| 1 | 6.6 kV, 25 kA High Voltage Switchboard for Mundra --HTP-New MPPL P 25-Mundra-01 | 6.6 kV, 25 kA indoor type High Voltage
switchboard complete with all accessories
as per technical specifications, data sheet
and equipment details as below
Panel Board (HTP--New MPPL (P 25)-Mundra-01)
Consisting of 02 Main incomer feeders, 01
Generator incomer feeder, 06 nos. Motor
Outgoing feeders, 05 nos. VFD outgoing
feeder, 3 nos. of plant outgoing feeder, 02
nos. Distribution Transformer outgoing
feeders, 01 no APFC outgoing feeder, 02
nos. Bus Coupler feeders including 01 no.
marshalling panel and 03 no. BUS PTs as
indicated in data sheet & equipment details
attachment-2A,3A) | 1 | Set | con4.ip.up | 210 |
| 2 | 6.6 kV, 25 kA High Voltage switchboard for Mundra -- HTP-New MPPL P 25-Mundra-02 | 6.6 kV, 25 kA indoor type High Voltage
switchboard complete with all accessories
as per technical specifications, data sheet
and equipment details as below
(HTP---New MPPL (P 25)�Mundra-02)
Consisting of 02 Main incomer feeders, 07
nos. Motor Outgoing feeders, 02 nos.
Distribution Transformer outgoing feeders,
01 no APFC outgoing feeder, 01 nos. Bus
Coupler feeder including 01 no.
marshalling panel and 02 no. BUS PTs as
indicated in data sheet & equipment details
attachment-2A,3A) | 1 | Set | con4.ip.up | 210 |
| 3 | 6.6 kV, 25 kA High Voltage switchboard for IPS-1, Bhabhar--HTP-New MPPL P 25-IPS1 Bhabhar-01 | 6.6 kV, 25 kA indoor type High Voltage
switchboard complete with all accessories
as per technical specifications, data sheet
and equipment details as below
Panel Board
(HTP---New MPPL (P 25)�IPS1
(Bhabhar)-01)
Consisting of 02 Main incomer feeders, 01
Generator incomer feeder, 04 nos. Motor
Outgoing feeders, 03 nos. VFD outgoing
feeder, 02 nos. Distribution Transformer
outgoing feeders, 01 no APFC outgoing
feeder, 02 nos. Bus Coupler feeders
including 01 no. marshalling panel and 03
no. BUS PTs as indicated in data sheet &
equipment details attachment-2A,3A) | 1 | Set | con4.ip.up | 210 |
| 4 | 6.6 kV, 25 kA High Voltage switchboard for IPS-2--HTP-New MPPL P 25-IPS 2-01 | 6.6 kV, 25 kA indoor type High Voltage
switchboard complete with all accessories
as per technical specifications, data sheet
and equipment details as below
Panel Board
(HTP---New MPPL (P 25)�IPS 2-01)
Consisting of 02 Main incomer feeders, 01
Generator incomer feeder, 04 nos. Motor
Outgoing feeders, 03 nos. VFD outgoing
feeder, 02 nos. Distribution Transformer
outgoing feeders, 01 no APFC outgoing
feeder, 02 nos. Bus Coupler feeders
including 01 no. marshalling panel and 03
no. BUS PTs as indicated in data sheet &
equipment details attachment-2A,3A) | 1 | Set | con4.ip.up | 210 |
| 5 | 6.6 kV, 25 kA High Voltage switchboard for IPS-3 --HTP-New MPPL P 25-IPS 3-01 | 6.6 kV, 25 kA indoor type High Voltage
switchboard complete with all accessories
as per technical specifications, data sheet
and equipment details as below
Panel Board
(HTP---New MPPL (P 25)�IPS 3-01)
Consisting of 02 Main incomer feeders, 01
Generator incomer feeder, 04 nos. Motor
Outgoing feeders, 03 nos. VFD outgoing
feeder, 02 nos. Distribution Transformer
outgoing feeders, 01 no APFC outgoing
feeder, 02 nos. Bus Coupler feeders
including 01 no. marshalling panel and 03
no. BUS PTs as indicated in data sheet &
equipment details attachment-2A,3A) | 1 | Set | con4.ip.up | 210 |
| 6 | HT Panel Spares Complete Set of Spares for Each Panel | HT Panel Spares Complete Set of spares for each panel as per Technical Specifications, data sheet
and equipment details | 5 | Set | con4.ip.up | 210 |
| 7 | Supervision charges for Panels | Supervision charges for erection, testing &
commissioning of switchboards at site
including requisite control wiring between
shipping sections, relay setting and coordination,
to & fro travel charges, lodging,
boarding etc. complete in all respects as
per technical specifications.
10 man-days for each panel | 50 | ManDays | con4.ip.up | 210 |