RequiredOEM Authorization Certificate Bid to RA enabled No Online UPS Modular Type ( 1 pieces ) Technical Specifications * As per GeM Category Specification Specification Specification Name Values Bid Requirement (Allowed Values) GENERIC Online UPS Modular type should supoort for Data Centres
RequiredNetwork operating centres
RequiredSecurity operation centres
RequiredState and District centres
RequiredCommand and Control centre etc.
Requiredacross the Country to provide impetus to the e- Governnance services e.g.Public food Yes * 1/10 distribution
Requirede Way bill
RequiredCounseling
Requirede-Office
RequiredIVFRT etc.
Requiredservices under Digital India Programme Modular type UPS equipped with microprocessor/Digital signal processor and power modules
RequiredPower expansion facility
RequiredLCD/Digital display upto maximum expandable capcity
RequiredCable entry
RequiredRS 232 port and SNMP port with each power module and with suitabale rack (compatible maximum expandable) with complete lockable door having visibility for maximum expandable capacity Yes * Output power capacity including re dudancy/Expandable (Rack facility) upto/Minimum backuptime (including redudancy) Minimum VAH (VAH shall be calculate Battery voltage x Battery Ah x No. of batteries = Total VAH) 60 KVA/120KVA/45 Minutes/73800 VAH 60 KVA/120KVA/45 Minutes/73800 VAH VAH tolerance -1% of the defined capacity * Hot swappable power module Yes * Battery module using two or more strings in parallel for redudanct supply and battery module shall be fuse protected Yes * Inverter Technology PWM with IGBT
Requireddouble conversion * Output wave form Pure sine wave * Country of origin for India * 2/10 Inverter Noise level </= 65 dB </= 55 dB
Required</= 65 dB
Required</= 70 dB Type of cool (Minumum 2 Fans for each power module) Air cooled * Parallel (Power Modules) load sharing redundant operation with all accessories Yes * Installation and commissioning Yes * UPS shall be supply with insallation and operation manual Yes * INPUT Input AC Three Phase * In put Voltage Range 320 V to AC to 470 V AC 3 Phase 320 V to AC to 470 V AC 3 Phase
Required340 V to AC to 470 V AC 3 Phase Input frequency range 50 +/-6% Hz 50 +/-6% Hz Input power factor at full output load leading to unity with active power factor correction (APFC) (from 25% load to 100% load) >/=0.99 * Distortion (current) </= 3% </= 3% UPS shall have DG set compatibility Yes * OUTPUT Output AC Three Phase * Out put voltage 380/400/415
Required3 phase
Required4 wire * Voltage regulation (Steady state) at No load to full load
Required0.6 lag to Unity PF
RequiredDuring entire back up time
RequiredComplete input voltage range +/-1% * Output powr factor >/= 0.90 >/= 0.90 Frequency 50 Hz +/-0.5 % Hz * CONSTRUCTION Minimum thickness (in mm) of Rack Enclosure for Modular UPS duly powder coated 1.2 1.2 UPS shall be free from Yes * 3/10 workmanship defects
Requiredsharp edges
Requirednicks
Requiredscratches
Requiredburst
Requiredetc. All fasteners shall be fixed properly. The equipment shall be complete with all parts and all parts shall be functional UPS enclosure's degree of protection as per IS:13947 (Part 1)/1993 latest IP20 IP21
RequiredIP20 Standard quality Out put terminals shall be provided for output connection Yes * UPS shall have static and manual by pass facility Yes * UPS shall be supplied with required rated power cable (Copper) 5 Meters * Total Harmonic Distrotion (THD) for 100% linear load < 3% < 3% Total Harmonic Distrotion (THD) for 100% non-linear load < 4% < 5%
Required< 4% Operating temeprature 0 deg C to +40 deg C * Humidity Upto 95% non- condensing * Operational: 1000 meters above sea level at 40 deg. C maximum Yes * Crest factor on full non- linear load Not less than 3:1 * Over all efficiency on rated full load of 0.8 PF (min.) AC output >/=90% >/=90% Inverter efficiency on rated full load of 0.8 PF (min.) AC output >/=95% >/=95% UPS shall withstand Over load capacity - 125% (Output with mains AC-AC) for 5 Minutes (Minimum) for 5 Minutes (Minimum)
Requiredfor 10 Minutes (Minimum) UPS shall withstand Over load capacity - for 60 seconds (Minimum) * 4/10 150% (Output with mains AC-AC) UPS shall withstand Over load capacity - 125% (Output in battery run DC-AC) for 2 Minutes (Minimum) for 2 Minutes (Minimum)
Requiredfor 30 Seconds (Minimum) UPS shall withstand Over load capacity - 150% (Output in battery run DC-AC) for 30 seconds (Minimum) * Load power factor 0.8 lagging to unity Yes * Transient response time (for 100% load change
Requiredoutput must remain within +/-1% and recovery) <20 milli seconds * PROTECTION Short circuit protection Yes * Over load protection Yes * Over temperature protection Yes * In put low/high voltage control Yes * DC low/high voltage trip Yes * Back feed protection for both
Requiredmains and bypass input Yes * BATTERY Battery shall conforming to JISC:8702(Pt.I
RequiredII&III) latest or equivalent BIS standard Yes * Battery type SMF VRLA SMF VRLA Country of origin for Battery India * Battery recharge time (after complete discharge to 90% charge) and charge rating: Battery recharge time to 90% charge after 100% DoD 8 to 10 hours 8 to 10 hours Battery charger (One in each power module) should be capable to charge battery on C10 rating Yes * 5/10 Battery cutoff voltage during back up Not less than 10.5 V * Batteries shall supply with With metal rack With metal rack Modular UPS shall supply with DC Cable from UPS to battery and batteries to UPS
RequiredBattery interlink cables
Requiredbattery breaker Yes * Meters
RequiredIndicators and Display All the meters and display LCD/Digital type shall support for maximum expanadable capacity Yes * Input: Voltage line to line and line to neutral
Requiredcurrents
Requiredfrequency
Requiredpower factor display Yes * Bypass: Phase voltage
Requiredline to line voltge
Requiredfrequency display Yes * UPS Output: Phase voltage
Requiredphase currents
Requiredline-line voltage
Requiredpower factors
Requiredfrequency display Yes * Local load: Load of each phase (% age of total load)
RequiredActive power (KW)
RequiredApparent power (KVA)
Requiredand Ractive power (KVAR) of each phase
Requiredload crest factor display Yes * Battery: Battery bus voltage
Requiredbattery charge and discharge current
Requiredforecasted battery back up time
Requiredbattery capacity (Ah) Yes * Parrallel load (for parallel operation system): Apparent power (KVA) of each phase
RequiredActive power (KW) of each phase
Requiredreactive power (KVAR) of each phase Yes * UPS shall have an indication for Mains on
RequiredLoad on battery
RequiredYes * 6/10 Inverter
RequiredBattery level
RequiredLoad level
RequiredInverter over load UPS shall have audible alaram for over temperature
Requiredmains failure
Requiredbattery low
Requiredinverter overload Yes * Communication interface: SNMP/MODB US/HTTP/JAVA/UPSMON SMTP etc.
Requiredand 2 serial port USB/RS232
RequiredRS485
Required1 logic level port
Required4 Dry contacts ports Yes * Log History storage facility with display (minium 200 events) Yes * WARRANTY AND SERVICES Warranty for Modular UPS (on site comprehensive warranty) (in years) 3 3
Required5 Warranty for battery (replacement warranty) (in years) 2 2
Required3
Required5 After sales and complaint service within 24 hours within 24 hours PAN India service support on 24 x 7 basis Yes Yes
RequiredNo AMC support available after 3 year warranty Yes Yes Quarterly preventive maintenance Yes Yes Manufacturer shall provide and support for installation
Requiredcommissioning
Requiredspares
Requiredtechnical support all over India Yes Yes Availability of spares in close proximity (Spares should be easily available close to the site) Yes Yes
RequiredNo CERTIFICATIONS ISO: 9001 Certification Yes * ISO: 14001 Certification Yes * 7/10 Environmental compliance certificate RoHS Yes * CE Certification and marking Yes Yes UPS shall meet and comply with the General and safety requirements as per IEC:62040-1 Yes * UPS shall meet and comply with the Electromagnetic compatibility (EMC) requirements as per IEC:62040-2 Yes * Damp Heat Test : in accordance with IS:9000(part 5/sec.2)1981 at Temperature of 40 degree C
Requiredtwo cycles of (12+12) hours each 2007) Yes Yes
RequiredNo Dry Heat Test : in accordance with IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) at 55 degree C for 16 hrs Yes Yes
RequiredNo Cold Test : in accordance with IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) at -10 degree C for 4 hrs. Yes Yes
RequiredNo Availability of the Type Test Report from Central Govt. NABL/ILAC Accredited lab covering all technical requirements. Yes * All the test reports and certificates shall furnish by the supplier to the buyer/consignee on demand Yes * * Bold specifications are the golden parameters. * Bidders may note that In respect of non-golden Parameters
Requiredthe specifications 'Values' chosen by Buyer will generally be preferred over 'Bid requirement ( allowed Values) by the Buyer. 8/10