Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.7 LAccepted-AOC | L1 | Accepted-AOC accepted | |
| 2 | L2₹23.8 L+₹3.3 L (16.3%)Rejected-AOC | L2 | Rejected-AOC rejected | |
| 3 | L3₹24.5 L+₹4.0 L (19.8%)Rejected-AOC | L3 | Rejected-AOC rejected |
Tender Value
₹25 L
EMD Value
₹25,000
Closing Date
22 Oct 2020, 5:00 pmClosed
City Engineer
JCMC Jalgaon
Providing supplying spares and rectification of electrical and mechanical equipment in pump house and switch yard of raw water pump house near Waghur Dam Annual maintenance
2020_JCMCJ_615036_1
Tender Notice No 46
Open Tender
Civil Works - Water Works
Item Wise
365 days
JCMC Jalgaon
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
via Payment Gateway
₹25,000
29 Jan 2021
8 Oct 2020
23 Oct 2020
8 Oct 2020
22 Oct 2020
8 Oct 2020
Amount
H.T. PANEL (3.3 KV VCB) - 11 nos. Material for Safety alignment of all shutters
supply of 3.3 KV CT
Supply of3.3 KV PT
Spring charging motor
Closing and tripping coil
All Indicator lamps of panel
Over current relay
Earth fault relay
Trip relay and trip circuit
Under voltage relay
Ammeter
Voltmeter
Push button
MCB DP 10 A AC/DC ON /OFF
MCB 63 A TPN
MCB 32 A TPN
MCB 16 A TPN
Space heater
Thermostat
Toggle switch
Socket 4 pin control fuse links
Digital Multifunction meter
Annunciator 04 window 110 v DC
Annunciator 16 window 110 v DC
Hooter 110 v DC
HRC fuse links of various capacity up to 16 A
Temperature scanner
Misc. spares of all VCB panels
C & R PANEL Safety alignment of shutter
Over current relay
Earth fault relay
Breaker control switch (T &C switch)
Local remote control switch
Push button
MCB DP 10 A AC/DC
MCB 63 A TPN
MCB 32 A TPN
MCB 16 A TPN
Toggle switch
Digital Multifunction meter
Annunciator 04 window 110 v DC
Annunciator 16 window 110 v DC
Hooter 110 v DC
Triple pole s/w,32 amp with neutral link
HRC fuse links of various capacity up to 16 A
LT PANEL Safety alignment of shutter
MCCB Moulded case Circuit breaker 250 A
MCCB Moulded case Circuit breaker 100 A
Triple pole s/w,32 amp with neutral link
MCB 63 A TPN
MCB 32 A TPN
MCB 16 A TPN
HRC fuse links of various capacity up to 16 A
Ammeter
Voltmeter
Local remote control switch
Battery Charger All door meters i.e. (Ammeter& voltmeter), indication lamps etc.
All door meters i.e. (Ammeter& voltmeter), indication lamps etc.
panel internal wiring
Batteries 2V-300AH all batteries, acid level.
all batteries connections .
Transformer 33 KV/3.3KV - 2 nos Oil Filtration by filtration M/C only including BDV, PPM tests HV & LV connections & earthing, all HV & LV side bushings
Horn Gap fuse, Lightening Arrestor Fuse barrel, fuse link for 33 kv line.
33 KV Isolator All resting bolts & insulators
All resting bolts, insulators & operating mechanism
33 KV VCB Space heater, panel door indicators as well as push button etc.
Earthing in switchyard Replacing existing earth pit material by new conductive chemical to improve earth value to satisfy electrical Inspector
Spreading clear metal.
Illumination system in yard
Spares required Gaskets, hardware, nut bolts etc
EOT Crane Required spares of all motors
Motor 3.3 KV, 375KW - 6 nos DE & NDE bearings
HT Grease & HT Warnish
motor cover found jamming
Rotor balancing Workshop charges earth terminal & cable connections lugs
Spares as bearings per no
12UPH4 split casing pump, kirloskar make gland, sleeves & bearings
Workshop work of pump
Balancing of impeller Workshop charges
Consumables for O/H of motor & pump cotton waste.
Kerosens / DW 40 /Rustolene, HT grease etc
Hardware miscellaneous as required
CAPACITOR BANKS H.T. 120 KVAR unit capacitor meter
High voltage HRC fuse 3.3 kv/50 amp for capacitor unit
H.T. cable aluminium tupe 3 core – 95 sq mm 11 kv grade.
Indoor & outdoor termination kit for HT cables of size 95-150 sq mm
Indoor & outdoor termination kit for HT cables of size 185-600 sq mm
H.T. PANEL (3.3 KV VCB) - 11 nos. Safety alignment of all shutters
Checking tiggtness of all cable connections
Lugs tightness checking per 1 no Lug
Bus bar tightness and joint caps
Epoxy insulators tightness & insulation test
CT connection tightness checking and test if found faulty needs to replace
PT connection tightness checking and test if found faulty needs to replace
Spring charging motor testing
Closing and tripping coil testing
Checking of breaker internal wiring tighting
All Indicator lamps and lamps of panel checking
Over current relay testing
Earth fault relay testing (optional)
Trip relay and trip circuit testing
Under voltage relay testing
Ammeter test
Voltmeter test
Breaker control switch (T &C switch)
Local remote control switch test & check
Push button checking
MCB DP 10 A AC/DC ON /OFF checking
MCB 63 A TPN connections tightness
MCB 32 A TPN connections tightness
MCB 16 A TPN connections tightness
Space heater checking
Thermostat checking
Toggle switch checking
Socket 4 pin control fuse links connections tightness
Hooter 110 v DC connections tightness
HRC fuse links of various capacity up to 16 A
Wiring repair & dressing connections tightness
Complete PM of 1 no VCB panel
Inspection charges for spares of all VCB panels
C & R PANEL Safety alignment of shutter
Checking the tightness of all cable connections and gland tightness
Over current relay testing
Earth fault relay testing
Trip relay and trip circuit testing
Under voltage relay testing
Ammeter test
Voltmeter test (optional)
Breaker control switch (T &C switch) checking
Local remote control switch test & check
Push button checking
MCB DP 10 A AC/DC connections tightness checking
MCB 63 A TPN connections tightness
MCB 32 A TPN connections tightness
MCB 16 A TPN connections tightness
Space heater checking
Thermostat checking
Toggle switch checking
Hooter 110 v DC connections tightness
Triple pole s/w,32 amp with neutral link connections tightness
HRC fuse links of various capacity up to 16 A
Wiring repair & dressing connections tightness
Inspection charges for spares of all C & R panel
LT PANEL Safety alignment of shutter
Checking the tightness of all cable connections and gland tightness
MCCB Moulded case Circuit breaker 250 A connections tightness
MCCB Moulded case Circuit breaker 100 A connections tightness
Triple pole s/w,32 amp with neutral link connections tightness
MCB 63 A TPN connections tightness
MCB 32 A TPN connections tightness
MCB 16 A TPN connections tightness
HRC fuse links of various capacity up to 16 A
Ammeter test
Voltmeter test
Local remote control switch test & check
MCB 63 A TPN connections tightness
MCB 32 A TPN connections tightness
MCB 16 A TPN connections tightness
Wiring repair & dressing connections tightness
Battery Charger Physically Checking all door meters i.e. (Ammeter& voltmeter), indication lamps etc.
Physically Checking of panel internal connections tightness etc.
Batteries 2V-300AH Physically Checking all batteries conditions, acid level.
Checking physically all batteries connections tightness.
All batteries corrosion removal.
Transformer 33 KV/3.3KV - 2 nos Checking humming sound before shutdown Physical inspection of oil level Physical inspection and attended of Bucolz Relay condition Physical inspection of leakages if any from gasket or any other spot Physical Inspection of HV and LV connections and attended Physical Inspection of HV and LV Bushing condition and attended Physical Inspection of WTI and OTI meters condition and attended Physical Inspection of PTs and their sincere condition and connections and attended Taking oil from top and bottom drain plug for BDV testing Checking BDV test for physical, chemical & Electrical parameters of Oil from authorized lab
Oil Filtration by filtration M/C only including BDV, PPM, test Thoroughly cleaning of complete Transformer Checking HV & LV connections & earthing tightness Checking tightness of all HV & LV side bushings, Cleaning thoroughly
Complete O/H of one Transformer (Included all above items)
Auxillairy Transformer 33 kv/415 V Physically checking with all respect i.e. leakages & tightness of all connections etc
Post insulators in Switchyard Checking all post insulators, if doubt full then IR value should be taken.
Checking of tightness of conductors on post insulators
Horn Gap fuse, Lightening Arrestor Thoroughly cleaning of insulators Physical checking of tightness of resting bolts & insulators Checking of earthing connection for both.
Air brake switch suitable for 33 kv line.
Fuse barrel, fuse link for 33 kv line.
33 KV Isolator Physical checking of tightness of resting bolts & insulators
Physical checking of tightness of resting bolts, insulators & operating mechanism
Physically checking for operational alignments.
33 KV VCB Checking of all hardware’s & foundation bolts tightness etc.
Checking of all inter panel connection tightness etc.
Checking of Space heater, panel door indicators as well as push button etc.
Earthing in switchyard Checking earth value by dismantling of all earthing connections
Replacing existing earth pit material by new conductive chemical to improve earth value to satisfy electrical Inspector
Cleaning of complete yard taking out grasses & spreading clear metal.
Checking of Illumination system in yard
Spares required Gaskets, hardware, nut bolts etc
EOT Crane Checking all operations of crane
Checking all forward reverse operations of all motors with contactors &braking conditions
Overhauling of all motors
Cleaning of panel bd & rail etc complete
Motor 3.3 KV, 375KW - 6 nos Complete O/H of motor Dismantling of coupling Dismantling of both covers of motor Dismantling of DE & NDE bearings
HT Warnish to stator & rotor
Workshop work if motor found jamming
Rotor balancing if required Labour charges Assembly of complete motor Checking earth terminal & cable connections No load trial of motor
12UPH4 split casing pump, kirloskar make Dismantling of pump & inspection for run out parts
Removal of Impeller, gland, sleeves & bearings
Replace if bearing, sleeve, gland etc if found damaged
Workshop work if pump found jamming
through cleaning all parts, upper, lower casings etc
Balancing of impeller Labour charges
Assembly of complete pump
Coupling of pump & Motortrial after complete assembly of overhauled pump.
Hardware miscellaneous as required
CAPACITOR BANKS H.T. 120 KVAR unit capacitor meter
Physical checking of tightness of connections, resting bolts, insulators &operating.
High voltage HRC fuse 3.3 kv/50 amp for capacitor unit
L.T. Capacitor Bank
H.T. cable aluminium tupe 3 core – 95 sq mm 11 kv grade.
Indoor & outdoor termination kit for HT cables of size 95-150 sq mm
Indoor & outdoor termination kit for HT cables of size 185-600 sq mm
durgam Electrical Enterprises
Varad Electric Works
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .