Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.4 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹34.2 L+₹2.7 L (8.66%)Rejected-Finance | L2 | Rejected-Finance Rejected | |
| 3 | L3₹34.9 L+₹3.4 L (10.7%)Rejected-Finance | L3 | Rejected-Finance Rejected | |
| 4 | L4₹35.2 L+₹3.7 L (11.6%)Rejected-Finance H NO 5 117 BODUPPAL INDIRANAGAR COLONY GHATKESAR MANDAL HYDERABAD 500092 | MEDCHAL MALKAJGIRI | TELANGANA | 500092 | L4 | Rejected-Finance Rejected | |
| 5 | Rejected-Technical PRAGATHI PRIDE APARTMENT 3 4 520 FLAT NO 203 BARKATPURA HYDERABAD 500 027 | HYDERABAD | TELANGANA | 500027 | - | Rejected-Technical Rejected |
Tender Value
Refer Docs
EMD Value
₹68,280
Closing Date
5 Apr 2021, 3:00 pmClosed
CCE(RND)South
PB NO 1569, Akbar Road, Secunderabad
PROVISION OF CREATION OF DATA CENTRE ROOM AT FIRST FLOOR FOR KAUTILYA AT RCI, HYDERABAD
2021_DRDO_623734_1
23195/CIV/KAU/PLG
Limited
Civil Works - Others
Item Rate
150 days
RCI
As per NIT
2 documents required · 2 mandatory
₹500
Yes
CCE(RND) SECUNDERABAD
₹68,280
Yes
9 Apr 2021
23 Mar 2021
6 Apr 2021
23 Mar 2021
5 Apr 2021
27 Mar 2021
24 Mar 2021 - 26 Mar 2021
Amount
SUBHEAD - I : DEMOLITION :
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. (a) IN CEMENT MORTOR
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead. For thickness of tiles 10 mm to 25 mm
Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 metres lead.
Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge.
Dismantling steel work (grills) manually/ by mechanical means in built up sections without dismembering and stacking within 50 metres lead as per direction of Engineer-in-charge.
Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : Of area 3 sq. metres and below
Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : Of area beyond 3 sq. metres
Dismantling of flushing cistern of all types (C.I./PVC/Vitrious China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead.
Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved.
CREDIT FOR FLUSH DOOR
CREDIT FOR GLASS PARTION WITH GLASS DOOR
CREDIT FOR MISC ITEMS LIKE WATER CLOSET, SMOKE DETECTORS, SPRINKLERS ETC
SUB HEAD - II : BRICK WORK, PLASTERING & PAINTING
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand).
Providing of 12 mm cement plaster of mix in all surface with (a) cement mortar 1:6 (1 cement : 6 fine sand) at all levels.
Providing and Applying two coats of oil bound distemper of approved brand and shade over and including one coat of primer, including preparation of surface etc.,complete as directed.& with plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : (a) Two or more coats on new work.
SUB HEAD - III : FLOORING WORK:
Providing and laying double charged vitrified floor tiles of Size 800x800 mm.(thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including grouting the joints with white cement and matching pigments etc., complete. Made of NITCO Company :Model name -Bermuda or Made of Somany ompany :Model name Celestial /Elegance series or Made of Kajaria company :Model name Super Glossy Nanotech K-6016/6018/6019/6101/6012 & Jhonson Make : Quarzet DK & Quarzet HL Or Equivalent
Providing and laying double charged Vitrified tiles . (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting and plaster of walls including painting of walls over 12 mm thick bed of cement mortar 1:3 (1cement: 3 coarse sand), including routing the joint with white cement & matching pigments etc.Made of NITCO Company :Model name -Bermuda or Made of Somany ompany :Model name Celestial /Elegance series or Made of Kajaria company :Model name Super Glossy Nanotech K-6016/6018/6019/6101/6012 , Jhonson Make : Quarzet DK & Quarzet HL Or Equivalent.
Providing and laying rectified Glazed Non skid Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours White,Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including grouting the joints with white cement and matching pigments etc., complete. Make of NITCO Company : Model name Exotica/Maxima series or ,Made of Somany Company : Model name Trecker/Sprinkler series or , Made of Kajaria Company : Model Name GaniliaCrema /Beige/Almono Made of Johnson /Equivalent
Providing and fixing Ist quality Ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades as approved by Engineer-in-Charge, in skirting, and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. Makes : Johanson , sandex Series or equivalent
SUB HEAD - IV : WOOD WORK / UPVC WORK :
Providing and fixing partly panelled and party glazed door for director room shutter of with 35rnm thick teak wood for frame work, 12mm thick ply wood panelling for bottom an 5.5mm thick plain glass panelling for top , exposed Ply wood surfaces to have 3.5 mm thick veener of approved shade & design, veneered surfaces shall be finished with melamine polish ,SS hardware fittings like hinges, handles, lock, hydraulic door closer etc., complete all as shown in drawings and as directed
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. a) 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
Extra for Not Providing and fixing ISI marked, IS : 1341, M.S. heavy weight butt hinges with necessary screws etc. complete : (a) 125x90x4.00 mm.
Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : a) 150x10 mm.
Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : a) 125 mm.
Providing and fixing aluminium hanging floor door stopper, ISI marked,anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. a) Twin rubber stopper.
Providing and fixing of rubber nylon door buffer (dia of 40mm and 50mm long) on wall with rowl plug and screw.
Providing and fixing bright finished brass 100 mm mortice latch and lock, ISI marked, with six levers and a pair of anodised (anodic coating not less than grade AC 10 as per IS : 1868) aluminium lever handles of approved quality with necessary screws etc. comp
Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, with necessary accessories and screws etc. complete.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :
For fixed portion
Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15)
Providing & fixing of 74mm thick partion made out of aluminium frame work size 50x25x1.5mm 600x600mm vertically and horizontally cladded with 11mm thick MDF board on bothsides along with 1mm thick laminate of approved shade and design including 8mm toughend glass, preparation of drawings as directed by E-n-C
Providing and Fixing of acoustic paneling / acoustic treatment to walls upto sill level with 35 x 35mm aluminium frame work placed @ 600mm (maximum) centre to centre in both vertical and horizontal directions filled with 25mm thick fiber glass wool insulation of density 48 kg/m3, 12 mm thick commercial plywood paneling with 25 mm dia holes for sound absorption to the extent of surface area as directed, finished in approved pattern with 3.5mm thick veneer duly melamine polished / Textured painted / luster painted of approved brand and shade / fabric paneling with 12mm thick soft board with fabric of approved brand and shade / wall paper etc.. complete all as shown in drawings and as directed
Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with zinc coating of 120 gms/sqm(both side inclusive), consisting of floor and ceiling channel 50mm wide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with joints staggered to avoid through cracks, Galvanised M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each with zinc coating of 120 gms/sqm(both side inclusive)) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corners (25 mm x 25 mm x 0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture's specification and direction of engineer in charge all complete.
200 mm overall thickness partition using 8 mm thick double skin multipurpose cement bonded wood particle board manufactured as per IS: 14276 with suitable cement bonded board screws
SUB HEAD - V : FALSE CEILING WORK
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre,shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I.
wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint , all as per manufacturer's specification and also including the cost of making openings for light fittings, grills,diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : (a)12.5 mm thick tapered edge gypsum moisture resistant board. (Make : Gproc , L Strong , Armstrong)
SUB HEAD - VI : SANITARY INSTALLATIONS WORK :
Providing and fixing wall mounted water closets twilight SW sanitary/ bathroom fitings and fixtures as per direction of E-in-C
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: (a) White Vitreous China Table Top Basin (Make : Hindware,Jaquar or equivalent) (Hindware Cat. No. -10001)
SUB HEAD - VII : FURNITURE WORK, MISC WORKS:
Supply and placement of Executive table 2350x2350x750, Primary Work Surface: Made of 25mm Thick Pre-laminated twin board of E1-P2 grade and approved shade confirming to IS-12823:1990, Edge banded with matching 2 mm thick PVC lipping., Modesty Panel: Made of 25mm thick MDF one side pre-laminate board confirming to IS-14587:1998 with 0.4mm PVC membrane pressed on to top, Understructure: Made of 25mm Thick Pre-laminated twin board of E1-P2 grade and approved shade confirming to IS-12823:1990, Edge banded with matching 2 mm thick PVC lipping. Panel Drawer Slides. Drawer extension is 325 MM. Drawers have a soft closing & anti slam mechanism. Handles are provided for ease of opening. Pedestal is provided with lock for security. (All dimensions tolerance will be +/- 10mm). Make Godrej /Wipro/Featherlite
Supply of Officer Chair high back revolving type with Synchro Mechanism and fitting and gas lift system, with PU arms with nylon base twin castor wheels with seat & back cushion with fabric of approved shade. Make Godrej /Wipro/Featherlite
Supply of visitor chair with revolving type with fitting/gas lift system, with P.U. arms with nylon base with castor wheels with seat and back cushions with fabric of approved shade. Make Godrej /Wipro/Featherlite
Supply of 5 seater sofa in approved configuration of preferred size made out of teakwood frame work, seat and back with 2nd class hard wood , seat cushioned with 75mm thick high density foam and extra padding with 20mm thick foam for making shape on seat & back. Back with 50 mm thick high density foam duly upholstered with fabric of approved shade & quality all exposed wooden surface finished with Melamine polish etc. all complete. Make Godrej /Wipro/Featherlite
Supply of Center Table 900 x 525 x 400 mm with frames and legs made out of 60 x 35 mm teakwood sections with 10 mm thick glass on top, top frame and legs polished in melamine finish etc., all complete as per drawing. Make Godrej /Wipro/Featherlite
Supply and placement of filling cabinet good quality 2 Drawer LFC 3.0 Ft( with PF Top).The storages system is know down are made up of CRCA having shelves. The storage system comes with two filing drawers. The storage is equally divided shelf. The complete storage system has a centerlized locking mechanisim pre fitted to it. the storage shell have anti tilt mechanisim which prevents toppling of storage. the cabinate shall come with smooth full extension ball bearing runners with 40kg load bearing capacity. the cabinate shall come with individual index folder for each compartment. the top of storage is made up of 0.8mm thick CRCA duely powder coated to approved finish. the caracass and shelf are made up of 0.8mm CRCA duely powder coated. the shelf comes with stiffner with the thickness of 15mm duely tested for 40kg UDL. the drawers have double extension ball bearing slides. the powder coating is of 50-60 microns make Godrej /Wipro/Featherlite
Supply and fixing of LED tv of size 65 inches
Providing & fixing Roller Blinds on the windows at all heights, all materials and labour etc complete including material and colour shade in respects as per direction of engineer having following specifications i) compostion: fibre glass ii) thickness: 0.32mm iii) weight : 410grams per sqm iv) degree of opacity: 100 %
Providing and Fixing of fabric backed wall paper of approved brand, shade and pattern including cost of fixing of existing wall surfaces etc., complete all as directed.
Providing and Fixing wall graphics of approved design printed over vinyl sheet of 3M Scotch or approved equivalent make including cost of fixing to existing wall surfaces etc., complete all as directed
Providing and Fixing laminated film of 3M Scotch or approved equivalent make to existing glass surfaces etc., complete all as directed
SUBHEAD- VIII : INTERNAL ELECTRIFICATION:
Lights Points
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required
Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 5/6 A modular switch, connections etc. as required.
Light/Fan Fixtures
Supply of the following LED Light Fixtures with electronic driver , heat dissipating element including necessary accessories etc., complete on wall/ Ceiling / suspended from ceiling/ recess including all fixing accesssories such as leads,Teak wood round block, downrods, MS clamps, nuts, GI chain and bolts etc complete as required.
36W LED luminaire Recess Mounted 2ft x 2ft LED Luminaire with Diffuser similar to Philips Cat No: SM366C LED32 -6500 PU OD WH / Equivalent Make of Wipro.
22W LED luminaire purelins slim suspended Mounted 2meter LED Luminaire similar to Philips Cat No: SP780X LED22S-6500 PSU W5L113 OD WH/ Equivalent Make of Wipro.
6W LED luminaire Recess Mounted Spot LED Luminaire similar to Philips Cat No: DN590B M LED6S-6500 PSU WH WB / Equivalent Make of Wipro.
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting/ LED fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Supply of Exhaust fans with PVC blades following size sweep with gravity louvres shutters Exhaust fans of following
250mm Sweep 1250rpm
Installation of exhaust fan in the existing opening, including making good the damage,connection, testing, commissioning etc. as required.
Upto 450 mm sweep
Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 25 A modular socket outlet and 25 A modular switch, connections etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
SUBHEAD- IX : POWER WIRING
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)
4 way (4 + 12), Double door
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40 A, Four Pole, RCCB, 30mA.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
5A - 32A, Single pole, MCB, 10kA
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
SUBHEAD- X : UPS WIRING
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)
4 way (4 + 12), Double door
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40 A, Four Pole, RCCB, 30mA.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
5A - 32A, Single pole, MCB, 10kA
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
SUBHEAD-XI : SHOP ELECTRICALS
Supply of following size 1.1KVgrade XLPE insulated armoured aluminium conductor underground cable, The cable shall conform to IS 7098 Part-1.
4C X 10 Sq.mm Aluminium
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE/ copper conductor cable of 1.1 kV grade as required.
4 X 10 sq. mm (25mm)
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
SUBHEAD-XII : TELEPHONE/LAN CONDUTING
Supply and laying of 25mm dia. Medium class PVC conduit concealed in wall/ ceiling/floor including all accessories such as junction boxes, conduit bends, etc completed as required for Telephone & Lan etc.,
Supply and laying of 25mm dia. Medium class PVC conduit With GI WIRE concealed in wall/ ceiling/floor including all accessories such as junction boxes, conduit bends, etc completed as required for Telephone & Lan etc.,
Supply and fixing of Telephone outlet (RJ11) with anodised GI box with front plate and plug in type telephone socket .
Supply and fixing of LAN outlet (RJ48) with anodised GI box with front plate and plug in type LAN socket .
SUB HEAD-XIII : SPECIAL EARTHING
Earthing with copper earth plate 600 mm X 600 mm X 3 mmthick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Earthing with GI earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosurewith cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm GI strip on surface or in recess with DMC Insulated Supports for connections etc. as required. Metre
Supplying and laying 25 mm X 5 mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required.
SUB HEAD -XIV :- FIRE ALRAM
Supply installation, testing and commissioning of analog addressable type multi sensor (smoke/heat) photo electric detectors with base and LED indication lamp along with all fixing accessories.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Supply and laying of 25mm dia medium class FRLS PVC conduit concealed in wall /ceiling / above false ceiling including bends,elbows, junction boxes, saddles, spacers etc., and other material required for fixing complete as per requirement.
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
SUB HEAD -XV :- AIR CONDITIONING
VRF Outdoor Unit
Supply, testing & commisioning of total VRF system of Variable Refrigerent Flow outdoor units comprising multiple digital scroll compressors / Inverter Compressors ,low noise propellor type aero spiral fan,Condenser coil,refrigerant shut off valves,safety devices, lead free PC boards suitable for operation on R410A and on 415 V+/- 10%, 50 Hz, 3 phase A/C supply. power supply provide only one point for each set of out door units , Including Refrigerant Gas charging to the system and units, Out door unit M S Stand ,Lifting,Shifting, Positioning , systems nitrogen testing , vaccumizing & Commissioning of the Units at Ground level
Indoor Units
I)Supply, testing & commisioning of Casstee type indoor units comprisisng with pre-filter,fan section with low noise fan multispeed motor, coil section with DX coil, outer cabinet, decorative panel for cassette units,drain water lift-up meachanism, insulation, pipe connections including card less remote , fresh air intake etc. of various capacities as per specifications and drawings.Including Lifting,Shifting, Positioning & Commissioning of the Units
a) 3.0TR Casstee Unit
Supply and Installtaion of Refnet Joints desired sizes and type suitable to connecting indoor units and out door units has necessary compling with manufacture guide lines .
Supply, Installation, Testing and Commissioning of Hard copper REFRIGERANT PIPING of various sizes with necessary supports, fittings, interconnecting the liquid and suction lines between the AHU and the outdoor unit. The piping shall be carried out of Hard drawn copper pipes of type 'K with soldered / brazed socket fittings. Isolating valves shall be provided to isolate each compressor, strainers, sight glass and any other component requiring proper operation and maintenance. The suction line shall be insulated with 19mm thick closed cell insulation for above 25mm dia, 13mm thick for pipes below 25mm dia & exposed piping shall be covered with treated woven glass fibre reinforced covering and further finished with 24G Aluminium cladding as per the specifications and approved drawings. (out side piping)
a)28 mm dia
b)19.1 mm dia
c) 9.5mm dia
Supply, Installation, Testing and Commissioning of Hard copper REFRIGERANT PIPING of 16swg various sizes with necessary supports, fittings, interconnecting the liquid and suction lines between the aircooled outdoor units and the indoor units. The piping shall be carried out of Hard drawn copper pipes of type 'K with soldered / brazed socket fittings. Isolating valves shall be provided to isolate each compressor, strainers, sight glass and any other component requiring proper operation and maintenance. Both the suction and liquid lines shall be insulated with 19mm thick closed cell insulation for above 25mm dia , 13mm thick for pipes below 25mm dia . The insulation finished with treated woven glass fiber reinforced covering for inside Piping as per the specifications and approved drawings.
a)28.1 mm dia
b)19.1 mm dia
c) 15.9mm dia
d) 9.5mm dia
DRAIN:
Supply, Installation, Testing and Commissioning of CPVC (Chlorinated Poly Vinyl Chloride)4 kg/cm2 pipes condensate drain piping insulated using 9 mm thick nitrile rubber tubes including fitting and supports as per specified .
a) 25 mm dia.
b) 32 mm dia.
Fresh Air piping
Supply, Installation, Testing and Commissioning of CPVC (Chlorinated Poly Vinyl Chloride) 4kg/cm2 pipes for Cassette units Fresh air connections insulated using 9 mm thick nitrile rubber tubes including fitting and supports and out side wire mesh with insert screen as per the site condition
a) 50 mm dia.
b) 40 mm dia.
Supply, Installation, Testing and Commissioning of CONTROL CABLING of 3C x 2.5 sq.mm. copper cable for communication between indoor and outdoor units to be suitably laid in PVC conduit as per site requirement.
Supply of following size 1.1KVgrade XLPE insulated armoured copper conductor underground cable, The cable shall conform to IS 7098 Part-1.
4C X 10 Sq.mm Copper
Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE/ copper conductor cable of 1.1 kV grade as required.
4 X 10 sq. mm (25mm)
OLD VRF INDOOR CASSETTE UNITS SHIFTING
First floor left wing VRF system pump down the Gas and disconnect the Existing Cassette unit
Shifting the existing cassette units into new room & PA room (next to the Director room) , installation to be done inculding support rod , anchor fasterns and hardware etc complete
Supply, Installation, Testing and Commissioning of Hard copper REFRIGERANT PIPING of 16swg various sizes with necessary supports, fittings, interconnecting the liquid and suction lines between the aircooled outdoor units and the indoor units. The piping shall be carried out of Hard drawn copper pipes of type 'K with soldered / brazed socket fittings. Isolating valves shall be provided to isolate each compressor, strainers, sight glass and any other component requiring proper operation and maintenance. Both the suction and liquid lines shall be insulated with 19mm thick closed cell insulation for above 25mm dia , 13mm thick for pipes below 25mm dia . The insulation finished with treated woven glass fiber reinforced covering for inside Piping as per the specifications and approved drawings.
a)28.1 mm dia
b)19.1 mm dia
c) 15.9mm dia
d) 9.5mm dia
Existing VRF copper piping to be done Nitrogen pressure testing , Vaccumizing , filling the R410A Refrigerant Gas charging to the system and units & Commissioning of the total left wing circuit .
Supply of the Refrigerant Gas R410A
Supply, Installation, Testing and Commissioning of CONTROL CABLING of 3C x 2.5 sq.mm. copper cable for communication between indoor and outdoor units to be suitably laid in PVC conduit as per site requirement.
BHARGAVA ENTERPRISES
MEDHA ENTERPRISES
Shri Lakshmi Narashima Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .