| 1 | L1₹10.9 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹11.5 L+₹56,000 (5.13%)Admitted-Finance 98 PANIYARE PURWA MAKRAND NAGAR SARAIMEERA KANNAUJ KANNAUJ UTTAR PRADESH 209726 | KANNAUJ | UTTAR PRADESH | 209726 | L2 | Admitted-Finance | |
| 3 | L3₹11.5 L+₹56,500 (5.17%)Admitted-Finance 154 A BARASIROHI NEAR IIT KANPUR KALYANPUR KANPUR NAGAR UTTAR PRADESH 208016 | KANPUR NAGAR | UTTAR PRADESH | 208016 | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | rbs engineering L2 | ELECTRO POWER SERVICES AND SOLUTIONS L3 | exSel Corporation L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply of SCADA cum Gateway Server with latest configuration for configuration, testing and commissioning of Gateway System at 132kV S/S Laharpur. Advantech/equivalent make with Intel Core i3-12500, 16GB RAM, Windows 10 OS, 512TB SSD, USB (6 Ports), RJ45 (2 Ports Rear), Single Power Supply License Software - Windows OS + Antivirus. Suitable for existing SCADA System as installed at 132KV Sub-station Laharpur. | 1 | No. | 99,500 ₹99,500 | 99,500 ₹99,500 | 98,000 ₹98,000 Lowest |
| 2.00 | Supply, configuration and testing of new industrial
gateway suitable to transfer the IEC-104 data to SLDC Lucknow & ALDC Modipuram. The following works to be carried out in gateway at substation level;
Works Included:
Supply of 2 no. of IEC-61850 Compliant Industrial
Gateway suitable for transfer to data at SLDC and ALDC having following features;
I. From 132kV S/ Laharpur to SLDC Lucknow.
II. From 132kV S/S Laharpur to ALDS Modipuram.
Specification of Gateway:
1. With dual RJ-45 Port which can be configured for Independent IP address as per site requirement.
2. Industrial Protocol Gateway: IEC 61850 Ethernet
Server to IEC 60870-5-104 Ethernet Client.
3. Compliant with IEC 61850-3 and IEEE 1613 Power
Substation Standards.
4. Works in environments from -40°C to +80°C
5.User friendly configuration with a Java-Based
Windows utility.
6.Embedded PPTP, IPsec and OpenVPN Client/Server for enhanced security.
7.Redundancy through embedded RSTP Protocol.
8. 5 Years manufacturer warranty. | 2 | Job | 1,98,000 ₹3,96,000 | 1,99,500 ₹3,99,000 | 1,96,000 ₹3,92,000 Lowest |
| 3.00 | Configuration of ICD/CID file for existing 132kV and 33kv feeders /bays. Following work to be carried out for SLDC Lucknow & ALDS-Modipuram:
1.Complete configuration and testing of Gateway as per the signal list and parameter provided by client to transfer the data on IEC-104
2.Programming and resetting of communication of link of Gateway from data transfer as per IP address provided by UPPTC.
3.Complete testing of Gateway and validation of real time data as per existing signal list
4. Complete checking of SAS gateway panel included architecture and settings. Following Feeders are Included.
1. 132KV SITAPUR BAY
2. 132KV OEL BAY
3. 132 KV TBC BAY
4. 132/33KV 20 MVA T/F BAY
5. 132/33KV 40 MVA T/F-I BAY
6. 132/33KV 40 MVA T/F-II BAY
7. 33KV LAHAPUR TOWN, TEHSIL
8. 33KV JAHAREKHAPUR, RL
9. 33KV SRB ECO BOARD BAY, INDUSTRIAL
10. 33 KV ITC SOLAR BAY, INDUSTRIAL
11. 33 LAHARPUR, RL
12. 33 KV HARGAON, N.P.
13. 33 KV TAMBAUR, N.P.
14. 33 KV TBC BAY | 14 | Bay | 27,000 ₹3,78,000 | 26,000 ₹3,64,000 | 25,500 ₹3,57,000 Lowest |
| 4.00For Rectification/modification/repair of existing Ethernet switch (2 Nos. Transmitting and Receiving data ) in Gateway Panel for healthy communication with SLDC & ALDC. | ||||||
| 5.00 | Supply and Installation of power supply cord for existing Ethernet Switch and its rectification of issue in existing ethernet switch. | 2 | Job | 58,000 ₹1,16,000 | 60,000 ₹1,20,000 | 55,000 ₹1,10,000 Lowest |
| 6.00 | Checking and troubleshooting of existing
Ethernet Switch using relevant software and tools for real time for data transfer to SCADA | 2 | Job | 27,000 ₹54,000 | 27,000 ₹54,000 | 24,000 ₹48,000 Lowest |
| 7.00 | Configuration of Switch for same cloud of the network control center for data transfer | 2 | Job | 15,000 ₹30,000 Lowest | 17,500 ₹35,000 | 15,000 ₹30,000 Lowest |
| 8.00 | Supply of FO cable/patch cord/LIU/Cat6 Cable and its related hardware, splicing work to complete the network communication for smooth execution of Gateway system.
- Checking healthiness and rectification of fault/issue of FO Network:-
- Splicing and termination of FO cable in each Kiosk
- Checking the healthiness of all protection relay's
communication to Gateway
- Checking the healthiness of existing IEC 61850-7
Ethernet switch in existing panel, however, in case of any faulty ethernet switch, same shall be arranged by UPPTCL for completion of work. | 1 | Set | 30,000 ₹30,000 | 25,000 ₹25,000 | 23,000 ₹23,000 Lowest |
| 9.00 | Supply of Armored FO Patch Cord (LC-LC – 3 Meter) | 15 | No. | 3,000 ₹45,000 | 3,500 ₹52,500 | 2,300 ₹34,500 Lowest |
Tender Value
Refer Docs
EMD Value
₹13,000
Closing Date
23 Mar 2026, 6:00 pmClosed
SE ETC Shahjahanpur
Electy Trans Circle Shahjahanpur
Work
2026_UPTCL_1113956_2
Short Term E. Tender No. 76 ETC(S)/2025-26
Open Tender
Electrical Works
Fixed-rate
60 days
Sitapur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
A/c No. 0423002100107147 IFSC Code No. PUNB0042300
₹13,000
18 Jun 2026
9 Mar 2026
24 Mar 2026
9 Mar 2026
23 Mar 2026
9 Mar 2026
9 Mar 2026 - 16 Mar 2026
Supply of SCADA cum Gateway Server with latest configuration for configuration, testing and commissioning of Gateway System at 132kV S/S Laharpur. Advantech/equivalent make with Intel Core i3-12500, 16GB RAM, Windows 10 OS, 512TB SSD, USB (6 Ports), RJ45 (2 Ports Rear), Single Power Supply License Software - Windows OS + Antivirus. Suitable for existing SCADA System as installed at 132KV Sub-station Laharpur.
Supply, configuration and testing of new industrial gateway suitable to transfer the IEC-104 data to SLDC Lucknow & ALDC Modipuram. The following works to be carried out in gateway at substation level; Works Included: Supply of 2 no. of IEC-61850 Compliant Industrial Gateway suitable for transfer to data at SLDC and ALDC having following features; I. From 132kV S/ Laharpur to SLDC Lucknow. II. From 132kV S/S Laharpur to ALDS Modipuram. Specification of Gateway: 1. With dual RJ-45 Port which can be configured for Independent IP address as per site requirement. 2. Industrial Protocol Gateway: IEC 61850 Ethernet Server to IEC 60870-5-104 Ethernet Client. 3. Compliant with IEC 61850-3 and IEEE 1613 Power Substation Standards. 4. Works in environments from -40°C to +80°C 5.User friendly configuration with a Java-Based Windows utility. 6.Embedded PPTP, IPsec and OpenVPN Client/Server for enhanced security. 7.Redundancy through embedded RSTP Protocol. 8. 5 Years manufacturer warranty.
Configuration of ICD/CID file for existing 132kV and 33kv feeders /bays. Following work to be carried out for SLDC Lucknow & ALDS-Modipuram: 1.Complete configuration and testing of Gateway as per the signal list and parameter provided by client to transfer the data on IEC-104 2.Programming and resetting of communication of link of Gateway from data transfer as per IP address provided by UPPTC. 3.Complete testing of Gateway and validation of real time data as per existing signal list 4. Complete checking of SAS gateway panel included architecture and settings. Following Feeders are Included. 1. 132KV SITAPUR BAY 2. 132KV OEL BAY 3. 132 KV TBC BAY 4. 132/33KV 20 MVA T/F BAY 5. 132/33KV 40 MVA T/F-I BAY 6. 132/33KV 40 MVA T/F-II BAY 7. 33KV LAHAPUR TOWN, TEHSIL 8. 33KV JAHAREKHAPUR, RL 9. 33KV SRB ECO BOARD BAY, INDUSTRIAL 10. 33 KV ITC SOLAR BAY, INDUSTRIAL 11. 33 LAHARPUR, RL 12. 33 KV HARGAON, N.P. 13. 33 KV TAMBAUR, N.P. 14. 33 KV TBC BAY
For Rectification/modification/repair of existing Ethernet switch (2 Nos. Transmitting and Receiving data ) in Gateway Panel for healthy communication with SLDC & ALDC.
Supply and Installation of power supply cord for existing Ethernet Switch and its rectification of issue in existing ethernet switch.
Checking and troubleshooting of existing Ethernet Switch using relevant software and tools for real time for data transfer to SCADA
Configuration of Switch for same cloud of the network control center for data transfer
Supply of FO cable/patch cord/LIU/Cat6 Cable and its related hardware, splicing work to complete the network communication for smooth execution of Gateway system. - Checking healthiness and rectification of fault/issue of FO Network:- - Splicing and termination of FO cable in each Kiosk - Checking the healthiness of all protection relay's communication to Gateway - Checking the healthiness of existing IEC 61850-7 Ethernet switch in existing panel, however, in case of any faulty ethernet switch, same shall be arranged by UPPTCL for completion of work.
Supply of Armored FO Patch Cord (LC-LC – 3 Meter)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.16 MB
BOQ_2091433.xls
BOQ • 0.28 MB
report.pdf
PDF • 0.19 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .