Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹130.2 CrAccepted-AOC | ₹130.2 Cr | L1 | Accepted-AOC Being the lowest tenderer and reasonable |
| 2 | L2₹140.7 CrRejected-Finance | ₹140.7 Cr | L2 | Rejected-Finance Not being the lowest |
| 3 | L3₹143.0 CrRejected-Finance | ₹143.0 Cr | L3 | Rejected-Finance Not being the lowest |
| 4 | L4₹143.4 CrRejected-Finance | ₹143.4 Cr | L4 | Rejected-Finance Not being the lowest |
| 5 | L5₹152.0 CrRejected-Finance | ₹152.0 Cr | L5 | Rejected-Finance Not being the lowest |
Tender Value
₹136.7 Cr
EMD Value
₹15 L
Closing Date
22 Jul 2021, 6:00 pmClosed
Chief Engineer(Navy) Mumbai
HQ Chief Engineer Navy Mumbai, 26 Assaye Buildings, SBS Road, Colaba, Mumbai-05
RECONSTRUCTION OF DEFICIENT SAILORS MARRIED ACCOMMODATION INCLUDING DEMOLITION OF AX, AY AND AZ BUILDINGS AT NAVY NAGAR, COLABA, MUMBAI
2021_MES_436186_1
87882/E8
Open Tender
Civil Works
1460 days
Colaba
As per tender documents
10 documents required · 10 mandatory
₹3,000
GE(P) NW Mumbai
₹15 L
Yes
HQ Chief Engineer Navy Mumbai
28 Sept 2021
13 Apr 2021
24 Jul 2021
13 Apr 2021
22 Jul 2021
15 Jul 2021
13 Apr 2021 - 23 Apr 2021
23 Apr 2021
Amount
Schedule-A' Part-I 'Buildings & Structures' Total of Schedule-'A' Part-I
Schedule-A' Part-II 'Site Clearance , Excavation & Earthwork, and Land Development' Total of Schedule-'A' Part-II
Schedule-A' Part-III 'Demolition and Dismantling' Total of Schedule-'A' Part-III
Schedule-A' Part-IV 'Internal Water Supply' Total of Schedule-'A' Part-IV
Schedule-A' Part-V 'Internal Electrification' Total of Schedule-'A' Part-V
Schedule-A' Part-VI 'Roads/Paths/Culverts' Total of Schedule-'A' Part-VI
Schedule-A' Part-VII 'External Water Supply' Total of Schedule-'A' Part-VII
Schedule-A' Part-VIII 'External Electrification' Total of Schedule-'A' Part-VIII
Schedule-A' Part-IX 'Sewage Disposal' Total of Schedule-'A' Part-IX
Schedule-A' Part-X 'Area Drainage' Total of Schedule-'A' Part-X
Schedule-A' Part-XI 'Rainwater Harvesting' Total of Schedule-'A' Part-XI
Schedule-A' Part-XII 'Fire Fighting System' Total of Schedule-'A' Part-XII
Schedule-A' Part-XIII 'Aviation Lights' Total of Schedule-'A' Part-XIII
Schedule-A' Part-XIV 'Lifts' Total of Schedule-'A' Part-XIV
Schedule-A' Part-XV 'Lightning Protection' Total of Schedule-'A' Part-XV
Schedule-A' Part-XVI 'Arboriculture' Total of Schedule-'A' Part-XV
Miscellaneous Items (Schedule 'A' Part - XVIII)
IRRIGATION
Providing and fixing sprinkler system for lawn and drip system for planters with appropriate nozzle sizes and with pressure pumps and valves where ever necessary from the water source. Water quality should be checked.
Internal Water Supply
S& F Overhead shower rose 80mm dia. Of ABS body chromium plated for fixing shower arm 15 mm size with bend of 45degree with flange. Make - Jaguar model OHS 1985 or equivalent in Crab tree/Kohler
S&F Wall mixer with provision for overhead shower connection with 115mm long bend pipe on upper side, connecting legs & Wall flanges. Make - Jaquar Model No CQT-23281UPR or equivalent in Crab Tree/Kohler brand.
S&F for concealed stop cock, Regular body with adjustable wall flange, size 20mm dia, Make - Jaquar Model No CQT-23089 or equivalent in Crab Tree/Kohler brand.
S&F Angular stop cock 15 mm dia, quarter turn Make - Jaquar Model No CQT-23059-G or equivalent in Crab Tree/Kohler brand.
S&F Sink cock with swinging casted round shape spout (Wall mounted model) 20 mm dia, quarter turn Make - Jaquar Model No CQT-23347 or equivalent in Crab Tree/Kohler brand.
S&F two way bib cock 15 mm dia. Make - Jaquar Model No CQT-23041 or equivalent in Crab Tree/Kohler brand.
S&F Health faucet (ABS body) with 01 meter long PVC tube & wall hook. Make - Jaquar Model No ALD-CHR- 583 or equivalent in Crab Tree/Kohler brand.
S&F 50 MM BRASS FORGED PRESSURE REDUCING VALVES complete all as specified. Make- ZOLOTO or equivalent
Internal Electrification
Supply and Fix Metal Flush Box - 8 module [Make: Legrand/ Havells or equivalent]
Supplying and fixing of modular type Blanking plate with ISI mark and approved make, including necessary fixing arrangement [Make: Legrand/ Havells or equivalent]
S & F ISI marked MCB for AC applications, having breaking capacity Icn = 10 kA, conforming to IS/IEC 60898-1-2002, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters 20A, FP MCB C-curve [Make: LEGRAND/HAVELLS/STANDARD or equivalent]
S & F ISI marked MCB for AC applications, having breaking capacity Icn = 10 kA, conforming to IS/IEC 60898-1-2002, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters 32A, FP MCB C-curve [Make: LEGRAND/HAVELLS/STANDARD or equivalent]
S &F LED tube light fittings decorative ultra slim linear fixture with extruded aluminium heat sink environmental friendly Energy efficient ready to use pack ,22 Watt min Lumens 650 ,4 feet, surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block etc. with all accessories intenallt prewired & including connecting up with 2 core flexible copper conductor cable with suitable size & suitable for and mounting clamps PVC square box 75x75mm - 2 nos etc all as specified and as directed. [Make: Wipro/Havells/Crompton Greaves or equivalent]
S &F LED tube light fittings decorative ultra slim linear fixture with extruded aluminium heat sink environmental friendly Energy efficient ready to use pack ,18 Watt min Lumens 650 ,4 feet, surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block etc. with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc all as specified and as directed. [Make: Wipro/Havells/Crompton or equivalent]
S &F LED tube light fittings decorative ultra slim linear fixture with extruded aluminium heat sink environmental friendly Energy efficient ready to use pack ,10 Watt ,2 feet, surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block etc. with all assoceries intenallt prewired & including connecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc all as specified and as directed. [Make: Wipro/Havells/Crompton or equivalent]
S &F LED tube light fittings decorative ultra slim linear fixture with extruded aluminium heat sink environmental friendly Energy efficient ready to use pack ,5 Watt ,1 feet, surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block etc. with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc all as specified and as directed. [Make: Wipro/Havells/Crompton or equivalent]
S & F 13.5 W LED 6000 K Bulkhead designed for modern homes available in non PIR as well as PIR sensor with premium quality diffuser for glare free light and easy to install snapfit installer. [Make: Wipro/Havells/Crompton or equivalent]
S&F Energy efficient BEE five star rated ceiling fan, 1200 mm sweep and connecting up including provision of three core flexible copper wire of size 23/0076 from ceiling rose to ceiling fan complete in all respect all as specified and directed.[Make : HAVELLS Cat No :- ES Neo Crompton Greaves/ Bajaj/Orient HSN code:8414]
S&F ceiling fan, 1400 mm sweep and connecting up including provision of three core flexible copper wire of size 23/0076 from ceiling rose to ceiling fan complete in all respect all as specified and directed.[Make : HAVELLS Cat No :-XP-390 Crompton Greaves/ Bajaj/OrientHSN code:8414]
S&F Fresh air Exhaust fan of size 230/250 mm sweep complete with and louvers connecting up including provision of three core flexible copper wire of size 23/0.0076 from ceiling rose to exhaust fan all as specified and as directed. [Make , - Havells Cat No :- Ventil Air-DX white/Crompton Greaves/Bajaj HSN code:8414]]
S&F Exhaust fan of size 230/250 mm sweep metal body complete with and louvers connecting up including provision of three core flexible copper wire of size 23/0.0076 from ceiling rose to exhaust fan all as specified and as directed.[Make , - Havells cat no :- Ventilair DB Neo/ Bajaj/Crompton HSN code:8414]]
S&F Exhaust fan heavy duty of size 450 mm sweep metal body complete with and louvers connecting up exhaust fan all as specified and as directed.[ Make , - Havells cat no :- Turbo Force SP/ Bajaj/Crompton HSN code:8414]](For pump house/Substation)
Supply and fix time switches astro type MicroRex analog time switches In accordance with IEC 60730-1 and 60730-2-7 Manual switching ON/automatic/OFF Hourly/daily/weekly switching dial with captive segments Clock precision: +/– 5 min for the daily time switch –10 °C to +55 °C operating temperature (Having longitude and latitude of Indian cities in memory) 250 V of 20 Amp rating with contactor fitted inside steel enclosure [Make: L&T: AUTS02DIG00 or equivalent] - (For Street Lights & Landscape-Decorative Lights)
Supply, Installation, Testing and commissioning of 1000 mm x 100 x 2 mm thick Ladder type hot dip galvanised cable trays including supports made with hot deep galvanised perforated sheets, structural angles, rods, anchor fasteners, nuts, washers etc including all required fitting & as per codal requirement.
Supply, Installation, Testing and commissioning of 450 mm x 100 x 2 mm thick mm thick Ladder type hot deep galvanised cable trays including supports made with hot deep galvanised perforated sheets, structural angles, rods, anchor fasteners, nuts, washers etc .including all required fitting & as per codal requirement.
S & F TPN DB-VTPN DPX³ MCB Double door DB's As per IEC 61439-3 Suitable for Flush Mounting and Surface Mounting ,With 100 A Copper Busbar for each phase, With 2 Neutral bar, 2 Earthbar and Cable ties for Cable management, Fully insulated busbar & shrouded Neutral bars, Improved Pan assembly for ease of installation, Prefitted masking sheet, Reversible Door for IP 43 & IP 54 DB's, With provision for FP MCB/Isolator/RCCB/RCBO as, incomer and SP/TP MCB's as outgoing [IP 43 -IK 09 with metal door Make: Legrand/Havells or equivalent]-(For Lobby DB's) VTPN DB 4 way
S & F TPN DB-VTPN DPX³ 160A MCCB Double door DB's As per IEC 61439-3, Suitable for Flush Mounting and Surface Mounting, With 250 A Copper Busbar for each phase, With 2 Neutral bar, 2 Earthbar and Cable ties for Cable management, Fully insulated busbar & shrouded Neutral bars, Improved Pan assembly for ease of installation, Prefitted masking sheet, Reversible Door for IP 43 & IP 54 DB's,With provision for DPX³ 160 MCCB as incomer and SP/TP MCB's as outgoing [IP 4 -IK 09 with metal door Make: Legrand/Havells or equivalent]-(For each floor in Electrical Duct) VTPN DB 4 way
Supply and Installation of Smart Single Phase Meter with the following specifications: • AC Single Phase Two Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt 865-867 MHz Radio Frequency communication facility with self healing Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry. • Meter Should support the following data : 30 min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, 30 load survey data for energy, monthly billing survey for Cumulative Energy and Max Demand • Meter should have connect / disconnect functionality operable from prepaid billing software • The meter should support open communication protocol DLMS with the software MAKE: Secure, L&T, Schneider
Supply and Configuration of the Web based Software with following modules: (i) Meter Data Management Module The meter data management module would be responsible for collecting the data from the concentrator and make the data available to the billing system. The meter data management system would capture and provide the following data: (a) 30 min instantaneous data from all the meters for seven parameters – Cumulative Energy, Cumulative Apparent Energy (as applicable), Power, Current, Voltage, Power Factor and Frequency (b) Monthly billing survey data for cum energy and max demand (ii) Postpaid /Prepaid Billing Module The billing module would collect the data from the meter data management module, calculate the energy consumption, calculate billing determinant and make energy data / billing data available to admin and end users. The billing module would include functionalities for tariff setup, bill format setup, bill adjustment, occupation billing and vacation billing. It would allow postpaid and prepaid functionality as required.
(iii) Occupation and Vacation Module The system would support occupation / vacation and billing reports. the software would be collecting data from DCU. The software would provide access to staff as well as the occupant for the data. (iv) Web site: There would be a dedicated website for the AGE and BSO team to view all the data and information. The designated users in MES would have the admin access to the application. The MES staff would also have the access of the key information on an android mobiles app (for admin use). (v) Customer Portal The system would include a customer portal for the resident /occupant to log in and view their own energy / billing data. There would be android and iOS mobile apps for the user to monitor its own data and balance on regular basis.
(vi) Energy Accounting Module The system would include features of energy accounting. The system would be able to account for total energy block wise, facility wise and would also allow calculations of unaccounted energy in case total energy meter is also available. (vii) Communication Module The system would provide communication of energy data and bills via print, email and SMS methods. (viii) Meter Master Data The system would support meter master data repository. The system would support meter replacement process. (ix) Excel Export The system would support export of metering and billing data in excel format.
Three year comprehensive maintenance including operating costs after two years of defect liability period. They would include the following items: (a) Monthly sim charges for the DCU. The contractor would ensure supply of appropriate SIMs to ensure necessary single availability. The contractor would change the sim or sim provider as required. In case of network issues, the contractor would liaison with the telecom service providers for necessary resolution. (b) Recurring SMS charges. The SMS would be issued for the payments alerts, low balance alerts and disconnection / connection alerts. (c) Software AMC. This would include necessary upgradations in the software such as support to the chrome browser changes, android version changes , iOS version changes. These changes happen on frequent basis and the software would support all the changes.
(d) Changes in the government tariff structure. The government tariff structure changes may require software upgrade. The same would be included in the AMC scope of work. (e) Remote server admin support - Ensuring adequate database back up, upgradations in the operating system, anti virus updates, database upgrade etc. (f) Reports Development - The additional reports as needed for the success of the project would be developed (g) Software installation on any alternate / backup server if required (h) The communication network monitoring and support (i) Configuration of the repaired / replaced hardware in the system (j) Trouble shooting and necessary actions to run the system as required. (k) Software bug fixing as and when required
S & F modular type 1 module RJ 11 telephone socket with shutter [Make: Legrand/Havells or equivalent]
Supplying & erecting 50 pairs x 0.5 mm dia PVC insulated armoured telephone cable 0.5 sq.mm PVC Sheathed solid tinned copper conductor cable laid in provided trench/ cable tray [Make: POLYCAB/Havells or equivalent]
Supplying & erecting 10 pairs x 0.5 mm dia PVC insulated armoured telephone cable 0.5 sq.mm PVC Sheathed solid tinned copper conductor cable laid in provided trench/ cable tray [Make: POLYCAB/Havells or equivalent]
S & F for 2 pair telephone cable having solid electrolytic annealed bare copper conductor of 0.5 mm nominal diameter with high density polyethylene insulation, paired, polyester taped, nylon rip cord and grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113 C including termination. [Make: POLYCAB/Havells or equivalent]
S & F 10 pair telephone distribution box with suitable S.S. frame for mounting tag module, Krone module and incorporated in 16 SWG MS box with proper lockable cover. The box should be fixed on wall with suitable fasteners including painting & earthing. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc [Make: POLYCAB/Havells/Delta or equivalent]
S & F 50 pair telephone distribution box with suitable S.S. frame for mounting tag module, Krone module and incorporated in 16 SWG MS box with proper lockable cover. The box should be fixed on wall with suitable fasteners including painting & earthing. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc [Make: DELTA or equivalent]
S & F modular type 1 module TV socket [Make:POLYCAB/Havells/Legrand or equivalent]
S & F for RG 11 co-axial cable having solid electrolytic grade annealed plain copper central conductor of 1.63 mm nominal diameter, gas injected physical polyethylene foam insulated, wrapped with aluminium mylar tape aluminium alloy wire braided, jelly flooded and PVC jacketed including termination. [Make:Polycab CO-X or equivalent]
S & F for RG 6 co-axial cable having solid electrolytic grade annealed plain copper central conductor of 1.02 mm nominal diameter, gas injected physical polyethylene foam insulated, wrapped with aluminium mylar tape aluminium alloy wire braided, jelly flooded and PVC jacketed including termination.[Make:Polycab CO-X or equivalent]
Supply & installation of 4-way Splitter box for TV cable termination including all necessary hardware, accessories, [Make: STAR or equivalent]
External Water Supply
WATER FEEDING LINE [From Fresh water Pump Room To Service Tank]
Supply and fix Foot Valve conforming to IS 4038 including all necessary GI fittings 100mm Dia
S & F of SS Vertical multistage pump. Each pump shall have TEFC 2900 RPM three phase electric motor, cast iron head, base plate SS Shaft/ Impeller/ Intermediate chamber. provided with mechanical seal, suitable for auto/ manual operation, with motors mounted on a single base frame, complete with all accessories, G.I. flanges, G.I. nut bolts, rubber gasket jointing, base plate, mounting channel frame, accessories and fittings, viz. mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring/rubber type mounting suitable for operation on 3- Phase, 415 V ± 10%, 50 Hz AC supply. etc complete and as directed and of the following capacities. (Domestic Treated Water inline pump from UG tank to OHT), 900 lpm capacity , 165 mtr head, 50HP.
Pump Panel Design, Supply, testing and commissioning of indoor type encoder with angle iron pedestal frame and including steel structure required for installation on cable trench , housing cubical type, free standing LT Panel confirming to IS 8683 AC 415 V 50 HZ 3 phase 4 wire made out of 2mm thick CRCA sheet steel, powder coated factory made, dust proof, vermin proof, index protection not less thanIP43 floor mounted front operated cubical, bus bar, internal wiring with suitable size PVC insulated copper conductor complete etc. all as directed and specified BUSBAR CHAMBER 250 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and full size Neutral Aluminium(Throughout the length) busbars with colour coded heat shrink sleeves supported on SMC type grip supports, 25 KA for 1 sec.
Supply, Installation, Testing and Commissioning of Float type Point Level Sensor with the following specifications; Type: Magnetic Magnet: Ring type Switch: Reed Switch (Epoxy sealed) Connecting Cable: Teflon Make: RECKTRONIC DEVICES AND SYSTEMS / TECHTROL / CRISTAL/UNIVERSAL
Supply & fixing on wall/ laying in trench 5 pair 0.5 mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable. (Make: POLYCAB/FINOLEX/RR CABLE)
Supply & fixing on wall/ laying in trench 4 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable. (Make: POLYCAB/FINOLEX/RR CABLE)
WATER FEEDING LINE [From Treated Water Pump Room To Service Tank]
S & F of Flushing Treated Water from UG tank to OHT, SS Vertical multistage centrifugal inline pump. Each pump shall have TEFC 2900RPM three phase electric motor, cast iron head, base plate SS Shaft/ Impeller/ Intermediate chamber. provided with mechanical seal, suitable for auto/ manual operation, with motors mounted on a single base frame, complete with all accessories, G.I. flanges, G.I. nut bolts, rubber gasket jointing, base plate, mounting channel frame, accessories and fittings, viz. mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring/rubber type mounting suitable for operation on 3- Phase, 415 V ± 10%, 50 Hz AC supply. etc etc complete and as directed and of the 500 lpm capacity , 161mtr head. 33 HP
1000Ltrs of Priming PVC Tank including all necessary GI fittings for Fresh& treated water pumps
M & L for 1.1 kV grade XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded aluminium compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete all as specified and directed by engineer-in-charge 4CX16 SQ.MM. CU ARM.XLPE CABLE
External Electrification
Supply, installation, testing and commissioning of silent DG Set, conforming to IS: 10002- 1981, complete with Diesel Engine of suitable BHP & AC Brushless SPDP alternator, conforming to IS: 13364- 1992, mounted on a common base frame & coupled through a flex disc complete with platform, control panel having meters, sound-proof canopy, etc. of capacity 625 kVA with inbuild AMF panel complete all as specified and directed. Make: Kirloskar, Crompton Greaves,Ashok Leyland,Mahindra
[a] Engine: 4/6 cylinder, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude, Inline fuel pump with class H electronic governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, 2X12 volt, 180 AH lead acid battery
[b] Alternator: Brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength Note : (a) The Alternator shall be of SPDP (b) The alternator follows IP-23,Class-H insulation (c) Confirming to IS-4722
[c] Control Panel: Manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish.
The control panel consists of the following parts:
[i] Controller: Aluminium bus bars with suitable capacity with incoming/outgoing terminals
[ii] Indicating lamps for ‘Load ON’ and ‘Set Running’
[iii] Instrument fuses duly wired and ferruled
[iv] MCCB 600 Amps of suitable rating with overload and short circuit protections
[d] Microprocessor based generator set monitoring and control system including an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics, LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, remote START-STOP
[e] Engine Metering: Oil pressure, engine temperature, starting battery voltage, engine running hours
[f] AC Alternator Metering: L-L voltage and L-N voltage, current (phase and total), kVA (phase and total) and frequency
[g] Engine Protection: Low lube oil pressure, high/low coolant temperature, battery over/under/weak volts, fail to crank/start, sensor failure, cranking lockout, low fuel level
[h] AC Alternator Protection: Over/under voltage, over/under frequency, loss of AC sensing.
[i] Data Logging: Engine hours, control hours and upto 5 recent fault codes
[j] Configurable glow plug control
[k] 24 V DC operation
[l] Silencer: Critical grade silencer suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB
[m] Mounting Arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads.
[n] Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning
(h) Civil works:- All civil works related to foundation, installation of panel and equipment & depth of foundation shall be minimum 300mm with ant vibration pads, or as recommended by manufacturers. Cable from DG set to AMF panel, AMF panel to main panel will be measured under relevant schedule. Note:-The fuel for final testing of 12 hours shall be supplied by the contractor and cost deemed to be included in the above offer. All other necessary equipments like resistance load strip heater of suitable capacity/rating and any other items required for final testing shall be provided by the contractor without any extra cost to department.
Supply and installation of copper wound transformer step down indoor type complete with standard fittings, HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:11171-2026 1000 KVA
Type Of cooling-Air Natural (AN)
Type-DRY TYPE ( CRT )
kVA Rating-1000KVA
Rated Voltage of Primary / Secondary-11000 / 433
Connection Primary / Secondary-Delta / Star
Rated Frequency-50 Hz
Installation-Indoor – IP 23
Class of Insulation-Class F
Conductor-Copper Nomex covered
Core-CRGO – M4 Silicon steel
Ambient-50ºC
Temperature Rise by Winding Resistance Method-90° C by winding resistance method
Over Load capacity-110% continuous
Number of phases-Three
Vector Group Reference-Dyn11
Duty-Continuous
Tap Switch-Off Circuit Tap Switch
Tapping-+7.5 % to -7.5 % in steps of 2.5 %
Terminals HV – Cable Box LV – Cable Box
Paint Shade-Epoxy Shade 631 of IS 5
Applicable standard-As per IS 11171 & 2026
NOTES:
The contractor shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs of the windings, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
Supply and installation of copper wound transformer step down indoor type complete with standard fittings, HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:11171-2026 630KVA
Type Of cooling-Air Natural (AN)
Type-DRY TYPE ( CRT )
kVA Rating-630KVA
Rated Voltage of Primary / Secondary-11000 / 433
Connection Primary / Secondary-Delta / Star
Rated Frequency-50 Hz
Installation-Indoor – IP 23
Class of Insulation-Class F
Conductor-Copper Nomex covered
Core-CRGO – M4 Silicon steel
Ambient-50ºC
Temperature Rise by Winding Resistance Method-90° C by winding resistance method
Over Load capacity-110% continuous
Number of phases-Three
Vector Group Reference-Dyn11
Duty-Continuous
Tap Switch-Off Circuit Tap Switch
Tapping-+7.5 % to -7.5 % in steps of 2.5 %
Terminals HV – Cable Box LV – Cable Box
Paint Shade-Epoxy Shade 631 of IS 5
Applicable standard-As per IS 11171 & 2026
NOTES:
The contractor shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs of the windings, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
S& F Mass Tech Bharat 2 wheeler charger,Input-10kW 3 Phase AC Voltage, Vehicles Served Simultaneously-3,Number of Plugs-3,Plug Type-IEC 60309 16AMP FEMALE, Plug Output Current-16AMP (Single Phase AC),Plug Output Voltage-180-260 Volt (Single Phase AC voltage),Authentication-QR Code and OTP,Power and Energy Monitoring-RS485 based electricity utility approved energy meter, Voltage Frequency-50/60 Hz, User Interface-6 Inch TFT LCD, mobile application, web application, Enclosure-IP 54, Exterior Materials- ABS Case, Regulatory Compliances CE, Weight-10 Kg (approx.), Mounting-Wall Mount/Pole Mounted optional, Under Voltage Limit-180V,Over Voltage Detection-260V, Earth Fault Detection- Yes, Ambient Temperature :-10°C to 55°C.
S & F Integration with Chargers & Payment Gateway, Online & Mobile App.
M & L for 1.1 kV grade aluminium conductor, XLPE insulated armoured cable conforming to IS 7098 (Part-1): 1988, having stranded aluminium compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination of complete all as specified and directed by engineer-in-charge for following sizes: 4 Core,10 SQ.MM. CU ARM.XLPE CABLE
All as per BOQ Sl Item no 22.072,but 4 Core, 6 SQ.MM. CU ARM.XLPE CABLE
Main Panel-1 Design, Supply, testing and commissioning of indoor type encoder with angle iron pedestal frame and including steel structure required for installation on cable trench , housing cubical type, free standing LT Panel confirming to IS 8683 AC 415 V 50 HZ 3 phase 4 wire made out of 2mm thick CRCA sheet steel, powder coated factory made, dust proof, vermin proof, index protection not less thanIP43 floor mounted front operated cubical, bus bar, internal wiring with suitable size PVC insulated copper conductor complete etc. all as directed and specified BUSBAR CHAMBER 2000 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and full size Neutral electrolytic grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.
APFC Panel(350KVAR) Supply, installation, commissioning and testing of Panel of suitable size, factory made, CPRI type tested, indoor cubical type, The capacitor bank shall be Internet of things (IoT) enabled and communicable/ integrable with BMS.The degree of protection of enclosures system of the APFC Panel shall be min. IP41 in accordance with IEC 60529 made out of 2 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of size 50 mm x 50 mm x 6 mm, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length size, including fixing lugs bolts, screws etc. all complete as specified and directed. Approved Makes- ABB / Schneider / Siemens make only. The OEM's specified cannot authorize any other partners / sub vendors to manufacture APFC Panels on their behalf.
OUTGOING 4 nos. 63 amps 3 pole MCCB suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 25 KA. 4 nos 25kVAr 415V 50Hz capacitor , 1 nos series 7% detuned reactor for harmonic filter,The reactors shall be of certified design confirming to IEC-60076 - 6 suitable size capacitor duty contactor, Contactor ON / OFF indicating lights with control MCB’s, Auto manual switch - 1 sets each. 3 nos. 100 amps 3 pole MCCB suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 25 KA. 3 nos 50kVAr 415V 50Hz capacitor , 1 nos series 7% detuned reactor for harmonic filter,The reactors shall be of certified design confirming to IEC-60076 - 6 suitable size capacitor duty contactor, Contactor ON / OFF indicating lights with control MCB’s, Auto manual switch - 1 sets each. 1 nos. 200 amps 3 pole MCCB suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 25 KA. 1 nos 100kVAr 415V 50Hz capacitor , 1 nos series 7% detuned reactor for harmonic filter,The reactors shall be of certified design confirming to IEC-60076 - 6 suitable size capacitor duty contactor, Contactor ON / OFF indicating lights with control MCB’s, Auto manual switch - 1 sets each. In addition to the PF Controller, the capacitor bank, should also have an energy server which would collect, store, and provides web access and visualization to various energy parameters and enable remote supervision from BMS.
To ensure maximum utilization, enable remote commissioning / trouble shooting of the capacitor bank, the energy server should monitor and display the following parameters remotely through a Web Page.- Status of stages (open / close / faulty).
Main Panel-2 Design, Supply, testing and commissioning of indoor type encloser, CPRI approved with angle iron pedestal frame and including steel structure required for installation on cable trench , housing cubical type, free standing LT Panel confirming to IS 8683 AC 415 V 50 HZ 3 phase 4 wire made out of 2mm thick CRCA sheet steel, powder coated factory made, dust proof, vermin proof, index protection not less thanIP43 floor mounted front operated cubical, bus bar, internal wiring with suitable size PVC insulated copper conductor complete etc. all as directed and specified (installed for 630 KVA TR Main panel)” (installed for 750KVA TR main panel) BUSBAR CHAMBER : 1600 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and full size Neutral Aluminium (Throughout the length) busbars with colour coded heat shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.
d) 250 amps 4 pole MCCB with TM based release for complete LSIG protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 36 KA. The MCCB shall be complete as per technical specifications -2 nos.
APFC Panel(250KVAR) Supply, installation, commissioning and testing of Panel of suitable size, factory made, CPRI type tested, indoor cubical type, The capacitor bank shall be Internet of things (IoT) enabled and communicable/ integrable with BMS.The degree of protection of enclosures system of the APFC Panel shall be min. IP41 in accordance with IEC 60529 made out of 2 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of size 50 mm x 50 mm x 6 mm, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length size, including fixing lugs bolts, screws etc. all complete as specified and directed. Approved Makes- ABB / Schneider / Siemens make only. The OEM's specified cannot authorize any other partners / sub vendors to manufacture APFC Panels on their behalf. The APFC Panel manufactured by OEM's only will be accepted & factory acceptance test ( FAT ) will be carried out at OEM's plant only.
OUTGOING 2 nos. 63 amps 3 pole MCCB suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 25 KA. 02 nos 25kVAR 415V 50Hz capacitor , 1 nos series 7% detuned reactor for harmonic filter,The reactors shall be of certified design confirming to IEC-60076 - 6 suitable size capacitor duty contactor, Contactor ON / OFF indicating lights with control MCB’s, Auto manual switch - 1 sets each. 4 nos. 100 amps 3 pole MCCB suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 25 KA. 4 nos 50kVAR 415V 50Hz capacitor , 1 nos series 7% detuned reactor for harmonic filter,The reactors shall be of certified design confirming to IEC-60076 - 6 suitable size capacitor duty contactor, Contactor ON / OFF indicating lights with control MCB’s, Auto manual switch - 1 sets each. In addition to the PF Controller, the capacitor bank, should also have an energy server which would collect, store, and provides web access and visualization to various energy parameters and enable remote supervision from BMS. To ensure maximum utilization, enable remote commissioning / trouble shooting of the capacitor bank, the energy server should monitor and display the following parameters remotely through a Web Page.- Status of stages (open / close / faulty).
Common Area Service Panel Design, Supply, testing and commissioning of indoor type encloser, CPRI approved with angle iron pedestal frame and including steel structure required for installation on cable trench , housing cubical type, free standing LT Panel confirming to IS 8683 AC 415 V 50 HZ 3 phase 4 wire made out of 2mm thick CRCA sheet steel, powder coated factory made, dust proof, vermin proof, index protection not less thanIP43 floor mounted front operated cubical, bus bar, internal wiring with suitable size PVC insulated copper conductor complete etc. all as directed and specified BUSBAR CHAMBER 760 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and full size Neutral Aluminium (Throughout the length) busbars with colour coded heat shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.supports, 25 KA for 1 sec.
OUTGOING 9 nos. 32 amps 4 pole MCB suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 10 KA. The MCCB shall be complete as per technical specification. 1 nos. 40 amps 4 pole MCB suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 10 KA. The MCCB shall be complete as per technical specification. 1 nos. 63 amps 4 pole MCB suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 16KA. The MCCB shall be complete as per technical specification. 2 nos. 40 amps 4 pole MCCB with TM based release for complete LSIG protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 25 KA. The MCCB shall be complete as per technical specifications. 1 nos. 80 amps 4 pole MCCB with TM based release for complete LSIG protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 25 KA. The MCCB shall be complete as per technical specifications. 1 nos. 100 amps 4 pole MCCB with TM based release for complete LSIG protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 25 KA. The MCCB shall be complete as per technical specifications. 1 nos. 150 amps 4 pole MCCB with TM based release for complete LSIG protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 25 KA. The MCCB shall be complete as per technical specifications.
Lift Panel Design, Supply, testing and commissioning of indoor type encloser, CPRI approved with angle iron pedestal frame and including steel structure required for installation on cable trench , housing cubical type, free standing LT Panel confirming to IS 8683 AC 415 V 50 HZ 3 phase 4 wire made out of 2mm thick CRCA sheet steel, powder coated factory made, dust proof, vermin proof, index protection not less thanIP43 floor mounted front operated cubical, bus bar, internal wiring with suitable size PVC insulated copper conductor complete etc. all as directed and specified BUSBAR CHAMBER 250 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and full size Neutral Aluminium (Throughout the length) busbars with colour coded heat shrink sleeves supported on SMC type grip supports, 25 KA for 1 sec.
Pressurization Panel Design, Supply, testing and commissioning of indoor type encloser, CPRI approved with angle iron pedestal frame and including steel structure required for installation on cable trench , housing cubical type, free standing LT Panel confirming to IS 8683 AC 415 V 50 HZ 3 phase 4 wire made out of 2mm thick CRCA sheet steel, powder coated factory made, dust proof, vermin proof, index protection not less thanIP43 floor mounted front operated cubical, bus bar, internal wiring with suitable size PVC insulated copper conductor complete etc. all as directed and specified BUSBAR CHAMBER 100 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and full size Neutral Aluminium (Throughout the length) busbars with colour coded heat shrink sleeves supported on SMC type grip supports, 25 KA for 1 sec.
Car Charging Panel Design, Supply, testing and commissioning of indoor type encloser, CPRI approved with angle iron pedestal frame and including steel structure required for installation on cable trench , housing cubical type, free standing LT Panel confirming to IS 8683 AC 415 V 50 HZ 3 phase 4 wire made out of 2mm thick CRCA sheet steel, powder coated factory made, dust proof, vermin proof, index protection not less thanIP43 floor mounted front operated cubical, bus bar, internal wiring with suitable size PVC insulated copper conductor complete etc. all as directed and specified BUSBAR CHAMBER 250Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and full size Neutral Aluminium (Throughout the length) busbars with colour coded heat shrink sleeves supported on SMC type grip supports, 25 KA for 1 sec.
S & F VERA BOLLARD with ROUND TOP,MODEL NAME: 5565*,MOUNTING: FLOOR MOUNT,WATTAGE: 16 W LED, Height : 900 mm., Make: K-LITE or equivalent
S & F TOP POST, MODEL NAME: 4922, MOUNTING: POLE MOUNT, WATTAGE: 50W LED, Make: K-LITE and S & F POST, MODEL NAME: QUADRA, MOUNTING: POLE MOUNT, HEIGHT : 3.6 mts, Make: K-LITE or equivalent
S & F TREE UPLIGHTER , MODEL NAME: 7052 , MOUNTING: FLOOR MOUNT\ WATTAGE: 7 W, Make: K-LITE or equivalent
S & F PATH FINDERS, MODEL NAME: 2741, MOUNTING: WALL MOUNT, WATTAGE: 12 W LED, Make: K-LITE or equivalent
S & F WALL WASHER LIGHT, MODEL NAME: 7897, MOUNTING: WALL MOUNT, WATTAGE: 6 W LED, SIZE: 145X100X250, Make: K-LITE or equivalent
S & F DESCRIPTION: POST TOP LUMINARIES, MODEL NAME: 7034, MOUNTING: FLOOR MOUNT WATTAGE: 60 W LED, SIZE - Ø600 x 2655, Make: K-LITE or equivalent
S & F FLOOD LIGHT, MODEL NAME: 6420, MOUNTING: WALL MOUNT, WATTAGE: 60W LED, SIZE - 347 x 135 x 180mm , Make: K-LITE or equivalent
S & F FLOOD LIGHT, MODEL NAME: 6420, MOUNTING: WALL MOUNT, WATTAGE: 60W LED, SIZE - 347 x 135 x 180mm , Make: K-LITE or equivalent
Supply, installation, testing and commissioning of sandwich type (3P4W,100%N), busbar trunking system complete with two runs of 25 mm X 3mm aluminium earthing strip and accessories all as specified and directed. Make: L&T/Schneider/ ABB/ Siemens The busbar trunking system shall conform to the following technical specifications: i] System details : The Busbar Trunking System shall be suitable for operational Voltage of 415V / 690V / 1000V with supply frequency of 50Hz / 60Hz, minimum insulation voltage of 1100V & impulse withstand voltage of 8kV & higher.
ii]Standards : The Busbar Trunking System shall be designed to comply in accordance with the following international standards, IEC 61439 – Part 1 : Low voltage switchgear & control gear assembly- General rules IEC 61439 – Part 6 : Busbar Trunking Systems (busways) IEC 60529 : Degree of protection IS 8623 – Part 2 : Specification for Low Voltage Switchgear & Control gear Assemblies IS 1893 – Part 1 : Criteria for Earthquake Resistant Design of Structures IEEE 693:2005 : High Seismic Qualification Level Wherever required and specified, the Busbar Trunking System shall conform to Fire Rating of 600 deg C for 2 Hours. Busbar Trunking System should also have Seismic Zone-5, Flame Propagation and Fire Resistance certification.
iii]General : The Busbar Trunking System shall be of sandwich construction, non-ventilated and natural cooled design. It shall be possible to mount the Busbar Trunking System in any orientation without affecting the current rating. iv]Busbars : 1] The busbars should be made of high conductivity electrical grade Aluminium (>60% IACS) 2] Purity of Aluminium conductor should not be less than 99.6% 3] Aluminium busbars should be Tin plated at the joint area to avoid oxidation 4] Where an earth conductor is required, it shall be possible to provide internal earth conductor of the same high conductivity material as the phase conductors and at least of 50% cross section of the phase conductor. Provision for mounting external earth strip to be provided on both side of busduct if required. 5] It should be possible to provide a 200% Neutral where specified in BOQ
v] Insulation : 1] Each bus bar shall be individually insulated by means of Class-F Insulation, if it is multilayer insulation then each layer must have temperature withstand capacity of 155 deg C (Class-F) as well as breakdown voltage of minimum 6kV. 2] Mica insulation is not allowed which can’t be wrapped completely on conductor edges 3] The insulation should be UL certified 4] Insulation must be Halogen free & RoHS compliance
vi] Housing : 1] The housing shall be made with 1.6mm thick electro-galvanized sheet steel of superior grade with Epoxy powder coating to withstand stringent site conditions; e.g. Humid, Costal, Acidic, etc 2] Enclosure must be dust & vermin proof and Provision for mounting external earth strip should be available on Busduct. 3] IP rating of indoor busduct must be IP-54 / IP-55 & Outdoor busduct should be IP-65 / IP-66 plus canopy should be provided for protection of Busduct from direct sunlight & heavy rains. 4] Enclosure must be powder coated from both sides (internal & external)
vii] Joints : 1] The joint design shall have inbuilt provision of absorbing expansion & contraction of 12mm per joint during operation. 2] The joint insulation must be of single piece molded design of thermoset material for longer life and higher temperature withstand & better insulation property. 3] The joint construction must allow +/- 3mm adjustment at the time of installation, for ease of adjusting to site measurement variations. 4] Stopper arrangement must be provided at every joint to prevent excessive insertion of conductors while jointing 5] The joint bolt must be insulated with a bolt insulator. The bolt insulator must be of molded one piece. 6] The joint design shall have inbuilt provision to prevent excessive insertion of busduct which can damage the bolt insulator. 7] The busbar ends shall not have holes or slots at the joints to avoid reduction in cross section area which will lead to temperature increase. The electrical continuity shall be through pressure plates, achieving a high contact area of joint cross section and expansion capability. 8] It shall be possible to install and remove the joints without disturbing the adjacent feeder section 9] Joint set should have insulators with temperature withstand capacity of class-F
viii] Plug-in Unit / Tap off units : 1] Plug-in Units must be type teste d design from NABL accredited laboratory for tests like, Thermal cycling test, Temperature rise test, Short time withstand voltage, Mechanical operations, Impulse withstand voltage, Clearance & Creepage, Mechanical impact and ingress protection test 2] Plug-in unit must achieve IP-54 protection & IK10 mechanical impact 3] Plug-in Units must have interlocks with Busduct, door and MCCB for human safety 4] Busduct interlock – a) When the MCCB in the Plug-in unit is in ‘ON’ position, the operator should not be able to open the door. b) MCCB can’t be switched ON even when Plug-in Box is mounted on Busduct; it is possible only if interlock plate is engaged with feeder 5] Door interlock – a) Door can’t be opened when MCCB is ON b) MCCB can’t be switched ON until door is completely closed c) Door defeat feature should be available to use in case of emergency 6] The design of plug-in units shall be such that, the Earth conductor shall be of ‘First-Make’ ‘Last-Break ’type.
7] It should be possible to mount Plug-in Unit even when Busduct is in live condition but while insertion MCCB must be in OFF condition 8] The Plug-in unit will be suitable for accommodating MCCBs or other accessories, as required. The Plug-in unit should allow the flexibility of accommodating different reputed MCCB makes, to be mutually agreed depending on the tender requirements. 9] Plug-in Unit must be operated using side handle without MCCB ROM, and provision of Padlocking must be provided for human safety 10] Plug-in Unit must have Lifting provision for ease of handling and Guide pin for ease of installation 11] LED indicator must be provided on Plug-in Unit door which will glow once MCCB is switched ON 12] Plug-in units should be plug-in type up to 400A & Bolt-on Type from 630A 13] It should be possible to offer Bolt-on Type Tap-off Box for 100A & higher ratings to withstand vibration due to crane movement, heavy machines in industries
ix] Testing : 1] The busduct shall be type tested at a reputed test laboratory (certified by ASTA or ERDA) for the tests as per IEC-61439 Part-1 (Low voltage switchgear & control gear assembly- General rules) & Part 6 (Bus bar trunking systems & bus ways) 2] Short circuit testing of busduct should be for duration of 1 Sec. Neutral & Earth conductor should also be tested for 60% short circuit rating of phase conductor 3] Degree of ingress protection (IP rating) shall also be tested at any reputed independent laboratory as per IEC-60529 4] Busduct tested for maximum severe Seismic condition of Zone-5 as per IS 1893-2002 and High Seismic Qualification Level as per IEEE 693-2005. Seismic testing done in severe most combination and orientation (Horizontal + Vertical installation along with Plug-in box in live condition)
Supply of 415V/690V/1000V Sandwich construction Busbar trunking system with Multilayer Class-F insulation and; Conductors : Aluminium Rating : 2000A Configuration : 3P4W IP Rating : IP54 Enclosure : GI 1.6mm thickness Impulse Withstand Voltage : 8kV Paint Shade : RAL7032 Epoxy Powder Coating
Straight Run Feeder IP54
Flange End (fabrication cost only)
Horizontal Bend/Vertical Bend (fabrication cost only)
Reducer (fabrication cost only) 2000 to 1600 & 2000 to 1250
Plug-in Point (fabrication cost only)
Vertical Spring Hanger/Fix hanger (1 No per Floors per Riser)
Tinned Copper Braided Flexibles -360mm (with Hardware - Nuts and Bolts)
GI Earthing Strip - 25x3 ( with Hardware - Nots and Bolts )
Shaft Cantilever angle support with C Channel for Vertical spring or Rigid hangers
End feed Panel without switchgear ( Suitable forACB ) - Al Busbar Arrangement
Complete with Aluminium busbar or Cu Flexible with provision for rotary handle mechanism with bottom Cable entry and top Busduct outgoing provision. 2000 Amp 4P 50kA MDO MTX 1.5G for EFU
Supply of 415V/690V/1000V Sandwich construction Busbar trunking system with Multilayer Class-F insulation and; Conductors : Aluminium Rating : 1600A Configuration : 3P4W IP Rating : IP54 Enclosure : GI 1.6mm thickness Impulse Withstand Voltage : 8kV Paint Shade : RAL7032 Epoxy Powder Coating
Straight Run Feeder IP54
Plug-in Point (fabrication cost only)
Vertical Spring Hanger/Fix hanger (1 No per Floors per Riser)
Reducer (fabrication cost only) 1600 to 1250A
GI Earthing Strip - 25x3 ( with Hardware - Nots and Bolts )
Shaft Cantilever angle support with C Channel for Vertical spring or Rigid hangers
Supply of 415V/690V/1000V Sandwich construction Busbar trunking system with Multilayer Class-F insulation and; Conductors : Aluminium Rating : 1250A Configuration : 3P4W IP Rating : IP54 Enclosure : GI 1.6mm thickness Impulse Withstand Voltage : 8kV Paint Shade : RAL7032 Epoxy Powder Coating
Straight Run Feeder IP54
Plug-in Point (fabrication cost only)
Vertical Spring Hanger/Fix hanger (1 No per Floors per Riser)
Reducer (fabrication cost only)- 1250 to 800A
GI Earthing Strip - 25x3 ( with Hardware - Nots and Bolts )
Shaft Cantilever angle support with C Channel for Vertical spring or Rigid hangers
Supply of 415V/690V/1000V Sandwich construction Busbar trunking system with Multilayer Class-F insulation and; Conductors : Aluminium Rating : 800A Configuration : 3P4W IP Rating : IP54 Enclosure : GI 1.6mm thickness Impulse Withstand Voltage : 8kV Paint Shade : RAL7032 Epoxy Powder Coating
Straight Run Feeder IP54
Plug-in Point (fabrication cost only)
Vertical Spring Hanger/Fix hanger (1 No per Floors per Riser)
Reducer (fabrication cost only)- 800 to 250
GI Earthing Strip - 25x3 ( with Hardware - Nots and Bolts )
Shaft Cantilever angle support with C Channel for Vertical spring or Rigid hangers
Supply of 415V/690V/1000V Sandwich construction Busbar trunking system with Multilayer Class-F insulation and; Conductors : Aluminium Rating : 250A Configuration : 3P4W IP Rating : IP54 Enclosure : GI 1.6mm thickness Impulse Withstand Voltage : 8kV Paint Shade : RAL7032 Epoxy Powder Coating
Straight Run Feeder IP54
Plug-in Point (fabrication cost only)
Vertical Spring Hanger/Fix hanger (1 No per Floors per Riser)
End Cover
GI Earthing Strip - 25x3 ( with Hardware - Nots and Bolts )
Shaft Cantilever angle support with C Channel for Vertical spring or Rigid hangers
Plug-in Box with Mechanical Interlocking suitable for L&T MCCB but without Switchgear (standard size) 16A -100A
MCCB for PIB 63 Amp 4P 50kA TM MCCB Make: L&T or equivalent
TOOL KIT
S & F 70 Watt LED streetlight having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of > 100 lm/W, integral SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS 15885 (Part- 2/Sec- 13): 2012, IP 66 protection, polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm, including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket having 40 mm diameter light grade GI pipe, nuts, bolts, washers, GI clamps with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by engineer- in- charge. 70W [Make: BAJAJ, Philips, Havells or equivalent]
M & L for hot dipped galvanized iron octagonal pole of 6 mtr height, minimum galvanizing of 70 micron, top -70mm dia , bottom 130 mm dia and 3 mm sheet thickness in single section with joints with box plate of minimum dimensions 200mm x200mmx 12mm , foundation bolts, single area GI bracket of 900-1000 mm for mounting the light fitting at an angle of 120°,Bakelite sheet with one 6A SP MCB and 16 mm stud type connector (4 Nos) inside the pole at door opening for cable connection, common templates minimum 1 for each 15 poles, all fixed and bolted on suitable PCC pedestal as per manufactures recommendation & specifications and all as directed. Make of poles shall be Bajaj/ Crompton/ Subham/Jindal.
S & F weather- proof PVC junction box of size 250 mm x 200 mm x 100 mm, having IP 65 protection for outdoor installation fixed with 4 way Bakelite cable terminals including 03 Nos. of polymide gland with check nuts fixed on poles with flat aluminium clamps of size 20 mm x 3 mm, nuts, bolts, washers, etc. complete all as specified and as directed by engineer- in- charge. Make: Sintex, Hensel, HPL
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine suitable for 200mm Dia pipe
Fire Fighting System
HYDRANT SYSTEM
Supplying,Installing,Testing and Commissioning of cast iron double flange butterfly valve of approved make
a) 250 mm dia.
Supply,Installation,Testing and Commissioning of double flange Ball type NRV
a) 200 mm dia.
b) 150 mm dia.
c) 80 mm dia.
M & L for PN 1.6 rated CI 'Y' -type strainer for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps all complete as specified and directed.
a) 250 mm dia.
b) 80 mm dia.
S & F of orifice plate made out of 6 mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete all as specified and directed by engineer-in-charge. Make: Newage, AAAG, Minimax
Supply and fix branch pipe with nozzle of 20 mm dia for hose reel conforming to IS 8090
Supply and fix Automatic air release valve 50mm dia suitable for domestic water with 50mm gun metal stop valve complete
Providing & Fixing standard Fireman's axe with heavy insulation rubber handle conforming to IS:926 complete.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1.1 Kv grade with stranded conductor:4CX16 SQ.MM. CU ARM.XLPE CABLE
FIRE PUMPS
Fire Remote Panel Start/Stop push button (for each pump),Auto manual switch (for each pump) & on-off indicator (for each pump) for main fire Hydrant pump, main fire Sprinkler pump, Diesel engine driven pump, Hydrant & Sprinkler jockey pump
Supply,Installation,Testing, perfect aligning and proper levelling and commissioning of fire service main Fire Hydrant multistage multioutlet pump, of 2850 LPM (Litres/min.) at 200m/118m head centrifugal type, 215 HP,(160 kW) or of suitable HP,the pump shall be of cast iron construction with bronze impeller, stainless steel shaft, flexible coupling and gland packing seal and the complete unit shall be mounted on a common structural steel base frame and shall include accessories such as foundation bolts, casing relief valve, pressure relief valve,Suitable cement concrete foundation duly plastered with anti vibration pads etc complete with all accessories as specified and directed by engineer-in-charge.
NOTES:
[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.
[ii] The shut-off head shall not exceed 120% of rated head.
[iii] The coupling guard shall be of zero access type.
Make: PEW,Kirloskar, Mather & Platt, Crompton Greaves
Supply,Installation,Testing, perfect aligning and proper levelling and commissioning of fire service main Fire Sprinkler multistage multioutlet pump, of 2850 LPM (Litres/min.) at 200m/118m head centrifugal type, 215 HP,(160 kW) or of suitable HP,the pump shall be of cast iron construction with bronze impeller, stainless steel shaft, flexible coupling and gland packing seal and the complete unit shall be mounted on a common structural steel base frame and shall include accessories such as foundation bolts, casing relief valve, pressure relief valve,Suitable cement concrete foundation duly plastered with anti vibration pads etc complete with all accessories as specified and directed by engineer-in-charge.
NOTES:
[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.
[ii] The shut-off head shall not exceed 120% of rated head.
[iii] The coupling guard shall be of zero access type.
Make: PEW,Kirloskar, Mather & Platt, Crompton Greaves
Supply,Installation,Testing, perfect aligning and proper levelling and commissioning of Jockey multistage multioutlet pump for Hydrant & Sprinkler of 180 LPM at 200m/118m head, 3 ph. 415 A.C.20 HP, (15 kW) or of suitable HP with suitable Stages ,the pump shall be of cast iron construction with bronze impeller, stainless steel shaft, flexible coupling and gland packing seal ,the complete unit shall be mounted on a common structural steel base frame and shall include accessories such as foundation bolts, casing relief valve, pressure relief valve,Suitable cement concrete foundation duly plastered with anti vibration pads. etc complete with all accessories as specified and directed by engineer-in-charge.
NOTES:
[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.
[ii] The shut-off head shall not exceed 120% of rated head.
[iii] The coupling guard shall be of zero access type.
Make: PEW,Kirloskar, Mather & Platt, Crompton Greaves
Supply,Installation,Testing, perfect aligning and proper levelling and commissioning of Radiator cooled 4 stroke, engine speed of 1500 RPM, Diesel engine driven pumping set of horizontal, centrifugal, single stage fire pump having cast iron body, bronze impeller, stainless steel shaft & capable of delivering 2850 LPM against a total head of 200m complete with all accessories, Suitable cement concrete foundation duly plastered with anti vibration pads. as specified and directed by engineer-in-charge.
NOTES:
[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.
[ii] The shut-off head shall not exceed 120% of rated head.
[iii] The coupling guard shall be of zero access type.
Make: PEW,Kirloskar, Mather & Platt, Crompton Greaves
Supply and Installation of Non clog vertical submersible pumps with chrome steel impeller, non-clog to pass 40 mm size particles including Supply, installation with guide rail and lifting chain, cables, Earthing, testing complete with 2 years maintenance. Duty (Flow and head) lpm x m- 100x25, 1 HP (Pump room sump pump) complete with all accessories as specified and directed by engineer-in-charge.
CONTROL PANEL FOR FIRE PUMPS
Fire Pump Panel Design, Supply, testing and commissioning of indoor type encloser, CPRI approved with angle iron pedestal frame and including steel structure required for installation on cable trench , housing cubical type, free standing LT Panel confirming to IS 8683 AC 415 V 50 HZ 3 phase 4 wire made out of 2mm thick CRCA sheet steel, powder coated factory made, dust proof, vermin proof, index protection not less thanIP43 floor mounted front operated cubical, bus bar, internal wiring with suitable size PVC insulated copper conductor complete etc. all as directed and specified BUSBAR CHAMBER 1000 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and full size Neutral Aluminium (Throughout the length) bus bars with colour coded heat shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.
FIRE ALARM & PUBLIC ADDRESS
FAVA SYSTEM
Supply, installation, testing & commissioning of Microprocessor based 10-loop panel, True Peer-to-Peer Networkable Addressable Integrated Main Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 event plus 1000 alarm log history events, QWERTY keypad for programming. The panel shall have degrade mode. The panel should be equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 300 analog addressable devices. The panel shall work in degrade mode in case of CPU failure. Four access levels, flash EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. The panel shall be complete with Integrated 8 channel Digital Voice Evacuation System Controller capable of broadcasting Evacuation Messages on same peer-to-peer Network and Fire Fighters Telephone TWO way Communication System capable of supervising all the speaker circuits with adequate zone control and accessories. Failure of fire alarm CPU shall not result in failure of voice alarm controller. Note: The fire alarm panel shall be serviceable by any system integrator Approvals : UL listed & FM Approved Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Repeater Panel with minimum 640 character LCD display with control keypad Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Graphics User Interface for Monitoring & Control of complete Fire, Voice Evacuation & Telephone Talkback System. The GUI based main network software shall network with other panels on True Peer-to-Peer network. It shall be capable of graphically representing each facility being monitored with floor plans and icons depicting the actual locations of the various systems, and / or sensors’ locations. It shall have the facility to change the sensitivity of any detector. The software shall be capable of monitoring 200 Nodes with 100 MB baud Transmission rate on Fibre Optics Network and 12 MB baud Transmission on cable and 2,50,000 network points. The software shall provide the facility to Monitor, Control all the Digital PAVA as well as 2 way communication from main control room using voice signals over Fire Network along with the Fire detection signal. The Graphic workstation shall act as an independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for operation. Failure of Fire Panel CPU shall not result in failure of GUI. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Workstation for GUI Processor • Intel® 6th generation Core™ i5 Operating System • Windows 10 Pro 64-bit Memory2 • Up to 2 DIMM slots Non-ECC dual-channel 2133 MHz or more DDR4 SDRAM – 8 GB • Monitor – Standard VGA Monitor 22 inch or more with 4:3 and/or 16:9 aspect ratio and with minimum screen resolution capability of 1920 X 1320. Ports • Minimum 1 Standard PCI Slot • Bays, 2 internal 2.5” Keyboard, Mouse with Multimedia functionality Cabinet Size Large Cabinet tower model / horizontal with 6 inch or more cabinet thickness. Smaller cabinet profiles will not work. Connectivity • Integrated Intel® I219-LM Ethernet LAN 10/100/1000 Should Support optional wireless M.2 802.11ac + Bluetooth 4.1 Power Approved Makes: HP/DELL/LENOVO
Supply, installation, testing & commissioning of MODBUS Interface Gateway for communication with BMS / Other Utilities. MODBUS shall support 22500 data points. MODBUS Gateway shall act as an independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for operation. Failure of Fire Panel CPU shall not result in failure of MODBUS Gateway. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Addressable Photoelectric Smoke Detector with sensitivity range of 0.5 to 4.0% obs/ft. The detector shall have multi co-operative sensing technology for faster response & avoid false alarms. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Designed to meet UL268, 7th Edition Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Addressable Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 4.0% obs/ft. The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Designed to meet UL268, 7th Edition Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Multi sensor Heat/Gas Detector in Kitchen with necessary power supply & interface module to integrate with fire alarm system. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Addressable Manual Call Point ( Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Sounder cum Strobe rated at 75 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder/System Sensor
Supply, installation, testing & commissioning of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes/Directional Sounder. The control module shall provide supervised NAC output rated at 24VDC, 2A at resistive load. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Addressable Relay Module for Third Party Outputs. The relay module shall provide DPDTcontact rated at 24V DC, 2A at resistive load. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Addressable Monitor Module for Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of 24VDC power supply unit for sounder cum strobes. The unit shall have in built battery charger & sufficient back of 24 hours in stand by & 30 mins in alarm condition. The power supply unit shall be monitored by fire alarm panel. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Addressable Fire Fighter's Telephone Jack with suitable interface module for two way communication between Remote Fire Fighter & Fire Command Center Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, testing & commissioning of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
Supply, installation, Testing and commissioning of 2C X 1.5 sqmm fire survival circuit integrity unarmoured cable of 300/500v rated with class 2 annealed copper conductor /N having cross linkable ceramified silicon insulation as per BSEN 50363 along with drain ire, Aluminium tape screening and LSZH to BS 7629-1 outer sheath should meet fire performance circuit integrity test as per BS EN 50200 and BS 6387 CWZ (950 drg C for 3 hours) Outer sheath should be red colour. Cable shall be laid in concealed conduit. Make: Polycab/Finolex/RR cables.(For Fire Alarm System)
Supply and fixing Rigid non- metallic concealed PVC conduit of 25 mm size exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hook etc.
VOICE ALARM SYSTEM EQUIPMENT
S& F 480W power Amplifier for high power speakers. Failure of Fire Panel CPU shall not result in failure of Amplifier operation. The sufficient size of PA rack shall be considered to mount power amplifiers. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder/Honeywell
S& F 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling Mount Speakers. The speakers shall be of same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
S& F 10W Multi-Tap (5W; 10W), Wall Mount speakers. The speaker shall be compatible with supplied Amplifiers and shall work on 70.7Vrms. Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder/Honeywell
S& F PA Rack for Power Amplifiers. (Contractor shall furnish the size of rack as per amplifier qty.)
Supply, installation of 2C 1.5sq.mm. twisted armoured FRLS Copper cable with necessary mounting accessories. Approved Makes: Finolex/Polycab/RR-Kabel
PRESSURIZATION SYSTEM
Supply, installation, testing & commissioning of Cabinet type
a) 10000 CFM @ 50 MMWG
b) 7000 CFM @ 50 MMWG
Supply, installation and testing of GI Ducting
Supply, fabrication, installation and testing the flexible connections constructed of fire resistant resin double sleeve as per the approved shop drawings.
Supply of powder coated grill with damper size--600 X 450mm
S& F Powder coated with On/Off indication lamp panel isolator & 2.5 RM power cable
a) 10000 CFM @ 50 MMWG
b) 7000 CFM @ 50 MMWG
MS FABRICATION WORK FOR SUPPORTING
LIGHTNING PROTECTION
Supply, Installation, Testing and Commissioning of 1 metre Vertical Aluminium Air terminal of dia 15mm to meet the requirement of IS/IEC 62305.Tested for Electrical, Mechanical, Environmental test and should have Impulse current withstand capability of 100KA (Class H)and as per IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of Aluminium Square Tape Clamp for Cross connection and T connection of 25x3mm Aluminium Tape should be tested for electrical resistivity test ,Environmental Test (salt spray & humidity test),Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of U bolt rebar to Cable Clamp should be tested for Environmental Test (salt spray & humidity test),Contact resistance test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of 50sq mm Green/Yellow PVC insulated Copper cable with terminal Lug, should have Each stranded of 1.7 mm diameter as per requirements of IS/IEC 62305 and IEC 62561-2:2012.
Supply, Installation, Testing and Commissioning of Bi-metallic Connector should be tested for Environmental Test (salt spray & humidity test), Contact resistance test ,Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of Moisture inhibiting compound to meet the requirements of IS/IEC 62305.
Supply, Installation, Testing and Commissioning of Test link should be tested for Environmental Test (salt spray & humidity test),Contact resistance test, Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of maintenance free Earthing system comprising of 250micron copper bonded earth rod 3 mtr x 3/4" Dia long Earth electrode, inspection pit with polymer lid is load rated to 5000kg and suitable for general to heavy duty, copper rod to tape clamp and 25Kg of Earth Enhancing compound whose resistivity is less than 0.12 as per IEEE 80-2013 & IS 3043-2018 for normal soil condition . The compound shall be free from carbon and graphite and conductive in nature and should accommodate 60% of its volume. The rod should be threaded on both ends and all component should be tested as per IEC 62561. Note: 3m length shall vary depending upon soil resistivity.
Supply, Installation, Testing and Commissioning of 25x3mm Copper Tape Conductor with fixing accessories and should be tested for electrical resistivity test , Tensile strength, Environmental Test (salt spray & humidity test) to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of Copper Square Tape Clamp for Cross connection and T connection of 25x3mm Aluminium Tape should be tested for electrical resistivity test ,Environmental Test (salt spray & humidity test),Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
AVIATION LIGHTS
S& F of Aviation yellow painted die-cast aluminium alloy housing, built-in 75VA step up transformer, heat resistant, clear thick glass and all mounting accessories.as per ICAO-ANNEX 14 [Make: BAJAJ Luminaire Type:BJAOL 1 with Neon Lamp Product No: 20075 or equivalent]
S& F of Aviation yellow painted die-cast aluminium alloy housing, red coloured polycarbonate dome and all mounting accessories as per ICAO-ANNEX 14 [Make: BAJAJ Luminaire Type:BJAOL 2 BC Product No: 24973 or equivalent]
S & F weather- proof PVC junction box of size 139 mm x 119 mm x 70 mm, having IP 65 protection for outdoor installation fixed with 4 way Bakelite cable terminals including 03 Nos. of polymide gland with check nuts fixed on poles with flat aluminium clamps, nuts, bolts, washers, etc. complete all as specified and as directed by engineer- in- charge. Make: Sintex, Hensel, HPL
HOT WATER SUPPLY
Supply and Fixing water heater storage type electric, capacity 25 Litrs, BEE 5 star rated, Rated power input-2000W,Rated Voltage & frequency-230 V, 1Phase, 50 Hz AC, Rated Input Current-8.69 A, Energy Efficiency feature-Energy saving high density PUF insulation, Geyser protection from water splash-IPX4 technology to protect electrical parts from water splash, No, Net contents-1 N storage electric water heater , 1 N user manual , 1 N multi-function safety valve , 2 N fasteners & 2 N flexi pipes [Make: Havells/Racold/ Bajaj or equivalent]
ARBORICULTURE
HARDSCAPE FINISHES MATERIAL
M&L for providing and laying 75 mm thk grass paver blocks of size 600 mm x 400 mm, over sub base of 40 mm thk sand bedding and 230 mm thk soling and on compacted earth all complete as per the drawing. Rate inclusive of cost of all materials, miscellaneous consumables, labours ,transportation of material to all required locations by approved means , tools, plant and machinery, hire and fuel charges and all other incidental charges etc., all required as per specifications, drawings and as directed by EIC. The item rates shall hold good for work at all Levels ,lead, lifts,Heights,Depths etc. Make - Vyara, Location- Ground floor pathway.
M&L for Providing and fixing M20 grade precast square concrete kerb of size 600 x 300 x 125 mm , embedded in cement mortar 1:4 including 100mm thick M15 grade PCC bed along the edge of the plantation and roads as per detailed drawings after making the surface to required level fixing blocks with fine and uniform joints , joints filled with fine sand and neat cement , securing the free ends ,maintaining the share curves , lines ,cutting if necessary all specials like round edge tiles , curing and cleaning washing etc all complete. Make - Vyara, Location- Ground floor all edges of hardscape.
M&L for providing and laying of vacuum dewatered RCC flooring - BROOM FINISH CONCRETE Make - Everlast or as equivalent as approved by GE, Location- Podium area.
M&L for Providing and finishing specified concrete of 4 Inch, M35 grade total 200 mm thick with 50 mm thk layer of A pigmented water resistant powder, broadcast between the colour hardener and the stamp impression mats, to release the moulds and a variety of multiple tone colour effects with Stamped Impression Concrete Finish including application of sealer, removal of excess release agent, curing etc. complete as per instruction and satisfaction of EIC. Make - Everlast, Location- Multi purpose court 1 & 2.
M&L for providing and laying waterproofing in double layer and slope-making for water tank Slab in following parts and conforming to latest ASTM Standards, as per the specifications listed below and as approved by the engineer-in-charge with a guarantee of 10 years , Location- Podium area and Podium parapet planter.
DRAINCELLS 35mm thk. Supplying and laying Drain board in planters of approved make & as per vender specification with overlap as required, necessary joinery complete as per drawing and as directed by Project Manager. (Rate to include laps) , Location- Podium parapet planter.
Supplying and laying GEOTEXTILE Membrane 180 GSM Providing and laying slip/ protective layer of required gsm geotextile membrane to be laid over surface with an overlap as per approved methodology, accessories, sequence, drawing and manufacturers specifications etc. complete. Location- Podium parapet planter.
Supplying and laying of metal framed seating or brick wall seating with WPC Cladded as per approved. Make - Shubhwood, Location- Ground floor and Podium.
Supply only FRP Pots of size 36x30x30 inches (As approved), Location- Podium.
Supply only FRP Pots of size 300mmx 300mm x 450 mm (As approved), Location- Podium.
SOFTSCAPE
Providing & Laying well compacted garden soil, and manure, mixing and laying of garden mix
Supply and providing planting soil of good quality, loamy, properly screened coarse, having Ph between 5-6, containing adequate amount of humus, friable and free from perennial weeds, stones and other foreign material. The Soil Shall be in a proportion of 2:8 where 2 proportion of (Compost mixture with FYM,SSP & neem cake) and 8 proportions of red earth well screened. Along with labour charges for loading unloading of soil as well as the compost materials. (1cum=0.353 brass )
Garden soil
Supply and Providing Compost Mixture (1 proportions of compost mixture with following ingredients in a ratio of (5:3:2)
Vermi Compost (@ 20kg / cuft.) 5 portion
Neem cake (@ 17.21kg / cuft.) 3 portion
Rice husk (@ 4.73 kg / cuft.) 2 portion
Preparing Planting bed
Excavating the ground to required depth of 300mm-450mm, removing and Conveying unwanted stuff to a required distance as directed, and creating a uniform base layer with backfilling clean site soil where ever required. Filling fresh garden soil & compost mixture as mentioned above in excavated area in proportion to a height of 300mm. Mixing garden soil & manure thoroughly well, levelling, watering on previous night. Planting well rooted shrubs 300mm-750mm .height, apart as directed and maintaining till well established by watering, weeding, stirring,replacing casualties etc. complete. Along with labour required for the same
Supply of Trees
Supply and planting of tree sapling: The tree sapling shall be healthy, vigorous specimen, well shaped, properly branched and well established, of the height specified. The tree sapling shall be planted in the positions demarcated, supporting it with a straight stout stake of bamboo, watered etc. The cost also to include digging of pits & carting away soil 1.0M X 1.0M X 1.0M for a tree complete as per specifications
a) Azadirachta indica 3.5 M c/c distance, Height (Ft)'10'-12 'Above bag, Tree Girth (inchs) 4''-5'' min, No.of Branching 5-6 minimum.
b) Bauhinia variegata alba 3.5 M c/c distance, Height (Ft) 10'-12 ' above bag, Tree Girth (inchs) 4''-5'' min, No.of Branching 4-5 minimum.
c) Felicium decipens 3.5 M c/c distance, Height (Ft) 8'-10 ' above bag, Tree Girth (inchs) 4''-5'' min, No.of Branching 4-5 minimum.
d) Lagerstromia speciosa 3.5 M c/c distance, Height (Ft) 8'-10 ' above bag, Tree Girth (inchs) 4''-5'' min, No.of Branching 4-5 minimum.
e) Lagerstromia thorelli 3.5 M c/c distance, Height (Ft) 8'-10 ' above bag, Tree Girth (inchs) 4''-5'' min, No.of Branching 4-5 minimum.
f) Nyctanthes arbor-tristis 3.5 M c/c distance, Height (Ft) 8'-10' above bag, Tree Girth (inchs) 4''-5'' min, No.of Branching 4-5 minimum.
g) Plumeria alba 3.5 M c/c distance, Height (Ft) 8'-10' above bag, Tree Girth (inchs) 4''-5'' min, No.of Branching 3-4 minimum.
h) Saraca asoca 3.5 M c/c distance, Height (Ft) 8'-10' above bag, Tree Girth (inchs) 4''-5'' min, No.of Branching 4-5 minimum.
i) Terminalia mentaly 3.5 M c/c distance, Height (Ft)'10'-12 'above bag, Tree Girth (inchs) 4''-5'' min, No.of Branching 4-5 minimum.
SHRUBS
Supply and planting of shrubs: The shrubs shall be healthy, vigorous specimens, well shaped, heavily branched (wherever applicable), densely foliated, well established and of specified height. The planting of shrub sapling shall be done in positions demarcated, with bamboo supports wherever necessary, watering etc. The cost also to include digging of pits 0.45M X 0.45M X 0.45M for shrubs complete as per specifications.
a) Alpinia Zerumbet 'Variegata' 0.45 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
b) Canna malvensis variegata 0.45 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
c) Crinum asiaticum 0.45 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
d) Cyperus alternifolius 0.45 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
e) Hymenocallis littoralis 0.45 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
f) Ixora duffy pink 0.3 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
g) Philodendron xanadu 0.45 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
h) Pseuderanthemum reticulatum 0.45 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
i) Sanchezia nobilis 0.45 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
j) Spathiphyllum 0.45 meter C/C distance, Height 1'-6'' above bag, Canopy 0.45 meter.
GROUND COVERS (upto 1ft ht.)
Supply and planting of ground covers and grasses: Gr.Covers and grasses shall be healthy and of specified variety. The planting of ground covers and grass saplings shall be done in positions demarcated, with watering etc. The cost also to include laying of garden soil to the required slope and preparing the planting base complete as per specifications.
a) Dianella tasmanica 'Variegata' 0.15 meter C/C distance, Height 9'' above bag, Canopy 0.30 meter.
b) Ophiopogon japonicus 'Variegata' 0.15 meter C/C distance, Height 9'' above bag, Canopy 0.15 meter.
c) Pandanus pygmaeus 0.15 meter C/C distance, Height 9'' above bag, Canopy 0.30 meter.
d) Rhoeo spathacea compacta 0.15 meter C/C distance, Height 9'' above bag, Canopy 0.15 meter.
Supply and planting of grasses: grasses shall be healthy and of specified variety, planting by dibbling method as directed and maintaining till well established by watering, weeding, clipping, rolling, etc. complete.
a) Zoysia japonica 0.15 meter c/c distance, Height 6'' above bag.
CREEPERS
a) Tarlmounia elliptica (vernonia creeper) 0.3 meter c/c distance, Height 1'-6'' above bag, Canopy 0.45 meter.
COMPREHENSIVE MAINTENANCE OF LIFTS
Comprehensive maintenance and repair of fully automatic electrically operated passenger lift of any make and 20 Passenger capacity lift installed in building comprising of all devices and accessories through out 12 months on all days including holidays for period of 03 years after expiry of defects liability period as shown below and all as specified and directed by GE.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(a) 3rd year after expiry of defects liability period
Comprehensive maintenance and repair of fully automatic electrically operated fire elevator lift of any make installed in building comprising of all devices and accessories through out 12 months on all days including holidays for period of 03 years after expiry of defects liability period as shown below and all as specified and directed by GE.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(a) 3rd year after expiry of defects liability period
PILE FOUNDATION
M&L for drilling into any type of soil strata including temporary casing lowering upto non-collapsible strata for following dia cast in situ piles all as required and getting out and disposal of spoil outside MD land and depositing at a place including erecting pilling equipment of any type complete with all accessories centering in position and removing on completion of each pile all as shown on drawing ,specified & as directed by Engineer in Charge
(a) 600mm dia
(b) 1000mm dia
M&L for drilling into Soft/disintegrated/weathered rock including temporary casing lowering upto non-collapsible strata for following dia cast in situ piles all as required and getting out and disposal of soft/ disintegrated/weathered rock outside MD land and depositing at a place including erecting pilling equipment of any type complete with all accessories centering in position and removing on completion of each pile all as shown on drawing ,specified & as directed by Engineer in Charge
(a) 600mm dia
(b) 1000mm dia
M&L for drilling into hard rock including temporary casing lowering upto non-collapsible strata for following dia cast in situ piles all as required and getting out and disposal of hard rock outside MD land and depositing at a place including erecting pilling equipment of any type complete with all accessories centering in position and removing on completion of each pile all as shown on drawing ,specified & as directed by Engineer in Charge
(a) 600mm dia
(b) 1000mm dia
Note for Sl item No 29.001 to 29.09 (a) Reinforcement required shall be measured and paid separately. (b) Spoil shall be disposed off outside MD land and depositing at a place as directed by the Engineer- in Charge. The unit rate quoted against item Nos 29.001 to 29.09 shall interralia be deemed to include for this operation and no extra payment shall be admissible on this account. (c) Drilling of piles shall be measured and paid from marked average ground level to bottom of pile.
M&L for steel (Fe 500d) CRS of following dia with binding wire, cover block & cutting, bending, binding and fixing with lowering of pile cage into pile of 600mm dia complete all as directed by Engineer in Charge
20mm dia
Ditto but 8mm to 12 mm dia in stirrups, spacers and binders
8mm dia
12mm dia
M&L for steel (Fe 500d) CRS of following dia with binding wire, cover block & cutting, bending, binding and fixing with lowering of pile cage into pile of 1000mm dia complete all as directed by Engineer in Charge
20mm dia
25mm dia
Ditto but 10mm to 16 mm dia in stirrups, spacers and binders
10mm dia
16mm dia
M&L for RMC M35 design mix concrete and Tremie Concreting as per IS 456 of 2000 in piles cast in situ piles of 600mm dia of any length using tremie pipe concrete method including cutting and knocking down waste concrete complete all as shown on drg., specified and directed. Note : RCC will be measured and paid from cutoff level and rate quoted shall be inclusive of cutting and knocking of RCC waste above cut off level
M&L for RMC M40 design mix concrete and Tremie Concreting as per IS 456 of 2000 in piles cast in situ piles of 1000mm dia of any length using tremie pipe concrete method including cutting and knocking down waste concrete complete all as shown on drg., specified and directed. Note : RCC will be measured and paid from cutoff level and rate quoted shall be inclusive of cutting and knocking of RCC waste above cut off level
M&L complete for High Strength Dynamic Load Test using capwac analysis as per ASTM4945 and IRC 78 on following dia pile in accordance with IS provisions for Initial Test including all necessary arrangements providing and setting up all necessary accessories and equipments carrying out the prescribed test as required/specified under the expert supervision noting the result, taking out the accessories and equipment on completion of test submitting the result in soft and hard copy quintuplicate all as directed by Engineer in Charge
(a) 600mm dia
(b) 1000mm dia
M&L complete for Integrity Test on following dia pile in accordance with IS provisions including all necessary arrangements providing and setting up all necessary accessories and equipments carrying out the prescribed test as required/specified under the expert supervision noting the result, taking out the accessories and equipment on completion of test submitting the result in soft and hard copy quintuplicate all as directed by Engineer in Charge
(a) 600mm dia
(b) 1000mm dia
M&L complete for High Strength Dynamic Load Test using capwac analysis as per ASTM4945 and IRC 78 on following dia pile in accordance with IS provisions for Routine Test including all necessary arrangements providing and setting up all necessary accessories and equipments carrying out the prescribed test as required/specified under the expert supervision noting the result, taking out the accessories and equipment on completion of test submitting the result in soft and hard copy quintuplicate all as directed by Engineer in Charge
(a) 600mm dia
(b) 1000mm dia
Rds Project ltd.
IRON TRIANGLE LIMITED
Som Projects Pvt. Ltd.
VISHAL INFRASTRUCTURE LTD
Jatan Constructions Private Limited
Shubham EPC Private Limited
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.07 MB
Download all tender documents and submit your bid