel etc. complete as required.
Servicing of 630 - 1600 Amps capacity 3ph 415/500 Volt withdrawal type LT ACB (L&T/ C&S make) complete with removal from panel board opening/ dismantling the required parts for servicing, checking, cleaning, testing & rectification of defects, oiling greasing moving gear assembly and arc contacts with CR-2 spray and cadmium solution, and testing of micrology with testing kit for actual working of earth fault over load short circuits etc i/c re- assembling, re-commissioning in the LT panel etc. complete as required.
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 630 A, 50 kA,TPMCCB
400 A, 35 kA,TPMCCB
250 A, 35 kA,TPMCCB
100 A, 16 kA,TPMCCB
Less of Account of buy back of following dismantled material
Assorted size TP MCCB
M/s.Yania Engineers
Super Electrical Co.
PARASAR ELECTRICALS & REFRIGERATION
A K Electric Works
Master Engineering Services
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .