Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.2 LAccepted-AOC | ₹23.2 L Quoted ₹24.0 L | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹26.6 L+₹2.6 L (10.9%)Rejected-AOC BUILDING NO FLAT NO 19 6TH CROSS ROAD SANJEEVINI NAGAR MUDALAPALYA BANGALORE 560072 | BANGALORE | BANGALORE | KARNATAKA | 560072 | ₹26.6 L+₹2.6 L (10.9%) | L2 | Rejected-AOC BEING NOT LOWEST |
| 3 | L3₹27.6 L+₹3.6 L (15.2%)Rejected-AOC NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | ₹27.6 L+₹3.6 L (15.2%) | L3 | Rejected-AOC BEING NOT LOWEST |
| 4 | L4₹28.6 L+₹4.7 L (19.6%)Rejected-AOC 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | ₹28.6 L+₹4.7 L (19.6%) | L4 | Rejected-AOC BEING NOT LOWEST |
| 5 | L5₹29.2 L+₹5.3 L (22.1%)Rejected-AOC RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | ₹29.2 L+₹5.3 L (22.1%) | L5 | Rejected-AOC BEING NOT LOWEST |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
10 Feb 2020, 6:00 pmClosed
MR ARIZ AHMED
GE U ELECTRIC SUPPLY DELHI CANTT-10
REPAIR AND MAINTENANCE OF LT SWITCH GEAR LT PANEL FEEDER PILLAR BOX POLE PAINTING SMC BOX EARTHING REPAIR TO HIGH MAST LIGHT AND LT CABLE NETWORK AND ALLIED WORK AT SP MARG TPT COMPANY IN THE AREA OF AGE U ELECT SUPPLY NO III UNDER GE U ELECT SUPPL
2019_MES_298656_3
GE ELECT/D-79/2019-2020
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE U ELECTRIC DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹70,000
Yes
14 Mar 2020
30 Jan 2020
12 Feb 2020
31 Jan 2020
10 Feb 2020
5 Feb 2020
Amount
Supply and making in repair new LT 1100 V end termination with suitable size of aluminium lugs duly crimped for LT 3 ½ core armoured aluminium conductor cable after isolating supply to transformer/LT panel and disconnecting brunt/fault cable from the bunch of cables in trenches, galleries, removing cable loop, opening the cable gland and connecting back after end terminals, testing and commissioning for (XLPE) all as specified and directed.
(a) Cable Size 185 Sqmm to 240 Sqmm
(b) Cable Size 300 Sqmm to 500 Sqmm
(c) Cable Size 95 Sqmm to 150 Sqmm
(d) Cable Size 25 Sqmm to 70 Sqmm
M&L in replacement Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.25 m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised iron side complete all as specified, including testing and commissioning complete all as directed. Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in soft/loose soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 type C2 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement 6mm dia both ways as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe medium grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI lead wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
Supply and laying in replacement GI earth strip of size 32 x 6 mm in trenches/fixed to walls/ transformer/LT panel /2 pole/4 pole with saddles and fixing screws etc., from earth pit to test point all as specified and directed.
Supply & fixing in replacement danger notice plate of 1.6 cm thick mild steel vitreous enamelled white, with letters, figures and conventional and boxes in signal red colour and fixed with MS clamps, bolts & nuts of approved size for HT 25 x 20 cm size all as specified and directed.
Repairs to LT / HT pillar box / cope point box by opening door hinges and taking rusted portion of door incl removing bends / dents and refixing the door with new hinges, handles, making good surfaces bolting etc all as specified and directed.
Excavation in trenches in soft and loose soil n.exc 1.5 mtr wide and n.exc. 1.5 mtr depth for laying and taking out of electric power cable and getting out all as specified and directed by engineer –in-charge.
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material not exceeding 50 mtr away and depositing where directed at a level n. exc 1.5 mtr above the starting point .
Material & labour for river washed and screened dry sand for filling under and above the under ground cable for cushioning of cables etc.complete all as specified and directed by engr –in-charge, Note : Measurement shall be taken after punning down.
S&Laying in replacement sub class B bricks having minimum compressive strenth 75 Kg/sqm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
All as per Srl item No 10 here in before but using old bricks obtain under item No 06 .
Supply and lay in replacement unreinforced precast concrete cable covers class HV Type -1 with peak size 300 x 180 x 40 mm. compete all as specified and directed
All as per srl item No 12 here-in-before but using old tiles obtained under srl item No 06.
Supply, Laying, connecting, testing and commissioning in replacement ( including taking out existing cable) LT cable of PVC sheathed XLPE cable armoured aluminium conductor 1100 V graded , 4 core,10 sqmm, after taking out/down old existing unserviceable from trenches / ducts/ road crossing and poles complete all as specified and directed.
All as per srl item No 14 here-in-before but size of 3.5 core, 25 sqmm.
All as per srl item No 14 here-in-before but size of 3.5 core, 35 sqmm.
All as per srl item No 14 here-in-before but size of 3.5 core, 50 sqmm.
All as per srl item No 14 here-in-before but size of 3.5 core, 70 sqmm.
All as per srl item No 14 here-in-before but size of 3.5 core, 95 sqmm.
All as per srl item No 14 here-in-before but size of 3.5 core, 120 sqmm.
All as per srl item No 14 here-in-before but size of 3.5 core, 185 sqmm.
All as per srl item No 14 here-in-before but size of 3.5 core, 240 to 300 sqmm.
Supply, in replacement jointing and testing, straight through joint, heat shrinkable type, suitable for HT, 11 KV (E) XLPE cables, aluminium stranded conductors cable 3 core, 240 to 300 Sqmm.
All as per srl item No 23 here -in-before but size of 3 core,120 to185 sqmm.
Material and labour in replacement for GI pipe light grade laid in trenches for cable protection of size 50mm dia. complete all as specified and directed
Material and labour in replacement for GI pipe light grade laid in trenches for cable protection of size 80 mm dia. complete all as specified and directed
Supply only following expendable items for replacement :
(a) CTC liquid 300 ml bottle.
(b) cotton waste
(c ) Fuse wire 100 Amp
(d) Fuse wire 60 Amps
(e) Fuse wire 40/30 Amps
(f) PVC insulation tape of thickness 0.125 mm 25 mm width 25 Mtr length.
(g) HT insulation tape of thickness 25 mm width 25 Mtr length. Make : BIRLA 3M
Material and labour for servicing /testing and calibration of line breaker/control panel including outdoor CT, PT and relays in control panel of indoor VCB of capacity 630/400A Amps and rating 11 KV complete as details mentioned as under:-
(a) Details of servicing of breaker :- (i) Checking of Closing/Tripping coil assembly (ii) Adjustment of mechanism if required. (iii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth. (iv) Checking the contact for wear. Replace if the contact piece has worn out. (v) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts. (vi) Check for rust and wear. (vii) Checking of spring charge mechanism (viii) Visual check for rust and deformation. (ix) Check for loosened bolts and nuts, broken spring washers and snap pins etc. (x) Check for loosened connections, rust, damaged lead wires. (xi) Checking of control circuit & tighten the connections if any. (xii) Check close & trip coil. (xiii) Replacement of Dashpot/shock absorbers . (xiv) Replacement of carbon brush of spring charging motor (xv)Cleaning of porcelain bushing (xvi)Checking of limit switch
Supply only closing coil assembly in replacement 24/50/110v DC for VCB all as specified & directed.
Supply only fix tripping coil in replacement 24/50/110V DC for VCB all as specified & directed.
Supply only 11 Kv PT HV Back up fuse in replacement cat no 12Kv ABCNA 3.15A 38/10 as per OEM Recomendation
Supply only space heaters in replacement of 1 KW, 220Volts along with adjustable thermostat and replacement of burnt wiring of the haeaters complete
Material and labour for painting of LT panels by duly cleaning the surface from dust and grease and applying one coat of synthetic enamel paint by using spray gun colour as directed by the Eng - in - Charge and lettering the LT pannels with black/white paint using stencils or making lettering by using stickering with minium size of letter to be of 5 Cm all as specified and directed
M&L for cement painting of with prepared white ( snow sem ) for transformer /LT /HT poles plinth area/ Copings of any size all as specified for the following :- ( including scrapping & cleaning with wire brush )
Preparation of surfaces of steel Pole by scraping with emry paper and making free from rust, dust and any foreign material and apply one coat of aluminum paint including letter writing not exceeding 50 cm width, on poles such as Pole No and source point of electric supply with black paint and flurcent paint in circumference of poles / mast towers of various heights complete all as specified and directed.
Preparation of surfaces RCC Pole o f 9 mtr by scraping with emry paper and making free from rust, dust and any foreign material and apply two coats of cement based weather proof distemper including letter writing not exceeding 50 cm width, on poles such as Pole No and source point of electric supply with black paint and fluorescent paint in circumference of poles / mast towers of various heights complete all as specified and directed.
Opening of the side cover of high mast light disconnection of the gear assembly of the mast cleaning the gear system by using old lub oil of the sump gears, checking its moving components, filling of gear oil SAE 140 grade 0.5 ltrs with new oil.
Decarbonising/cleaning complete LT Panel board/ pillar boxes of 415/380/230 Volts 3 phase bus bar chamber with electrical connections, complete bus bar from the bus bar chamber, cleaning with CTC(Carbon Tetra Chloride) and ensure proper decarbonising, refixing the same after applying Backtol Red solution to the bus bar insulator & checking all the connections, tightening the nuts, bolts & thimbles of in-coming/out-going system complete incl replacement of defective rusted bolts & nuts all as specified and directed.
Taking down the old deterioted/damaged rubber mats from the sub stations, supply & lay synthetic insulating rubber matsof size: 2m x 1mx 19 mm all as specified & directed
Taking down the LT air circuit breakers of various capacities from 800 amps to 1250 amps for repairs, servicing comprising the following and refixing the same, re-orientation and labour for taking down the defective parts and refixing the same spare parts all as specified and directed (a) Checking/repair of mechanical system of ACB. (b) Checking/repair of the manual closing/tripping of breaker.
Taking down the burnt MCCB s from the LT panels/feeder pillar boxes, supply & fix ,test & commissioning of MCCB all as specified & directed.
MCCB 100Amps/10KA, 3 Pole, thermo magnetic releases rupturing capacity Ics=100% Icu
MCCB 63Amps/10KA, 3 Pole , thermo magnetic releases rupturing capacity Ics=100% Icu
MCCB 63Amps/30KA, 3 Pole, thermo magnetic releases rupturing capacity Ics=100% Icu
MCCB 100Amps/30KA, 3 Pole , thermo magnetic releases rupturing capacity Ics=100% Icu
MCCB 100Amps/36KA, 3 Pole, thermo magnetic releases rupturing capacity Ics=100% Icu
MCCB 250Amps/36KA, 3 Pole, micorprocessor based rupturing capacity Ics=100% Icu
MCCB 320Amps/36KA, 3 Pole , micorprocessor based rupturing capacity Ics=100% Icu
MCCB 400Amps/36KA, 3 Pole , micorprocessor based rupturing capacity Ics=100% Icu
Taking out old street light fittings and supply and fixing of new generation energy saving and environment friendly long life verasalite pressure die- cast aluminium IP 65 road way luminare with high power LEDs of 40 Watts capacity as light source and exclusively designed for poly carbonate cover with electronic drive & surge protector along with GI Pipe 32 mm size, light grade 1.5mtr length with necessary wiring and clamps, nut & bolts assembly for fixing on pole all as specified and directed
Taking out old street light fittings and supply and fixing of new generation energy saving and environment friendly long life verasalite pressure die- cast aluminium IP 65 road way luminare with high power LEDs of 25 Watts capacity as light source and exclusively designed for poly carbonate cover with electronic drive & surge protector along with GI Pipe 32 mm size, light grade 1.5mtr length with necessary wiring and clamps, nut & bolts assembly for fixing on pole all as specified and directed
Supply and Fixing against repairs surface mounted LED, down lighter in powder coated white fair finish, integral electronic driver & surge protector of 18 watts LED 6 K capacity for working at 250 v 50 Hz AC supply all as specified and directed.
Supply and fix in replacement multi functional energy meter in replacement suitable for 440 Volts, 50 Hz AC supply digital type with bright LED indication and displaying the basic parameter of voltage, current, power factor, KW, KVAR, KVA with 0.5 accuracy along with necessary control wiring all as specified and directed.
Taking down unserviceable indication lamp and supply, fix and testing indication lamp (LED type) with showing red, yellow and green in colour of 22.5mm dia monitor on LT panel board suitable for 240V AC supply all as specified and directed.
M&L for replacement of conical/single bus bar system epoxy insulators suitable for LT 415 volts panels board/pillar box/cope point fix to bus chamber for bus bar support including nuts, bolts, washers all as specified and directed.
Taking down old unserviceblae LT current transformer, supply, fix, test and commissioning of resin cast copper wound type LT current transformer for rating 100/5A to 500/5A on LT panel board and connections secondary terminals to ammeter.
Supply & fix FRP pole box in replacement 140 x 140 x 95mm consisting of 1 No 50 A 4 pole connector and 1 No 32 A TPN taking down the old/corroded junction boxes and fixin with proper clamps and glands all as specified and directed
Supply and fix Astronomical Programmable in replacement every 1 min, back up of 6 years, 28 memory locations, with built in battery Digital time switch Current carrying capacity of 16A with 1WO + 1CO all as specified and directed by taking down the old damaged timer.
Supply and fix contactor in replacement, 4 pole, 415V, 40A cap , MCX , 2 NO+2 NC utilsed for heavy duty by taking down the old perished / deteriorated contactor aganist repairs all as specified and directed
Taking down the old corroded Unserviceable LT Panel with a switch gears and Supply and Fixing of indoor LT Pillar Box Cubicle type , 440 volts 3 phase, vermin proof along with the following acessories and switch gears complete all as specified and directed.
Fabrication Details : Main frame 3.15 mm thick CRCA sheet and MS angle 25 x 25 x 3 mm, frame with front and back openable, double door sytem lockable / openable by keys with lovers and air vent gasket foe natiral flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry for entry for armoured cables of adequate sizes with glands and the inner shall partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled) 50mm space all around with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symvol of bone and kull and ingress of protection of outer shall be IP-54, base frame on ICMS channel of 50 x 50 x 6 mm with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP 54 and locking arrangements Bus bar details : Material shall be aluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar 2000A for phase and 1000 A for neutral . Flat, neutral 40x10mm Al flat and bus bar support of F class insulators epoxy type, earthing of 40x6 mm GI Flat.
Painting Detais : Pillar box shall be of powder coated with pure polyster simens grey structural RAL 7032 sahde.
Wiring : Pannel wiring shall be of 1.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps
Switch Gear Details (a)Incommer/ Out going :- MDO type 1250A 4 pole ACB . with microprocessor based protection
Note : Rate quoted includes for necessary Earth work PCC foundation of LT pannel and includes the cost of all Accessories and switch gears
Taking down the old corroded Unserviceable LT Junction Box and Supply and Fixing of Out door /wall mounted with cable entry from bottom , 440 volts 3 phase, vermin proof along with the following acessories and switch gears complete all as specified and directed.
Fabrication Details : Main frame 3.15 mm thick CRCA sheet and MS angle 25 x 25 x 3 mm, frame with front and back openable, double door sytem lockable / openable by keys with lovers and air vent gasket free natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry for entry for armoured cables of adequate sizes with glands and the inner shall partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled) 50mm apace all around with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symvol of bone and kull and ingress of protection of outer shall be IP-55, base frame on ICMS channel of 50 x 50 x 6 mm with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP 54 and locking arrangements Bus bar details : Material shall be alluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar 250A for phase and 125 A for neutral . Flat, neutral 40x10mm Al flat and bus bar support of F class insulators epoxy type, earthing of 40x6 mm GI Flat.
Painting Detais : Pillar box shall be of powder coated with pure polyster simens grey structural RAL 7032 sahde.
Wiring : Pannel wiring shall be of 1.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps
Accessories for Pillar Box : Multifunction meter with communication point RS 485/232, 5 display, class 0.5/1 and Indication Lamps (LED) - 03 No.
Switch Gear Details (a)Incommer:- 100-125 A MCCB DU 125 D Type 30 KA 4 pole with Spreader terminals (b)Outgoing:-(i)63A,3 pole,18 KA,MCCB along with sprader terminals along with sprader terminals-2 nos (ii)40A A,3 pole,18 KA,MCCB along with sprader terminals along with sprader terminals-1 no,s
Note : Rate quoted includes for necessary Earth work PCC foundation of LT pannel and includes the cost of all Accessories and switch gears
Taking down the old corroded Unserviceable LT Junction Box and Supply and Fixing of Out door /wall mounted with cable entry from bottom , 440 vplts 3 phase, vermin proof along with the following acessories and switch gears complete all as specified and directed.
Fabrication Details : Main frame 3.15 mm thick CRCA sheet and MS angle 25 x 25 x 3 mm, frame with front and back openable, double door sytem lockable / openable by keys with lovers and air vent gasket foe natiral flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry for entry for armoured cables of adequate sizes with glands and the inner shall partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled) 50mm space all around with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symvol of bone and kull and ingress of protection of outer shall be IP-54, base frame on ICMS channel of 50 x 50 x 6 mm with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP 55 and locking arrangements Bus bar details : Material shall be alluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar 400A for phase and 125 A for neutral . Flat, neutral 40x10mm Al flat and bus bar support of F class insulators epoxy type, earthing of 40x6 mm GI Flat.
Painting Detais : Pillar box shall be of powder coated with pure polyster simens grey structural RAL 7032 sahde.
Wiring : Panel wiring shall be of 1.5 sq mm copper standard with 5A MCB wiring for control wiring and indication lamps
Switch Gear Details (a)Incommer:- 400 A MCCB 50 KA 4 pole with Spreader terminals (b)Outgoing:-(i)250 A,3 pole,36 KA,MCCB along with sprader terminals along with sprader terminals-2 no,s (ii)160A A,3 pole,36 KA,MCCB along with sprader terminals along with sprader terminals-2 no,s (iii)125A,3 pole,18 KA,MCCB along with sprader terminals along with sprader terminals-3 no,s
Note : Rate quoted includes for necessary Earth work PCC foundation of LT pannel and includes the cost of all Accessories and switch gears
Taking down the old corroded Unserviceable LT Junction Box and Supply and Fixing of Out door /wall mounted with cable entry from bottom , 440 volts 3 phase, vermin proof along with the following acessories and switch gears complete all as specified and directed.
Fabrication Details : Main frame 3.15 mm thick CRCA sheet and MS angle 25 x 25 x 3 mm, frame with front and back openable, double door sytem lockable / openable by keys with lovers and air vent gasket free natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry for entry for armoured cables of adequate sizes with glands and the inner shall partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled) 50mm apace all around with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symvol of bone and kull and ingress of protection of outer shall be IP-54, base frame on ICMS channel of 50 x 50 x 6 mm with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP 54 and locking arrangements Bus bar details : Material shall be alluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar 250A for phase and 125 A for neutral . Flat, neutral 40x10mm Al flat and bus bar support of F class insulators epoxy type, earthing of 40x6 mm GI Flat.
Painting Detais : Pillar box shall be of powder coated with pure polyster simens grey structural RAL 7032 sahde.
Wiring : Panel wiring shall be of 1.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps
Accessories for Pillar Box : Multifunction meter with communication point RS 485/232, 5 display, class 0.5/1 and Indication Lamps (LED) - 03 No.
Switch Gear Details (a)Incommer:- 250 A MCCB DU 250 D Type 35 KA 4 pole with Spreader terminals Make:L&T/or equivalent in Schnider (b)Outgoing:-(i) 125A,3 pole,25 KA,MCCB along with sprader terminals along with sprader terminals-2 no,s Make: L&T/or equivalent in Schnider (ii) 63A,3 pole,25 KA,MCCB along with spreader terminals along with sprader terminals-4 no,s
Note : Rate quoted includes for necessary Earth work PCC foundation of LT pannel and includes the cost of all Accessories and switch gears
Material and labour for removal of the existing indoor LT pannel with out damaging the panel and installation by disconnection of all the incoming and out going cables with proper shut down having with 1 incommer and 8 no out going MCCBs making base foundation frame by fabrication by using steel not less than 100 Kg with ICMS 50 and 60*60*6 mm angulars to install the exiting LT panel in the same position elevated from the floor to height of 50 CM from the floor level with proper grouting / anchor fasteners / and necessary civil works
Taking down the burnt change over switch from the change over panel and supply and fixing of new change over switch 4 pole (FP) with enclosure of 250 Amps capacity all as specified and directed.
Taking down the burnt change over switch from the change over panel and supply and fixing of new change over switch 4 pole (FP) with enclosure of 400 Amps capacity all as specified and directed.
Supply, installation & commissioning and testing in replacement of SHF/VRLA Battery, Battery charge panel comprising 12 Nos. 2 Volts 100 AH tubular cell, self contained floor mounted sheet steel cabinet with two tiers for housing the batteries. The charging equipment will be operated from 240Volt +/- 10%, 50 c/s supply. The cabinet should be complete and internally wired auto/mannual switch. The charger unit should house, resstance control DC ammeter , Voltmeter and fuses, AC supply failure alarm. Complete accessories required for commissioning is included in the scope of work. DC distribution board comprising of 32 Amps DPMCB as incomer and 2 nos of 10 A DP MCB as O/G Battery Charger with batteries Automatic Float cum boost charger of 16 A to give 24 V DC output at 110 Ah capacity
S&F in replacement Identification plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters not exceeding 50 mm width , figures showing the details of 11KV feeder and fixed with M S clamps, bolts and nuts of approved size, as directed by the engineer in charge.
S & F in replacement of hooter complete complete with switch etc suitable for warming HT 11 KV VCBs internal chambers
M & L for 2 coat of synthetic enamel painting over a coat of red oxide to steel surfaces of chain link / mesh fencing including preparation of old surface complete all as specified.
M&L for re-painting of HT 11 KV VCB panel consisting not less than 6 Nos VCB/Bus Coupler of approx size 4 to 6 Sqm VCB panel with 2 coats of super enamal paint over a coat of red-oxide with sparygun including writing of Inoming/outgoing/Bus coupler Name/numbers not exceeding 75mm width letters size as directed and as specified at SP Marg Sub Station.
Material and labour for removal of unserviceable service wire of 2 core 4 sqmm and laying of new aluminium service wire of 2 core 4 sq mm from street light fitting to junction box not less than 7 mtr per pole
Material and Labour only for repairing and rectification of faults in 16 / 32 mtr High mast lights by checking the control panel Trailing Cables, timers. contactors and replacing the defective electrical parts, Servicing and greasing to the winch gear wheel mechanisum for electrical and manual operation of the carrier along with replacement of dog clamps of the wire rope and replacment of the existing old unserviceable light fittings with controll gears with new LED light fitiings complete and fixing of the control panel for desired operation all as specified anddirected by the Eng-in-Charge Note :(I) Necessary Digital timers /Power contactors and LED light Fittings shall be measured under Relevant Items. (II) Necessary arrangements for Safety and T&P repairs shall be under taken by contractor
Supply Only in replacement Energy Efficient LED High MAST Light Fitting of 200 W capacity consisting of high power LEDs with choice of general spread optics to ensure uniform distrubution, IP 66, comprising of clear heat ressistant toughened glass, die caste aluminium construction and maintanance free operatable at 120-270VAC Pf > 0.95 Integral driver Surge protector along with necessary 3 Core 2.5 sqmm copper cable connections up to junction box along with mounting GI bracket all as specified and directed
Note: Contractor has to give Guarantee for 60 months for the HIGH MAST light fitting including the electronic Driver power drive from the date of installation. And contractor has to take necessary arrangements for fixing of the luminaries duly following the safety for men and material
M&L PCC cable Route indicator of size 350x200x200mm with slanting top duly embossed 'HT CABLE' or 'HT LOOP' and placed on PCC foundation 1:4:8 thick and 100mm width all round the cable route indicator complete all as directed. (NOTE - Unit rate quoted is deemed to be inclusive of excavation and earth work, pcc etc. all as required)
S&F in replacement 4 mm dia MS wire 75x75mm mesh, made upto into mattress or cages appx 2.00 mtr height and fixed with flat iron/angle by welding in position and distance not less than 1.5 mtr between supports complete all as specified and as directed including dismantling of old unserviceable fencing.
Material and labour for cement concrete type D-2, 1:4:8 (using 40 mm graded crushed stone aggregate) for sub floors, sub-bases, floors and paving etc complete all as specified and directed including demolition of old unserviceable PCC.
Supply & Fixing in replacement steel tubular pole 410 SP-55 (09 metres long) complete with cast iron base plate finial taper plug nuts, bolts and washers all as specified in IS including the following:- (a) Excavation in post holes in any types of soil, return filling, well ramming and disposal of surplus soil to a distance not exceeding 50 mtr from the starting points. (b) PCC (1:4:8) type D2 using 40 mm graded stone aggregate as in foundationup to ground level all as specified and directed. (c) PCC (1:3:6) type C-2 using 40 mm graded stone aggregate as in foundation necessary form work for plinth block/ collar all as specified and directed. (d) PCC (1:3:6) type C-2 using 20 mm graded stone aggregate as in coping including necessary form work for plinth block/ collar all as specified and directed. (e) Painting of poles with one coat of red oxide primer and two coat of aluminum paint before fixing and one coat of aluminum paint after fixing complete embedded portion shall be painted with two coat of black bituminus paint above plinth block.
Supply & fixing in replacement of SMC Junction box for street light having side hinged, outside dimention 333x233x120mm and inside dimention 300x200x105mm including 4 Nos aluminium bus bar of 63 Amps rating and connecting of existing LT power cable complete all as directed.
Taking out old LED street light fitting and supply and fixing of new generation energy saving and environment friendly long life verasalite pressure die- cast aluminium IP 65 road way luminare with high power LEDs of 60 Watts capacity as light source and exclusively designed for poly carbonate cover with electronic drive ,surge protector along with GI Pipe 32 mm size, light grade 1.5mtr length with necessary wiring and clamps, nut & bolts assembly for fixing on pole all as specified and directed
Taking out OLD LED gate light fitting and supply and fixing of new generation energy saving and environment friendly long life verasalite pressure die- cast aluminium IP 65 road way luminare with high power LEDs of 30 Watts capacity as light source and exclusively designed for poly carbonate cover with electronic drive ,surge protector along with GI Pipe for base fixing with PCC Work 1:2:4 type B0 with necessary wiring and clamps, nut & bolts assembly for fixing on pole all as specified and directed
Sipply only in replacement LED Aviation Light Fitting with wattage not less than 10 Watts IP 66, comprising of clear heat ressistant toughened glass, die caste aluminium construction and maintanance free operatable at 120-270VAC Pf > 0.95 Integral driver Surge protector along with necessary 3 Core 2.5 sqmm copper cable connections up to junction box along with mounting GI bracket all as specified and directed
Rahul Enterprises
Vijay Electricals
M P TYAGI ENGINEERS AND CONTRACTORS
MV Engineers And Contractors
Microsys Controls India
Ridhi engineers and builders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .