Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.3 CrAdmitted-Finance | ₹20.3 Cr | L1 | Admitted-Finance |
| 2 | L2₹29.9 CrAdmitted-Finance GREAMS DUGAR 4TH FLOOR OLD NO 149 NEW NO 64 GREAMS ROAD COIMBATORE 600006 | COIMBATORE | COIMBATORE | TAMIL NADU | 600006 | ₹29.9 Cr | L2 | Admitted-Finance |
| 3 | Rejected-Technical NO 82 ALLINGI GOUNDER THOTTAM THIRUMALAIGIRI NADUCOMBAI POST KALAPPANAICKENPATTY NAMAKKAL 637 404 | NAMAKKAL | TAMIL NADU | 637404 | - | - | Rejected-Technical Not Responsive |
| 4 | Rejected-Technical NO 1A 41 SUB LANE 1 PARAMATHI ROAD NAMAKKAL 637 001 | NAMAKKAL | TAMIL NADU | 637001 | - | - | Rejected-Technical Not Responsive |
| Sl No | Description | Qty | Unit | SDSP ENGINEERING PROJECTS LLP L1 | SATTVA ENGINEERING CONSTRUCTION LIMITED L2 |
|---|---|---|---|---|---|
| 1.00Construction of Integrated Command & Control Center at CMWSSB Head office Chintadripet Chennai. | |||||
| 2.00Bill No. 1 - Preparation of site | |||||
| 3.00 | Clearing scrub jungle | 1,403 | Sqm | 5 ₹7,015 | 16 ₹22,448 |
| 4.00 | Uprooting and removing large palmyrah /coconut stumps | 10 | Each | 150 ₹1,500 | 7,899 ₹78,990 |
| 5.00 | Soil Investigation & Survey | 1 | LS | 1,00,000 ₹1 L | 1,18,490 ₹1.2 L |
| 6.00 | Temporary Power | 1 | LS | 63,000 ₹63,000 | 78,993 ₹78,993 |
| 7.00 | Barricading | 140 | Rm | 97 ₹13,580 | 1,896 ₹2.7 L |
| 8.00 | Demolition of Existing Structures | 1 | LS | 50,000 ₹50,000 | 1,57,986 ₹1.6 L |
| 9.00BILL NO.2 - CIVIL WORKS | |||||
| 10.00 | BORED PILE 450 mm Dia
Providing and installing Bored cast-in-situ reinforced cement Concrete pile of specified diametre and length below the pile cap in RMC M 35 concrete to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including Bentonite solution machinery charges labour chargres etc., all complete. (Length of pile for payment shall be measured from bottom pile to the bottom of pile cap). | 910 | Rmt | 3,011 ₹27.4 L | 2,684 ₹24.4 L |
Updated dates
Tender Value
Refer Docs
EMD Value
₹7.8 L
Closing Date
11 Feb 2026, 3:00 pmClosed
Superintending Engineer (C and M)
Office of Superintending Engineer, Contracts Monitoring, 4th Floor, CMWSS Board, No.1, Pumping Station Road, Chintadripet, Chennai 600 002
Construction of Integrated Command and Control Center at CMWSSB Head office Chintadripet Chennai
2025_CMWSS_631020_1
CNT/WSS/NCB/MWB/3706/2025-26
Open Tender
Construction Works
365 days
Chennai
Please refer Tender documents
6 documents required · 6 mandatory
₹0
₹7.8 L
4th floor, tender opening hall
14 May 2026
13 Dec 2025
12 Feb 2026
13 Dec 2025
11 Feb 2026
24 Dec 2025
17 Dec 2025
Bill No. 1 - Preparation of site
Clearing scrub jungle
Barricading
BILL NO.2 - CIVIL WORKS
BORED PILE 450 mm Dia Providing and installing Bored cast-in-situ reinforced cement Concrete pile of specified diametre and length below the pile cap in RMC M 35 concrete to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including Bentonite solution machinery charges labour chargres etc., all complete. (Length of pile for payment shall be measured from bottom pile to the bottom of pile cap).
BORED PILE 500 mm Dia Providing and installing Bored cast-in-situ reinforced cement Concrete pile of specified diametre and length below the pile cap in RMC M 35 concrete to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including Bentonite solution machinery charges labour chargres etc., all complete. (Length of pile for payment shall be measured from bottom pile to the bottom of pile cap).
BORED PILE 600 mm Dia Providing and installing Bored cast-in-situ reinforced cement Concrete pile of specified diametre and length below the pile cap in RMC M 35 concrete to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including Bentonite solution machinery charges labour chargres etc., all complete. (Length of pile for payment shall be measured from bottom pile to the bottom of pile cap).
BORED PILE 750 mm Dia Providing and installing Bored cast-in-situ reinforced cement Concrete pile of specified diametre and length below the pile cap in RMC M 35 concrete to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including Bentonite solution machinery charges labour chargres etc., all complete. (Length of pile for payment shall be measured from bottom pile to the bottom of pile cap).
BORED PILE 900 mm Dia Providing and installing Bored cast-in-situ reinforced cement Concrete pile of specified diametre and length below the pile cap in RMC M 35 concrete to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including Bentonite solution machinery charges labour chargres etc., all complete. (Length of pile for payment shall be measured from bottom pile to the bottom of pile cap).
Dismantling RCC by manual / by using deploying machineries
Excavation inhardstiff clay, stiff blackcotton, hardred earth, shales, muram, gravel stoney earth and earth mixedwithsmallsizeboulders asperSS20Bwithinitial lead of 10m and lift of 2.0m
Excavation inhardstiff clay, stiff blackcotton, hardred earth, shales, muram, gravel stoney earth and earth mixed with small size boulders as per SS20B with initial lead of 10m and lift of 2.0m - Extra for every additional ten metres lead or part thereof over initial lead
Supplying and filling in foundation and basement with excavated soil other than sand in layers of not more than 15cm thick well rammed watered and compacted etc., complete complying with standard specification.
Supplying and filling Crushed stone sand (M-sand) for foundations and basement including watering consolidating ramming, etc., complete
Providing Pest control and Anti-termite treatment by appointing a specialised agency as per the specifications mentioned by the Bureau of Indian Standards and Agencies specifications (whichever is higher), for General Civil, Plumbing,/ Drainage and timber/ Carpentry works, Gypsum related work, including a 10-year guarantee under suitable undertaking on stamp paper etc, complete as directed. (Mode of measurement to be on carpet-area of floor and not the area of surface treated.)
Cement Concrete 1:3:6 (One Cement, Three crushed stone sand and Six broken stone jelly) using 40mm size hard broken stone jelly excluding cost of centering shuttering reinforcement grills and fabrication charges but including curing etc. complete and as directed by the departmental officers. - Mixing by mechanical means
Providing formwork for centering shuttering etc. for all RCC works including strutting for height upto 3.29m using mild steel sheets of size 9 90 X 60 cm 10 gauge stiffened with MS angle of 25 X 25 X 3mm for boarding, laid over adjustable span & jacks and supported by 50mm dia pipes for general pipes scaffolding systems @ a spacing of 1.20m c/c and vertical connected at a height of 2.0m c/c including 'C' & 'U' clamps and base receiver cup at bottom for connecting pipes etc and removable systems etc., Rate to include all materials, labour charges, wastages , placing, transportation, lead & lifts, tools & plants, fuels, fixing in position at all levels, heights, masking tape in sheet joints, consumables, etc. as complete with all respects complying with relevant standard specification, as directed by the Client / Engineer-in-charge.
Providing form work with centering for soffits of reinforced cement concrete slabs or plain surfaces including strutting upto 3m high
For column footing plinth beam bed blocks templates staircase, steps piers, raft beam, raft slab etc.
For plane surfaces such as rectangular or square rcc columns, sunshades, top and bottom slab of rcc boxing, etc.
For plane surfaces such as vertical slab, side slabs of boxing, vertical drops, facia, vertical walls etc.
Supplying and fabricating CRS/Thermo Mechanically Treated High Corrosion Resistance bars manufactured by Primary steel producers/Integrated Steel Plants as per IS:1786-2008,including fixing with binding wires, assembling and laying in position for all RCC works
Providing and Laying M 35 Design Mix (Cement - 400 kg/cum) for all reinforced cement concrete with minimum cement content conform to IS 456-2000 using ordinary Portland cement of grade 53 from approved manufacturer, manufactured sand, 20 mm and down graded size coarse aggregates, necessary approved admixtures as per requirement. works for Raft, Grade beam, Shear wall, RCC walls, Lift walls, Plinth beams, Column, footings, Grade slab, Roof slab & beam, Curved slab, beam, Column drops, Pergola, Staircase waist and landing slab lintel, Sunshades, parapet Cum drops, Steps, canopy, window boxing slab, Loft, fins facia Planter box binders basement retaining wall, machine foundation, elevation features and other similar structures etc..excluding necessary centering, shuttering and reinforcement which shall be measured and paid separately under relevant items. Rate to include all designing the mix, batching plant, mechanical mixing, transporting and placing at all levels, leads, lifts, tools & plants, fuels, all materials, labour charges, wastages , laying, pumping the concrete to all levels, providing sleeves / openings in RCC slabs, compaction by vibrator, curing etc. as complete with all respects complying with relevant standard specification, as directed by the Engineer- in-charge
For Basement
For Ground Floor
For First Floor
For Second Floor
For Third Floor
Stock brick work with II class bricks in cement mortar 1:4 (Crushed stone sand (M-sand)) for over 23cm thick wall including curing etc. complete
For Basement
For Ground Floor
For Third Floor
Brick partition walls of 11.50cm thickness using best quality II Class Ground Chamber Burnt Bricks of size9" x 41/2" x 3" in Cement Mortar 1:3 (One Cement and Three Sand), using hop iron ith reinforcement if found necessary. The lop iron shall be should be supplied by department at free of cost,including curing etc. complete and as directed by the departmental officers
Plastering with cement mortar 1:3 (Crushed stone sand (M-sand)) for 15mm thick including curing, etc., complete
Plastering with cement mortar 1:4 (Crushed stone sand (M-sand)) for 12mm thick including curing, etc., complete
Plastering with cement mortar1:4 (Crushed stone sand (M-sand)) for 20mm thick including curing, etc., complete
White washing one coat
Painting with two coats of readymixed plastic emulsion paint first class quality and of approved colour over a primingcoat including thorough scrapping clean removal of dirt,etc.,complete and including necessaary plaster of paris, putty, etc., wherever required.
Painting two coats with approved cement paint over cement plastered wall surface, ceiling and other new surfaces including cleaning preparing the surfaceand curing, etc., complete
Paving Hydraulic Pressed Cement Double Charged Vitrified Tiles of size 600x600x8mm finished thickness with small Verona or Indian MarbleChips (other than Salem Magnasite) with CM1:3, 20mm thick and painted with same colour Cement including polishing with power polisher to a high degree of polish so as to be perfectly smooth and glossy with GREY colour. Location : Office Space, Reception, Dining, Etc.
Ceramic tile Floor 305 mm x 305mmx6mm Paving the floor with palin/design ceramic tiles (colour and shade as directed) of size 305mmx305mmx6mm in all floors over a base layer of cement mortar 1:3 (one cement and three crushed stone sand (Msand)) 20mm thick laid in situ and pointed with same coloured cement. Location: Toilet Area.
Dadooing walls with glazed tiles of sizes 15cmx15cmx6mm thick laid in CM1;2,10mm thick and pointing with white cement using 0.4Kg/m2 including finishing the joint and pointing flush with tile surface,etc.,complete . Location: Toilet Area.
Paving the floor with best approved quality fine polished Granite Stone Slabs (Steel Grey - Size:1200mm x 600mm, 16mm to 18mm Thick ) of following size and Variety with machine cut edges laid over a cement mortar bed of 20mm thick using cement mortar 1:3 (One cement and three crushed stone sand) with required Cement Slurry and Mortar Plasticizer and laid in true right angles with minimum possible width of joints and pointing the joints with white cement mixed with mathcing colouring pigments etc., complete complying with standard speicification and as directed by the departmental officers.(The granite stone slabs and other materials to be used shall be got approved by the Executive Engineer concerned before use on work)complete as per standard. Location: Staircase Lobby, Tread & Risers.
Best Indian T.W. panelled door shutter for double leaf door. The shutter shall be of 40mm thick with moulded panels in 20mm thick inclusive of 6 Nos. of butt hinges 125mm long furniture iron fittings 1 No. of iron padlock 15cm long for locking arrangements 2 Nos. of Jappened cabin hooks and eyes 200mm long and 6mm thick including fixing position, etc., complete.
Providing and
Providing and laying Brick jelly Lime concrete 1 : 2 : 5 in Toilet sunken areas, including Leading, Lifting, mixing, laying finishing etc, and laid in layers not more than 15 cm thick and compaction etc, Complete.,
Water Proofing for Bathroom/Toilet/ balcony/utility with Cementatius Waterproof coating Providing and Applying CFTRI approved two component flexible polymer modified acrylic cementitious waterproofing coating with a mix ratio of (5 Liquid :7 Powder) to the RCC surface like Roof, bathroom, toilet, balcony & utility area applied @ 2.2kg/m2 in 2 coats to achieve 1.2mm DFT, having Elongation at break >120% as per ASTM D 412, Tensile strength >1N/mm2 as per ASTM D 412, Adhesion strength: 0.80N/mm2 as per ASTM D 4541, crack bridging upto 2mm as per ASTM C 836. The finished cost to include surface preparation, making coving of 50 mm X 50mm at all right angles of wall Junction with Polymer Repair Mortar and lay 45 gsm glass fibre mesh over the angle fillet when the first coat in still wet, treatment of cracks completely as per specification
PROTECTIVE PLASTERING Plastering with cement mortar 1:3 (Crushed stone sand (M-sand)) for 12mm thick including curing, etc., complete.
Supplying and laying of Interlocking Paver Block Stone 83mm thick Over a base layer of crushed stone sandfilling incl. Cost of materials laying and Labour charges etc complete complying with the standard specification and as directed by the departmental officers.
Structural Glazing: 8mm+12mm+6mm Providing, assembling and Supplying of Double Glazed Performance glass, heat Strengthened clear Glass (IGUs) of size and shape as required and specified of approved, comprising of an outer heat strengthened clear glass of following thick of approved colour and shade with reflective soft coating on surface #2 and an inner heat strengthened clear glass of following thick , spacer tube 12mm wide , dessicants, including primary seal and secondary seal ( structural silicon sealant ) etc. all complete for the required performance , as directed by the engineer -in - charge. The heat strengthened clear glass having properties as visible Light transmittance (VLT) of 25 to 35 %, Solar heat gain coefficient less than or equal to 0.27 and U value of 3.0 to 3.3 W/m2 or lower degree K etc. The IGUs shall be assembled in the factory/ workshop of the glass processor. For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm.
Existing Administrative office building to be connected with the proposed ICCC Building in 3rd based on the sutability of the site condidtion.
Supply and fixing of 15mm dia CP pillar cock for wash basins with pipe nipples, teflon tape, all accessories required etc. The cost shall include cutting and making good the wall wherever required, including cost of materials, labour, all complete as per specifications
Supplying & fixing in position 15 mm dia PVC Bib Tap of approved make conforming to I.S. Specifications & quality including cost of shellac, thread etc., complying with standard specifications & including cutting & threading wherever necessary. (Taps should be got approved by the Executive Engineer before use on the work)
WATER SUPPLY - PIPES AND FITTINGS
65 mm dia (73.2 mm Avg OD)
25 mm dia (28.6 mm Avg OD)
Supply, fixing, testing and commsisioning of uPVC pipes (Schedule 80) confirming to ASTM F-441 standard including all including all uPVC fittings fixing accessories, solvent wall chipping, support for fixing pipes and making good the walls and floors.
20mm dia
40mm dia
Supplying, fixing and testing of lever operated gun metal Wheel/Gate valves with fittings of screwed end type. all complete as per specifications
65 mm dia GM Gate Valve
50 mm dia GM Gate Valve
40 mm dia GM Wheel Valve
25 mm dia GM Wheel Valve
SOIL & WASTE - PIPES & FITTINGS
Supply, fixing, testing and commsisioning uPVC Pressure pipe (Ring-fit) soil waste vent pipe of Class 3 (6 Kgf/cm2) conforming to IS 4985-2000 including all CPVC fittings fixing accessories, solvent wall chipping , support for fixing pipes and making good the walls and floors.
50 mm dia
40 mm dia
Supply, fixing, testing and commsisioning uPVC SWR (Type B, Ring fit) soil waste vent pipe conforming to IS 13592-1992 including all CPVC fittings fixing accessories, solvent wall chipping , support for fixing pipes and making good the walls and floors.
110mm dia
75mm dia
Supply, fixing, testing and commsisioning uPVC Pressure pipe (Ring-fit) soil waste vent pipe of Class 5 (10 Kgf/cm2) confor
ming to IS 4985-2000 including all CPVC fittings fixing accessories, solvent wall chipping , support for fixing pipes and making good the walls and floors.
160 mm dia
Supplying & fixing in position PVC Nahini / Floor trap of size 100x75mm including stainless steel gratings of approved brand & quality, fixed over a bed of brick jelly lime concrete 1:2:5 ( One part of lime, two parts of sand & five parts of 40 mm size brick jelly ) & finished with cement mortar 1:3 ( One cement & three sand ) including dismantling masonry works wherever found necessary & making good the damaged portions to the original condition & giving connections to the cast iron pipes etc., complete, complying with standard specification. (The PVC Nahini / Floor trap should be got approved by the Executive Engineer before use on works )
Supplying and fixing in position PVC cowls of following dia of best approved quality conforming to BIS, etc., complete complying with standard specifications. (The PVC cowl should be got approved by the Executive Engineer before use on works).
110mm Dia
75mm Dia
Providing and fixing square mouth SW gully trap 100mm dia grade ' A' complete with C.I grating burnt brick masonry with CM (1:4) and plastering with water tight heavy duty double seal C.I cover, frame of 45x45 cm size The weight of the cover to be not less than 4.52 kg of frame to be not less than 2.75 Kg.
450 X 450mm size ' P' trap
Construction of inspection chambers of following sizes with earth work excavation for foundation with 23cm thick brick jelly cement concrete bed in C.M.1:4:10 using 40mm Brick jelly for foundation, brickwork inC.M. 1:6 for chambers, plastering withC.M. 1:3 12mm thick, benching, channelling, 75mm thick RCC loose slab covering in C.M.1:2:4 mix using 20mm blue granite jelly including necessary reinforcement, etc., complete for
Inside size of 600mm x 600mm and depth exceeding 1200mm
75mm dia
Providing and fixing FRCcover and frame of size 60 x 60cm including necessary masonry work and plastering, etc., complete
RAIN WATER DRAINAGE - PIPES AND FITTINGS
Supply, fixing, testing and commsisioning uPVC Pressure pipe (Ring-fit) soil, waste vent pipe of Class 3 (6 Kgf/cm2) conforming to IS 4985-2000 including all CPVC fittings fixing accessories, solvent wall chipping , support for fixing pipes and making good the walls and floors.
Erection of Pre-Cast/Modular Ring Recharge Pit 0.9m Dia, 6m Depth with Sand,Pebble,Boulder Filling of 530mm Each along with the drilling Borewell 150mm dia upto a depth of 3m with 125mm dia Blue slotted PVC pipe including top cover slab all around the building .
Making Through holes in plain or Reinforced Cement Concrete with Diamond Core drilling system by using Bosch Power Tools of Following Diameter in Various thickness and Dia
150mm Dia
Supply and fixing of MS angle supports, channels and other supporing structure for suspending, mounting pipes and other fittings
RO PLANT:
Supplying and erecting in position of 2000 liters capacity Industrial Model Reverse Osmosis Water-cum Purifier to deliver Potable Water with World Health Organisation (WHO) Standards with following accessories. (a) MS Skid - 1 No. (b) Media 11054 No. Vessel with 20 nb Multiport Valve (with Media Pubble and Fine Sand and Activated Carbon Filling) set (c) Feed Pump 0.50 HP – 1 No. (d) Vertical Pump 2-9, 2.00 HP / Single Phase – 1 No. (e) Membrane 40 x 40 filmtech (or) equilaents / Osmonic (USA) - 1 No. and Membrane Pressure Vessel 40 x 40 -1 No. & Pressure Gauge - 2 Nos. (f) Flow Meter - 1 No. 20” Filter with Housing - 1 No., Low Pressure Switch - 1 No., Level Switch - 1 No. & Necessary CPVC Pipes and Fittings. The system shall be provide with Two Panel Control System with necessary Stainless Valves and Fittings and Float Control etc. The rate should be inclusive of all civil works, wherever necessary to install the System in position and intact
Supply,Erection and Testing & Commisioning of SS body water dispenser approved by concern department Engineer before use on work
Supply ,erection and testing & commisioning of 3HP submersible pumpset in the Open borewell fitted with bronze impellers and having delivery size of 40mm - 430V along with 3mts cable and manufactures standard control panel which is mandatory and as directed by the officer incharge.
Labour charges for the erection of submersible pumpset in borewell/openwell including fixing and jointing submersible cable with proper clamps upto the starter to required depth and also fixing of riser pipes to the required depth valves erection clamps, pressure gauges upto the exterior wall of pump room and erection of panel board consisting of TPICN switches starter, Voltmeter, Ammeter, three pilot (indicating) lamps capacitor single phasing preventor, water level guard and laying and jointing the cables and twin earthing as per IE rules etc., complete and testing the pumpset and trail run for 10 days.
Bill No.4 : Fire Fighting System
SPRINKLER SYSTEM
Supply, erection, jointing, testing & commissioning of `C' Class M.S heavy grade piping as per IS : 1239 - 2004 / IS:3589 - 2001. The pipes being suspended from beams, RCC roof slabs with necessary specials such as tees, bends, flanges redcuers etc., complete.Rate quoted shall also include for painting of pipe with one coat of primer & two coats of synthetic enamel paint of approved colour & make.
150 mm dia
SOIL & WASTE - PIPES & FITTINGS
Supply, fixing, testing and commsisioning uPVC Pressure pipe (Ring-fit) soil waste vent pipe of Class 3 (6 Kgf/cm2) conforming to IS 4985-2000 including all CPVC fittings fixing accessories, solvent wall chipping , support for fixing pipes and making good the walls and floors.
100 mm dia
80 mm dia
65 mm dia
SPRINKLER SYSTEM
Supply, erection, jointing, testing & commissioning of `C' Class M.S heavy grade piping as per IS : 1239 - 2004 / IS:3589 - 2001. The pipes being suspended from beams, RCC roof slabs with necessary specials such as tees, bends, flanges redcuers etc., complete.Rate quoted shall also include for painting of pipe with one coat of primer & two coats of synthetic enamel paint of approved colour & make.
32 mm dia
25 mm dia
Supply, erection, testing and commissioning of slim seal type butterfly valves with Shperoidal graphite iron disc (SG iron), with nitrile rubber seal and tested to 10kg/sq.cm including a set of suitable GI flange, as per BS 10 Table - 1, bolts, nuts GI washer, neoperene rubber gaskets etc., complete. (intervalve make)
Supply,erection, testing and commissioning of 15mm dia nomial bore quartzoid bulb pendent type sprinklers with temprature rating of 68 deg C, conventional type including with CI taper special confirming to BS 164. The rate shall also include suspending arrangement with ceiling, wall arrangement with ceiling, wall beam clamps,fasteners etc., complete.
Supply, erection, jointing, testing & commissioning of `C' Class M.S heavy grade piping as per IS : 1239 - 2004 / IS:3589 - 2001. The pipes being suspended from beams, RCC roof slabs with necessary specials such as tees, bends, flanges redcuers etc., complete.Rate quoted shall also include for painting of pipe with one coat of primer & two coats of synthetic enamel paint of approved colour & make.
Spray recessed (adjustable) rossette (68 deg.C) sprinkler quick response
Pendant Type
Supplying, Installing, testing and commissioning flow switch including installed on the sprinkler main distribution line connected to the main sprinkler annunciation panel located in the ground floor.
Providing, fixing pipe supports from columns / wall or suspenders from roof slab to suit various dia of pipes made out of GI / MS adjustable rods threaded for a sufficient length to adjust the height of support along with clamping arrangement for holding pipes of anchor fastening, arrangement design of hanger and should confirm with specification
Supply, fixing, testing and commsisioning of uPVC pipes (Schedule 80) confirming to ASTM F-441 standard including all including all uPVC fittings fixing accessories, solvent wall chipping, support for fixing pipes and making good the walls and floors.
100mm dia
80mm dia
50mm dia
Supply and testing of approved type rosette plates for sprinklers at false ceiling.
Flexible hose 1500 mm Long
Supply of Extention nipple
HOSE REEL SYSTEM
Supply, installation of Fire Fighting Application 180 degree swinging type, hose reel drum with 20mm dia braided thermoplastic hose of 30 metres long, so as to extend to necessary distance by self rolling spin
dle wheel including necessary 20mm dia ball valve and open and close spray nozzle, warm clip, etc., as per the standard pattern of any reputed make at every floor nearer to hydrant valve, including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary., etc., complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFE GUARD / SAFE GUARD / EQUIVALENT.
Supply, erection, testing and commissioning of Fire Fighting 4 Way Fire Brigade Inlet with necessary gun metal 63mm dia non return spring shutter arrangements, so that to control one way flow at the time of emergency water supply by fire and rescue service fire engine entry including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: KIARTAR / OMEX / EQUIVALENT.
Supply, erection, testing and commissioning of Air Release Valve of 20mm dia, so as to release airlock in 100mm dia MS pipe at top most wet riser, including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: KARTAR / EQUIVALENT.
Supply, erection, testing and commissioning Mono Block type Fire Fighting Pressurisation Pump of 450 LPM with suitable base frame including necessary vibration bad mounting etc., including conveying, fixing and incidental charges., etc., complete as per standard specification and as directed by the Departmental Officers. (Make: Kirloskar / Equivalent)
Making Through holes in plain or Reinforced Cement Concrete with Diamond Core drilling system by using Bosch Power Tools of Following Diameter in Various thickness and Dia
MISCELLANEOUS
Supply and fixing of stored pressure ABC (Mono Ammonium Phospate) Powder Type Fire Extinguisher of 4.5 kg. capacity as per IS:15683 with pressure gauge, discharge hose & control nozzle, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc, complete as per standard specification and as directed by the Departmental Officers. Make: EXCELLENT / SAFETY FIRST / EQUIVALENT
Supply and fixing of Carbon-di-Oxide Gas Type 2 kg. capacity Fire Extinguisher as per New IS15683, complete with control valve, discharge hose with horn, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc., complete as per standard specification and as directed by the Departmental Officers. Make: EXCELLENT /SAFETY FIRST / EQUIVALENT
Supply and fixing of Clean Agent Type 5 kg. capacity Fire Extinguisher as per New IS15683, complete with control valve, discharge hose with horn, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc., complete as per standard specification and as directed by the Departmental Officers. Make: EXCELLENT /SAFETY FIRST / EQUIVALENT
DG SET
Supply and Erection of 200 KVA DG Acoustic enclosure as per standard manufacturing ,3- ph 415 V 50 Hz skid mounted operation, synchronizing panel Diesel Power Generator (Silent Type) including the scope as follows: Supply, Installation, testing and commissioning of Radiator based water cooled D.G. set along with necessary Hospital silencer, expansion bellows, exhaust piping with necessary support structure of MS channels & I - Beams, harmonic filter if required, and all other accessories required for installation of D.G. set as per specification and datasheet. The set should have following specifications. The DG Set shall be suitable for indoor and outdoor application and should have the required IP Protection.
Design supply and installation of extended exhaust piping to collect & expel exhaust gases from engine cylinders, for the DG set
R mtrs
MV SWITCHGEAR & POWER PANELS:
Supply, loading, unloading alongwith Mathadi charges and shifting to Main LT Panel Room at Podium-P4 level, installation, testing and commissioning of cubicle type panels as specified and shown on drawing. The boards shall be designed and fabricated as per general specifications, technical details, specifications and notes as part of this tender /BOQ and relevant BIS codes. Also, refer to General Notes and Specifications for Panels/Boards. All the tools, tackles and Machineries shall be part of vendor scope.
All Panels are IEC 61439
GENERAL NOTES FOR ACB's & MCCB's:
ACB's & MCCB's shall be of 3P or 4P as called for in the BOQ.
Ics = Icu = 100% for the MCCB's, MPCB's & ACB's
MCCB's shall be with extended rotary handle.
Protection relay testing & tripping relay coordination is in vendor's scope.
Notes:
Main Aluminium busbars as specified in the drawings with bar type feeder connections & all internal wiring (with FRLS wires) and connections.
Earthing all components,frame etc. to a common internal earth bar.
Painting all sheet metal works.
All accessories & supporting structure.
Brass glands and crimping lugs for sending and receiving ends.
All ammeters with C.T's and voltmeter and energy meters with necessary fuses as shown and as required.
All Load Managers, Power Monitors to have parameters like KW, KVA, A, V,KWhr,Hz,PF,KVAR, Active & Reactive component of power, RS 485 port to have BMS compatibility as required & desired to complete the system.
Panel components as specified.
MS base frame with finish as per specification.
All switch gear to have short circuit levels as specified.
All communicable meters should be looped inside the panels and this loop has to be brought to one terminal point in the panel for connectivity.
No BMS cable should be directly connected to VFD and hence these points will have to brought on to the terminal blocks inside the panel.
All energy meters shall be dual source and communicable type.
EMC & RFI FILTRATION FOR VFD's.
VFD’s for sensitive installations where life critical data communications are of importance ,like Hospitals, Airports, Electronic Industry, Data centres, Communication centres. These installations Must have ‘C1’ category of RFI & EMC filters for 50 meters of cable length. These are applicable to all the VFD’s of AHU’s, fans, blowers, pumps and cooling towers. For these above mentioned critical applications, if chiller motors and pump motors are more than 90Kw, then ‘C2’ category of filters to be used if ‘ C1’ is not available. VFD’s for normal buildings and others similar installations shall have ‘C3’ category of RFI & EMC filter for AHU’s , fan
s, blowers, pumps, cooling towers & Chillers .
THDI for VFD's between 35% and 40% .
All VFD's shall be IP-20, if installed inside the panels and shall be IP55 if installed without enclosure.
Incomer switchgear, bus bars, supports and outgoing switchgear shall be of same fault level withstand capacity as mentioned for the panel.
All starter feeder / VFD feeder in panels means complete with starter & VFD as the case may be as per specifications.
Use separate PLC's for Load management and separate for interlocking of breakers and bus couplers and closing of bus couplers.
Fire Suppression System provision to be made (with 8mm drilling) in the desired panels as mentioned in the SLD, during panel manufacturing.
All ACB body earthing to provided.
APFC panel - MLTP Terminal to cut off APFC power while power feed from DG source.
Door locks Zinc alloy powder painted with provision for pad locking.
Busbar insulation: Black heat shrinkable, fire retardant, self extinguishing type sleeves suitable to withstand 110 degree celcius.
Completely modular & compartmentalized, form 3B separation. Separate adequately spaced Unit Chamber, Bus bar & cable compartments.
Gland earthing provision to be given in the panel.
All Load Managers shall be of CL-0.2 accuracy & all Ammeters shall be of CL-0.5 accuracy.
All metering CT's shall be of CL-0.2S.
All panels shall be as per IEC-61439 Standard.
Considered TP+100%NL for MCCB's & ACB's wherever TPN MCCB/ACB is mentioned in SLD.
All panels that are intended to be at terrace level or above ground floor to have tranport section limited to max. 900-1100mm.
Main LV Panel
EB Incomer:
1 Nos. 400 Amps 4 Pole 50kA MCCB with shunt release shutter assembly, door interlock and all other accessories with three over current and one earth fault releases as shown in the Electrical schematic drawing.
Each Incomer shall have
1 No. 400A/5A CT with CL: 1 5P10,15VA with suitable control fuse For APFCR RELAY in the capacitor panel, and CT for REF for Transformer Neutral to be incorporated as per SLD
1 No. Spike Protection Device with connected with suitable control fuse(Type B+C)
1 No.Maximum Demand controller and 1 No. Digital type Multifunction meter with RS Port and connected with 1 No..400A/5A CL.1 15VA CT
1 Set.of 2 overcurrent and 1 Earth fault relay are connected with 1 NO.400-/5A CL.5P10 15VA CT
Master Trip relay & Stand By Earth fault relay, over voltage relay with all related connected accessories.
1 Set of 'RYB' and 'ON','OFF','TRIP' indication lamps connected with suitable control fuse
DG Incomer:
1Nos. 400 Amps 4 Pole 50KA MCCB with shunt release shutter assembly, door interlock and all other accessories with three over current and one earth fault releases as shown in the Electrical schematic drawing.
DG Incomer shall have
1 No.Digital type Multifunction meter with RS Port and connected with 1 NO.400/5A CL.1 15VA CT and necessary protection CTs as per SLD
Interlock Arrangements:
Both EB & DG incomers shall be electrically and mechanically interlocked through burden rope as per the Truth Table mentioned in the SLD and should be compatible to PLC(Programmable Logic Controls.) operations. I/C of DG, Transformer and Bus Coupler should be suitable to all type of conditional operation. Necessary control should be incorporated to the Client requirement and safety operations. All control circuits should fail safe condition to be incorporated.
BusBar:
400 Amps TPN 50KA Al. busbars : Current density consider 0.8 Amp/1Sq.mm. Neutral Busbar shall be the same size of Phase busbar.
Earthing : 2R 50 x 6mm Aluminium flat
OUTGOINGS
All incoming and outgoing breakers should have over current, Time adjustable short circuit and earth fault releases. Necessary Flange connection for Bus duct entry to be included. All the Outgoing feeder shall be ON/OFF/Trip status for BMS , indication lamps , & MULTIFUNCTION METER , with emergency lockable push buttons, all ACB and MCCBs should have one (spare) potential free contactor, Combined digital type Multi function meter with LAN port. Each LAN port of the meter connected through individual cable. , The rate shall inclusive of necessary CTs, control switches, Front operating handles etc., All switch boards shall be fabricated as per the detailed specification enclosed. Suitable size outgoing cable chamber and extra busbars should be provided for connecting the number of outgoing cables as per the schematic drawing. 320A MCCB Switch - 2Nos 250A MCCB Switch - 3 Nos 160A MCCB Switch - 1 Nos 100A MCCB Switch - 2 Nos
The transformers incomer, DGs incomer shall be provided with protection relays REFR with CTs at transformer side (Restricted Earth fault Relay), Both the incomers should be interlocked with mechanical and electrical arrangementsby hardware control wiring along with PLC (Programmable Logic Controls). The Hardware control wiring & PLC operation
400Amps 4P aluminium busbars:- All the neutral busbars shall have the same capacity of phase busbars. Necessary proper ventilation to be provided for heat disceptation
Note: All MCCBs shall have rotary handle mechanism and spreader wherever necessary.
MAIN PANEL AS DESCRIBED ABOVE
FIRE PUMP PANEL Supplying, installation, testing and commissioning of Fire Fighting Electrical Control Panel of cubical construction, floor mounted type fabricated using CRCA sheet, compartmentalised with hinged lockable door dust and vermin proof, cable alley, inter connection having switch gears and accessories mounting and internal wiring, earth terminals, numberings, necessary metering protections and indications complete in all respect suitable for operation on 415volt, 3
phase, 50 Hz AC supply with enclosure protection class IP 54 and mounted with the followings. (i). Incomer a. 1 No. 160A 4P MCCB Outgoings : b. 40A 4P MCB with RYB Indicator - 2 Nos c. 100A 4P MCCB with RYB Indicator - 2 Nos
AC Panel Supplying,erecting,connecting & commissioning FLOOR MOUNTED CUBICLE TYPE 14 SWG thick CRCA sheet compartmentalised modular type with powder coated SUB POWER PANEL.The Board shall be incorporated with the following:- INCOMER: 200 AMPS TPN MCCB With 25KA(Ics) Withstanding Capacity With adjustable Over load and Short circuit releases with RYB Indications. OUTGOINGS : 100 AMPS FP MCCB with 16KA(Ics) - 1 No. (for 20HP ODU - 1 nos) 63 AMPS 4P MCCB with 16KA(Ics) - 8 No's (for 18HP ODU - 1no, 14HP ODU - 1 nos, 12HP ODU - 1nos, 10HP ODU - 2 Nos, 12HP ODU - 1 No and 2 Nos of spare)
Mechanical Panel Supplying,erecting,connecting & commissioning Wall Mounted Cubicle type 14 swg thick CRCA Sheet compartmentalised modular type with powder coated sub power panel .The Board shall be incorporated with the following:- INCOMER: 100 AMPS TPN MCCB With 25KA(Ics) Withstanding Capacity With adjustable Over load and Short circuit releases with RYB Indications. OUTGOINGS : 63 AMPS FP MCCB with 16KA(Ics) - 4 No's. (for lift motor - 2 nos and Spare - 2Nos )
UPS Main Power panel Supplying,erecting,connecting & commissioning Wall Mounted Cubicle type 14 swg thick CRCA Sheet compartmentalised modular type with powder coated sub power panel .The Board shall be incorporated with the following:- INCOMER: 100 AMPS TPN MCCB With 25KA(Ics) Withstanding Capacity With adjustable Over load and Short circuit releases with RYB Indications. OUTGOINGS : 63 AMPS FP MCCB with 16KA(Ics) - 9 No's. (for UPS DB's Lighting and power - 7 nos and Spare - 2Nos )
Lighting Power panel Supplying,erecting,connecting & commissioning Wall Mounted Cubicle type 14 swg thick CRCA Sheet compartmentalised modular type with powder coated sub power panel .The Board shall be incorporated with the following:- INCOMER: 100 AMPS TPN MCCB With 25KA(Ics) Withstanding Capacity With adjustable Over load and Short circuit releases with RYB Indications. OUTGOINGS : 63 AMPS FP MCCB with 16KA(Ics) - 6 No's. (for Lighting and power - 4 nos and Spare - 2Nos )
Street Lighting panel Supply , fixing , unloading , testing and commissioning:- Incomer - 25 A FP MCB,16kA - 1 no Outgoing : 25 A , 4P MCB,16kA - 8 Nos , 25 A , 2P MCB,16kA - 2 Nos with Logitudue based timer for auto control with Necessary RYB Indicator Panel inclusive of Surge protections,MFM, RYB Indicator, 63A TPN AI Busbar
Supply, Installation, testing & Commissioning of RCCB/RCBO/MCCB/ MCB Isolators as per technical Specifications, as shown in the drawing and as per section 1.0 mentioned above complete with all necessory accessories required to complete the job including structural supports.
63A, 4P, 300mA, `S' Type RCBO IP67 in M.S. Enclosure fixed on Din channel along with cable termination box suitable for Ar. Cable up to 16 sq mm & fixing arrangement -for VRV Outdoor unit for common space
40A, 4P, 300mA, `S' Type RCBO IP 67 in M.S. Enclosure fixed on Din channel along with cable termination box suitable for Ar. Cable up to 16 sq mm & fixing arrangement -for and Odu units Passenger lift
SITC of 30kVA UPS with 60 min battery backup complete with the required accessories as specified including the cost of the battery, interconnecting flexible cables/wires between the inverter and battery racks and within the battery racks and all the other necessary accessories to complete the job. UPS full load and backup test in factory is must. Isolation transformer not required in UPS with Mod bus card for BMS contetivity UPS full load and backup test in factory is must. Isolation transformer not required in UPS - for Computer systems
SITC of 10kVA UPS with 120 min battery backup complete with the required accessories as specified including the cost of the battery, interconnecting flexible cables/wires between the inverter and battery racks and within the battery racks and all the other necessary accessories to complete the job. UPS full load and backup test in factory is must. Isolation transformer not required in UPS with Mod bus card for BMS contetivity UPS full load and backup test in factory is must. Isolation transformer not required in UPS - for Lighting
SITC of 10kVA UPS with 120 min battery backup complete with the required accessories as specified including the cost of the battery, interconnecting flexible cables/wires between the inverter and battery racks and within the battery racks and all the other necessary accessories to complete the job. UPS full load and backup test in factory is must. Isolation transformer not required in UPS with Mod bus card for BMS contetivity UPS full load and backup test in factory is must. Isolation transformer not required in UPS - for Server rack , security systems
100 amp, 4P MCCB with fixed thermal & magnetic releases in M.S. Enclosure fixed on Din channel along with cable termination box suitable for Cable up to 35 sq. mm & fixing arrangement for UPS (IP 42)
40 amp, 4P MCB with fixed thermal & magnetic releases in M.S. Enclosure fixed on Din channel along with cable termination box suitable for Cable up to 35 sq. mm & fixing arrangement for UPS (IP 42)
DISTRIBUTION BOARDS:
Supply, installation, testing & commissioning of 500V Distribution Boards as specified & shown on drawing with:
Copper busbars together with tapped neutral bar for individual phases. All Indoor DBs are IP 42 & IP43 & outdoor is IP 54
Copper earth strip with tapping for EEC
Interconnections and earthing.
Sheet steel enclosure suitable for recessed or surface mounting with hinged lockable doors interlocked with the incomer switch.
Phase to phase barriers in case of 3Ph boards. PPI kit to be consider for phase barrier
Necessary support frame & painting, labelling, phase indicating lamps etc. complete.Standard DB to be consider without fuses & fabricated DB to be consider with Fuses. Supports required for DB will be consider on KG basis in item number 1.4.
Weatherproof Enclosure suitable for outdoor mounting. (IP-55) (for all external and street lighting DBs)
1 # Timer & 1 # Daylight Sensor with all necessary components (for all external lighting DBs)
DB enclosure thickness of 1.2mm as per manufacturing standard.
Lighting / Lighting+Power Distribution Boards as specified
8 Way 7 Segment TPN Double door Lighting Distribution Board for Computer systems and Floor wise Raw power Lighting and power DB comprising of:
Necessary support frame & painting, labelling, phase indicating lamps etc. complete.Standard DB to be consider without fuses & fabricated DB to be consider with Fuses. Supports required for DB will be consider on KG basis in item number 1.4.
Incomer:
63 Amp 4P MCB
DB enclosure thickness of 1.2mm as per manufacturing standard.
3# 63Amp DP RCCB(30 mA)
Outgoing:
Necessary support frame & painting, labelling, phase indicating lamps etc. complete.Standard DB to be consider without fuses & fabricated DB to be consider with Fuses. Supports required for DB will be consider on KG basis in item number 1.4.
24 # 6/10/16/20 Amp SP MCB
DB enclosure thickness of 1.2mm as per manufacturing standard.
6 Way 7 Segment TPN Double door Lighting Distribution Board for UPS Lighting and power comprising of:
40 Amp 4P MCB
3# 32Amp DP RCCB(30 mA)
18 # 6/10/16/20 Amp SP MCB
8 Way SPN Distribution Board for Lift Lighting & Power and Stilt floor ups lighting comprising of:
32 Amp DP RCBO (30mA)
8# 6/10/16/20 Amp SP MCB
LT CABLES, CONTROL CABLES & CABLE TRAYS:
The rate shall also include the following:
Effecting adequate and proper connections at terminations.
Providing all fixing accessories such as clamping devices nuts, bolts and screws.
Excavation for laying of cables, filling of sand, brick protection, back filling of earth, watering, ramming and making good as approved in directly ground burry.
Wherever the cables are of aluminum and bus bars of copper bimetallic lugs shall be used.
All cable shall be laid with one diameter gap or as specified or as called for.
All cable shall be IS approved.
Fire retardent paint one meter on both side of wall penetration and at terminati
on as per specifications.
Burried LT cables to be laid atleast 750mm below ground.
All cutouts / sleeves shall be sealed with fire retardant sealent as approved.
Use Tinned copper thimbles/lugs with copper cables/copper wires.
Nylon cable tie is not acceptable, matelic cable tie/clamp to be consider for cable laying.
Supply, laying, fixing, testing & commissioning of following sizes of heavy duty 1.1kV grade XLPE insulated, Extruded FR-LSH PVC inner sheath Type ST-2, FR-LSH PVC outer sheath Type ST-2, stranded Aluminium/Copper conductor Armoured/Unarmoured cables as per IS:7098 Part-I on existing cable trays/ in existing hume pipes/ PVC pipes/ GI pipes/ on surface of slabs, walls or masonary/ RCC trenches/ ducts including cables ties, GI saddles, clamps and necessary hardware.
Armoured Aluminium XLPE Cables:
3.5C x 240 sq.mm. A2XFY FRLS 1.1 kV Cable
3.5C x 95 sq.mm. A2XFY FRLS 1.1 kV Cable
3.5C x 35 sq.mm. A2XFY FRLS 1.1 kV Cable
3.5C x 25 sq.mm. A2XFY FRLS 1.1 kV Cable
All cutouts / sleeves shall be sealed with fire retardant sealent as approved.
Use Tinned copper thimbles/lugs with copper cables/copper wires.
Nylon cable tie is not acceptable, matelic cable tie/clamp to be consider for cable laying.
Supply, laying, fixing, testing & commissioning of following sizes of heavy duty 1.1kV grade XLPE insulated, Extruded FR-LSH PVC inner sheath Type ST-2, FR-LSH PVC outer sheath Type ST-2, stranded Aluminium/Copper conductor Armoured/Unarmoured cables as per IS:7098 Part-I on existing cable trays/ in existing hume pipes/ PVC pipes/ GI pipes/ on surface of slabs, walls or masonary/ RCC trenches/ ducts including cables ties, GI saddles, clamps and necessary hardware.
Armoured Copper XLPE Cables:
3.5C x 240 sq.mm. A2XFY FRLS 1.1 kV Cable
3.5C x 95 sq.mm. A2XFY FRLS 1.1 kV Cable
4C x 10 sq.mm. 2XWY FRLS 1.1 kV Cable
4C x 6 sq.mm. 2XWY FRLS 1.1 kV Cable
4C x 6 sq.mm. 2XWY FRLS 1.1 kV Cable
4C x 4 sq.mm. 2XWY FRLS 1.1 kV Cable
3C x 6 sq.mm. 2XWY FRLS 1.1 kV Cable
Making cable end termination of following sizes of heavy duty 1.1kV grade XLPE insulated, Extruded FR-LSH PVC inner sheath Type ST-2, FR-LSH PVC outer sheath Type ST-2, stranded Aluminium/Copper conductor, Armoured/Unarmoured cables as per IS:7098 Part-I including cost of aluminium/tinned copper, heavy duty crimpping lugs, Single compression glands, insulation tape and all necessary material to complete the termination.
Terminations for Alumunium XLPE Cables:
Terminations for Copper XLPE Cables:
Supply, fabrication and installation of Hot dip galvanised factory built perforated type cable trays complete with all bends, tees, elbows, reducers, supports & fixing arrangement etc. of various widths in single tier/two tier/ three tier/ five tier fashion either on one side of the wall or on two sides of the wall or ceiling/wall/floor. (All bends & tees shall be of factory built of same make as that of tray). Cable tray supports are supposed to be included in the rate of the trays. Nothing extra to be paid for cable tray supports. Cable trays and supports shall be as per specifications. Cable tray supports shall also be Hot dip galvanised. Use modular factory fabricated cable tray supporting system as per specifications. Contractor to be responsible for the design and execution of a failsafe cable supporting system.
Cable tray supports shall be included in cost of cable tray. Support to be considered as MS for indoor installation & GI for outdoor installation.
150mm wide tray 2mm thick & 50mm collar
300mm wide tray 2mm thick & 50mm collar
450mm wide tray 2mm thick & 50mm collar
600mm wide tray 2mm thick & 50mm collar
LIGHT FIXTURES:
Supply,Installation, testing & commissioning of light Fixtures complete with:
All fixing accessories & mounting bracket.
Earthing of fittings.
Connections with CU conductor PVC flex connection cord , ceiling rose junction box cover plate to the light fixures including the terminations with all necessary accessories. i) Cost of connectors, Junction box cover plate included. ii) Cost of ceiling rose & flex connrction cord not included
with mounting bracket for the external terminal lights as shown in the drawings
All Light Fixures with Electronic Ballast with THD <10%.
Supply of light fittings shall be in client's scope.
Cost should be inclusive along with required accessories like chains/supports/brackets & consumables to be considered in ITC part of light fitting.
All Light Fixures with Electronic Ballast with THD <10 %
SITC of 18W Battern LED Linear Light similar to PHILIPS or equivalent make subject to architects\ clients approval.
SITC of 18W LED Bulk Head similar to PHILIPS or equivalent make subject to architects\ clients approval.
SITC of 10W LED mirror light. Philips or equivalent subject to architects/clients approval.
SITC of 18W Round LED Surface mount Light similar to PHILIPS or equivalent make subject to architects\ clients approval.
SITC of 1x15W LED recessed type light fixture of Philips or equivalent subject to Lighting consultant/clients approval.
SITC of 24W LED Square panel light fixture. Philips or equivalent subject to architects/clients approval.
SITC of 10W LED Parapet wall light fixture. Philips or equivalent subject to architects/clients approval.
SITC of 1x60W Exhuast fan of Crompton or equivalent subject to Electrical consultant/clients approval.
Supply and fixing of 65mm dia GI pipe (Class 'B') of 4 metre length with 300mm x 300mm x 6mm MS base plate duly welded at the bottom and with concreting and construction on masonary pedestal with MS box of 30cm x 20cm x 10cm with angle iron frame work with door with lock and key arrangements and with supply and fixing of 30 W LED street light fitting with bulb and fixing of 1 No. 70W SV lamp and with supply and fixing of 16A fuse unit, (500V), 5A SP switch inside the MS box and painting with suitable colour
CONDUIT WIRING:
Supply and installation Conduit wiring for lights/ socket outlets consisting of:
PITC of 25 mm / 32 mm / 50 mm dia PVC HMS grade Conduit for Conceal Conduiting including bends , junction boxes, pull boxes, GI pull ( fish) wire including necessary civil work such as chese, cutting, chipping, making good for recessed conduiting.
PITC of PVC HMS grade conduit - 25 mm
PITC of PVC HMS grade conduit - 32 mm
PITC of 25 mm / 32 mm dia , 16 SWG GI Conduit for surface conduiting including bends , junction boxes, saddles & spacers , hardware with all the required accessories.
PITC of wiring with 2.5 sq.mm. / 4.0 sq.mm. wires/cables:
PITC of 2 x 2.5 sq mm + 1 x 2.5 sq mm stranded CU conductor PVC insulated FRLS flexible wires with terminations and all required accessories. (for primary light points)
PITC of 2 x 1.5 sq mm + 1 x 1.5 sq mm stranded CU conductor PVC insulated FRLS flexible wires with terminations and all required accessories (for secondary light points)
PITC of 2 x 4 sq mm + 1 x 4.0 sq mm stranded CU conductor PVC insulated FRLS flexible wires with terminations and all required accessories (for power points main point)
PITC of 2 x 2.5 sq mm + 1 x 2.5 sq mm stranded CU conductor PVC insulated FRLS flexible wires with terminations and all required accessories (for power points loop point)
PITC of 2 x 4 sq mm + 1 x 4.0 sq mm stranded CU conductor PVC insulated FRLS flexible wires with terminations and all required accessories
Supply & Installation of switches, sockets, mild steel electrogalvanised switch box etc. complete with earthing. Make Legrand: Myrius
2# 6A Plate type switch
3# 6A Plate type switch
4# 6A Plate type switch
5/6# 6A Plate type switch
7/8# 6A Plate type switch
1# 6A Two Way switch
16A plate type switch + 6/16A plate type socket.
6A plate type switch + 6A plate type socket.
16A plate type switch + 6/16A plate type socket. (IP:67)
ELEVATOR LIGHTING:
SITC of 25 mm dia, 16 SWG MS Conduit for surface conduiting including bends , junction boxes, saddles & spacers , hardware with all the required accessories.
For Lighting
Supply & Installation of switches, sockets, mild steel electrogalvanised switch box etc. complete with earthing. Make Legrand: Myrius
For Power
Wires:
SITC of 2 x 2.5 sq mm + 1 x 1.5 sq mm stranded CU conductor PVC insulated FRLS flexible wires with termination with all the required accessories. (For primary point wiring)
SITC of 2 x 1.5 sq mm + 1 x 1.5 sq mm stranded CU conductor PVC insulated FRLS flexible wires with termination with all the required accessories. (For secondary light points)
SITC of 2 x 4.0 sq mm + 1 x 4.0 sq mm stranded CU conductor PVC insulated FRLS flexible wires with termination with all the required accessories. (For power points)
SITC of switches, sockets, mild steel electrogalvanised back box etc. complete with earthing and all the required accessories.
1# 6A Plate type switch
SITC of 1x9W LED Bulkhead Luminaire with 1# 9W LED Lamp with all th
EARTHING:
Earth wire/strips
Supply & laying Cu/G.I. earthing strips for interconnecting the earthing stations, panels, DB's etc. in built-up trenches, on walls/ceiling, buried in ground, generally as specified & shown on drawings complete with:
Fixing accessories.
Corrosion protection of buried conductors with bituminous coating and covered with PVC tapes.
GI Strips:
50 x 6 mm G.I. Strip
25 x 6 mm G.I. Strip
Copper Strips:
50 x 6 mm Cu. Strip
25 x 6 mm Cu. Strip
GI PLATE EARTHING - EARTH PIT
Providing & making earthing stations including testing at locations as called for, including providing and laying of 600 x 600 x 6.3mm thick GI plate electrode, 20mm dia medium class GI pipe, CI funnel with 18 gauge GI wire mesh, masonry chamber with concrete base, heavy duty manhole cover, lockable cover with frame 300 x 300mm and bitumastic paint , packing of mixture of charcoal & common salt around plate electrode including test joint complete with digging earth and back filling required as per IS:3043 (Depth as per site conditions, however, not less than 3m).
COPPER PLATE EARTHING - EARTH PIT
Providing & making earthing stations including testing at locations as called for, including providing and laying of 600 x 600 x 3.15mm thick copper plate electrode, 20mm dia medium class GI pipe, CI funnel with 18 gauge GI wire mesh, masonry chamber with concrete base, heavy duty manhole cover, lockable cover with frame 300 x 300mm and bitumastic paint , packing of mixture of charcoal & common salt around plate electrode including test joint complete with digging earth and back filling required as per IS:3043 (Depth as per site conditions, however, not less than 3m).
GI Wires
8 SWG GI for DB's
The rates shall include the following :
Assembling loose components of the various equipment as per manufacturer's instructions.
Bonding on to masonry /concrete work including cutting /drilling holes through walls /floors and grouting with cement mortar 1:2.
All fixing accessories such as rawl bolts, nuts screws etc. as required.
Effecting adequate and proper connections.
Effecting proper bonding to earth.
Touching up all damaged paint over equipment with one coat of red oxide primer and two finishing
Providing all fixing accessories such as clamping devices, nuts and bolts, screws where laid in trenches/trays.
Providing thimbles, insulation tape etc. at joints and terminations as called for.
Providing proper supports for cable terminal boxes as called for.
All protective relays testing are in the scope of Electricals Contractor.
SAFETY AND TESTING EQUIPMENTS:
Supplying and erection of the following equipment at suitable place in the sub-station building as required.
M.S. buckets 4 nos. of 20 litres capacity painted with red oxide paint & lettered as ‘Fire’ with White and mounted on free standing stand, as required including filling with dry sand.
First aid box as approved by St. John Ambulance Brigade /Indian Red Cross society conforming to IS : 2217 - 1963.
Providing and fixing High Voltage danger notice plate 250 mm. x 200 mm. made of M.S. 2 mm. thick and vitreous enamelled white on both sides and with inscription in signal red colour on front side as required.
Providing and fixing Medium Voltage Danger Notice Plate 200 mm. x 200 mm. made of MS 2 mm. thick and vitreous enamelled white on both sides and with inscription in signal red 'colour on front side as required.
Insulating Mats
Elastomer mat 1000 mm. wide, 2mm thick, for upto 3.3kV grade as per Latest BIS Codes (IS: 15652/2006). (Vendor to check the thickness of the mat as per latest IS code & Quoe accordingly and also mention the thickness provided).
Elastomer mat 1000 mm. wide, 3mm thick, for above 11kV and upto 65kV grade as per Latest BIS Codes (IS: 15652/2006). (Vendor to check the thickness of the mat as per latest IS code & Quoe accordingly and also mention the thickness provided).
Insulating Rubber Gloves
Rubber gloves of 11kV grade as per per Latest BIS Codes
Pairs
GRID FOR LIGHTNING PROTECTION IN SOIL FOR BUILDING
Design, supply, installation, testing and commissioning of following Building Earthing and Lightening Protection Systems
Supply, erection and testing of building lightning arrestor for the building height of 50feet with 1set of lightning spike, 1No. 11KV post top insulator, 1No. 5 to 10feet long 2" dia GI pipe, 25x3mm bare copper flat as earth conductor from terrace to ground, supporting bus bar insulator or 32mm PVC pipe etc. The rate shall excludes schafolding, necessary supporting clamps but including civil works for stone cutting to fix MS frame on wall / floor wherever required.
APPROVALS:
INSTALLATION APPROVAL CHARGES:
Designing and preparation of CEIG drawings, obtaining Approval and safety certificate including submission of Completion report and rectification report.
AC Panel Supplying,erecting,connecting & commissioning FLOOR MOUNTED CUBICLE TYPE 14 SWG thick CRCA sheet compartmentalised modular type with powder coated SUB POWER PANEL.The Board shall be incorporated with the following:- INCOMER: 200 AMPS TPN MCCB With 25KA(Ics) Withstanding Capacity With adjustable Over load and Short circuit releases with RYB Indications. OUTGOINGS : 100 AMPS FP MCCB with 16KA(Ics) - 1 No. (for 20HP ODU - 1 nos) 63 AMPS 4P MCCB with 16KA(Ics) - 8 No's (for 18HP ODU - 1no, 14HP ODU - 1 nos, 12HP ODU - 1nos, 10HP ODU - 2 Nos, 12HP ODU - 1 No and 2 Nos of spare)
Bill No. 6 : CCTV, Voice & Data Works
40 Amp 4P MCB
4C x 10 sq.mm. 2XWY FRLS 1.1 kV Cable
4C x 6 sq.mm. 2XWY FRLS 1.1 kV Cable
4C x 6 sq.mm. 2XWY FRLS 1.1 kV Cable
CCTV Systems - Internal
SITC of 18W Round LED Surface mount Light similar to PHILIPS or equivalent make subject to architects\ clients approval.
SITC of 1x15W LED recessed type light fixture of Philips or equivalent subject to Lighting consultant/clients approval.
SITC of 24W LED Square panel light fixture. Philips or equivalent subject to architects/clients approval.
Supply,Installation, testing and Commissioning of the following list of items
4MP IP Dome Camera
Camera Accessories
8TB Hard Disk
32 channels NVR switch including of required poe switches , ofc patch cables, patch panel, 42U Rack with Tray, Fan & PDU
22U Rack with Tray, Fan & PDU including of required poe switches , ofc patch cables, patch panel with required NVR Channels
63A, DP, 100mA, `S' Type MCCB IP47 in M.S. Enclosure fixed on Din channel along with cable termination box suitable for Ar. Cable up to 16 sq mm & fixing arrangement -for Main server rack
300mm wide tray 2mm thick & 50mm collar
PITC of PVC HMS grade conduit - 25 mm
PITC of CAT 6 Cable, Telephone cable and Fibre net wiring
PITC of CAT 6 with terminations and all required accessories. For Data , Camera , WIFI , Intercom
Supply and laying of FRLS PVC insulated 2 core 1.5 sq.mm. Armoured Copper Cable on ceiling / wall using fixing accessories like screws, plug, clamps, etc., as per standard methods and as directed by the Departmental Officers
Data,Wifi systems,Telephone systems,attendance systems
Supply,Installation, testing and Commissioning of the following list of items
wifi 6 2x2 Access Point
CAT6 I/O with Backbox and Face Plate
IP Phone - Table mounted
RJ 45 Jack for Data point
Hybrid IP EPABX System and Telephone 6 Trunk + 10 SIP Trunk + 64 Analog Extensions Expandable Up to 96 analog Extension + 112 IP Port
Supply,Installation, testing and Commissioning of the following list of attendance systems:-
Attendance system
Exit switch
EM Lock (600 LBS)
L/U Clamp for Door
proximate thin card (Billing at actuals based on the user)
Fire Alarm systems :-
Supply,Installation, testing and Commissioning of the following list systems:-
Manual call point Addressable
Hooter Module Addressable
Addressable Fire Alarm Control Panel consists of display board which will have 160 Character Display with Touch key pad, Mother board 32 Bit Processor, In-built RS-485 Networking Circuit for peer to peer networking, In-built USB 2.0 Port, Loop Card having 254 devices of both detectors and modules in a single line circuit, SLC supports both Class A and Class B wiring Approval 2 Loop panel
Addressable Smoke Detector
Addressable Heat Detector
LED Video Wall
Supply fixing and commisioning of 20x5 ft active LED Videowall P1.56 including Videowall controller with 20 HDMI Input, Work station, 20 KVA UPS, with all fabrication, structure frames and accessories
Shifting of existing Videowall and its allied works MCC room
Shifting of existing Videowall and its allied works -GIS room
PA System with Video Confrence system with related Accessories (Bosch/CCSD-CML)
Bill No. 7 HVAC -VRF System works
VRF INDOOR & OUTDOOR UNIT
VRF SYSTEM
Supply of VRV/VRF Modulating outdoor units, with Inverter scroll compressor with variable speed Inverter compressor, S Box , Sense Mesh , electrical & microprocessor panel, isolating valves and all the necessary accessories for proper functioning of the units, having following capacities.
Supply of Indoor Units of the following actual capacities. The scope includes required supports with necessary Panels, bolts, screws & nuts etc, and necessary interconnections with Power supply / earthing / Refrigerant Connections Complete as required and as per drawing.
Casette type 4 way
Casette type 1 way
Hi Wall unit (With Wireless Remote)
Supply of Refnet Joints/ Branch Distributors for Indoor & Outdoor units with insulation
Supply & Installation of of Hard copper REFRIGERANT PIPING of various sizes with necessary supports, fittings, interconnecting the liquid and suction lines between the VRF outdoor units and the indoor units with 19mm thick insulation
6.35mm Dia
9.52mm Dia
12.7mm Dia
Addressable Smoke Detector
Addressable Heat Detector
LED Video Wall
Supply fixing and commisioning of 20x5 ft active LED Videowall P1.56 including Videowall controller with 20 HDMI Input, Work station, 20 KVA UPS, with all fabrication, structure frames and accessories
Shifting of existing Videowall and its allied works MCC room
Shifting of existing Videowall and its allied works -GIS room
PA System with Video Confrence system with related Accessories (Bosch/CCSD-CML)
Bill No. 7 HVAC -VRF System works
VRF INDOOR & OUTDOOR UNIT
VRF SYSTEM
Supply of VRV/VRF Modulating outdoor units, with Inverter scroll compressor with variable speed Inverter compressor, S Box , Sense Mesh , electrical & microprocessor panel, isolating valves and all the necessary accessories for proper functioning of the units, having following capacities.
Supply of Indoor Units of the following actual capacities. The scope includes required supports with necessary Panels, bolts, screws & nuts etc, and necessary interconnections with Power supply / earthing / Refrigerant Connections Complete as required and as per drawing.
Casette type 4 way
Casette type 1 way
Hi Wall unit (With Wireless Remote)
Supply of Refnet Joints/ Branch Distributors for Indoor & Outdoor units with insulation
Supply & Installation of of Hard copper REFRIGERANT PIPING of various sizes with necessary supports, fittings, interconnecting the liquid and suction lines between the VRF outdoor units and the indoor units with 19mm thick insulation
6.35mm Dia
9.52mm Dia
15.9mm Dia
19.1mm Dia
28.6mm Dia
31.8mm Dia
Supply & Installation of 4C x 0.5 sq. mm. unarmoured copper cable in 20 mm dia PVC conduit for communication between indoor and outdoor units of VRF system
Supply, installation, testing and commissioning of initial Charge of refrigerant gas - R 410A
Supply of Touch Screen Central Remote Controller as Specified.The controller should be capable to Monitor and control upto 128 Indoor units, Scheduling, Interlock Control, Drawing View, Multi Level Grouping, Web Access, Emergency Stop & Alarm, error Alarm by E-mail, Compatible for Power Consumption monitoring and Energy Management, BMS Integration through BACnet IP/Modbus TCP, History/Operation Trend including cable, necessary support etc.,
Bill No. 8 - PASSENGER LIFTS
PASSENGER LIFTS (G+3) SS 304 Grade with 1m/sec. speed with ARD 13 - Persons Passenger Lift Car Size (2000 x 1100) - Gearless Lift without Machine Room( Higher End)
Bill No.9 LANDSCAPING
Supply and stacking of pit sand / earth filling sand at site to the departmental gauge for pre measurements obtained from sand deposits and should clean without solid particles
Supply & stacking of red earth at site to the departmental guage for pre-measurements which is of light textured, crystalline, porous and friable and not of generally acidic or neutral but not of alkaline and should be fertile, including seignior age charges, cost of transportation, loading, unloading, stacking and inclusive of all taxes etc., complete.
Spreading of red soil, gravel or sand including watering and rolling which hand roller for every 75 mm thickness - including hire charges of roller
Shade grass
Indoor Plants
Potted Plants
Palms Tree
Supplying and Planting of Pungam tree sapling of B31 height 240 –300 cm in polythene bag of size 20x21 inch including supporting stack of 5 cm dia casurina pole of 10 feet height, including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site in-charge
Providing Pest control and Anti-termite treatment by appointing a specialised agency as per the specifications mentioned by the Bureau of Indian Standards and Agencies specifications (whichever is higher), for General Civil, Plumbing,/ Drainage and timber/ Carpentry works, Gypsum related work, including a 10-year guarantee under suitable undertaking on stamp paper etc, complete as directed. (Mode of measurement to be on carpet-area of floor and not the area of surface treated.)
Supplying of plastic Potted plants Bogainvillea size of dia 12 inch including loading and unloading charges, transportation, etc as directed by the site in- charge
Supply and planting of Araucaria heterophyllum ornamental foliage tree of height 180-210cm in polythene bag of size 21×21 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
Supply and planting of Bougainvillea dwarf ornamental foliage shrub of height 30- 45cm in polythene bag of size 7×8 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
Supply and planting of Washingtoniafilifera ornamental foliage palm of height 120 - 150cm in polythene bag of size 21×21 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
Supply and planting of Leucophyllumfruitescens ornamental specimen plant of height 90-120cm in polythene bag of size 21×21 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
BILL NO.10 - INTERIOR & FURNITURE WORK
FIRST FLOOR
GENERAL WORK
GLASS PARTITONS :Supply of Single glazed partition system with 10mm thick toughend glass and shall be able to provide a sound reduction upto 36db. The glass panels shall be supported by Natural Anodized Aluminium Ground Profiles (AGGP) in 26x40mm (H), and connected to 26x40mm (H) ceiling profile (AGGP) attached to the suspended partition/ false ceiling. On the vertical edges the glass panels are wrapped around with 24x26mm Vertical profile (AGVP). Glass to glass joints shall be done using joint tape. The glass to glass joint at the corner to have 90°corner profile (AGHLA-90° - AGHLT-90°). The perpendicular glass junction (T-junction) AGTT - AGLA profile to be used. Glazed partition FFL to false ceiling shall be 2400mm ht. Finishes of all aluminium frame components shall be Natural Anodized Finished. Rate shall be inclusive of all transport.
GYPSIUM PARTITION: Providing and fixing 75 mm thick GI / Aluminum partition consisting of GI / Aluminum floor and ceiling tubes (of approved type and make) of 50 mmX25mm box sections (of suitable thickness) placed at 600mm centre to centre on 50 mm floor and ceiling Aluminum / GI box sections. Ceiling Aluminum box section to be taken to the U/S of coffer slab and suitably fixed to result in a very rigid frame. Horizontal bracing as required should be provided. 1 layer of 12.5 mm thick Gypsum Board to be fixed on either sides of the Aluminum / GI partition.. Joints of each layer of boards to be staggered. Finally square and tapered edges of the 12.5 mm thick Gypsum board are to be jointed and finished so as to have a flush look which includes filling and finishing with jointing compound, joint paper/fibre tape and two coats of drywall top coat suitable for Gypboard (as per recommended practice of India Gypsum/St Gobain).
Gypsam celing :Supply and Fixing of Saint Gobain Ultra Gyp Channel Frame work ,L - Angle Support and the Intermediate Channel Should be 3 to 4 feet per span Length and the bottom Section should be 2 feet.Saint Gobain 12.5mm thick gypsum board to be fixed.The Joints of the board should be finished with fibre tape with 2 coat of putty (saint gobain or POP ) and the joints should be even at all levels engineer in charge.
Calcium Cilicate celing :Supply and Fixing of Saint Gobain Ultra Gyp Channel Frame work ,L - Angle Support and the Intermediate Channel Should be 3 to 4 feet per span Length and the bottom Section should be 2 feet.Saint Gobain Calcium cilicate board to be fixed.The Joints of the board should be finished with fibre tape with 2 coat of putty (saint gobain or POP ) and the joints should be even at all levels engineer in charge.
DOORS
TOUGHENED GLASS DOORS :
Providing and fixing door made of 12mm toughened glass of approved make, supported on brushed finished stainless steel finish top an
d bottom hung patch fittings and Floor spring of Dorma make. The glass panel edges shall be properly machine polished. The 60% of the glass shall be fixed with 3M film for frosted/ etched effect to the pattern as indicated in the detail drawings. This also includes providing necessary hardware like handles, patch lock etc. of Hafele / Dorma /Geze or equivalent.
FLUSH DOORS
Providing, fabricating and placing single leaf door made with 38mm thick flush door finished in laminate of approved shades on both the surfaces of the shutters with grooves to pattern as indicated as per the detail drawing. 6mm thick glass vision panel of size 150x1800 with allround beading. The door will be fixed into wooden frame of size 100 x 50mm as per the detail drawings. The shutter shall have 1/2" x 2" Teak wood lipping all-round. All the exposed wooden surfaces shall be stained to shade as directed by the Architects and polished melamine. This also includes providing and fixing in position necessary hardware like handles, heavy duty floor spring, locks etc.of approved make with provision for fixing Access control readers/ locks as recommended by Architects...
FIRE DOORS
SHAFT DOORS
Supply, Fabrication and erection of double shutter Shaft Door (1000 X 2100mm) of Salwood frame (Size 100 X 62mm) with 6mm Thick tempered Black back painted glass on enox profile. Refer approved shop drawing for details, sizes and location of patch fittings and iron mongeries with Louvers (as applicable), Holds & Locks including material, labour, tools and tackels etc in Shaft / Janitor room
FIXED FURNITURES
STORAGES: P/F low ht. storage SC-2 750/900/1050/1200 high 450mm deep in 19mm thk.both sides prelam Board construction with 12mm thk. Ply backing. The horizontal and vertical divisions shall be as per the drawing/details. All edges will have edge banding tape/laminate of matching colour. All the shutters shall have autoclosing hinges and laminate/edge binding on the edges.
WORK STATIONS: P/F low ht. storage SC-2 750/900/1050/1200 high 450mm deep in 19mm thk.both sides prelam Board construction with 12mm thk. Ply backing. The horizontal and vertical divisions shall be as per the drawing/details. All edges will have edge banding tape/laminate of matching colour. All the shutters shall have autoclosing hinges and laminate/edge binding on the edges.
Supply and convey of fabricated specifically premium designed Ergonomic chair.
Supply and convey of fabricated specifically premium designed Executive chair with head rest.
Supply and convey of visitor chair.
Design, fabrication of Ultra classic design semi oval type table for Video conference hall with mat finish laminate and provision for installing power cable and voice controller systems with non-slip table top as approved by the Engineer.(10 Seater)
MANAGER CABIN: P/F low ht. storage SC-2 750/900/1050/1200 high 450mm deep in 19mm thk.both sides prelam Board construction with 12mm thk. Ply backing. The horizontal and vertical divisions shall be as per the drawing/details. All edges will have edge banding tape/laminate of matching colour. All the shutters shall have autoclosing hinges and laminate/edge binding on the edges.
L TYPE WORK STATIONS: P/F low ht. storage SC-2 750/900/1050/1200 high 450mm deep in 19mm thk.both sides prelam Board construction with 12mm thk. Ply backing. The horizontal and vertical divisions shall be as per the drawing/details. All edges will have edge banding tape/laminate of matching colour. All the shutters shall have autoclosing hinges and laminate/edge binding on the edges.
Supplying and Planting of Pungam tree sapling of B31 height 240 –300 cm in polythene bag of size 20x21 inch including supporting stack of 5 cm dia casurina pole of 10 feet height, including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site in-charge
Providing Pest control and Anti-termite treatment by appointing a specialised agency as per the specifications mentioned by the Bureau of Indian Standards and Agencies specifications (whichever is higher), for General Civil, Plumbing,/ Drainage and timber/ Carpentry works, Gypsum related work, including a 10-year guarantee under suitable undertaking on stamp paper etc, complete as directed. (Mode of measurement to be on carpet-area of floor and not the area of surface treated.)
Supply and planting of Leucophyllumfruitescens ornamental specimen plant of height 90-120cm in polythene bag of size 21×21 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
BILL NO.10 - INTERIOR & FURNITURE WORK
Supplying of plastic Potted plants Bogainvillea size of dia 12 inch including loading and unloading charges, transportation, etc as directed by the site in- charge
Supply and planting of Araucaria heterophyllum ornamental foliage tree of height 180-210cm in polythene bag of size 21×21 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
FIRST FLOOR
Supply and planting of Bougainvillea dwarf ornamental foliage shrub of height 30- 45cm in polythene bag of size 7×8 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
Supply and planting of Washingtoniafilifera ornamental foliage palm of height 120 - 150cm in polythene bag of size 21×21 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
GENERAL WORK
GLASS PARTITONS :Supply of Single glazed partition system with 10mm thick toughend glass and shall be able to provide a sound reduction upto 36db. The glass panels shall be supported by Natural Anodized Aluminium Ground Profiles (AGGP) in 26x40mm (H), and connected to 26x40mm (H) ceiling profile (AGGP) attached to the suspended partition/ false ceiling. On the vertical edges the glass panels are wrapped around with 24x26mm Vertical profile (AGVP). Glass to glass joints shall be done using joint tape. The glass to glass joint at the corner to have 90°corner profile (AGHLA-90° - AGHLT-90°). The perpendicular glass junction (T-junction) AGTT - AGLA profile to be used. Glazed partition FFL to false ceiling shall be 2400mm ht. Finishes of all aluminium frame components shall be Natural Anodized Finished. Rate shall be inclusive of all transport.
Gypsam celing :Supply and Fixing of Saint Gobain Ultra Gyp Channel Frame work ,L - Angle Support and the Intermediate Channel Should be 3 to 4 feet per span Length and the bottom Section should be 2 feet.Saint Gobain 12.5mm thick gypsum board to be fixed.The Joints of the board should be finished with fibre tape with 2 coat of putty (saint gobain or POP ) and the joints should be even at all levels engineer in charge.
Calcium Cilicate celing :Supply and Fixing of Saint Gobain Ultra Gyp Channel Frame work ,L - Angle Support and the Intermediate Channel Should be 3 to 4 feet per span Length and the bottom Section should be 2 feet.Saint Gobain Calcium cilicate board to be fixed.The Joints of the board should be finished with fibre tape with 2 coat of putty (saint gobain or POP ) and the joints should be even at all levels engineer in charge.
DOORS
TOUGHENED GLASS DOORS :
Providing and fixing door made of 12mm toughened glass of approved make, supported on brushed finished stainless steel finish top an
d bottom hung patch fittings and Floor spring of Dorma make. The glass panel edges shall be properly machine polished. The 60% of the glass shall be fixed with 3M film for frosted/ etched effect to the pattern as indicated in the detail drawings. This also includes providing necessary hardware like handles, patch lock etc. of Hafele / Dorma /Geze or equivalent.
SHAFT DOORS
Supply, Fabrication and erection of double shutter Shaft Door (1000 X 2100mm) of Salwood frame (Size 100 X 62mm) with 6mm Thick tempered Black back painted glass on enox profile. Refer approved shop drawing for details, sizes and location of patch fittings and iron mongeries with Louvers (as applicable), Holds & Locks including material, labour, tools and tackels etc in Shaft / Janitor room
FIXED FURNITURES
STORAGES: P/F low ht. storage SC-2 750/900/1050/1200 high 450mm deep in 19mm thk.both sides prelam Board construction with 12mm thk. Ply backing. The horizontal and vertical divisions shall be as per the drawing/details. All edges will have edge banding tape/laminate of matching colour. All the shutters shall have autoclosing hinges and laminate/edge binding on the edges.
3 Seater Sofa: Made with Solid Silver wood frame and branded High density foam and fabric. Wooden base with metal laminate skirting to be considered and got approved from the Architects. Size: 8' W x 2'6" D Basic cost of Upholstery 500/mtr
Single Seater Sofa: Made with Solid wood frame and branded High density foam and fabric. Metal Legs to be considered and got approved from the Architects Size: 3' W x 2'6" D. Basic cost of Upholstery 500/mtr
Centre Nesting Table: Made with Solid wood / Metal frame. Top shall have polished Marble and got approved from the Architects. Size: 450mm dia & 350mm dia
SUSPENSION SYSTEM AND PROCEDURE OF WORKS: Supply and installation of suspension grid system with main Tee and cross Tees to provide a stable suspension system for quick laying of acoustic ceiling tiles of nominal size 600 mm x 600 x 19/ 15 mm. The width of flange of all Tees shall be 24 mm as per the manufacturers specification.The Tees shall be double webbed with bake enamelled fascia cap and all other exposed surfaces galvanised or suitably treated against corrosion. Free ends of tees shall be mounted with quick release high tensile spring steel clips to provide a plug-in positive-lock for easy removal without tools.Suspension points shall not exceed centre-to-centre distance of 1200 ~ 1250 mm and shall be professionally executed with twin 4-mm GI suspension rod and adjustable suspension (butterfly) clip of spring steel. The entire grid system shall be designed to bear a distributed load of minimum 18 kg/sqm. Design of grid layout shall be produced with co-ordinating suspension points in tandem with other service duct / cable tray layouts. The grid layout is to be superimposed on the ceiling service ducting / cabling layout and got approved from the Architects.
PAINT: P/A Accent Paint of approved shade and colour in minimum three coats, including preparation of surface, scrapping, sand papering, scaffolding, primer etc complete.
Design, fabrication of Ultra classic design semi oval type table for Video conference hall with mat finish laminate and provision for installing power cable and voice controller systems with non-slip table top as approved by the Engineer.(10 Seater)
Providing and Laying of carpet flooring
SECOND FLOOR
Providing, fabricating and placing single leaf door made with 38mm thick flush door finished in laminate of approved shades on both the surfaces of the shutters with grooves to pattern as indicated as per the detail drawing. 6mm thick glass vision panel of size 150x1800 with allround beading. The door will be fixed into wooden frame of size 100 x 50mm as per the detail drawings. The shutter shall have 1/2" x 2" Teak wood lipping all-round. All the exposed wooden surfaces shall be stained to shade as directed by the Architects and polished melamine. This also includes providing and fixing in position necessary hardware like handles, heavy duty floor spring, locks etc.of approved make with provision for fixing Access control readers/ locks as recommended by Architects.
Supplying and Planting of Pungam tree sapling of B31 height 240 –300 cm in polythene bag of size 20x21 inch including supporting stack of 5 cm dia casurina pole of 10 feet height, including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site in-charge
Providing Pest control and Anti-termite treatment by appointing a specialised agency as per the specifications mentioned by the Bureau of Indian Standards and Agencies specifications (whichever is higher), for General Civil, Plumbing,/ Drainage and timber/ Carpentry works, Gypsum related work, including a 10-year guarantee under suitable undertaking on stamp paper etc, complete as directed. (Mode of measurement to be on carpet-area of floor and not the area of surface treated.)
Supply and planting of Leucophyllumfruitescens ornamental specimen plant of height 90-120cm in polythene bag of size 21×21 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
BILL NO.10 - INTERIOR & FURNITURE WORK
P/F FD1 Fire door with single/double 50 mm thick fire resistant flush shutter of solid core of inorganic vermiculite bonded board with a bulk density of 400 kg/M3 with sheet metal reinforcement at hinge lock and closer location with 120 minutes fire rating conforming to B.S 476 (Part 20 and Part 22) and I.S. 3614 Part of , with heat activated in tumescent fire seal strips (imported from UK or equivalent) of size 10mmx3mm on all sides of the shutter
except bottom provided in suitable grooves with stainless steel ball bearing butt hinges (100 mm x 76 mm x 2 mm) with necessary screws including 1.5 mm thick fire retardant laminate on outside and regular laminate 1mm thk conforming to BS-476, inside and iron mongery. Size 1000x2400
Supply and planting of Araucaria heterophyllum ornamental foliage tree of height 180-210cm in polythene bag of size 21×21 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
FIRST FLOOR
Supply and planting of Bougainvillea dwarf ornamental foliage shrub of height 30- 45cm in polythene bag of size 7×8 inch including loading and unloading charges, transportation, stacking of saplings at site, earth work excavation of required size, planting of sapling, refilling of excavated earth etc as directed by the site-in-charge.
Supply and convey of fabricated specifically premium designed Executive chairs
GENERAL WORK
GLASS PARTITONS :Supply of Single glazed partition system with 10mm thick toughend glass and shall be able to provide a sound reduction upto 36db. The glass panels shall be supported by Natural Anodized Aluminium Ground Profiles (AGGP) in 26x40mm (H), and connected to 26x40mm (H) ceiling profile (AGGP) attached to the suspended partition/ false ceiling. On the vertical edges the glass panels are wrapped around with 24x26mm Vertical profile (AGVP). Glass to glass joints shall be done using joint tape. The glass to glass joint at the corner to have 90°corner profile (AGHLA-90° - AGHLT-90°). The perpendicular glass junction (T-junction) AGTT - AGLA profile to be used. Glazed partition FFL to false ceiling shall be 2400mm ht. Finishes of all aluminium frame components shall be Natural Anodized Finished. Rate shall be inclusive of all transport.
Gypsam celing :Supply and Fixing of Saint Gobain Ultra Gyp Channel Frame work ,L - Angle Support and the Intermediate Channel Should be 3 to 4 feet per span Length and the bottom Section should be 2 feet.Saint Gobain 12.5mm thick gypsum board to be fixed.The Joints of the board should be finished with fibre tape with 2 coat of putty (saint gobain or POP ) and the joints should be even at all levels engineer in charge.
Calcium Cilicate celing :Supply and Fixing of Saint Gobain Ultra Gyp Channel Frame work ,L - Angle Support and the Intermediate Channel Should be 3 to 4 feet per span Length and the bottom Section should be 2 feet.Saint Gobain Calcium cilicate board to be fixed.The Joints of the board should be finished with fibre tape with 2 coat of putty (saint gobain or POP ) and the joints should be even at all levels engineer in charge.
Design, fabrication of Ultra classic design semi oval type table for Video conference hall with mat finish laminate and provision for installing power cable and voice controller systems with non-slip table top as approved by the Engineer.(10 Seater)
DINING TABLE: Providing and fixing Dining table.
2 seater Granite countertop with half moudling; wrought iron base and legs as per design
6 seater Granite countertop with half moudling; wrought iron base and legs as per design
4 seater Granite countertop with half moudling; wrought iron base and legs as per design
Main Door
Dining chairs Bought out chairs with powder coated framing and fabric upholstered seat - fabric as per design
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.10 MB
TenderDocuments.rar
Tender Documents • 13.04 MB
BOQ_754662.xls
BOQ • 0.99 MB
Download all tender documents and submit your bid