Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹127.2 CrAdmitted-Finance 610B NILGIRI BLOCK ADITYA ENCLAVE AMEERPET HYDERABAD 500038 | HYDERABAD | TELANGANA | 500038 | ₹127.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹148.5 CrAdmitted-Finance 605 607 6 FLOOR SHRIKANT CHAMBERS PHASE 1 6 FLOOR ADJACENT TO R K STUDIOS MUMBAI 400071 MAHARASHTRA INDIA | ₹148.5 Cr | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Sri Avantika Contractors (I) Limited L1 | Capacite Infraprojects Ltd L2 |
|---|---|---|---|---|---|
| .01CIVIL | |||||
| 1.00 | Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as wellas 10 Sq.m on plan including getting out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as directed by Engineer-in- Charge:All kinds of soil | 8,335 | Sq.m | 273 ₹22.8 L | 68.65 ₹5.7 L |
| 2.00 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. All kinds of soil | 9,434.75 | Cu.m | 339 ₹32.0 L | 192.76 ₹18.2 L |
| 3.00 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 Sq.m on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kind of soil. | 307.51 | Cu.m | 556 ₹1.7 L | 336.7 ₹1.0 L |
| 4.00 | Close timbering over areas including strutting, shoring and packing cavities (wherever required) etc. complete. (Measurements to be taken of the face area timbered): Depth exceeding 1.5 m but not exceeding 3 m | 131.6 | Sq.m | 283 ₹37,242.80 | 896.07 ₹1.2 L |
| 5.00 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. | 10,375.42 | Cu.m | 371 ₹38.5 L | 173.22 ₹18.0 L |
| 6.00 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete | 6,439.8 | Cu.m | 1,458 ₹93.9 L | 2,138.14 ₹1.4 Cr |
| 7.00 | Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. All kinds of soil | 714.42 | Cu.m | 253 ₹1.8 L | 431.5 ₹3.1 L |
| 8.00 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. | 15 | Cu.m | 4,424 ₹66,360 | 6,805.72 ₹1.0 L |
| 9.00 | Surface dressing of the ground including removing vegetation and in-equalities not exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m. All kinds of soil. | 18,199.76 | Cu.m | 71 ₹12.9 L | 55.29 ₹10.1 L |
Tender Value
₹128.7 Cr
EMD Value
₹1.4 Cr
Closing Date
9 Feb 2026, 3:00 pmClosed
Executive Engineer, LPWD Kavaratti
Executive Engineer, LPWD Kavaratti
Construction of Polytechnic College at Minicoy Island, UT of Lakshadweep (Revised) (Re Tender-II)
2025_UTL_3138_3
NIT No. 32/NIT/EE Kvt/2025-26
Open Tender
Civil Works
730 days
Minicoy
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹1.4 Cr
19 Feb 2026
16 Jan 2026
9 Feb 2026
16 Jan 2026
9 Feb 2026
16 Jan 2026
CIVIL
Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as wellas 10 Sq.m on plan including getting out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as directed by Engineer-in- Charge:All kinds of soil
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. All kinds of soil
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 Sq.m on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kind of soil.
Close timbering over areas including strutting, shoring and packing cavities (wherever required) etc. complete. (Measurements to be taken of the face area timbered): Depth exceeding 1.5 m but not exceeding 3 m
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete
Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. All kinds of soil
Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete.
Surface dressing of the ground including removing vegetation and in-equalities not exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m. All kinds of soil.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing: 1:5:10 (1 cement : 5 coarse sand (zone-III) : 10 graded stone aggregate 40 mm nominal size).
Providing and laying damp-proof course 50mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20mm nominal size derived from natural sources).
Extra for laying concrete in or under water and/or liquid mud including cost of pumping or bailing out water and removing slush etc. completenThe quantity will be calculated by multiplying the depth measured from the sub-soil water level up to centre of gravity of concrete under sub-soil water level with quantity of concrete in cum executed under sub-soil water. The depth of centre of gravity shall be reckoned correct to 0.1m. 0.05m or more shall be taken as 0.1m and less than 0.05m ignored
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Foundations, footings, bases of columns, etc. for mass concrete
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Suspended floors, roofs, landings, balconies and access platform
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Lintels, beams, plinth beams, girders, bressumers and cantilevers
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Columns, Pillars, Piers, Abutments, Posts and Struts
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Stairs, (excluding landings) except spiral-staircases
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Edges of slabs and breaks in floors and walls. Under 20 cm wide
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Weather shade, Chajjas, corbels etc., including edges
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
Providing fusion bonded Epoxy coating not less than 175 micron thickness and upto 300 micron to reinforcement bars of any diameter as per IS-13620-1993/ ASTM-775 M including repairs to cut ends,welded spouts and handling damages with reccomended liquid epoxy compatible with the coating and testing of coating at plant etc complete as directed by engineer ion charge.
Providing fusion bonded epoxy coating by mechanized & qualified process including blast cleaning, heating using Induction heater, electrostatically spraying the epoxy powder, complete fusion to give coating thickness up to 300 microns, gradual cooling without affecting the properties of steel, testing as per IS13620, flexibility/bend & holiday test, other applicable test for IS13620 Standard.
Extra for laying reinforced cement concrete in or under water and/ or liquid mud, including cost of pumping or bailing out water and removing slush etc., complete. The quantity will be calculated by multiplying the depth measured from the subsoil water level up to the centre of gravity of the R.C.C. under subsoil water with the quantity of R.C.C. in cubic metre executed under subsoil water. The depth of centre of gravity shall be reckoned correct to 0.1 m. 0.05 m or more shall be taken as 0.1 m and less than 0.05 m ignored. No extra payment shall be made for placing reinforcement or centering & shuttering under sub - soil water conditions.
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate /retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level. Concrete of M30 grade with minimum cement content of 350 kg /cum.
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate /retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth level upto floor V level. Concrete of M30 grade with minimum cement content of 350 kg /cum.
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate /retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth level upto floor V level.. Concrete of M35 grade with minimum cement content of 370 kg /Cu.m
Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical localtion in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self- centering arrangement that freely rotates / moves in all directions. The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge. (Material shall confirm to ASTM 6063). Floor Joint of 100 mm gap
Providing and fixing of expansion joint system related with wall joint (internal/external) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall confirm to ASTM 6063) Wall Joint of 100 mm gap
Providing and fixing of expansion joint system of approved make and manufactures for various roof locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members with, self aligning and self centering arragement support plates asper ASTM B221-02. The system shall be such that it provides watertight roof to roof/roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminum base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063 Roof Joint of 100 mm gap
Providing and laying autoclaved aerated cement blocks masonry with 150mm/ 230mm/300 mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately).
Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand ) etc complete
Providing and applying Antitermite treatement by injecting chemical emulsion Imidacloprid emulsiable concentrate .075% for pre-constructional treatement and creating a chemical barrier as per IS 6313 (Part ll) 2001 for wall trenches, foundation, top surface of plinth filling, foundation of wall and floor, along the external perimeter of the building,etc. complete conforming to manufacturers specification and as directed by the Engineer-in-Charge.(Plinth area only to be measured for the payment ) (The above work shall be carriedout by an agency having sufficient experience and should ensure a warranty for a period of 10 years. Only skilled and experienced persons shall be employed for this purpose.)
Providing,diluting and injecting chemical emulsion to 12mm dia holes in Masonry/earth fiiling and plugging with cement mortar 1:2 to match the line and level of sorrounding area for PRE-CONSTRUCTIONAL anti-termite treatmentwith Imidacloprid (30.50% SC) or approved equivalent. Plinth area in plan at GF shall only be measured (for all below specified steps) and paid. A guarantee bond of 10 years shall be furnished. A) Bottom surface and the sides of the excavation made for masonry foundations at the rate of 5 liters/Sq.m (wherever applicable) B) Top surface of the plinth filling of 5 liter/Sq.m of internal plinth area etc. complete. C) At the rate of 5 liter/ Sq.m to the internal vertical surface from original Ground level to top of the earth filled in the plinth. D) At the rate of 5 liter/ Sq.m to the external vertical surface below finished Ground level to the full depth of the filling complete. The work includes all costfor chemical, drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing finish etc all complete as per the direction of Engineer-In-Charge
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with :Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade. Area of slab over 0.50 Sq.m
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
Stone tile (polished) work for wall lining over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and cement slurry @ 3.3 kg/Sq.m including pointing in white cement complete.8mm thick.Granite of any colour and shade
Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured). Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick : Float glass panes. 4 mm thick glass pane (weight not less than 10kg/Sq.m).
Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured). Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick : Float glass panes. 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm)
Extra for providing frosted glass panes 4 mm thick instead of ordinary float glass panes 4 mm thick in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured).
Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete :100X58X1.90 mm
Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete : 250x10 mm
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISi, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.
Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 300x10 mm
Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 200x10 mm
Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.
Providing and fixing bright finished brass 100 mm mortice latch and lock, ISI marked, with six levers and a pair of anodised (anodic coating not less than grade AC 10 as per IS : 1868) aluminium lever handles of approved quality with necessary screws etc. complete.
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of crosssection 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
30 mm thick Fiberglass Reinforced Plastic (F.R.P.) flush door shutter in different plain and wood finish made with fire retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate all around, with suitable wooden blocks inside at required places for fixing of fittings and polyurethane foam (PUF)/Polystyrene foam to be used as filler material throughout the hollow panel, casted monolithically with testing parameters of F.R.P. laminate conforming to table - 3 of IS: 14856, complete as per direction of Engineer-in-charge.
Providing and fixing factory made uPVC glazed/wire mesh windows/doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh / Glazing of plain/ toughened/ laminated/ double glass unit with / without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately. Two track two panels sliding window with Aluminium channel for roller track, wool pile, nylon rollers with SS 304 body.Using R3 series with frame (55mm & above) x (40mm & above) & sash (30mm & above) x (55mm & above) with zinc alloy (zamak) powder coated handle on every panel along with multi-point locking system (Height upto 1.8m)
Providing and fixing factory made uPVC glazed/wire mesh windows/doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh / Glazing of plain/ toughened/ laminated/ double glass unit with / without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 – Part 3 (ii) Sites with structure height more than 20m for all wind speeds. Three track three panels sliding window with two glazed & one wire mesh panels with Aluminium channel for roller track, wool pile, nylon rollers with SS 304 body. Using R2 series with frame (70mm & above) x (40mm & above) & both glazed and fly screen sash (25mm & above) x (50mm & above) with zinc alloy (zamak) powder coated touch locks with hook. (Height upto 1.2 metr.
Providing and fixing factory made uPVC glazed/wire mesh windows/doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh / Glazing of plain/ toughened/ laminated/ double glass unit with / without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately Three track three panels sliding window with two glazed & one wire mesh panels with Aluminium channel for roller track, wool pile, nylon rollers with SS 304 body.Using R4 series with frame (115mm & above) x (45mm & above) & both glazed and fly screen sash (44mm & above) x (55mm & above) with zinc alloy (zamak) powder coated handle on every glazed panel along with multi-point locking system. (Height above 1.8m)
Providing and fixing factory made uPVC glazed/wire mesh windows/doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh / Glazing of plain/ toughened/ laminated/ double glass unit with / without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately. Fixed window / ventilator with mullion / transom. Using R2 series with frame (39mm & above ) x (39mm & above) & mullion (39mm & above) x (60mm & above). (Height upto 1.2 metre)
Providing and fixing factory made uPVC glazed/wire mesh windows/doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh / Glazing of plain/ toughened/ laminated/ double glass unit with / without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately. Casement window double panels with fixed mullion with S.S. 304 friction hinges as per size and weight of sash, multi-point locking system, zinc alloy (zamak) powder coated handles.Using R2 series with frame (39mm & above) x (39mm & above) & sash (39mm & above) x (60mm & above) & mullion (39mm & above) x (60mm & above). (Height upto 1.2 metre).
Providing and fixing factory made uPVC glazed/wire mesh windows/doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh / Glazing of plain/ toughened/ laminated/ double glass unit with / without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately. Casement window double panels with fixed mullion with S.S. 304 friction hinges as per size and weight of sash, multi-point locking system, zinc alloy (zamak) powder coated handles.Using R4 series with frame (64mm & above) x (50mm & above) & sash (64mm & above) x (70mm & above) & mullion (64mm & above) x (70mm & above). (Height above 1.8 metre).
Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontal side & 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mm thick GI sheet ( Zinc coating not less than 120gm/m²) suitable for mounting 120 min Fire Rated Glazed Door Shutters. The frame shall be filled with Mineral wool Insulation having density min 96Kg/m³ . The frame will have a provision of G.I. Anchor fastners 14 nos ( 5 each on vertical style & 4 on horizontal style of size M10 x 80 ) suitable for fixing in the opening along with Factory made Template for SS Ball Bearing Hinges of Size 100x89x3mm for fixing of fire rated glazed shutter . The frame shall be finished with a approved fire resistant primer or Powder coating of not less than 30 micron in desired shade as per the directions of Engineer - in- charge . (Cost of SS ball bearing hinges is excluded).
Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c, including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and asper direction of Engineer-in-charge with glass of required thickness having 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested in approved NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The maximum glazing size shall not be more than 1100x2200 mm (w x h) or 2.42 Sq.m.
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x0.90 mm M.S. laths with 0.90 mm thick top cover
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.
Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer. MS Tube
52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer's specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ Sq.m including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ Sq.m including grouting the joint with white cement & matching pigments etc. complete. Size of Tile 600x600 mm
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Providing and fixing 15 cm wide, 45 cm overall semi-circular plain G.S. sheet gutter with iron brackets 40x3mm size, bolts, nuts and washers etc., including making necessary connections with rain water pipes complete.
Providing and fixing Gysum false ceiling (12.5 mm) at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/Sq.m (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) : 2011 (Board with BIS Certification marks)
Providing & fixing 8 mm thick Calcium Silicate false ceiling at all height including providing & fixing of framework made of special section, power pressed from M.S. sheets and galvanised with zinc coating of 120 gms/ Sq.m (both side inclusive) as per IS : 277 and consisting of angle cleat of size 25mm wide x 1.6mm thick with flanges of 27mm and 37mm, at 1200mm c/c, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25 x10 x0.50mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I chanels 45 x15 x 0.90mm running at the spacing of 1200 mm c/c, to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26 mm each having lips of 10.5mm, at 450mm c/c, shall be fixed in a direction perpendicular to G.I intermediate channel with connecting clip made out of 2.64mm dia x 230mm long G.I wire at every junction, including fixing perimeter channels 0.50mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/ partitions with the help of Rawl plugs at 450mm centre, with 25mm long dry wall screws @ 230mm interval, including fixing of Calcium Silicate Board to ceiling section and perimeter channels with the help of dry wall screws of size 3.5 x25mm at 230mm c/c, including jointing & finishing to a flush finish of tapered and square edges of the board with recommended jointing compounds, jointing tapes,finishing with jointing compounds in three layers covering up to 150mm on both sides of joints and two coats of primer suitable for boards, all as per manufacture's specification and also including the cost of making opening for light fittings, grills, diffusers, cut outs made with frame of perimeter channels suitably fixed, all complete as per drawings, specificaton and direction of the Engineer in charge but excluding the cost of painting with: 8 mm thick Calcium Silicate Board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process.
15 mm cement plaster on the rough side of single or half brick wall of mix : : 1:4 (1 cement: 4 fine sand)
12 mm cement plaster finished with a floating coat of neat cement of mix : 1:4 (1 cement: 4 fine sand)
Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. 20 mm cement plaster
6 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand)
Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 Sq.m) over and including priming coat of exterior primer applied @ 2.20kg/10 Sq.m
Finishing walls with Acrylic Smooth exterior paint of required shade : New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives. New work (Two or more coats applied @ 1.43 litre/ 10 Sq.m. Over and including priming coat of exterior primer applied @ 0.90 litre/10 Sq.m.
Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. On steel work
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. Two coats
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content.With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre
Cutting holes of required size in brick masonry wall for fixing of exhaust fan including providing and fixing 300 mm dia PVC pipe conforming BIS-12818 and making good the same etc. complete as per direction of Engineer-in-charge.
Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS:15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.
Painting runway/taxi track/apron marking with adequate nos of coats to give uniform finish with road marking paint of superior make as approved by the Engineer-incharge, i/c cleaning the surface of ail dirt, scales, oil, grease and other foreign mater;al etc. and lining out complete. New work (Two or more coats)
Providing and fixing at or near ground level factory made RCC pavement slab of M-30 grade of size 450x450x50 mm, including reinforcement with 6 mm dia M.S. bars 4 nos on each side, including setting in position in footpath to the required level and line over a bed of 20 mm average thick cement mortar 1:5 (1 cement : 5 coarse sand), having joint thickness not more than 5mm except on curve, including filling of joints with same cement mortar and making grooves etc. complete as per direction of Engineer-in-charge.
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineerin-charge).
Supplying and stacking of hard stone (for stone pitching) 22.5 cm thick at site.
Dry stone pitching 22.5 cm thick laid in courses and required profile with hammer dressed stones having no side less than 15 cm, with minimum depth of 20 cm including preparing the bedding surface etc. all complete. (Payment for Stone to be made separately).
Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. With material conforming to Grade-II (size range 53 mm to 0.075 mm ) having CBR Value-25
Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-inCharge. 60mm thick cement concrete paver block of M-35 grade with approved colour, design & pattern.
Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-inCharge. 80 mm thick C.C. paver block of M-30 grade with approved color design and pattern.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion :Powder coated aluminium (minimum thickness of powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge. Pre- laminated particle board with decorative lamination on both sides
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 8 mm thickness (weight not less than 20 kg/Sq.m)
Providing and fixing 12 mm thick toughened glass panel of approved brand and manufacture, including making necessary arrangements for fixing required fittings, all complete as per direction of Engineer-in-charge
Providing and Placing in position suitable PVC water stops conforming to IS:12200 for construction/ expansion joints between two RCC members and fixed to the reinforcement with binding wire before pouring concrete etc. complete : Serrated with central bulb (225 mm wide, 8-11 mm thick)
Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : (a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours. (b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
Providing and applying fibre reinforced elastomeric liquid water proofing membrane with resilient acrylic polymers having Sun Reflectivity Index (SRI) of 105 on top of concrete roof in three coats @10.76 litre/ 10 Sq.m. One coat of self-priming of elastomeric waterproofing liquid (dilution with water in the ratio of 3:1) and two coats of undiluted elastomeric waterproofing liquid (dry film thickness of complete application/system not less than 500 microns). The operation shall be carried out after scrapping and properly cleaning the surface to remove loose particles with wire brushes, complete in all respect as per the direction of Engineer-in-Charge.
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerin-charge. The product performance shall carry guarantee for 10 years against any leakage. For vertical surface two coats @0.70 kg per Sq.m
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerin-charge. The product performance shall carry guarantee for 10 years against any leakage. For horizontal surface one coat @1.10 kg per Sq.m.
Providing and laying factory made Precast concrete solid blocks of 200 mm thickness of grade M10 made of C&D waste from approved manufacturer in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing and laying factory made Precast concrete solid blocks of 200 mm thickness of grade M10 made of C&D waste from approved manufacturer in superstructure above plinth level up to floor V level. Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing and laying half block masonry with factory made Precast concrete solid blocks of 100 mm thickness of grade M10 made of C&D waste from approved manufacturer in superstructure above plinth level up to floor V level: Cement mortar 1:4 (1 cement : 4 coarse sand)
Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete
Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor two level upto floor five level with thickness 15cm in : CM 1:6 ( 1 cement : 6 coarse sand) etc complete
Providing and constructing Solid concrete block masonry M-10 grade in C.M 1:6 (1cement, 6 coarse sand) with Solid blocks of 30x20x15 cm size or nearest and approved quality including scaffolding, raking out of joints,curing, cost and conveyance of all materials,labour, lead, lift, etc. complete for all types of masonry works below plinth level as directed by Engineer-in-Charge at all levels.
Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/window/Ceosetory windows & other Frames/Chowkhat comprising of virgin PVC polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 750 kg/Cu.m, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold fast/lugs/SS dash fasteners of required dia and length complete as per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash fasteners shall be paid for separately).Note: For WPC solid door/window frames, minus 5mm tolerance in dimensions i.e depth and width of profile shall be acceptable. Variation in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made.Frame size 65 x 100 mm
Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid plain flush door shutter of required size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/Cu.m and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge. (Note: stainless steel butt hinges and necessary S.S screws shall be paid separately). 35 mm thick
Design and execution, of post tensioning works, including, decoiling the strands, cutting to the required lengths, supplying and laying of HT strands sheathing (GI corrugated ducts 0.3 mm thick) jointing with couplers, and inserting the strands, profiling, fixing live end anchorages, including the supply of stressing anchorages, suitable for 5-5 & 5-3 tendons, grout vents, making dead end anchorages, including flowering the strands, fixing tendon support bars, supervising the fixing of anti- bursting reinforcement, stressing the cables, end trimming, grouting the cables, with cement slurry, mixed with admixtures, with required tools, plants, machineries and consumables etc., Rate to Exclude, for providing water, power, cement PT Slab
Design and execution, of post tensioning works, including, decoiling the strands, cutting to the required lengths, supplying and laying of HT strands sheathing (GI corrugated ducts 0.3 mm thick) jointing with couplers, and inserting the strands, profiling, fixing live end anchorages, including the supply of stressing anchorages, suitable for 5-5 & 5-3 tendons, grout vents, making dead end anchorages, including flowering the strands, fixing tendon support bars, supervising the fixing of anti- bursting reinforcement, stressing the cables, end trimming, grouting the cables, with cement slurry, mixed with admixtures, with required tools, plants, machineries and consumables etc., Rate to Exclude, for providing water, power, cement PT beam
Providing material and labour for wet drilling accurate and clean holes of specified diameter in RCC walls, slabs, beam or any other RCC member without vibration by core cutting (diamond drilling) holes of 152mm dia machine of approved make for laying service lines including scaffolding, safety majors, disposing the debris, cleaning, making good, providing epoxy mortar/ micro concrete/ patch repair mortar for concrete for grouting the gaps around the pipes for all levels/ all height, after approval of engineer in charge etc compete. Measurement shall be taken for the depth of holes in running meter for specified diameter. Holes shall made by authorized approved agency. Scanning of reinforcement shall be carried out before core cutting if required and as suggested by Engineer in charge. Location of core cutting shall be approved by Engineer in charge.
Towards Design, Detailing, Fabrication & Supply and Erection of Pre Engineered Steel Building. i) Primary & Secondary members (Columns ,Rafters, Purlins with Mezzanine) ii) Structural accessories like Bed Bolts, HSS bolts, Hill side Bolts iii) 1 Coat of Primer and 1 Coat of Enamel Paint
Providing and fixing stainless steel (Grade 316) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
Supplying,fabrication and installing of swing louvers (Panel size 600mmx2800mm) made of 6mm thick fundermax HPL panel rivetted with SS rivet to 50mm×50mm GI square frame as per the approved drawing, which shall be fixed on 5mm thick MS plate on RCC beam/lintel/floor etc with high quality bearing on top and bottom for movement and shaft/handle arrangement for swinging louvers. The work includes finishing frame work with Epoxy paint (two or more coats) applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete as per direction of Engineer-in-Charge .The cost includes all materials,accessories, labour,scaffoldling etc complete
Providing & fixing Poly carbonate multi wall plain sheet 8 mm thick as approved by the Engineer in charge and should be supplied in a single length of 12 M or as decide by the Engineer in charge. The sheets shall be fixed using self drilling/ self tapping screw of size ( 5.5x55mm) with EPDM seal complete upto any pitch in horizontal /vertical / curved surface, but excluding the cost of purlins, rafters, trusses, and including cutting to size and shapes where ever required.
Frosted Film - Supply & laying of Frost/Privacy Film appoved design and color for All Glass Partitions and GLass doors. Rate including laying. (The successful manufacture should submit 10 years Warranty certicate to the clients. Product to be certified by Manufacturer's Representative)
Providing and fixing in position factory made Poly Urethane Foam (PUF) sandwich wall/roof/floor light weight solid core panels (50mm thick) made of core material of Polyurethane foam of density 40-42 Kg / M3 is sandwiched between two micro-ribbed layers of Galvalume sheets. The panels shall have a unique interlocking arrangement and are self-supportive. The panels to be placed against a concrete / masonry wall (or) against a proper steel fabricated structure.The interface joints, vertical and corner shall be further strengthened by using appropriate PPGL flashing and rivets. The panel shall fixed vertically and horizontally locked. Panels should be used as wall & roofing with additional structural support, steel or RCC depending upon the design.The work includes supply and installtion of nessarry flashings of required thickness as per the direction of Engineer In Charge All the operation shall be completed in all respect as per drawings, Manufacturers specifications and under the overall direction of Engineer-in-Charge (Cost of all the material is included except "structural steel work" which will be paid seperately). Non load bearing panels 50mm thick of required size
Providing and Fixing of Building signages as per following specifications - Sign to be made shall be made of 3 mm aluminium / Acrylic Box Letters (100mm thick letters). Sign Face shall be in 3mm 0/40 Translucent Acrylic with Male / 10mm Water Proof Sun board Female Joint Adequate LED of Samsung Make shall be fitted with the required wiring & Waterproof Transformer to have the uniform Light. A provision for Weather Proof Box shall be made to keep the Transformers. The signages to be fixed on the structural ACP + MS framework with required sizes as per the design. The item includes design of supporting arrangement, fabrication, installation and commissioning the signages with structural framing including channels, angles, gusset plates and anchoring the frame by anchor fasteners to the Building. The structural framing should be painted with primer and enamel paints
Supply and fixing of Floor indication/ Fire exit/ Staircase/ Room indication signages of size 300mm x 150mm x 5mm or nearest size either hanged on ceilings/ fixed on walls with LED unit of approved make. The signage should be made up of acrylic material or fire resistant material on ACP.The signage should include a built-in UPS backup. It should be affixed to the existing background using appropriate chains and hooks, all complete as per the architectural design.
Providing and fixing of wall panelling with 19 mm thick 710 BWP fire retardant plywood conforming to IS: 5509 /10701 grade internal frame work over which 12 mm thick 710 BWP fire retardant plywood is fixed on. Exposed area finishing with 12.5mm thick gypsum board with ash wooden skirting, as per design approved by Architects.
Providing and Fixing Channelled Woodworks perforated panels of width 192mm, thickness of 15mm and length 2400 mm, made of a Moisture resistant fibre board substrate with a laminated facing as per the approved shade (Portland Maple, Sea Beech, Siam Wood & Mystique Walnut, Interior White, Alumina Pearl) and a melamine balancing layer on the reverse side including Installing Skirting for Channelled wall panel of width 50mm or more as required by the Engineer-in-Charge. Finish off the edges using wooden moulding of matching colour for the wall Panel. The boards shall have a special perforation pattern where the reverse surface has a “Helmholtz” fluted perforation with consecutive 3mm wide groove followed by 21mm of visible pane. The edges of the panel shall be “tongue-and-grooved” to fix special clips for installation and seamless visual. The back of the perforated panel shall have sound absorbing non-woven Soundtex acoustical fleece hot pressed to achieve NRC of 0.5. (Average value of Absorption Co-efficient readings taken at 250 Hz, 500 Hz, 1000 Hz and 2000 Hz) as per ASTM C423 and Humidity Resistance (RH) of 70% with camber limit less than 1mm/1000mm and bow less than 1mm/300mm.Ceiling Installation : The panel shall be downwardly installed with tongue and groove mechanism using Inside clip on Prelude 43 with 24 mm wide T - section flanges having rotary stitching on all T - sections i.e., the Main Runner, 1200 mm & 600 mm Cross Tees with a web height of 43mm, 35mm and 30mm respectively. The deflection loading of the system shall be 17.8 kg/m2 (as per standard installation layout mentioned below) and main beam tested as per ASTM C635 (Deflection limit less than L/360) with deflection loading of 21.4kg/m. The end details of the main beam and cross tee shall be made of pre hardened steel and the cross tee is designed to provide double locking between “cross tee to cross tee” and “cross tee to main beam”. All main beam to main beam and cross tee to cross tee connection shall have a pull out strength of more than 100kg. The T - Sections shall be made of hot dipped galvanized steel of 100 gsm as per IS 277 (2003) and pre-painted steel with baked polyester paint with 0T bending capability. The grid shall be installed with suspension system of approved make. SUSPENSION SYSTEM accessories manufactured and supplied by approved manufacturer consisting of M6 Anchor Fasteners with hanger hole, pre–Straightened Hanger wire of dia – 2.5 mm of 1.80 m length having a tensile strength of 344-413 MPa and a minimum loading strength of 110 kgs. Additionally, adjustable hook clips made of 0.7mm thick Grade 1 C55 galvanized spring steel of dimension 100 x 20mm and 4 mm aquiline wire to be used for level adjustment during installation purpose in main runners. The rate is including cost and conveyance of all materials, labour charges, scaffolding, sundries etc complete as directed by the Engineer-in-Charge at all levels. Wall Area Installation : The panel shall be mounted by tongue and groove mechanism using inside clip on Knauf aluminium extruded keel made of Grade 6063-T5 having dimensions 3000(L) x 24(H) x 15.5(W). The keel shall also be used for transition of the butt end of adjacent panel at every 7.2m.
Supplying and installation of Black out roller blinds as per the detailed Technical specification and deatiled drawing. Including all fixing charges and necessary fittings. Base rate of fabric is Rs. 700/-
Disposal of earth work by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 5 km for all lifts, complete as per directions of Engineer-in-charge.
Providing and applying antiskid epoxy of minimum 1mm thickness with UV resistant PU top coat and marking court lines with UV resistant paint.The work includes surface preparation with a suitable floor grinder, vacuuming dust from floor, priming the surface with epoxy floor primer,after filling cracks with epoxy grout ,proper mixing of epoxy paint components and applying etc all complete as per manufacturer's specifications and instruction of Engineer in charge
Procuring healthy grass free from weeds and foreign materials and laying on the soil medium as turfing,the rate include for grass cost, transport to site, cost and application of manure, planting, labour, supervision and maintenance for 2 months after planting Pearl Grass
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Royal palm
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Foxtail palm
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Bismarkia palm
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Jackfruit tree
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Elenji tree
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Coconut tree
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Malpighia Topiary in steel mesh
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Eugenia Topiary
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Clerodendrum Inerme -Hedge
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Murraya Exotica - Flower bush
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Heliconia Caribea
Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Areca tree
Supplying , stacking and spreading sludge / well decayed farm yard manure from thesource,Mixing earth and manure or in proportion specified or directed, Spreading of dung manure or / and good earth in required thickness. and fine dressing the ground as per natural gradiantapproved by the engineer in charge incl. screening, loading, unloading, conveyance and stacking at site.
Providing and fixing wash basin with brass brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- (a) White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer. Make: Jaquar, Kohler, Grohe, Cera high end series.
Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required : Single half stall urinal with 5 litre P.V.C. automatic flushing cistern Make: Jaquar, Kohler, Grohe, Cera high end series.
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing stainless steel toilet paper holder. Make: Jaquar, Johnson, Cera high end series.
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore. Make: Jaquar, Johnson, Cera high end series.
Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms.
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink with drain board 510x1040 mm bowl depth 250 mm. Make: Jayana, Nirali, Carysil high end series.
Providing and fixing C.P. brass angle valve for basin trap and geyser points of approved quality conforming to IS:8931 15mm nominal bore Make: Johnson,Cera high end series.
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC SDR 11) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall (Above ceiling and Ducts) 20 mm nominal outer dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC SDR 11) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall (Above ceiling and Ducts) 25 mm nominal outer dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC SDR 11) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall (Above ceiling and Ducts) 32 mm nominal outer dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC SDR 11) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall (Above ceiling and Ducts) 50 mm nominal outer dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. Make: Astral, Supreme, Finolex, Prince 15 mm nominal outer dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. Make: Astral, Supreme, Finolex, Prince 20 mm nominal outer dia Pipes
Excavation for foundation/utility services upto 1.5 m depth including sorting out and stacking of useful materials and disposing off the excavated stuff with all lead and lift.(E) Hard Rock
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm. in depth consolidating each deposited layer by ramming and watering. (Ramping by manual or mechanical means)
Providing and fixing S.W. gully trap with C.I. grating brick masonry chamber and water tight C.I. cover with frame of 300mm x 300mm size (inside) with standard weight.(i) Square mouth traps.(B) 150mm x 100mm size P or R type (make-Local )
Constructing Brick masonry road Inspection chamber 450mm x 450mm x 775mm with horizontal grating complete. C. M. 1:6. Foundation concrete 150 mm thick in C. C. 1:4:8 of trap metal size 25 mm to 40 mm thick, inside cement plaster in C. M. 1:3 and cement pointing outside in C. M. 1:3 and ms gratings on top. Upto 1 Mt. depth from G. L. to pipe invert level incl. complete civil works but excl. cost of excavation and refilling, with cast in situ RCC slab in one single piece with fixing of CI-MH Frame and cover (incl cost of CI-MH Frame and cover) with 23 mm thick brick masonry wall in C.M.1:6. With precast slab in two parts 15mm. for rain water/storm water drainage
Construction of Manhole chambers(Inspection chambers) 600mm X 600 mm and depth 1.0 m in brick or bela stone masonry, locally available in C. M. 1:6. Foundation concrete 150 mm thick in C. C. 1:4:8 of trap metal size 25 mm to 40 mm thick, inside cement plaster in C. M. 1:3 and cement pointing outside in C. M. 1:3 and top cover of precast RCC slab 100 mm thick (with key hole in two parts, each with handles or MS Bar etc. complete as given size) Upto 1 Mt. depth from G. L. to pipe invert level incl. complete civil works but excl. cost of excavation and refilling, with cast in situ RCC slab in one single piece with fixing of CI-MH Frame and cover (incl. cost of CI-MH Frame and cover) with 23 mm thick brick masonry wall in C.M.1:6. With precast slab in two parts 15mm.
Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of concealed flush tank,flushing capacity 3 litre/ 6 litre (adjustable to 4 litre/ 8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete.. Make: Jaquar, Kohler, Grohe, Cera high end series.
Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin tap of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- (a) White Vitreous China Wash basin counter top type 550x420 mm with a 15 mm CP Brass single hole basin mixer. Make: Jaquar, Johnson, Cera high end series.
Providing, Fixing, Commissioning at site Urinal Partition with Curved shaped frosted glass fixing with brass screws, nuts , and washers complete including cutting and making good the walls and floors wherever requiredEtc complete. 900x450x10 mm tk. Make: Jaquar 1110uc/ equ.
Providing and fixing of grab bars 300 mm Stainless steel in physically disabled toilet including all necessary fitting, SS Screws & Accessories etc.Complted in all manners and satisfied to of EIC. complete. Make: Jaquar, Kohler, Grohe, Hindware, Cera high end series.
Providing and fixing of grab bars Vertical Swing 18-8 S, type-304, 18-gauge (1mm) stainless steel tubing with satin-finish. 1–1/4 (25mm) outside diameter wall mounted in physically disabled toilet including all necessary fitting, SS Screws & Accessories etc.Complted in all manners and satisfied to of EIC.complete. Make: Jaquar, Kohler, Grohe, Hindware, Cera high end series.
Providing, Fixing, Testing and Commissioning at site ablution Health Spray Faucet with wall hook and 1.2 mtr. Chrome plated PVC hose pipe, etc. complete in all respects. Queo - Addons/Kohler/Grohe/jaquar
Providing, Fixing, testing and commissioning of Single Lever Diverter with provision for spout and over head shower with shower arm, shower rose, wall flange and spout, all accessories etc, complete.Queo - Johnson/ KOHLER /Grohe Metropole, jaquar OR Equ.
Providing and Fixing of Stainless Steel Hand Dryer with all required connections and following specifications. Weld-free cover fixed to the base with two safety screws and lock withspecial speedflow key. Aluminium base. Includes silent-blocks to damp mechanical vibrations. Fire resistant plastic UL 94-V0 fan scroll. High-speed motor with safety thermal cut-off.The motor revolutions canbe adjusted manually by the potentiometer. • Aluminium centrifugal double asymmetrical inlet fan wheel. Disconnects automatically after 60 seconds of continuous use. Electronic infrared detection sensor. Adjustable detection by potentiometer(5- 25 cm). Ultra-flat: 10 cm deep (complies with ADA regulations). complete. Make: Jaquar, Kohler, Grohe, Hindware, Cera high end series.
Providing, Fixing, testing and commissioning of shower cock with shower arm, shower rose, wall flange and spout, all accessories etc, complete.Queo - Johnson/ KOHLER /Grohe Metropole, jaquar OR Equ.
Providing and erecting water cooler having storage capacity 80Ltr. & cooling capacity 40 Ltr.per hour @ an ambient temp of 450 C. The outlet temp. of the water should drop by 150 C within a hour, The water cooler should be comprising of hermetically sealed compressor, fan motor, condensing unit, water tank surrounded by evaporating coil, thermostats, relay etc. complete with necessary inlet & outlet connection. The body of water cooler will be made from Stainless Steel.
Supplying & erecting 5 stage single reverse osmosis water purification system with M.S. powder coated frame, pre filter housing with 'O' ring pre sediment filter GAC filter, carbon filter suitable buster DC pump capacity 80 psi, mention with 40 Osg inline type post carbon filter auto low & high pressure switches with following size of storage tank & LPH capacity & erected as directed with one year comprehensive maintenance guarantee. [B] 25 Ltr / Hr with 30 Ltr. S.S. Pressure Tank
Supplying, Fixing, testing and commissioning at site in position uPVC pipe -6kg/cm2) (IS:4985) Solvent Welded fittings with bosses where required e.g. tees, bends, coupling, door bends, junctions, cowls, door TEE , Door Elboe where ever required etc., complete. (Soil & Waste in Shaft) Make: Astral/Supreme/Ajay 110 mm O.D. (6Kgf/cm2 IS:4985)
Supplying, Fixing, testing and commissioning at site in position uPVC pipe -6kg/cm2) (IS:4985) Solvent Welded fittings with bosses where required e.g. tees, bends, coupling, door bends, junctions, cowls, door TEE , Door Elboe where ever required etc., complete. (Soil & Waste in Shaft) Make: Astral/Supreme/Ajay 75 mm O.D.(6Kgf/cm2 IS:4985)
Supplying, Fixing, testing and commissioning at site in position uPVC pipe -6kg/cm2) (IS:4985) Solvent Welded fittings with bosses where required e.g. tees, bends, coupling, door bends, junctions, cowls, door TEE , Door Elboe where ever required etc., complete. (Soil & Waste in Shaft) Make: Astral/Supreme/Ajay 63 mm O.D ( 4Kgf/cm2) Vent pipe in shaft
Providing, Fixing, testing and commissioning at site in position uPVC pipe ( IS : 4985 ) With Rubber Ring or Solvent Welded fittings with bosses where required e.g. tees, bends, coupling, etc. complete. (For Rain water pipes in shaft & Ceiling) Make: Astral/Supreme/Ajay 110 mm O.D ( 4Kgf/cm2)) Rain water pipe in shaft
Supplying, Fixing, testing and commissioning at site in position u PVC pipe of 6Kgf/cm2including PVC fittings with bosses where required e.g. tees, bends,door TEE , Door Elboe where ever required coupling and adapters and jointing with adhesive approved by fitting manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site universal clamps & anchor fasteners(8mm) , threaded rod(8mm),nuts ,washers, wherever required etc. complete.Make: Astral/Supreme/Ajay 50 mm O.D. (6Kgf/cm2 (IS:4985)
Supplying, Fixing, testing and commissioning at site in position u PVC pipe of 6Kgf/cm2including PVC fittings with bosses where required e.g. tees, bends,door TEE , Door Elboe where ever required coupling and adapters and jointing with adhesive approved by fitting manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site universal clamps & anchor fasteners(8mm) , threaded rod(8mm),nuts ,washers, wherever required etc. complete.Make: Astral/Supreme/Ajay 75 mm O.D. (6Kgf/cm2 (IS:4985)
Supplying, Fixing, testing and commissioning at site in position u PVC pipe of 6Kgf/cm2including PVC fittings with bosses where required e.g. tees, bends,door TEE , Door Elboe where ever required coupling and adapters and jointing with adhesive approved by fitting manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site universal clamps & anchor fasteners(8mm) , threaded rod(8mm),nuts ,washers, wherever required etc. complete.Make: Astral/Supreme/Ajay 110mm O.D (6Kgf/cm2 (IS:4985)
Supplying, Fixing, testing and commissioning at site in position Deep Seal UPvc fabricated Multi floor trap (4”), with suitable supporting on GI slotted rails (1.6mmthick) full threaded rod, anchor fasteners etc. Complete in all respects. 50/75 mm dia outlet (In Ceiling)Astral/Supreme/Ajay
Supplying,Fixing, Testing and commissioning at site in position 150x150mm square C.P cast brass or stainless steel anti cockroach grating cover ss (304) of matching size of UPvc fabricated floor trap / multi inlet trap complete in all respects. Chilly/Eligna/
Supplying,Fixing, testing at site in position 160mm dia square /circular grating Terrace rain water outlet (Cast Iron)(for 110mm dia pipe)
Providing, Fixing at site in position uPVC Pipes (as per ASTM D – 1785 sch-40 ) of approved make For Cold Water Supply, complete with all necessary (ASTM D – 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc) (External / Inshaft) 1 ¼ “ (32mm) dia.
Providing, Fixing at site in position uPVC Pipes (as per ASTM D – 1785 sch-40 ) of approved make For Cold Water Supply, complete with all necessary (ASTM D – 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc) (External / Inshaft) 1 1/2 “ (40mm) dia.
Providing, Fixing at site in position uPVC Pipes (as per ASTM D – 1785 sch-40 ) of approved make For Cold Water Supply, complete with all necessary (ASTM D – 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc) (External / Inshaft) 2” (50mm) dia (External / in Shaft)
Providing, Fixing at site in position uPVC Pipes (as per ASTM D – 1785 sch-40 ) of approved make For Cold Water Supply, complete with all necessary (ASTM D – 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc) (External / Inshaft) 2 ½” (65mm) dia (External / in Shaft)
Supplying,Fixing at site in position full way lever operated forged brass gate valve of brass body with forged brass hard crome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings ¾ ''(20mm) dia.
Supplying,Fixing at site in position full way lever operated forged brass gate valve of brass body with forged brass hard crome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings 1” (25mm) dia
Supplying,Fixing at site in position full way lever operated forged brass gate valve of brass body with forged brass hard crome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings 1 ¼ “ (32mm) dia.
Supplying,Fixing at site in position full way lever operated forged brass gate valve of brass body with forged brass hard crome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings 1 1/2 “ (40mm) dia.
Supplying,Fixing at site in position full way lever operated forged brass gate valve of brass body with forged brass hard crome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings 2” (50mm) dia
Supplying, Fixing, testing and commissioning at site Puddle Flange fabricated from Upvc ASTM Grade sch-40 pipes & uPVC sheet (600 mm long) 1 ¼ “ (32mm) dia.
Supplying, Fixing, testing and commissioning at site Puddle Flange fabricated from Upvc ASTM Grade sch-40 pipes & uPVC sheet (600 mm long) 1 ½” (40mm) dia (External / in Shaft)
Supplying, Fixing, testing and commissioning at site Puddle Flange fabricated from Upvc ASTM Grade sch-40 pipes & uPVC sheet (600 mm long) 2” (50mm) dia (External / in Shaft)
Supplying, Fixing, testing and commissioning at site Puddle Flange fabricated from Upvc ASTM Grade sch-40 pipes & uPVC sheet (600 mm long) 2 ½” (65mm) dia (External / in Shaft)
Supplying, Fixing, testing and commissioning at site Puddle Flange fabricated from Upvc ASTM Grade sch-40 pipes & uPVC sheet (600 mm long) 3” (80mm) dia (External / in Shaft)
Supplying, Fixing, testing and commissioning at site Puddle Flange fabricated from Upvc ASTM Grade sch-40 pipes & uPVC sheet (600 mm long) 4” (100mm) dia (External / in Shaft)
Supplying, Fixing, testing and commissioning at site Puddle Flange fabricated from 100 mm dia GI pipe with 6mm tk plate (600 mm long) for FIRE Tank
Supplying and Laying of pipes and conveying to position; cleaning, laying and jointing to true lines and gradients, with proper bedding uPVC pipe of IS 4985(6kgf/cm2) including jointing the pipe as per specification, testing the pipe line after installation all per provisions of IS: 1742-1983 (Code of practice for building drainage) complete as directed by the Employer 160 mm OD (6/kg/cm2)
Providing and supplying of Class SN8 Structured Wall polyethelene Piping systems (Pipe with online/offline coupler and elastomeric sealing ring) with non-smooth External Annular Corrugated and Smooth Internal Surfaces (Double Wall) for non-pressure underground Sewerage & Drainage application as per EN:13476-3 including all local and central taxes, transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to the departmental stores etc. complete.(ID 150 mm diameter) Make: Astral, Supreme, Finolex, Prince 160 mm OD (6/kg/cm2)
Providing and supplying of Class SN8 Structured Wall polyethelene Piping systems (Pipe with online/offline coupler and elastomeric sealing ring) with non-smooth External Annular Corrugated and Smooth Internal Surfaces (Double Wall) for non-pressure underground Sewerage & Drainage application as per EN:13476-3 including all local and central taxes, transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to the departmental stores etc. complete.(ID 150 mm diameter) Make: Astral, Supreme, Finolex, Prince 200 mm OD (6/kg/cm2)
Providing and fixing C.I. cover with frame (Medium duty) 450x450 mm , total weight of cover and frame to be not less than 108kg FOR SUMP TANKS
Providing and fixing C.I. cover with frame (Medium duty) 450x450 mm , total weight of cover and frame to be not less than 23 kg for OHT
Supply, installation, testing and commissioning of percolation well (Recharge well) including all work like drilling, compressor work, gravel packing, mud slurry disposal, clay packing and including of all materials like 300mm UPVC pipe, 300mm wire screens, 300mm collar joint, accessories, gravels, sand, sand filteration module etc. Site cleaning, mud pit, mud refilling for borewell must be in the contractor's scope. Contractor has to maintain the percolation well upto three years after installation.
Supply,Installation, Testing and commissioning of Clear water transfer open well submerssible pump of adiquate hp with discharge 3 lps at 20 mtr head, SS body, ss shaft with bronze impeller mounted on a single base plate with controll panel and auto level controller. 1 working+ 1 stand by
TERRACE DWS BOOSTER PUMP Duty Conditions of 6 lps @ 35 mtr - head(Each pump 3LPS 35 mtr Head - 2 Pump system-1 Working+1standby) Compact skid mounted Booster pumps with SS 304 casing, SS316 impeller , SS316 shaft , C I base and TEFC motor with mechanical seal. Pump to be have single VFD logic controller. - Electric control panel with logic controller, relays, calibrated pressure switch, pressure transmitter including cabling within panel, incorporating dry run protection, potential contacts for BMS integrating , sucton and discharge headers, pressure vessal 60 ltr capacity. 1 working+ 1 stand by
Fixing, testing and commissioning at site Automatic Dewatering system having 2 nos (1w+1s) Vertical Bottom suction submersible pump Having CI: body / Ci: impeller / SS : shaft . Each pump should be capable to deliver 3 lps @ 8mtr , having 0.75 kw /1hp / 3phase motor . A wall mounting micro controlled automatic control panel should be provided for the working of pumpset as 1w+1s in cascading operation . The control panel should have LCD screen showing Voltage , Ampere , Pump running status , error logs, faulty pump indication etc. The panel should protect the pumpset from over and under voltage , over and under load , dry run , etc . Automatic operation of pumpset should be with float switch.(deliver pipeline size : 40mm )(Basement Pit )
WATER TREATEMENT PLANT Supply, Installation, Testing & Commissioning of 14,000 Lpd Water Treatment Plant with Reverse Osmosis Process with all mechanical work like piping, mechanical components as follows but excluding the electrical works and civil work. a) PAC off Chlorine Dosing system -1nos,Pressure sand filter FRP-1 no ,Activated carbon filter FRP-1no,
SEWAGE TREATMENT PLANT 50 KLD Modular Membrane Bioreactor (MBR) based Sewage Treatment Plant, Design Flow KLD 60.0 LPH 2000.0 Type Fully-Automated, Design MLSS mg/L 6000.0 – 8000.0.Membrane Membrane Bioreoctor (MBR) to provide an advanced level of organic and suspended solids removal with 0.4 Microns pore isze, provides high filtrate quality. Operating Hours h 24.0, Design Flexibility % 30 - 100 with transfer pumps, air blowers, medias, membrine, tube settlers and all connected pipe lnes and necessary power connections and cubicle control panel in all respect. 3 years operation and maintanance of Sysytem is included,OUTLET Results Parameter Unit Outlet Value pH - 6.5-8.5 TDS mp/I <2100 TSS mp/I <20 BOD5 mp/I <10 COD mg/I <50 Total Nitrogen mp/I <5 Phosphorus mp/I <5 Ammonia Mp/I <5 Fecal Califorms MPN/ml Less than 1000
Supply, installation, testing & commissioning of Single headed, S.S. ISI marked, ISO approved, oblique pattern hydrant landing valve with 80 mm dia flanged inlet and 63 mm dia instantaneous type female outlet complete with SSl cap and G.I. chain, twist release type plug and all accessories required for complete installation as per IS:5290(Type 'A')Make: Safeguard, Minimax, New Age
Supply, installation and testing of Controlled Percolating (CP) Fire Hose ISI marked (IS:8423) 63 mm dia x 15 m long complete with instantaneous type S.S. 63 mm dia, ISI marked Male & Female couplings (IS:903) bound and riveted to hose pipe with copper rivets and 1.5 mm copper wire including all accessories as required for complete installation. (For external hydrants) Make: Safeguard, Minimax, New Age
Supply, installation, testing and commissioning of compact type first aid fire hose reel with wall mounting swinging-type drum complying to EN 671-1 standards with ISI marked, 19 MM x 30 M long thermoplastic hose. 560 MM Dia powder coated sheet metal frame, water ways made from Non-Ferrous aluminium Alloy metal, High quality semi-rigid marked (Type-1 or Type-2) flame resistant, kink and abrasion resistant, thermoplastic Hose. Rotary operated leak proof, hydraulically crimped with corrosion-free Stainless Steel Grade 304 fitting, shut-off nozzle with shut, spray & jet functions, etc. and tested to 1.2 MPA( 12 Bar pressure) installation brackets, complete in all respects including all accessories as required for complete installation. INLET PIPE CONNECTION FROM RISING MAINS TO HOSE REEL SHALL BE PROVIDED WITH GI HEAVY CLASS PIPES WITH UNIONS OR WITH READY MADE TYPE FLEXIBLE RUBBER HOSE IN STANDARD LENGTH, HYDRAULICALLY FITTED END CONNECTIONS ETC .Make: Monsher, Minimax, New Age
Supply, installation, testing and commissioning of Gun-metal 4-way fire brigade inlet connection 63mm dia instantaneous type male coupling with built in check valves and 150mm dia flanged outlet complete with bolts, nuts and rubber insertions as per I.S:904 including all accessories as required for complete installation. Make: Safeguard, Safefire, Minimax, New Age
Supply, installation, testing and commissioning of GI pipe (IS:1239 Part-I) Heavy duty Class 'B' including cutting, welding etc. bends, elbows reducers, tees , clamps, hangers and all other accessories as required for complete installation etc. including cutting holes in brick or RCC walls/slabs and making good the same complete including painting with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade including all steel work. Note : Pipes up to and 50 mm dia shall be socket welded with DI fittings. For pipes inside the plant room 80mm dia
Supply, installation, testing and commissioning of GI pipe (IS:1239 Part-I) Heavy duty Class 'B' including cutting, welding etc. bends, elbows reducers, tees , clamps, hangers and all other accessories as required for complete installation etc. including cutting holes in brick or RCC walls/slabs and making good the same complete including painting with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade including all steel work. Note : Pipes up to and 50 mm dia shall be socket welded with DI fittings. For pipes inside the plant room 100 mm dia
Supply, installation, testing and commissioning of wafer types' iron , without lugs, lever operated Butterfly valves (PN 1.6) complete suitable with with bronze/gunmetal seat and all accessories required for complete installation. Make : Leader/ Audco/ Zoloto 100 mm dia
Supply, installation, testing and commissioning of horizontal lift swing check type reflux non-return valves (PN 1.6) complete with matching flanges, rubber insertion, nuts, bolts and washer etc. of following sizes complete with all accessories required for complete installation. Make : Leader/ Audco/ Zoloto 100 mm dia
Supply, installation, testing and commissioning of Brass Air release valve, size 25mm with threaded inlet & provided with ball type float complete with all accessories required for complete installation. Make : Leader/ Audco/ Zoloto
Supply, installation, testing and commissioning of industrial type pressure switch having 1/4" BSP(F) connection IP:32 enclosure protection, phosphor bronze bellows as sensing element, SDPT contact system, switch rating 6A Inductive/lOA resistive 380 V AC, 0.2A Inductive/10A resistive 250V DC suit with ball valve etc. complete as required. Make: Infoss/
Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump). a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. d) Suitable cement concrete foundation duly plastered and with anti vibration pads.
Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump). a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. d) Suitable cement concrete foundation duly plastered and with anti vibration pads. 900 lpm at 35 m Head Make : Kirloskar, Mather & Platt India Limited
Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump). a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. d) Suitable cement concrete foundation duly plastered and with anti vibration pads. 450 lpm at 35 m Head Make : Kirloskar, Mather & Platt India Limited
Supply and installation of Weather proof Outdoor type hose cabinets fabricated from 14 SWG M.S. sheet with full glass door with locking arrangement (Water Proof), suitable to accommodate 2 nos.15 M long hose and 1 No branch pipe. Glass will be transparent Acrylic - 3mm thick. The cabinet shall be painted with coat of P O Red paint from outside and white paint from inside including all accessories as required for complete installation.(size shall be such that the above all items can be accommodated). (Double door type) as per industrial standards
Supplying, laying, fitting and fixing , testing and commissioning of under ground GI heavy duty 'C' class pipe confirming to IS 1239 The pipes shall have anti-corrosive wrapping coating and a wrapping treatment with pipe coat 4 mm thickness, after applying one or more coats of Asphalt primer. Rates shall include cutting, welding etc. bends, elbows reducers suitable for pipe joints, clamps and all other accessories including excavation of earth to sufficient depth to install the pipes, the pipes buried in ground excavation and refilling etc.as per the specification and as required complete as required for complete installation etc. including cutting holes in RCC walls/slabs and making good the same adequately supported on rigid supports duly painted as required complete in all respect including all up to building rising mains and for yard hydrants , 100 mm dia
Supplying, laying, fitting and fixing , testing and commissioning of under ground GI heavy duty 'C' class pipe confirming to IS 1239 The pipes shall have anti-corrosive wrapping coating and a wrapping treatment with pipe coat 4 mm thickness, after applying one or more coats of Asphalt primer. Rates shall include cutting, welding etc. bends, elbows reducers suitable for pipe joints, clamps and all other accessories including excavation of earth to sufficient depth to install the pipes, the pipes buried in ground excavation and refilling etc.as per the specification and as required complete as required for complete installation etc. including cutting holes in RCC walls/slabs and making good the same adequately supported on rigid supports duly painted as required complete in all respect including all up to building rising mains and for yard hydrants , 80 mm dia
Supply & installation of Pressure Gauge with 0-300 psi (0-21Kg/Sq.CM) range white background, black graduation scale with dual reading in Kg/Sq.CM & PSI, 1/4" BSPT bottom entry 100 MM dial, PHOSPHOROUS BRONZE bourden tube, brass moving parts, polished stainless steel case with positive seal against weather, moisture & dust, hardened glass, glycerine filled type with syphon tube and isolation cock,Make: Fiebig / H guru
Providing & fixing double flanged flexicon rubber expansion joint with unit control of standard length as per manufacturers specifications suitable for working pressure rated (PN16) and test pressure to be 150 % rated pressure of including rubber gaskets, flanges, nuts, bolts and washers complete as required 100 mm dia
Providing & fixing double flanged flexicon rubber expansion joint with unit control of standard length as per manufacturers specifications suitable for working pressure rated (PN16) and test pressure to be 150 % rated pressure of including rubber gaskets, flanges, nuts, bolts and washers complete as required 80 mm dia
Supply and fixing Co2 type Fire Extinguisher of capacity 4.5 kg filled with Co2 Gas with control discharge mechanism ( squeeze grip type) fitted with Bend and Horn applicable on Class B and C class of fire. Manufactured and marked to IS 15683 with ISI marking and cylinders having the approval of Chief Controller of Explosives, and including all accessories as required for complete installation.
Supply and fixing of dry chemical powder type (DCP) fire extinguishers (ABC Type) of 4 Kg capacity, Pressurized with nitrogen, mfg. to IS:15683 with ISI mark fitted with pressure gauge, GM cap nozzle complete with initial charges and installation brackets and screws with ISI marks etc. complete as approved and instructed by the engineer in charge including all accessories as required for complete installation..
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 A switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 2 way 5/6 A switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 A switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 A socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 A socket outlet
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required 1 or 2 Module (75mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required 3 Module (100mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required 4 Module (125mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required 6 Module (200mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required 8 Module (125mmX125mm)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (4 + 12), Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way (4 + 18), Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way (4 + 24), Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way (4 + 36), Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (8 + 24), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Earthing with CI. earth plate 1200 mm X 1200 mm X 12 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm Copper strip on surface or in recess for connections etc. as required.
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 35 sq. mm and upto 95 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 95 sq. mm and upto 185 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 185 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required. Above 120 sq. mm and upto 400 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 120 sq. mm (45mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 185 sq. mm (57mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 240 sq. mm (62mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 400 sq. mm (82mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq. mm (25mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 25 sq. mm (28mm)
S' type M.S. fan hook fabricated from suitable dia. M.S. rod duly painted for fixing of ceiling fan. The 'S' type hook shall be fixed to steel bar in RCC ceiling. The ceiling shall be replastered with sand, cement & neeru etc. The cost of labours for chipping out ceiling upto steel bar & fixing of 'S' hook & resurfacing the ceiling is included in the cost of item
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way (4 + 36), Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 6 way (4 + 18), Double door
11KV Outdoor Metering Cubicle SITC of 11KV Outdoor Metering Cubicle comprising of : 3 Nos. Current transformer (---/5A,15VA,class 0.2s) 1 No. Potential transformer(11KV /110V,100VA,class 0.2) Separate Compartment for CT/PT and TOD Meter with KSEB sealing facility TTB with Fuse and Carrier Provision for incoming and outgoing XLPE 11 KV Cable and cable entry from bottom side with cable box suitable for 3 x 300 sqmm XLPE, 11KV Al: cable Enclosure-Powder coated CRCA sheet 2MM –IP 54
11KV TOD Meter SITC of 11KV/ √3 / 110V/ √3 , Class 0.2S , 15VA HT TOD Meter suitable for mounting outdoor type with all standard accessories. 11 KV KSEB metering cubicle, lead wires etc.complete Carrying CT/PT units with TOD meter for testing and calibrating at the KSEB Testing Lab and taking back the same to the site is included in the scope of the contractor.Statutory testing fees shall be remitted and will be reimbursed against producing original receipt
NEUTRAL CTs Supply & Fixing of 1no Cast Resin Neutral CT with ratio 150/5A ,10VA, Cl.5P10, fixed in a suitable M.S box with view glass.
Supply of 11KV stranded compact circular aluminium conductor,conductors insulation screened with extruded semi conducting compound in combination with copper tape (0.3 kA for 1 sec.), cores laid up, inner sheath of PVC tape,galvanized steel flat strip armoured,and overall PVC sheathed cable conforming to IS 7098/11/85 with latest amendments & confirming to the GTP of Group A of following sizes. 3C - 150 Sq.mm HT Cable
SITC of D.G. set of following KVA 0.8 P.F.3 phase,50c/s,433V, comprising diesel engine, fuel tank, base plate, antivibration pad, battery, battery lead wire, battery charger self starting and self charging mechanism, and residential type silencer, control panel , in accoustic enclosure etc.with all standard accessories as per Electrical Inspectorate standards and pollution control board norms. 320 KVA
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) MAIN MV PANEL
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) APFC PANEL
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) SSB
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) SB2
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) SB3
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) VRF PANEL
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) SSB UTILITY PANEL
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) LIFT PANEL
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) PUMP PANEL
SITC of cubicle type medium voltage switch boards as per specifications mentioned below, comprising of ACBs / MCCBs., enclosed in 16 guage M.S.cubicle complete with angle iron frame work, panel doors , horizontal and vertical busbars and outgoing feeders, FRP separators, phase barriers, gaskets for door, feeders designations, etc., Main Switch Board shall be capable of withstanding 50 KA fault level. The panel shall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards) STP PANEL
SITC of 15kw Frame with 3.4kw x 4 modules three phase in and out. With indoor (IP21) with surge protection system with 60 min backup battery @ 10kva .8 PF load with min VAH of 16320 Dual string (SMF battery of reputed approved make. Input pf >0.99, with external input isolation transformer, with IGBT rectifier and inverter Double conversion technology, with input voltage range 320-460 @ full load, 50Hz Three Phase, output 400V, 50Hz Three phase, compatibility etc. 15 KVA UPS - Three Phase
SITC of 10kw Frame with 3.4kw x 3 modules three phase in and out. With indoor (IP21) with surge protection system with 60 min backup battery @ 10kva .8 PF load with min VAH of 16320 Dual string (SMF battery of reputed approved make. Input pf >0.99, with external input isolation transformer, with IGBT rectifier and inverter Double conversion technology, with input voltage range 320-460 @ full load, 50Hz Three Phase, output 400V, 50Hz Three phase, compatibility etc. 10 KVA UPS - Three Phase
SITC of 5kw Frame with 3.4kw x 3 modules three phase in and out. With indoor (IP21) with surge protection system with 60 min backup battery @ 10kva .8 PF load with min VAH of 16320 Dual string (SMF battery of reputed approved make. Input pf >0.99, with external input isolation transformer, with IGBT rectifier and inverter Double conversion technology, with input voltage range 320-460 @ full load, 50Hz Three Phase, output 400V, 50Hz Three phase, compatibility etc. 10 KVA UPS
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 120 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 185 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 240 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 400 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 4 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 6 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 25 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 X 4 sq. mm
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans LED Downlight Recessed Fitting 15 W
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans LED Surface Mount Fitting 12 W
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans LED Linear Fixture 20Watts 4ft Surface Mounted
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans Mirror Light 5W
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans Ceiling Fan -1200 mm ( BLDC)
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans Exhaust Fan -450 mm
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans 20w Surface light
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans 11W Bollard Lights
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans 80W Flood Light
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans 6M Pole & 60W LED Flood/Street Light with necessary arms for light fixtures (Civil works including)
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans 18W Bulkhead Light
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans 18W Bulkhead Light
SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans 18W Bulkhead Light
Providing and fixing Fully Solid Vertical Air terminals for wind stability as per IS/IEC -62305 part-3. For 1,2,3,4 meter air terminal 16mm rod tapered to 10 mm aluminium rod meter rod: Meets the requirement (IS/IEC 62305). Semi-hard (E-AlMgSiO5) Suitable for high wind load. All air terminal must have Interception Tip at the Top of air terminal. System consist of Fang Fix with base and clamp on the top air terminal is erected. Air terminal Joining Clip Stainless Steel SS 304 clamp made of cable bracket, lightning tested for 100 KA 10/350 micro sec waveform. Stainless Steel Wall Clamp or 16 KG stone of 365 mm diameter, high level of stability. No. of stones/wall clamps depending on wind load. Quick and easy mounting of interception rod using anchors. Concrete, frost-resistant, can be stacked. Govt approved Indian labs test certificate required. Make: Cape/Dehn 2 meter air terminal with Interception Tip mounted on Stainless Steel Wall Clamp mounting accessories.
Providing & fixing of 8mm solid aluminium round conductor with necessary holders @ required interval as specified below: Meets the requirement of (IS/IEC 62305) : semi-hard (E-AlMgSiO5 )with 50 sq.mm cross sectional area. Govt approved Indian labs test certificate required. Make: Cape/Dehn Conductor with Down Conductor Holder made of whether resistant plastic holder @ every 0.75 meters
Providing & fixing of 8mm solid aluminium round conductor with necessary holders @ required interval as specified below: Meets the requirement of (IS/IEC 62305) : semi-hard (E-AlMgSiO5 )with 50 sq.mm cross sectional area. Govt approved Indian labs test certificate required. Make: Cape/Dehn Conductor with Terrace Conductor Fibre Reinforce Concrete holder @ every 0.75 meters
T-Connectors Providing and fixing of Cross Connector/T Connector/Folding Clamp/Clamping Shoe/ Expansion Piece: to route vertical down conductor /mesh formation made of Aluminium Ferrule using screw free joints. Folding Clamp/Clamping Shoe for metal panels (up to 20mm thickness of the metal frame): Folding clamp/clamping shoe for metal frame thickness up to 20mm, made of stainless steel SS 304/316 grade , conforms to the requirements according to (IS/IEC 62305). Expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length at every 20 meters horizontally. Using round conductor 8mm aluminium conductor with straight Connector: using Aluminium Ferrule. Quick installation using crimp joints. Conforms to the requirements according to (IS/IEC 62305). Make sure all joints are strong and will be inspected at site. Galvanised Iron joints are not permitted to avoid risk of corrosion. Single bolt joints are not permitted to avoid risk of faulty loose joints and reduce risk of flash over. Govt approved Indian labs test certificate required. Make: Cape/Dehn
Test Joints Providing and fixing of Stainless Steel Test Joint suitable with suitable Outdoor Enclosure: For 8mm dia solid round aluminium conductor & 10mm dia copper coated solid steel round conductor having 100 microns of copper bonding . Conforms to the requirements according to (IS/IEC 62305).The enclosure should be outdoor glass-fibre reinforced polycarbonate opaque having minimum inner dimension of 75mm x 75 mm x 50 mm. The test link has to be straight and needs minimum 4 mounting screws for strong joints Inspection of bimetallic corrosion at site required. Seperation of 8mm Aluminium & 10mm Copper bonded steel is required for future inspection and contractor has to make sure both conductors permitted. Govt approved Indian labs test certificate required. Make: Cape/Dehn
Ring Earthing Providing and laying copper coated steel solid round conductor 10mm diameter from earth electrode directly in ground as required. copper coated steel, high corrosion resistant. Meets the requirement of (IS/IEC 62305) copper coating thickness of 100microns Should be tested and use exclusively for lightning protection earthing system and ring equipotential bonding. After test link needs to be routed inside Heavy duty conduit to avoid touch potential till ground level. Govt approved Indian labs test certificate required. Make: Cape/Dehn
Welded Joints Installation of Exothermic Weld Joints for 10mm round copper bonded steel conductor having 100 microns as per IS/IEC 62305. Each under ground joints has to be wrapped with petrolatum- coated chemical fibre fabric having 1.1mm thick and width 50mm. Govt approved Indian labs test certificate required. Make: Cape/Dehn
Earth Pits Providing and fixing of maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of min 3048mm length (10 feet), having a diameter of 20mm with copper bonding thickness of 250 microns as per UL 467. The Rod has to be either continuous or with self-coupling peg & bore arrangement with fault current withstand capability of 30 KA rms value for 1 second and I peak of 76 KA The rod must be having corrosion test, peel off test for uniform coating, 180 degree bend test with out peeloff of copper bonding. Exothermic welded Clamp for clamping as suggested as per NBC 2016.Ordinary Stainless steel/Copper alloy universal clamps are not recommended. For self coupling peg & bore arrangement rod needs Impact point on the bottom rod for easy insertion. Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The material should have a resistivity less than 0.2 Ωm. It should be free from hazardous substances.The mineral compound is required to have minimum 17.5 Kg of the total composite.The compound should be chemically inert and needs to submit Govt approved Indian labs test certificate. Concrete Earth electrode inspection chamber with weight bearing capacity of 50KN. The dimension shall be 320mmx 320mmx 190mm. Govt approved Indian labs test certificate required. Make: Cape/Dehn
Earth Pits Providing and fixing of maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of min 3048mm length (10 feet), having a diameter of 20mm with copper bonding thickness of 250 microns as per UL 467. The Rod has to be either continuous or with self-coupling peg & bore arrangement with fault current withstand capability of 30 KA rms value for 1 second and I peak of 76 KA The rod must be having corrosion test, peel off test for uniform coating, 180 degree bend test with out peeloff of copper bonding. Exothermic welded Clamp for clamping as suggested as per NBC 2016.Ordinary Stainless steel/Copper alloy universal clamps are not recommended. For self coupling peg & bore arrangement rod needs Impact point on the bottom rod for easy insertion. Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The material should have a resistivity less than 0.2 Ωm. It should be free from hazardous substances.The mineral compound is required to have minimum 17.5 Kg of the total composite.The compound should be chemically inert and needs to submit Govt approved Indian labs test certificate. Concrete Earth electrode inspection chamber with weight bearing capacity of 50KN. The dimension shall be 320mmx 320mmx 190mm. Govt approved Indian labs test certificate required. Make: Cape/Dehn
Solar PV 80KW Common load
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 150 sq. mm
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 150 sq. mm
Supplying and fixing of 25 mm Medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supply and drawing of UTP 4 pair Cat 6 LAN cable in the existing surface/recessed PVC conduit as required. one run
Supplying and fixing of 32 mm Medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of GI box of following size modules, alongwith modular base & cover plate for modular switches in recess etc as required. 1 or 2 Module (75mmX75mm)
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and drawing 2 pair, 0.5 sq mm FR PVC insulated copper conductor, un armoured telephone cable in the existing surface/recessed steel/ PVC conduit.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. Telephone socket
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required
Supply, installation, testing and commissioning of IP based IR Varifocal dome Camera, 1/3" CMOS, 4 MP, 2.7–12 mm MFZ, night vision compatible,IR range of 40 mtrs PoE, inbuilt micro SD card,Ethernet port, H.264, IP 66, ONVIF, UL, FCC & CE certified. All mounting accessories shall be included
Supply, installation, testing and commissioning of IP based IR bullet Camera, 1/3" CMOS,4 MP, night vision compatible,IR range of 40 mtrs PoE, inbuilt micro SD card,Ethernet port, H.264, IP 66, ONVIF, UL, FCC & CE certified. All mounting accessories shall be included
Supply, installation, testing and commissioning of IP based IR PTZ camera, 1/3" CMOS, 4 Megapixel,30X zoom, WDR, IR range of 200 Meters, inbuilt micro SD card,,Ethernet port,TDN, PoE, DWDR, BLC, AGC, DNR, OSD,H.264 High Profile dual-stream, ONVIF, Wall/corner Mount, IP-66. CE, FCC, C-Tick certified. All mounting accessories and mounting arm suitable for the location shall be included
32 Channel IP Cameras support, 4 SATA Ports ( Loaded with HDD for 60 days storage), Maximum users - 20 or higher, IR Range of 100 Mtr, Ptotocols - HTTP, HTTPS, TCP/IP, IPv4/IPv6, UPnP, RTSP, UDP, SMTP, NTP, DHCP, DNS, IP Filter, DDNS, FTP, SNMP, IP Search , ONVIF 2.4, SDK, CGI trigger Events - recording, PTZ, Tour, Alarm out, video Push, Email, FTP, Snapshot, Buzzer & Screen tips, recording Mode - manual, Schedule (Regular, Continuous), MD (video detection: motion detection, tampering, video Loss), Stop, Bandwidth - 200 Mbps, ONVIF 2.0
24 Channel IP Cameras support, 4 SATA Ports ( Loaded with HDD for 60 days storage), Maximum users - 20 or higher, IR Range of 100 Mtr, Ptotocols - HTTP, HTTPS, TCP/IP, IPv4/IPv6, UPnP, RTSP, UDP, SMTP, NTP, DHCP, DNS, IP Filter, DDNS, FTP, SNMP, IP Search , ONVIF 2.4, SDK, CGI trigger Events - recording, PTZ, Tour, Alarm out, video Push, Email, FTP, Snapshot, Buzzer & Screen tips, recording Mode - manual, Schedule (Regular, Continuous), MD (video detection: motion detection, tampering, video Loss), Stop, Bandwidth - 200 Mbps, ONVIF 2.0
16 Channel IP Cameras support, 4 SATA Ports ( Loaded with HDD for 60 days storage), Maximum users - 20 or higher, IR Range of 100 Mtr, Ptotocols - HTTP, HTTPS, TCP/IP, IPv4/IPv6, UPnP, RTSP, UDP, SMTP, NTP, DHCP, DNS, IP Filter, DDNS, FTP, SNMP, IP Search , ONVIF 2.4, SDK, CGI trigger Events - recording, PTZ, Tour, Alarm out, video Push, Email, FTP, Snapshot, Buzzer & Screen tips, recording Mode - manual, Schedule (Regular, Continuous), MD (video detection: motion detection, tampering, video Loss), Stop, Bandwidth - 200 Mbps, ONVIF 2.0
Supply, installation, testing and commissioning of 20 100/1000 SFP ports + 4 Combo 10/100/1000BASE-T/SFP ports + 4 10G SFP+ ports, L2 Management Switch - Core Switch
Supply, installation, testing and commissioning of 24 port- Edge PoE switch
Supply, installation, testing and commissioning of 16 port- Edge PoE switch
Supply, installation, testing and commissioning of Patch Panel UTP Keystone- 32 Port- Fully loaded (Cat 5e,Cat 6 & Cat 6 A )
Supply and installation of Cat 6 UTP patch cord, 1 mtr
Supply, installation, testing and commissioning of Server PC, Intel i7 processor, 24 inch LED monitor, Gigabit LAN port, USB port, 8GB DDR3 RAM,1TB HDD,1GB dual graphic card, 100/1000 LAN ports, optical mouse, Keyboard, DVD Writer. Genuine Win 8.1 Pro - Down grade to Win 7 professional, 24 inch LED monitor
Supply, installation, testing and commissioning of Surveillance / ESATA compatible Hard Disk of 4TB capacity to achieve the total storage for the NVR server
Supply, Installation, Testing & Commissioning of 42 inch full HD LED monitor with resolution 1920X1080 pixel including wall mounting accessories (location: security room & central control room).Material shall be UL/CE listed
Supply and installation of wall mounted 22U rack including cable manager, power supply units etc.to accommodate NVR, ethernet switch patch panel etc in control room
Supply and installation of wall mounted 9U rack including cable manager, power supply units etc.to accommodate NVR, ethernet switch patch panel etc in control room
Supply, installation, testing & commissioning of column speaker 6 watts
Supply, installation, testing & commissioning of voice alarm controller with all cables and accessories
Supply, installation, testing & commissioning of 480 W Booster Amplifier with all cables and accessories
Supply, laying and termination of 2 Core x 1.5 Sq.mm Armoured Al.Mylar Screened FRLS Twin Twisted PVC Insulated cable along with all accessories. Accessories include cable glands, locknuts,saddle clips, cable tie & other hardwares to achieve cable termination and installation. Cable shall be terminated in speakers and amplifiers
Supply, installation, testing & commissioning of standard AV rack with 600mm Width, 800 mm Outer Depth and 36U Height
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. RJ 45 socket
Supply and installation of Cat-6 shuttered 24 port patch panel
SITC of 24 port unmanaged ethernet switch
Supply and installation of 9U rack with Front glass door, Rear Perforated door with handle Lock & key. Front/Rear 19" mounting angles, top, bottom open, RAL 9005 with all other accessories
AX3600 WIFI6 Dual Band Multi Band Multi Gigabt Ceiling Mount Access Point / EAP660HD
Supply,laying and termination of 20 pair telephone cable, 0.5mm copper PVC insulated,unarmoured telephone cable drawn in the existing cable tray
Supply,laying and termination of 20 pair telephone terminal block housed in engineering plastic box with transparent hinged door
Supply,laying and termination of 10 pair telephone cable, 0.5mm copper PVC insulated,unarmoured telephone cable drawn in the existing cable tray
Supply,laying and termination of 10 pair telephone terminal block housed in engineering plastic box with transparent hinged door
Supply,installation,testring and commisioning of EPABX with the following specifications: 1. 08 Port Analog trunk with CLI and Power Failure Transfer and with Protection modules. 2. 02 PRI. 3 Charger/UPS with Batteries for backup of 1 hour.
10 PASSENGER LIFT Equipement Details : Machine Roomless - Gearless No. of Unit : One Controller Type : Micro Processor Based VVVF Capacity in Kgs/Persons : 544Kg/8P Speed in MPM : 60mpm/1.0mps Door Opening Type : Centre Opening Sliding Door Operation : Simplex No.of Stops : 3 (G,1,2) No.of Openings : 3 (G,1,2) Storey Served Front : 3 (G,1,2) Travel (mm) : 12900mm Hoistway Size (mm) : 2570 (w) x 2000 (d) Cabin Dimemnsions (WxDxH) (mm) : 1300x1600x2200 Pit Depth (mm) : 1500 Overhead (mm) : 4100 Entrance Dimensions (mm) : 800x2000 Ceiling : SS Honeycomb finish with LED Downlight Car Front/Rear/Side Panel : SS Honeycomb finish Handrail : 38mm dia Car Doors : SS Honeycomb finish Car Flooring : Vinyl Tile Floor Thickness : 1.5mm Thick Vinyl Tile Car Sill : Extruded Hard Aluminium Entrance Frame/Landing Doors : SS Honeycomb finish
Supply, Installation ,testing and commissioning of the following minimum capacity Air-cooled VRF (Variable Refrigerant Flow) Outdoor unit with variable speed inverter driven multiple compressors complete with suitable capacity drive motors conforming to IE3 as per IS 12615, air cooled condenser, R410A refrigerant, oil separator, with all accessories, and safety devices like thermal protector, pressure relief valve, high-low pressure cut off etc . Necessary structural supports, ODU vibration isolators shall be considered . Equipment shall be suitable for 3 phase, 415 V, 50Hz supply along with suitably rated starter panel & associated accessories, suitable interconnecting control cabling between IDUs, ODUs ,power cabling between isolator and single/multiple outdoor units along with associated electrical accessories. Required supports including structural supports /RCC/ cement concrete foundation shall be included as part of equipment . COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The efficiency of the equipment shall meet ECBC/ASHRAE latest standards etc. complete in all respects as per the technical specifications.(single feeder power source will be provided for outdoor units). All the structural corrosion resistant structural supports/concrete pedestals for mounting indoor/outdoor equipment's shall be included. Gas charging with refrigerent R 410 A shall be included at sufficient quantity recommended by the manufacturer. (Complete in all respects as per technical specification) 174 HP Air cooled
Supply,installation,testing and commissioning of following minimum capacity VRV/VRF Highwall type Indoor unit equipped with washable synthetic mediapre-filter, fan section with low noise fan/dynamically balanced blower, multispeedmotor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cordless remote control, drain pan, necessary accessories etc., suitable for operation on 230V±10%, 50Hz, single phase AC supply, complete as required. The unit shall have automatic force shutdown provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. 1.45 TR
Supply,installation,testing and commissioning of following minimum capacity VRV/VRF Highwall type Indoor unit equipped with washable synthetic mediapre-filter, fan section with low noise fan/dynamically balanced blower, multispeedmotor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cordless remote control, drain pan, necessary accessories etc., suitable for operation on 230V±10%, 50Hz, single phase AC supply, complete as required. The unit shall have automatic force shutdown provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. 2 TR
Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with 19mm thick nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Complete in all respects as per technical specifications.(Piping quantities are tentative and total cost quoted shall be suitable for site layout, unit location and installation requirement.) 9.5mm
Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with 19mm thick nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Complete in all respects as per technical specifications.(Piping quantities are tentative and total cost quoted shall be suitable for site layout, unit location and installation requirement.) 15.9 mm
Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with 19mm thick nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Complete in all respects as per technical specifications.(Piping quantities are tentative and total cost quoted shall be suitable for site layout, unit location and installation requirement.) 19.1 mm
Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with 19mm thick nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Complete in all respects as per technical specifications.(Piping quantities are tentative and total cost quoted shall be suitable for site layout, unit location and installation requirement.) 22.2 mm
Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with 19mm thick nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Complete in all respects as per technical specifications.(Piping quantities are tentative and total cost quoted shall be suitable for site layout, unit location and installation requirement.) 28.6 mm
Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with 19mm thick nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Complete in all respects as per technical specifications.(Piping quantities are tentative and total cost quoted shall be suitable for site layout, unit location and installation requirement.) 41.5 mm
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 150mm width x 50mm depth x 1.6mm thickness (with 40 x 40 x 6mm GI angle supports)
Supply fixing testing and commissioning of Control wiring / network wiring using recommended quality of multicore cables in PVC Conduit
Supply and Installation of REFNET joints as per manufactures recommended standards for indoor units.
Supply and Installation of REFNET joints as per manufactures recommended standards for outdoor unit.
Supply, installation, testing and commissioning of suitable Dia PVC condensate drain pipe of 6kg/sq.cm upto 5m connecting the drain pan of the indoor units to nearest drain point with necessary U-trap, insulated with 9 mm thick closed cell elastomeric insulation finished with 7mils factory laminated glass cloth along with required pipe fittings and accessories like Bends, Tees, reducers, clamps, suitably supported etc. complete in all respects as per the technical specifications. 25mm Dia
Supply, installation, testing and commissioning of suitable Dia PVC condensate drain pipe of 6kg/sq.cm upto 5m connecting the drain pan of the indoor units to nearest drain point with necessary U-trap, insulated with 9 mm thick closed cell elastomeric insulation finished with 7mils factory laminated glass cloth along with required pipe fittings and accessories like Bends, Tees, reducers, clamps, suitably supported etc. complete in all respects as per the technical specifications. 32mm Dia
Supply, installation, testing & commissioning of communication cabling in conduit between indoor unit to outdoor unit with all necessary support and accessories (Complete in all respects as per technical specification)
Supply, Installation ,testing and commissioning of PDI Compatible central controller, along with associated accessories for controlling entire VRF system & 25% spare capacity for future provisions with suitable interconnecting control cabling between IDUs, ODUs and central controller ,Power wiring with necessary supports and complete in all respects as per the technical specifications.
Supplying and fixing of 19 mm thick 40-60kg/m3 density, regular closed cell class 0 nitrile rubber insulation finished with 7 mils factory laminated glass cloth ,anti-microbial protection. Butt all joints tightly and seal all breaks and joints by adhering glass cloth tape, fixing of insulation using OEM recommended fixing details ,supports and adhesive, tapes etc. with R value less than 0.6. (Complete in all respects as per technical specification) 19 mm thick
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.73 MB
Tendernotice_2.pdf
PDF • 3.68 MB
Tendernotice_3.pdf
PDF • 0.50 MB
Tendernotice_4.pdf
PDF • 0.18 MB
Tendernotice_5.pdf
PDF • 0.35 MB
DocPolytechnicCollegeMCY.pdf
Tender Documents • 3.66 MB
TenderNotice.pdf
Tender Documents • 0.71 MB
BOQ_3626.xls
BOQ • 0.64 MB
Download all tender documents and submit your bid