Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.7 LAccepted-AOC VILLAGE TAPARIYAN BABINA CANTT BABINA JHANSI UP 284401 | BABINA | JHANSI | UP | 284401 | ₹28.7 L Quoted ₹29.4 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹38.5 L+₹9.1 L (30.8%)Rejected-Finance C 40 BHAGAT SINGH NAGAR BHIND ROAD GWALIOR MP 474005 | NA | NA | 474005 | ₹38.5 L+₹9.1 L (30.8%) | L2 | Rejected-Finance Other than lowest bidder |
| 3 | L3₹38.8 L+₹9.4 L (31.8%)Rejected-Finance A 63 ELDECO COUNTY PHASE II RAJGARH JHANSI U P 284135 | JHANSI | JHANSI | UTTAR PRADESH | 284135 | ₹38.8 L+₹9.4 L (31.8%) | L3 | Rejected-Finance Other than lowest bidder |
| 4 | L4₹44.9 L+₹15.5 L (52.6%)Rejected-Finance 240 1 A RAI COLONY CIVIL LINES JHANSI 284001 | JHANSI | JHANSI | UTTAR PRADESH | 284001 | ₹44.9 L+₹15.5 L (52.6%) | L4 | Rejected-Finance Other than lowest bidder |
| 5 | Rejected-Technical | - | - | Rejected-Technical Rejected due to not uploaded requisite documents as per NIT. |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
2 Apr 2024, 6:00 pmClosed
GE BABINA
GE BABINA CANTT BABINA 284401
REPAIR/ REPLACEDMENT OF EXTERNAL ELECTRIC SUPPLY WORKS INCLUDING LT PANEL/FEEDER PILLAR BOXES OF ZONE 2,6,7,8,11 AND 12 AREA AT BABINA CANTT
2024_MES_645080_1
8156/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE BABINA
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE BABINA
₹90,000
Yes
12 Jun 2024
4 Mar 2024
4 Apr 2024
4 Mar 2024
2 Apr 2024
19 Mar 2024
Amount
Excavation in trenches in soft/loose soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed.
Excavation in trenches in any type of soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed.
Returning filling in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed.
Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed.
M & L for laying of fine, clean sand (river sand) free from sharp materials and stone particals in trenches for cushioning of cable 8 cm thick under cable and 15 cm thick over the cable including gently punning complete all as specified and directed. Note:- The total thickness of sand shall be measured 18 cm after punning.
Supply and laying un-reinforced precast.concrete cable protection cover of class LV, type-1, flat size 250mm x 150mm x 40 mm, factory made of specified make , complete all as specified and directed.
M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) as in coping etc including form work for poles all as specified and directed by Engr-in-Charge.
M&L for PCC 1:4:8 type D-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete for poles all as specified and directed by Engr-in-Charge.
M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete including form work for poles all as specified and directed by Engr-in-Charge.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 400Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 185Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 150Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 95Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 70Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 50Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 25Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 16Sqmm 4 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 10Sqmm 4 core as per IS 7092 Pt -I complete all as specified and directed.
Supply , installing, testing and commissioning factory made and tested, CPRI approved LT feeder pillar, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated . The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and LT panel shall be as per IS/IEC 61439-I: 2011 & IS/IEC 61439-2 : 2011 and mounted on angular frame work of 50x50x5mm thick angle iron base frame work, minimum 60 cm high and fixed with PCC 1:4:8 type D2 (using 40mm graded stone aggregate) in foundation for fixing panels, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door shutter and locking arrangement and consisting of the following all as specified including taking down old feeder pillar and taking out LT cables from loop for connecting in new panel and necessary excavation etc and consisting of the following:- Note:- (a) Panel drawings and make of MCCB will be submitted by contractor for approved by GE before orders the panel. (b) The holes/ aprons of cable entry/ exit will be closed with suitable size of glands.
M & L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to galvanised earth lead 4 mm dia by means of bolts, nuts, check nuts and washers of galvd iron or steel surronded by charcoal of coke and salt and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 5 of MES schedule Pt I of 2009 and also including making test point for testing of earthing made out of gun metal or phosphorous bronge size 75x75x25 mm complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item.
S&F in replacement kiosk box for luminaires ,weather proof made out of HDPE/FRP housing fire retardant, non fusing, shock & rust proof, single piece moulded and cover with hinged door, pole mounting type comprising of four pole copper connectors of 16 Amps capacity with 6 Amp MCB single pole , of minimum size 300x200x125mm, fixed on pole with MS, clamps 30 x 5mm with necessary nuts, washer and incl applying two coats of synthetic enamel paint over a red oxide primer on steel surface/clamps and embossing/painting of Danger sign of size not less than 10cms x 7.5cms with letter and conventional skull and bones in single red color on front face of kiosk box complete all as directed. The quoted rate also includes cost for material & repalcement of 4 sqmm multistranded twincore aluminium cable ISI marked from overhead conductor to junction box and replacement of 3 core copper cable of 1.5 Sqmm ISI marked from junction box to security light length as per required at site. Make-Syntex/Supreme/Hensal
S & F in replacement of GI brackets for fixing LED street light fitting fabricated out of GI tubing 40 mm dia, medium grade, 1.2 mtr long , bend to 120 degree shape by cutting, welding and well finishing including MS clamp of flat iron of size 32 x 4 mm -02 Nos complete for steel poles / PCC pole as per site requirement with nut, bolt & washers for fixing of GI bracket complete all as specified and directed.
S&Fin replacement of new generation energy saving and enviromental friendly long life LED security/ street light fitting made up of innovative die cast aluminium housing high power LED as lighting source with IP-65 power consumption 45 W complete input voltage of 150-240 Volts (Normal rated voltage 240Volts) complete including replacement of twisted 3 core copper cable of size 1.5Sqmm dia for connecting phase, neutral and earth from junction box to LED light through copper connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED security/ street light fittings made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 70/72 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED security/ street light fittings made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 90 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED security/ street light fittings made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 120 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 100 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 150 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 250 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F for replacement & testing commissioning of outdoor type bus bar panel weather proof MS cubical panel board made of 3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 300 Amp capacity with MCCB 4 pole of Capacity 200 Amp 25 KA (Ics =Icu=100%) including one coat of redoxide and two coat of enamel paint powder coated, mounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hight and fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside and PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels & aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed.
S&F for replacement & testing commissioning of outdoor type bus bar panel weather proof MS cubical panel board made of 3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 300 Amp capacity with MCCB 4 pole of Capacity 160 Amp 25 KA (Ics =Icu=100%) including one coat of red oxide and two coat of enamel paint powder coated, mounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hight and fixed with PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside and PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels & aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed.
M & L for decorative LED post top gate light of capacity 20 W with IP 65 pretection resistant to impact and corrosion, glare free and better uniformity complete all as specified and as directed.
M & L for decorative LED bollard stainless steel 9 watt weather proof light(warm white) with acrylic diffuser complete with all accessaries complete all as specified and as directed.
Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP-31) 9.0 mtr long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with two coats of aluminium paint over one coat of red oxide primer and incl taking down existing old unserviceable poles complete all as specified and directed. (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size as directed.) Note :- Excavation incl earth work and PCC foundation will be measured and paid separately.
Supply, erecting and fixing in replacement of true vertical position, prestressed concrete pole 9.0 mtr long 102 mm x 172 mm at top and 152 mmx 279 mm at bottom class 10 (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size) including taking down of old unserviceble pole & shifting of cross arms ACR conductor , GI wire, insulator, street light brackets etc complete all as directed. Note :- Excavation incl earth work and PCC foundation will be measured and paid separately. The old unserviceable pole obtained from dismanting shall be remove by the contractor form cantt area/MOD. If the contractor has not removed the dismantled item a penality of Rs.500.00 per pole will be charged from the contractor as a penality.
S & F in replacement of MCCB, 04 Pole, capacity 40 Amps with ultimate breaking capacity 16 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 63 Amps with ultimate breaking capacity 16 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 100 Amps with ultimate breaking capacity 16 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 160 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 200 Amps with ultimate breaking capacity 36 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 250 Amps with ultimate breaking capacity 36 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S & F in replacement of MCCB, 04 Pole, capacity 400 Amps with ultimate breaking capacity 36 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed.
S&F TPN HRC type rewireable switch fuse unit of 415 Volt 50 Hz three phase of capacity 32 Amp including MS box with backelite fuse & fuse carrier fittings , operating insulated handle, top cover necessary locking arrangemnts etc as per IS/IEC 60947 1&3 including necessary wall mounting fitting as directed including taking down the existing all as specified and directed. Make : INDOASIAN / L&T/Havells
S&F TPN HRC type rewireable switch fuse unit of 415 Volt 50 Hz three phase of capacity 63 Amp including MS box with backelite fuse & fuse carrier fittings , operating insulated handle, top cover necessary locking arrangemnts etc as per IS/IEC 60947 1&3 including necessary wall mounting fitting as directed including taking down the existing all as specified and directed. Make : INDOASIAN / L&T/Havells
S&F TPN HRC type rewireable switch fuse unit of 415 Volt 50 Hz three phase of capacity 100 Amp including MS box with backelite fuse & fuse carrier fittings , operating insulated handle, top cover necessary locking arrangemnts etc as per IS/IEC 60947 1&3 including necessary wall mounting fitting as directed including taking down the existing all as specified and directed. Make : INDOASIAN / L&T/Havells
S&F TPN HRC type rewireable switch fuse unit of 415 Volt 50 Hz three phase of capacity 200 Amp including MS box with backelite fuse & fuse carrier fittings , operating insulated handle, top cover necessary locking arrangemnts etc as per IS/IEC 60947 1&3 including necessary wall mounting fitting as directed including taking down the existing all as specified and directed. Make : INDOASIAN / L&T/Havells
S & F in replacement of off load change over switch, 1000 Amps, 4 pole, AC 415 Volt, 50Hz in SS enclosure side handle operated complete all as specified and directed.
S & F in replacement of off load change over switch, 630 Amps, 4 pole, AC 415 Volt, 50Hz in SS enclosure side handle operated complete all as specified and directed.
S & F in replacement of off load change over switch, 200 Amps, 4 pole, AC 415 Volt, 50Hz in SS enclosure side handle operated complete all as specified and directed.
S & F in replacement of off load change over switch, 100 Amps, 4 pole, AC 415 Volt, 50Hz in SS enclosure side handle operated complete all as specified and directed.
S & F in replacement of off load change over switch, 63 Amps, 4 pole, AC 415 Volt, 50Hz in SS enclosure side handle operated complete all as specified and directed.
Supply & fixing GI tube 50 mm bore light grade with all fittings for laid in trenches/fixed along with poles/walls & floor of buildings etc under crossing of road for protection of cables including demolition and taking down of the old existing pipe including repair of the floor/wall and matching with the existing surface if required complete as directed by Engineer-in-Charge.
S & F and replacement of cross arms, bracing, supports clamps and back plates fabricated from structural steel sections incl nuts & bolts, washers, welding bending cold or hot, drilling holes for bolts in any shape or size and inclusive of one red oxide primer coat, one under coat and one finishing coat of synthetic enamel paint complete all as specified and directed.
M&L for painting of steel tubuler 11/9 mtr poles any type complete incl flat iron clamps, D clamps, Stay clamps, earth wire clamps, bracing, cross arm with two coat aluminium paint including prepration old painted surface initally & applying one coat of red oxide, applying two coat of aluminum paint over the red oxide, marking with alternate white and red strips 30 cm height 5 Nos strips with two coat of synthetic enamel paint (Ist quality of manufacturer )and also including numbering of poles with white paint are located on different locations complete all as specified and directed .
M & L for cutting of road up to 0.75m deep suitable for laying underground cable/MS tubes of any size/dia including GI pipe of 50mm dia and making good the disturbed area to match with the existing level with cement concrete including removing the surplus soil to a distance upto 50mtrs complete all as specified and directed.
Trimming of tree branches touching to over head lines, upto 1.5 mtr distance all around of ACSR conductors of span 30meter to 50 meter of HT/LT feeders and depositing cut branches away from site as directed and clearence of HT/LT pole and sub station premises all as directed by Engg-in-charges. Note: (i) Trimming of all branches of trees falling under one span between two pole shall be shall be considered as as one span only. (ii) Contractor have to arrange all T&P , safty equipments manpower and vehicle for trimming at different locations. Contractor or his rep has to ensure power shut down of overhead lines before carrying out trimming. Contractor shall be responsible for any lapses/ mishapning occured due to negelency of safty aspects.
Taking out under ground, HT/LT cables, any sizes, by excavation and earth work in any type of soil, removing bricks or PCC tiles of any size, re-laying in the same trenches for re-routing /after rectification of fault as required complete all as specified and directed NOTE:- (i) Joint and joiting materials, new cables, additional bricks, sand shall be measured & paid for separetely. (ii) Retrieved serviceable bricks or PCC cable cover and sand shall be re-laid on the cable & the cost for the same is deemed to be included in the unit rate. (iii) Cost for excavation, R&F, removing shall be included in quoted rate.
SHRI HARI CONSTRUCTION
ROHIT ENTERPRISES
M/s BRIJ KUMAR RAI
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .