Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.9 LAccepted-AOC 111 YADAV ELECRIC MARKET GB MARG LUCKNOW LUCKNOW UTTAR PRADESH 226018 | LUCKNOW | UTTAR PRADESH | 226018 | L1 | Accepted-AOC BEING LOWEST BIDDER | |
| 2 | L2₹9.9 L+₹75,004 (8.20%)Rejected-Finance D 2 36 VIBHUTI KHAND GOMATI NAGAR LUCKNOW UTTAR PRADESH 226010 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226010 | L2 | Rejected-Finance NOT BEING LOWEST BIDDER | |
| 3 | L3₹10.8 L+₹1.6 L (17.9%)Rejected-Finance 2 2 BLOCK B MAYUR RESIDENCY MISRAPUR KURSI ROAD LUCKNOW 226026 UP | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226026 | L3 | Rejected-Finance NOT BEING LOWEST BIDDER |
| Sl No | Description | Qty | Unit | Industrial Traders L1 | FUTURE Inc. L3 | Lucknow Refrigeration L2 |
|---|---|---|---|---|---|---|
| 1.00 | Comprehensive service/repair/maintenance for the automation of addresable fire alarm control panel and flow chart based on proggramable RTU at AF STN BKT including checking testing and cleaning of loop card main board, LCD display ,AC filter transformer,LED acid batteries ,inverter muti sensor sounder, MCP, repeater panel, zone monitor module, UV & IR detector, remote responce indicator, loop isolator, amplifier and sounders carrying out normal repair for trouble free and eficient functioning of entire fire alarm sysytem by providing one engineer/skilled technician for visit all as specified and directed.
Note-(i) Cost of new parts/component shall be paid seperately under relevant item of schedule A given here-in-after.
(ii)Contractor rep/technician will do testing in front of user and provide serviceability report duly signed by user. | 2 | Each Job | 10,332 ₹20,664 | 27,500 ₹55,000 | 8,000 ₹16,000 Lowest |
| 2.00 | Dismantling,Servicing of muti sensor detector with heat and smoke combination photoelectric as per exact location with the help of manufacturer instruction and testing for excat fault location including cleaning through air blower and re-install complete all as specified and directed. | 65 | Each Job | 488 ₹31,720 | 700 ₹45,500 | 400 ₹26,000 Lowest |
| 3.00 | S&F in repair 12 V,42 Ah battery for inverter supply for back up to all RTU panel complete all as specified and directed. | 2 | Each | 3,731 ₹7,462 Lowest | 4,750 ₹9,500 | 6,300 ₹12,600 |
| 4.00 | S&F in repair addresable fire alarm panel which consist of display board which will have have 2 loop fire alarm main control panel complying with BE EN 54 single loop panel of capacity from 99 detector & 99 moudule upto 200 hundred detector and moudles. Complete all as specified and directed. | 1 | Each | 37,103 ₹37,103 Lowest | 40,000 ₹40,000 | 85,000 ₹85,000 |
| 5.00 | S&F in repair multi sensor (smoke cum heat) detector voltage 17-28 V DC ,resest volatge less than 3V , standby current 500 um,alarm current 7 mA,remote output 2mA maximum open collector ,thermal rating 59 C (138 F), rate of raise temp 11.1 C smoke sensitivity (2.12+-0.61)% ft,high 1.1% ft,low 2.3% ft,air velocity 0-4000fpm,operating temp -10C to 50 C, humidity 0-95% RH, non -condensing etc complete all as specified and directed. | 25 | Each | 1,434 ₹35,850 | 1,500 ₹37,500 | 900 ₹22,500 Lowest |
| 6.00 | S&F in repair beam master detector with transmitter and receiver 240 V,operating temperature -25 to 55 deg C along with addresable control module etc complete all as specified and directed. | 2 | Each | 24,984 ₹49,968 | 12,000 ₹24,000 Lowest | 30,000 ₹60,000 |
| 7.00 | S&F in repair addresable type base with supply voltage (min) 17 V,max supply volatge(V max) 28 VDC,quiescent current at 24 V(IC) 30uA, leakage current at 24 V(IL) 2mA when isolating,24 VDC,max current 1 A continuous,3A paek complete all as specified and directed. | 25 | Each | 488 ₹12,200 | 650 ₹16,250 | 401 ₹10,025 Lowest |
| 8.00 | S&F in addressable type Manual Call point resettable type compatible with main fire alarm control board microprocessor based as per IS-2189 complete all as specified and directesd. | 8 | Each | 1,798 ₹14,384 | 1,500 ₹12,000 Lowest | 2,500 ₹20,000 |
| 9.00 | S&F in repair electronic sounder with range of 25-30 meter with output not less than 4 watt including necessary connection complete all as specified and directed. | 6 | Each | 2,618 ₹15,708 | 4,500 ₹27,000 | 2,500 ₹15,000 Lowest |
| 10.00 | S&F in repair Fire Extinguisher, water stored pressure type, 9 Ltrs cap, confirming to IS 15683 with hanging arrangement on wall complete all as specified and directed | 2 | Each | 10,562 ₹21,124 | 6,000 ₹12,000 | 1,700 ₹3,400 Lowest |
Tender Value
₹16 L
EMD Value
₹32,000
Closing Date
27 Jan 2026, 6:00 pmClosed
GE (AF) BKT
GE (AF) BKT, LUCKNOW
REPAIR / MAINT OF HANGER LIGHTS, FIRE ALARM SYSTEM AND OTHER CONNECTED WORK AT AF STN BKT
2026_MES_747522_1
8859/BKT/E8
Open Tender
Civil Works
Item Rate
270 days
GE (AF) BKT
7 documents required · 7 mandatory
₹500
GE (AF) BKT
₹32,000
15 May 2026
7 Jan 2026
29 Jan 2026
7 Jan 2026
27 Jan 2026
21 Jan 2026
Comprehensive service/repair/maintenance for the automation of addresable fire alarm control panel and flow chart based on proggramable RTU at AF STN BKT including checking testing and cleaning of loop card main board, LCD display ,AC filter transformer,LED acid batteries ,inverter muti sensor sounder, MCP, repeater panel, zone monitor module, UV & IR detector, remote responce indicator, loop isolator, amplifier and sounders carrying out normal repair for trouble free and eficient functioning of entire fire alarm sysytem by providing one engineer/skilled technician for visit all as specified and directed. Note-(i) Cost of new parts/component shall be paid seperately under relevant item of schedule A given here-in-after. (ii)Contractor rep/technician will do testing in front of user and provide serviceability report duly signed by user.
Dismantling,Servicing of muti sensor detector with heat and smoke combination photoelectric as per exact location with the help of manufacturer instruction and testing for excat fault location including cleaning through air blower and re-install complete all as specified and directed.
S&F in repair 12 V,42 Ah battery for inverter supply for back up to all RTU panel complete all as specified and directed.
S&F in repair addresable fire alarm panel which consist of display board which will have have 2 loop fire alarm main control panel complying with BE EN 54 single loop panel of capacity from 99 detector & 99 moudule upto 200 hundred detector and moudles. Complete all as specified and directed.
S&F in repair multi sensor (smoke cum heat) detector voltage 17-28 V DC ,resest volatge less than 3V , standby current 500 um,alarm current 7 mA,remote output 2mA maximum open collector ,thermal rating 59 C (138 F), rate of raise temp 11.1 C smoke sensitivity (2.12+-0.61)% ft,high 1.1% ft,low 2.3% ft,air velocity 0-4000fpm,operating temp -10C to 50 C, humidity 0-95% RH, non -condensing etc complete all as specified and directed.
S&F in repair beam master detector with transmitter and receiver 240 V,operating temperature -25 to 55 deg C along with addresable control module etc complete all as specified and directed.
S&F in repair addresable type base with supply voltage (min) 17 V,max supply volatge(V max) 28 VDC,quiescent current at 24 V(IC) 30uA, leakage current at 24 V(IL) 2mA when isolating,24 VDC,max current 1 A continuous,3A paek complete all as specified and directed.
S&F in addressable type Manual Call point resettable type compatible with main fire alarm control board microprocessor based as per IS-2189 complete all as specified and directesd.
S&F in repair electronic sounder with range of 25-30 meter with output not less than 4 watt including necessary connection complete all as specified and directed.
S&F in repair Fire Extinguisher, water stored pressure type, 9 Ltrs cap, confirming to IS 15683 with hanging arrangement on wall complete all as specified and directed
S&F in repair fire extingusher CO2, 4.5 Kg cap, confirming to IS 15683 (Light Wt Squeeze grip type) with hanging arrangement on wall complete all as specified and directed.
S&F in repair fire extinguisher, Dry chemical Powder, (ABC) Type, 6 Kg cap, confirming to IS 15683 with hanging arrangement on wall complete all as specified and directed.
S&F in repair fire extinguisher, Mechanical foam type, 9 liters cap, confirming to IS 15683 with hanging arrangement on wall complete all as specified and directed.
S&F in repair Fire Bucket dry sand, 10 Ltrs cap, confirming to IS 2546 complete all as specified and directed.
S&F in repair fire extinguisher, Dry chemical Powder, (ABC) Type, 1 Kg cap, confirming to IS 15683 with hanging arrangement on wall complete all as specified and directed.
S&F in Fireball fire extinguisher ball size ( 152 mm dia ) fire safety ball self activate reaction time 3-4 sec fast sensors compact with thermocol body with mounting accessories complete all as specified and directed.
Dismantling / taking down carefully defective/non functional highbay light of any type and size and supply and fixing in repair of LED highbay light Fitting complete of capacity 150 watt in new generation energy saving environmental friendly long life integral industrial with pressure dia cast alluminium housing IP 65 protection impact resistance 240 volt 50 hz thermal management including all fixing accessories i.e. adjustable bracket clamp made out of flat iron of size 50mm x 5mm thick nut and bolts complete all as specified and directed . Note-Light fitting will be fixed at hanger of height approx 12-15 mtr. All necessary T&P required for working at Hanger height should be arranged by the contractor and rate should be included in the unit quoted rate. Make- Bajaj /Havells /Phillips/ CG/ L&T.
S&F in 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed flexible two core cable flat or circular of size 4 Sqmm solid aluminium conductor complete all as specified and directed. Make of Cable :- Havells/ Plaza/Finolex/Polycab.
S&F in 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed flexible two core cable flat or circular of size 6 Sqmm solid aluminium conductor complete all as specified and directed. Make of Cable :- Havells/ Plaza/Finolex/Polycab.
S&F in 1100 volts grade heavy duty cable PVC insulated copper conductor, served with inner sheathing of PVC tape and overall PVC sheathed flexible two core cable flat or circular of size 1.5 Sqmm solid copper conductor complete all as specified and directed. Make :- Havells/ Plaza/Finolex/Polycab.
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated copper conductor, served with inner sheathing of PVC tape and overall PVC sheathed flexible two core cable flat or circular of size 2.5 Sqmm solid copper conductor all as specifiied and directed. Make :- Havells/ Plaza/Finolex/Polycab.
Petty repair works to internal electrification comprise of checking of nonfunctional existing electric circuits /wiring of light points/fan points/power points/energy meter etc and checking of fan/exhaust fan,switch/sockets ,DBS/MCCBs //MCB/ and other faults by deploying trained electrician with helper and tools and saftey equipments on daily basis for continuous electric supply and carrying out minor repairs as required to make the items functional or to restore electric supply with and including tightening of lose and broken connections ,insulating naked wires ,opening of DBs etc and refixing the same after necessary repair.Replacing defective items provided under relevents items here-in-after with and including petty repairs of items/materials i.e. fuses thimbles small wires of any size screw washer nut bolt etc and cutting of backelite sheet for fixing accessories making all electric connections in Md/OTM Accn and in any location within tech area of GE(AF) BKT every day except sunday and holiday during ofiice time all as specified and diected by Engr-In-Charge. Note :- (a) Spare parts shall be measured and paid seperately against 'Supply only' items and fixing rate included in quoted unit rate. (b) In case of functional requirement ,contractor is required to extend the service on sunday and public holidays as notified.
Supply only switch piano flush type 6 Amp. AC, 240 Volts one way complete all as specified and directed. Make :- Anchor / Havells/ Legrand/ L&T/ C&S.
Supply only in repair socket 6 Amp. AC, 240 Volts one way complete all as specified and directed. Make :- Anchor / Havells/ Legrand/ L&T/C&S.
Supply only bell push flush type single pole one way, 5/6 Amp, AC,230 V all as directed with frame cover complete all as specified and directed. Make :- Anchor / Havells/ Legrand/ L&T/C&S.
Supply only switch socket combination. Multi purpose 6 Pin 6 Amp flush type AC, 230V complete all as directed. Make :- Anchor / Havells/ Legrand/ L&T/C&S.
Supply only switch socket combination. Multi purpose 6 Pin 16 Amp flush type , AC, 230V complete all as specified and directed. Make :- Anchor / Havells/ Legrand/ L&T/C&S.
Supply only angle holder backelite with insulated body AC, 230V complete all as specified and directed.
Supply only call bell electric AC, 230V, Single phase, Dingdong type complete all as specified and directed. Make :- Anchor / Havells/ Legrand/ L&T/C&S.
Supply only Sleek LED mirror light 10 watt rating with diffuser 2ft long twisted flexible copper wire (approx 0.5 mtr long) complete all as specified and directed. Make :- Philips/Bajaj/ Havells/ CG.
Supply only decorative surface mounting LED dwonlighting with white diffuser 07 watt luminaire for 230 volt AC complete all as specified and directed. Make :- Philips/Bajaj/ Havells/ CG.
Supply only decorative surface mounting LED dwonlighting with white diffuser 3/5 watt luminaire for 230 volt AC complete all as specified and directed. Make :- Philips/Bajaj/ Havells/ CG.
Supply only square recessed / surface/suspended mounting LED slim ceiling light with extruded aluminium housing and milky diffuser of 36 W 2'X 2' slim panel LED driver 240 V ,50 Hz complete all as specified and directed. Make :- Philips/Bajaj/ Havells/ CG.
Supply only LED tube RETRO LED 16 to 22 watt of size 4 ft long complete all as specified and directed. Make :- Philips/Bajaj/ Havells/ CG.
Supply only capacitor 2.5 mfd complete all as specified and directed. Make- Havells/Legrand/ L&T.
Supply only Fan down rod made out of GI pipe (light grade) 15mm bore and 1.20 meter long including rubber real and suitable nuts and bolts,safty pin complete all as specified and directed.
Supply only exhaust fan louvers made out of mild steel suitable for exhaust fan of size 300mm sweep including taking down old complete all as specified and directed.
Supply only plug top 3, pin 15 Amp complete all as specified and directed.
Supply only stepped fan regulator flush type two module, 100 watt, AC, 230V, Single phase, complete all as specified and directed.
Supply only stepped fan regulator (single module) flush type , 100 watt, AC, 230V, Single phase, complete all as specified and directed.
Supply only modular type electronics fan regulator (single module), 100 watt, AC, 230V, Single phase, complete all as specified and directed.
M&L for submain wiring with two run of single core PVC insulated unsheathed multi stranded FRLS-H copper conductor cable of size 2.5 Sqmm 1100 volts grade and one run of PVC insulated unsheathed multistarnded copper conductor cable of size 2.5 Sqmm 1100 volts grade as earth continuity conductor drawn through in and including rigid PVC concealed / surface conduit of suitable size 20 /25 mm on roof/wall/ceiling including making good the disturbed surfaces of wall etc complete all as specified and directed by Engr-in-Charge Make-Polycab/Finolex/RR cables/Plaza/ Havells Note : Two run of single core cable and one run of earth wire will be measured as one length and conduit and its accessories is deemed to be included in the unit quoted rate.
S&F Submain wiring with two single core PVC insulated FRLS-H multistrand copper conductor cable of size 04 Sq mm drawn into and including non metallic medium duty rigid concealed PVC condute not less than 25 mm size ISI marked with all fittings / accessories and 04 Sq mm FRLS-H multistrand copper conductor cable as continuous earth wire complete. Make-Polycab/Finolex/Plaza/RR cabels Havells. Note :- for submain wiring: Two run of single core cable and one run of earth wire will be measured as one length and conduit and its accessories is deemed to be included in the unit rate quoted for this quoted items.
Taking down old unserviceable main switches/DB’s up to 100 Amps capacity fixed in wall and making good of all disturbed surfaces as per existing .
S&F sheet metal enclosure for DB’s when MCB to be used single pole and neutral double door, 4 way, AC,240 volt with 200 Amp bus bar rating complete all as specified and directed. Make :- Havells / Legrand / Seimens/ L&T.
S&F sheet metal enclosure for DB’s when MCB to be used single pole and neutral double door, 8 way, AC,240 volt with 200 amp bus bar rating complete all as specified and directed. Make :- Havells / Legrand / Seimens/ L&T.
S&F in sheet metal enclosure for DB’s when MCB to be used single pole and neutral double door, 12 way, AC,240 volt with 200 Amp bus bar rating complete all as directed. Make :- Havells / Legrand / Seimens/L&T C&S.
S&F in sheet metal enclosure double door (MCB DB) three phase and neutral with 200 Amps rated bus bar TPN, 4 way verticall type, with provision of MCB incommer, AC, 415 Volt complete all as specified and directed. Make :- Havells / Legrand / Seimens/L&T C&S.
S&F in sheet metal enclosure double door (MCCB DB) three phase and neutral with 200 Amps rated bus bar VTPN, 4 way vertical type, with provision of MCCB incommer, AC, 415 Volt complete all as specified and directed. Make :- Havells / Legrand / Seimens/L&T C&S.
S&F MCB single pole, 6 to 32 Amps, 240 Volts 50 HZ, 10 KA breaking capacity complete all as specified and directed. Make :- Havells / Legrand / Seimens/L&T C&S.
S&F MCB single pole, 32 to 40 Amps, 240 Volts 50 HZ, 10 KA breaking capacity complete all as directed. Make :- Havells / Legrand / Seimens/L&T C&S.
S&F MCB DP 40 to 63 Amps 240 Volts, 50 Hz, 10 KA breaking capacity complete all as directed. Make :- Havells / Legrand / Seimens/L&T C&S.
S&F MCB Four Pole 40 to 100 Amps 415 Volts, 50 Hz, 10 KA breaking capacity complete all as directed. Make :- Havells / Legrand / Seimens/L&T C&S.
S&F in MCCB 4 pole 100 / 125 Amp 415 volts 50 HZ 25 KA breaking capacity complete all as specified and directed. Make :-Havells / Legrand / Seimens/L&T C&S.
M&L for Technician & Helper and T&P including testing of equipments for carring outs comprehensive maintenance and testing of earthing any type as per existing procedure for lightening protection /eqpts/domestic etc in tech area & admin area by tightening of nut bolts arranging earth lead in allignment manner replacing unservicable earthing lead, test point, protection pipe etc (which will be paid under relevant item) and testing of earthing and recording result in register (as per procedure provided as directed ,If result found more than permissible limit reconditioning of earthing carried out by pouring water with salt /chemical as per direction and further testing the same earthing result and recording in register including levelling, refilling of earth settle down near pit complete all as specified and directed.
M&L for Earthing complete with galvanised steel earth plate electrode 60cm x 60cmx6 mm thick burried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 5 of MES Schedule Part-I connected to earthing point/DBs on completion with and including 15 mm bore light grade G.I. protection pipe (upto 7.5 M beyond outer edge of earth pit) precast PCC pit in mix (1:3:6) type C1 using 20mm graded stone aggregate with RCC (1:2:4) type B-1 using 20mm graded stone aggregate 40 mm thick cover reinforced with 6 mm dia M.S bars 3 Nos both ways with lifting hook made out of 6 mm dia bar, watering arrangement with funnel and wire mesh and 20 mm bore light grade G.I. watering pipe, common salt and charcoal filling including, necessary excavation and earth work, complete all as specified and directed.
Dismantling / taking down carefully defective/non functional aviation light of ant type and size supply and fix in repair aviation light fitting with integral LED aviation light comprising of alluminium hosing with polycarbonate enclosure capacity 20 Watt complete all as specified and directed. Make :- Philips/ Bajaj/ CG/ Havells/ L&T.
S&F in footlight LED based with chrome collar modular type of 4 module glossy finish 230 volt, 50 Hz complete all as specified and directed. Make :- Philips/ Bajaj/ CG/ L&T.
S&F in round shape 10/12 Watt 220 Volt AC surface mounted type with high efficiency PMMA diffuser soft glare free light complete with drivers,holders ,LED lamp suitable for roof ceiling including connection up with three core flexible copper conductor cable of suitable size complete. Make :- Philips/ Bajaj/ CG/ L&T.
S&F in brass made bracket single light fitting with 115 mm dia Round base , brass arm length 57 mm provided with 78 mm lengthx76 mm bredth gallery inside 2 pin brass holder ,frosted glass shade 170 mm finish black nikel and gold plated with 1x7/1x9 watt LED bulb all as specified and directed. Make :- Philips/ Bajaj/ CG/L&T.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
8859credit.pdf
Additional Documents • 0.18 MB
BOQ_837105.xls
BOQ • 0.55 MB
8859tenderdocuments.pdf
Tender Documents • 1.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .