Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.0 LAccepted-AOC | L1 | Accepted-AOC Accepted due to lowest | |
| 2 | L2₹30.5 L+₹13.5 L (79.6%)Rejected-Finance COLABA MUMBAI | L2 | Rejected-Finance Rejected due to not lowest |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
9 Jun 2020, 6:00 pmClosed
COL NK SAH
CWE (AF) LOHEGAON
SPECIAL REPAIR/REPLACEMENT TO OLD TRANSFORMER AT SUBSTATION NO 1 AND 2 AT SITE P AT AF STN THANE UNDER GE (AF) THANE
2020_MES_343384_1
82585/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
GE (AF) THANE
SPECIAL REPAIR/REPLACEMENT TO OLD TRANSFORMER AT SUBSTATION NO 1 AND 2 AT SITE P AT AF STN THANE UNDER GE (AF) THANE
5 documents required · 5 mandatory
₹500
GE (AF) Thane
₹40,000
Yes
14 Sept 2020
8 May 2020
11 Jun 2020
8 May 2020
9 Jun 2020
26 May 2020
Amount
Supplyy and fixing, testing and commissioning of step down transformer 250 KVA (IS-1180: 2016), 22000V/433V, 3 Phase, 50 C/S oil immersed, naturally cooled outdoor type transformer having no load voltage ratio 22000/433V, Vector group Dyn 11 with 21/2+5+71/2% tapping as under taken out on the HT side and connected to externaly hand operated 22 KV OFF circuit tap changing switch, HT winding connected in delta and LT winding connected in star and neutral brought out and connected to a separate terminal for earthing with outdoor open porcelain bushing on HV side and cable box on LV side with the tempreature rise not exceeding 40oC by thermo meter in oil and 45oC with first filing of oil with following (copper wound) complete with all connections complete all as specified and directed by Engr-in-charge. (a) 22 KV Externally hand operated OFF Circuit Tap Changing Switch locking device. (b) Oil conservator tank with drain plug and filling Cap (c) Silica gel dehidrating breather cahrged with silica gel (d) Oil level gauge (e) Oil filter valve (f) Oil Drain valve (g) Thermometer pocket (h) Diagram and rating plate (j) Two earthing arrangement (k) Lifting lugs (l) Four bidirectional plane roller (m) Air Vent Plug (n) Explosion Vent (o) Bare bushings on HV side (p) Cable box on LV side (q) Additional neutral terminal brought outside the LV cable box for earthing
Supplyy and fixing, testing and commissioning of step down transformer 315 KVA, (IS-1180:2016), 22000V/433V, 3 Phase, 50 C/S oil immersed, naturally cooled outdoor type transformer having no load voltage ratio 22000/433V, Vector group Dyn 11 with 21/2+5+71/2% tapping as under taken out on the HT side and connected to externaly hand operated 22 KV OFF circuit tap changing switch, HT winding connected in delta and LT winding connected in star and neutral brought out and connected to a separate terminal for earthing with outdoor open porcelain bushing on HV side and cable box on LV side with the tempreature rise not exceeding 40oC by thermo meter in oil and 45oC with first filing of oil with following (copper wound) complete with all connections complete all as specified and directed by Engr-in-charge. (a) 22 KV Externally hand operated OFF Circuit Tap Changing Switch locking device. (b) Oil conservator tank with drain plug and filling Cap (c) Silica gel dehidrating breather cahrged with silica gel (d) Oil level gauge (e) Oil filter valve (f) Oil Drain valve (g) Thermometer pocket (h) Diagram and rating plate (j) Two earthing arrangement (k) Lifting lugs (l) Four bidirectional plane roller (m) Air Vent Plug (n) Explosion Vent (o) Bare bushings on HV side (p) Cable box on LV side (q) Additional neutral terminal brought outside the LV cable box for earthing
M&L for earthing complete with copper earth plate electrode 600x3.15mm buried directly in ground with top edge of the plate not less than 1.5 mtrs below normal ground level and connected to earth test point by means of copper strip of size 20x3 mm all as specified and shown electric plate no 3 of MES SSR Part-I 2009 including earthowrk, PCC chamber, PCC chamber, CI cover, protection and watering pipe, funnel, mesh etc all as required at site complete all as specified and directed by Engr-in-charge . Note:- (i) 7.5 RM Copper strip in deemed to be included in quoted rates beyond 7.5 RM strip shall be measured and paid separately. (ii) Earth resistance of earth pit should be less than 0.5 Ohms. On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost. (iii) Rate quoted by the tenderer is deemed to include slat & charcoal upto & above 450mm top of Copper Plate.
M&L Copper Strip 32x6mm burried in ground complete all as specified and directed by Engr-in-charge
Supplying, jointing and commissioning indoor/outdoor type cable end termination jointing kit heat shrinkable type suitable for under ground XLPE cable size 3 core 95 Sqmm HT Cable complete all as specified and directed by Engr-in-charge
Supplying, jointing and commissioning outdoor type cable end termination jointing kit heat shrinkable type suitable for under ground XLPE cable size 3 core 150 Sqmm LT Cable complete all as specified and directed by Engr-in-charge
M&L test point terminal block made of gun metal or phosphorus bronze size 5x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hex. Head screw complete complete all as specified and directed by Engr-in-charge
Veer High Tech Solution
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .