Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹323.4 CrAccepted-AOC | ₹323.4 Cr Quoted ₹328.8 Cr | L-1 | Accepted-AOC L-1 Bidder |
| 2 | L-2₹340.5 CrRejected-AOC A 18 SECTOR 136 NOIDA UTTAR PRADESH 201304 | NOIDA | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201304 | ₹340.5 Cr | L-2 | Rejected-AOC L-2 Bidder |
Tender Value
₹255.4 Cr
EMD Value
₹5.4 Cr
Closing Date
3 Jun 2024, 4:00 pmClosed
SE(Contracts-II), RVPN,Jaipur
Superintending Engineer (Contracts-II) New MM Building, Old Power House Premises, Bani Park, Jaipur-302006 (Rajasthan)
Construction of 220kV GSS Bikampur and 220KV GSS Sawa along with associated transmission lines on Turnkey Basis under BN-9019002306
2023_RRVPN_375073_1
RVPN/EHV/SPV/BN-9019002306
Open Tender
Electrical Works
720 days
Jaipur
Please refer Tender documents.
26 documents required · 26 mandatory
₹29,500
As per bid specification
₹5.4 Cr
Jaipur
7 Oct 2024
9 Oct 2023
3 Jun 2024
9 Oct 2023
3 Jun 2024
22 Nov 2023
19 Oct 2023
Amount
MAIN MATERIAL/ ITEMS
Auto Transformer:
220/132 kV, 160 MVA Auto Transformer with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 160 MVA 220/132 kV Auto Transformer as per S-I , (1) above
Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers at S-I (1) above
Bus Reactor:
220 kV, 25 MVAR Bus Reactor with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 220 kV, 25 MVAR Bus Reactor above
Power Transformer:
132/33 kV, 31.5 MVA Power Transformer with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 31.5 MVA 132/33 kV Power Transformer S-II (4) above
Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers S-II, (4) above
Circuit Breakers
220 kV Circuit Breakers
220kV circuit breakers (3 Ph.) Along with support Structure
132 kV Circuit Breakers
132 kV circuit breakers (3 Ph.) Along with support Structure
33 kV Circuit Breakers
33 kV circuit breakers (3 Ph.) Along with support Structure
Instrument Transformers
Capacitor Voltage Transformer
Single-Phase, 220 kV, 4400 pf CVT
Single Phase 132 kV , 4400 pf CVT
33 kV Potential Transformer
Current Transformer (1-Phase)
C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
New Substation
Control Panel for 220 kV Transformer (220 kV Side) Type: SAS-THCB
Relay Panel for 220 kV Transformer (for both HV & MV) Type: SAS-THRB
Control Panel for 220 kV Bus Reactor (220 kV Side) Type: SAS-RCB
Relay Panel for 220 kV Bus Reactor (for both HV & MV) Type: SAS-RRB
Control Panel for 220 kV Feeder Type: SAS-FCB
Relay Panel for 220 kV Feeder Type: SAS-FRB
Control Panel for 220 kV Bus Coupler Type: SAS-BCCB
Relay Panel for 220 kV Bus Coupler Type: SAS-BCRB
220 kV Busbar Protection Relay Panel Type: SAS-BBRB
Control Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLCB
Relay Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLRB
Control and Relay Panel for 1x 50/31.5/25 MVA, 132/33 kV Power Transformer Type SAS-TCRA
Control Panel for 132 kV Feeder Type SAS-FCA
Relay Panel for 132 kV Feeder Type SAS-FRA
Control and Relay Panel for 132 kV Bus-Coupler Type SAS-BCRA
Control and Protection Panel for 33 kV Feeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD
Station HMI [Industrial grade Computer with 21"TFT monitor as per specification requirements]
Station HMI (Hot Standby)[Industrial grade Computer with 21"TFT monitor as per specification requirements]
HMI View Node[Industrial grad Computer with 21"TFT monitor as per specification requirements]
A3 Size B&W Laser Printer
Substation Automation System Network Panel Type SAS-NW
Modems (both sending and Receiving End) for communication to RCC & Sub SLDC for PLCC]
Data Concentrator Unit (DCU) at Substation for RAS mounted in suitable enclosure & fully wired
Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.
Substation Auxiliary Monitoring Panel Type SAS-SAMP
Other Items:
Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
Surge Arresters
Substation LT Transformer
33/ 0.433 kV, 250 kVA LT transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil
Batteries & Battery Charger
Batteries (Sizing shall be as per requirement of technical specification)
220 V [Min. 600 AH]
48 V [Min. 600 AH]
Battery Charger System
220 V Float and Boost
50 V Float and Boost
Lighting System
Outdoor Lighting & other Works
Lighting Fixture Type FL-1
Lighting Fixture Type FL-2
Outdoor Receptacle
Type-RP
Type-RO
Substation Premises Lighting
Lighting poles
Type-L1
Type-D1
Street Lighting Type-SL-L1 for mounting on poles
Street Lighting Type-SL-D1 for mounting on Poles
Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast and Other Loaction as designated complete with all controgears and accessories, items etc.
Lighting Panel Type ACP-2 as per technical specification
Lighting Panel Type ACP-3 as per technical specification
Indoor Lighting & Other Works
Electrification
Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, Hall and administrative office building as per the requirements of the specifications
Illumiation
Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements)
Indoor Lignting Panels
Lighting Panel (Indoor) Type ACP-1 as per technical specification
Lighting Panel (Indoor) Type DCP as per technical specification
Wall mounted fans Approx. 400 mm sweep
Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator
Exhaust Fans
Fire Fighting System
Nitrogen Injection Fire Protection System for Auto Transformer (160 MVA ) complete in all respects.
Nitrogen Injection Fire Protection System for Power Transformer (31.5 MVA ) complete in all respects.
DCP Type
Carbon di oxide type – 6 Liters.
Foam Type- 9 Liters
Sand type
i) GI Buckets 9 liters capacity
ii) Steel Stands for four buckets
Air Conditioning System
Air Conditioning for the Rooms specified in the specifications
1.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
Power Cables(XLPE)
1Cx630 sq.mm
3.5Cx300 sq.mm
Power Cable(PVC)
1Cx150 sq.mm
3.5Cx70 sq.mm
3.5Cx35 sq.mm
4Cx16 sq.mm
4C x 6 Sq. mm
2C x 6 Sq. mm
Control Cable (PVC)
4 CX4 Sq. mm
3Cx2.5 sq.mm
5Cx2.5 sq.mm
7Cx2.5 sq.mm
10Cx2.5 sq.mm
14Cx2.5 sq.mm
19Cx2.5 sq.mm
Substation Structures
Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
Non-Standard type Pipe Support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe Support structure as per specification requirements]
Isolators
220 kV (3-Phase) (Horizontal DOUBLE BREAK)
1600A, 50KA, isolator with one E/S
Post insulators for above Isolator
1600A, 50KA, isolator with two E/S
Post insulators for above Isolator
1600A, 50KA, isolator without E/S
Post insulators for above Isolator
1600A, 50KA, isolator without E/S (TANDEM Type)
Post insulators for above Isolator
132 kV (3-Phase) (Horizontal DOUBLE BREAK)
1250A, isolator with one E/S
Post insulators for above Isolator
1250A isolator without E/S
Post insulators for above Isolator
33 kV (3-Phase) (Horizontal DOUBLE BREAK)
1250A, isolator without E/S
Post insulators for above Isolator
800 A isolator without E/S
Post insulators for above Isolator
800A isolator withE/S
Post insulators for above Isolator
Switchyard Erection
Busbar & Interconnections
New Substation/ Switchyard
220 kV Switchyard Works:
Main-I Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/Porcelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
Main-II Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Pocelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
Aux Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string(DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
220 kV Overhead Jack Bus (for DMT Layout) on Twin ACSR Zebra(Bus-Coupler Bay)/ Single ACSR Zebra (Transformer/ Line on ACSR Zebra) with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Twin ACSR Zebra
Single ACSR Zebra
Equipment Interconnections to Main Bus, Overhead Bus including Single ACSR Zebra (for Line), Twin ACSR Zebra (forTransformer bay & B/C Bay), bus-bar materials, clamps, connectors, spacers, corona shields, including equipment connectors, Junction box including of all accessories etc. for the following:
220 kV DMT-type layout
Line bay
Transformer bay
Reactor bay
Bus-Coupler
Bus CVT Interconnections to Main Buses including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
132 kV Switchyard Works:
Main Bus: 132 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulator, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
Aux Bus: 132 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay), Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Twin ACSR Zebra
Single ACSR Zebra
Single Panther
Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV Transformer Bay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
132 kV Main & Aux-type layout
Line bay
Transformer bay
Bus-Coupler
Bus CVT Interconnections to Main Bus including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
33 kV Switchyard Works:
Main Bus: 33 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]
Aux Bus: 33 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]]
33 kV Overhead Jack Bus for Transformer Incomer (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
33 kV Main & Aux-type layout
Line bay
Transformer bay
Bus-Coupler
LT Transformer connection with ACSR Panther conductor, 33 kV DO Fuse Set alongwith required Clamp/connectors
Bus PT Interconnections to Main Bus including Single ACSR Panther , clamps, connectors, junction box including of all accessories etc.
Bus Post Insulators (BPI)
Earthing & Lightning Protection System
Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
40 mm Dia MS Rod
40mm Dia, 3.2 M Long MS Rod Earth Electrodes Directly Driven.
40mm Dia, 8 M Long MS Rod Earth Electrodes Directly Driven.
40mm Dia, 3.2M Long MS Rod Earth Electrode in untreated pit with test link
40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works
75X12 mm GS Flat
50X6 mm GS Flat
Earth Enhancing Compound for treated pits as above and other requirement as per specification
Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
Earth Wire for Shielding Protection of Switchyard
7/3.15 Galvenized Steel Wire
Earthwire tension clamps with D Shackle assembly
PG calmp to suit 7/3.15 mm GS earth wire
Cleat clamp on structure to suit 7/3.15 mm GS earth wire/ 50 X 12 mm GS Flat
Pad clamp on structure to suit 7/3.15 mm earth wire and 75 x 12 GS flat
Lug to suit 7/3.15 mm earth wire
Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
Bay Marshalling KIOSK
200 way (Stud Type Connectors)
AC Distribution Boxes (Outdoor Type)
Outdoor AC Distbibution Box (Double Front type)
Outdoor AC Distbibution Box (Single Front type)
Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
LT Switchgear
LT AC Main Panel
LT AC Distribution Board
Main Lighting Distribution Board
Emergency Lighting Distribution Board
220V DCDB
48V DCDB
PLCC EQUIPMENTS
220 kV Wave trap (2000A, 0.5 mH, 40 kA)
132 kV wave trap (1250A, 0.5 mH, 40 kA)
SSB single Channel Carrier Set (40 W) suitable for transmitting Data and super imposed channels along with Remote subscriber facility and emergency calling set.
A.F. Protection coupler microprocessor based suitable for Four commands.
Coupling Devices for Phase to Phase coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
HF Armoured Coaxial cable having 75 Ohms unbalanced impendance.
Microprocessor based 32/16 line Electronic Private Automatic Exchange (EPAX) with PLCC interphasing facility
Telephone Sets (Push Button Type)
20 pair Jelly Filled and armoured telephone cable with copper conductor of 0.63 mm
5 Pair jelly filled armoured telephone cable having copper conductor of Dia. 0.5 mm
5 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm
TESTING & MEASURING INSTRUMENTS, TOOLS & TACKLES AND MISCELLANEOUS ITEMS
(A) TESTING EQUIPMENT/ INSTRUMENTS [This shall consist of all the standard accessories, cables, software etc. required for satisfactory operation of equipment meeting functional requirements]
Insulation Tester (5000 Volts, Digital)
SF6 Leakage Detector
Digital Multimeter
Digital Clamp Meter
PLCC Maintenance/Testing Equipments:
Level generator with a range at 50Hz to 620kHz including facility for synchronization with SLM
8 digit time interval & frequency counter with the frequency range of 10 Hz to 10MHz & timer range of 1 microsec to 1 sec in decade steps.
Dual range 15 MHz oscilloscope with a display screen 8x10 sq.cm and the input impedance of 1 M ohm/25 pF with a deflection coefficient of 5Mv/div to 20 V/div.
4-1/2 digit LCD Multimeter with input impedance of 10Mohm & with a range of 0.1 mV to 1000 V DC, 0.1mV to 600v AC, 0-10 AMP AC,(40hz to 10KHz) & 0-20 Mohm With builtin power –supply.
Print testing Kit for PLCC terminal, protection coupler, EPAX , As per specifications appended at Annexure- V2-P3-S19-2, Volume-II, Part 3, Section-XIX
(B) Maintenance Tools& Tackles
Oil Sampling Bottle (1 Liter Capacity)
Vaccum Cleaner
Telescopic ladder aluminium 6 meter height
Ring spanner set
Tube spanner set
Pipe wrench 24 inch
Pipe wrench 18 inch
Hydraulic crimping tools up to 630 sq.mm
Threading die set for pipe threading
Welding machine (arc welding) 10kVA
Heavy duty drilling machine
Bench Vice
Insulated cuttingplier 12 inch
Insulated cuttingplier 8 inch
Screw driver 18 inch
Screw driver 12 inch
Hammer 8 lbs
Hammer 2 lbs
Chain pulley block 5 ton
Pipe derrick
Allen Keys
Box Spanners
(C )Office and Miscellaneous Equipments/ Items
Insulation Rubber mat (1mX2mX 12 mm)
Isulation Rubber Gloves (15 kV Tested)
Furniture for Control Room Building:
SCADA Room Furniture (Control Desk for specified consoles and Revolving Chair) matching with the overall interiors as per specification
Executive Desk bulit in wood and steel with lockable drawings on both side (6 feetX2 ½ feetx 2 ½ feet)
Junior executive table with three drawings on right side One Cup board left side with prelaminated decolam top 20mm thick over painted M.S. Frame ( 4 ½ feet x 2 ½ feetx 2 ½ feet).
Library Shelf with Glass Door (min 4 Shelf)
Steel tubular “S” type with continuous and one feet dia 14guage pipe, cane seat backing, teak wood with quality cane.
Archival Storage 4 Drive Type
Lateral Filing Cabinets
3 Drawer Unit
4 Drawer Unit
Steel Almirah of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system.
Steel Almirah (with Glass doors) of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system.
Minor Almirah of size 4 ½ feet x30 inch x 17 inch with three shelves making four compartments in 22 guage or better with two waylocking system.
Steel rack of size 5 feet x 3 feet x 16 inches with six shelves making five compartments (22 guage).
Steel file trays of size 16 inches x11 inches x 3 inches of guage 14 SWG.
Steel stools of size 15 inch x15 inch x 18 inch square pipe 16 guage
Steel waste paper baskets of size 12 inch (H) and Approx. 10 inch Dia Round.
Key board (wooden) with Glass door
First Aid Box
Shock Treatment Chart [Laminated with Frame]
Safety Instruction Boards [ Laminated with Frame]
(D) Drinking Water Arrangement
Water Cooler (Storage type, Storage Capacity 40 Ltr, Cooling Capcity 20 Ltr./hr)
RO/ Water Purifier
Refrigirator (380 Lt.)
Substation Name Board [1 No. Glow Type & 1 No. Painted Type] [Size and Color etc. be got approved from owner]
Danger Plate [Size and Color etc. be got approved from owner]
MANDATORY SPARES
(A) 220/132 kV TRANSFORMER
Bushing with metal parts & gaskets of each rating including Neutral bushing
Local and remote winding temperature indicator complete with sensing device & contacts
Oil temperature indicator with contacts & sensing device
Oil cooler pump with motor
Cooler fan with motor
Set of starter, contactor, relays and switch for electrical control panels (1 set of each type and range)
Buchholz relay complete with floats & contacts
(B) 132/33 kV Power Transformer
HV bushing with metal parts and gaskets
LV bushing with metal parts and gaskets
Neutral bushing with metal parts and gaskets
Magnetic oil level gauge with low oil level alarm contacts
Winding temperature Hot indicator
Cooler fans
Buchlotz Relay
(C )Circuit Breakers
(One pole of circuit breaker with grading capacitor complete with pole column and interrupter with M.B. but without support structure and operating mechanism.
Rubber gaskets, ‘O’ rings and seals
Fixed Contacts
Moving Contacts
Terminal pads and connectors
Closing Assembly Valve
Trip Assembly Valve
Auxiliary Switch Assembly
Operation Counter
Closing Coils
Tripping coils
Support insulator complete for one pole of breaker
One pole of circuit breaker without support structure and operating mechanism.
Rubber gaskets, ‘O’ rings and seals
Fixed Contacts
Moving Contacts
Terminal pads and connectors
Closing assembly valve
Trip assembly valve
Auxiliary switch assembly
Operation counter
Closing Coils
Tripping coils
Support insulator (set complete for one pole of breaker)
Instrument Transformer
Spare of 245kV Capacitive Voltage Transformer
(i) Complete CVT
Spare of 145kV Capacitive Voltage Transformer
(i) Complete CVT
Spare of 245kV Current Transformer
(i) Complete CT [1 No. each type supplied)
Spare of 145kV Current Transformer
(i) Complete CT (1 No. each type supplied)
Spare of 33 kV Current Transformer
(i) Complete CT (1 No. each type supplied)
(E) C&R panels (similar items as used in the quoted panels)
Bay Control Unit (220 kV Side of offered type)
Bay Control Unit (132 kV Side of offered type)
Bay Control & Protection Unit (33 kV Side of offered type)
Bay Unit (For 220 kV Busbar Protection of offered type)
Bay Protection Unit (Distance for 220 kV Feeders of offered type)
Bay Protection Unit (Line Distance cum Differential for 220 kV Feeders of offered type)
Bay Protection Unit (Distance for 132 kV Feeders of offered type)
Bay Protection Unit (Differential for 220 kV Transformers of offered type Main-I)
Bay Protection Unit (Differential for 220 kV Transformers of offered type-Main-II)
Bay Protection Unit (Differential for 132 kV Transformers of offered type)
Bay Protection Unit (Back-up Overcurrent & E/F of offered type)
Breaker failure relay (numerical type)
Trip circuit supervision relay
Self reset trip relay
Hand reset trip relay
Timer relay
DC supervision relays
Flag relays
Auxiliary relays
Multifunction Panel Meter
Fiber Optic Cable with Connectors
Transducers (Each Type used in the autoamtion system)
Ethernet Switch (of offered type)
(F) Station Transformer
10% of total Transformer Oil quantity in non-returnable drums
HV bushing
LV bushing
Pressure relief device
Tap charger contact
Set of valves
Set of gasket
Silica gel required for five replacements
(G) Surge Arrester
220kV class 198 kV rating LA complete as specified.
132kV class 120 kV rating LA complete as specified.
33 kV Class of 30kV rating LA Complete as specified
2 Nos. Terminal connector of each type as spare
(H) Battery & Battery Charger
220 V & 48 V Type Battery
Spare battery cell without electrolyte
Terminal connectors with bolts & Nuts
Float level indicators
Vent Plugs
220V/ 50V Battery Chargers
Set of Control Cards
Set of relays
Set of contactor
Micro-switches
Filter Capacitors
Thyristor/ Diode
Set of switches
Set of wound resistors
Potentiometers
Fuses of Thyristor with indicators
(I) L.T. SWITCHGEAR :
Relays
CTs AND PTs
Switches/Push buttons and Meters
TPN Switches/MCB
L.T. Breaker spares
a) Spring charging motor
b) Aux. Contact sets
c) Busbar Seal off insulators
d) Arc-chutes
e) Moving contacts
f) Arcing contacts (Fixed/Moving)
g) Springs (Closing/Opening)
h) Closing coil
i) Tripping coil
j) Aux. finger contact
k) Limit switches
l) Jaw contacts
Busbar
a) Busbar insulators
b) Interphase barrier
c) Busbar strip 1mm (Aluminium)
(J) LIGHTING SYSTEM
Single Pole MCB
Triple pole MCB
Fluorescent tube & Starter
a) Choke
b) Bottom Strips
c) Top covers & reflector (if applicable)
d) Holders
e) Complete fittings
Sodium vapour/Mercury vapour Lamps a) Lamp
b) Ballast
c) Condenser/ Igniter
d) Lamp holder
e) Lamp holder
f) Complete fittings
Incandescent lamp
a) Bulbs
b) Holders
c) Complete fittings
Switches and sockets
Junction box
Celing Fan
(K) Clamps & Connectors Set
(L) Fire Protection System
NIFPES System
Fitted Nitrogen Cylinder [48 Lit Water Capacity]
Hose Pipe with Fittings
Heat Sensor Assembly
Fire Survival Cable [sufficient for 1 system]
Limit Switches for Fire Detector
Fire Detector (for NIFPES System)
Thermostat
Heating Element
(M) Isolators
Solid core Insulator Stacks (Requirement of one Isolator)
Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key interlock for electrical control circuit as per approved schematic --- Each set containing one number of each type and rating as offered.
Limit switches & aux.switches--Each Set containing one no. of each type and rating as offered
Motor with gear assembly and bevel gear assembly.
Bearings (Requirement of one Isolator)
Current carrying assembly total (Requirement of one Isolator)
Solid core Insulator Stacks (Requirement of one Isolator)
Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key interlock for electrical control circuit as per approved schematic --- Each set containing one number of each type and rating as offered.
Limit switches & aux.switches--Each Set containing one no. of each type and rating as offered
Motor with gear assembly and bevel gear assembly.
Bearings (Requirement of one Isolator)
Current carrying assembly total (Requirement of one Isolator)
Solid core insulator Stacks ( Requirement of one Isolator)
Limit switches and auxiliary switches ---Each Set containing one no. of each type and rating as offered
Bearings (requirement of one isolator)
Current carrying assembly 2000A total (requirement of one isolator)
Motor with gear assembly and bevel gear assembly.
Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key inter lock for electrical control circuit as per approved schematic-- Each Set containing one no. of each type and rating as offered
Add: Any other supply item, if any, bidder may require completing the substation as per specification requirements.
Description of Work / Item(s)
Amount
Service part along with CIVIL
Auto Transformer:
220/132/11 kV, 160 MVA Auto Transformer with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 160 MVA 220/132/11 kV Auto Transformer as per S-I , (1) above
Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers at S-I (1) above
Bus reactor
220 kV, 25 MVAr Bus reactor with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 220 kV, 25 MVAr Bus reactor above
Power Transformer:
132/33 kV, 31.5 MVA Power Transformer with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 31.5 MVA 132/33 kV Power Transformer S-II (4) above
Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers S-II, (4) above
Circuit Breakers
220 kV Circuit Breakers
220kV circuit breakers (3 Ph.) Along with support Structure
132 kV Circuit Breakers
132 kV circuit breakers (3 Ph.) Along with support Structure
33 kV Circuit Breakers
33 kV circuit breakers (3 Ph.) Along with support Structure
Instrument Transformers
Capacitor Voltage Transformer
Single-Phase, 220 kV, 4400 pf CVT
Single Phase 132 kV , 4400 pf CVT
33 kV Potential Transformer
Current Transformer (1-Phase)
1000/1 A, 5C (Live Tank Type only)
1000/1 A, 3C (Live Tank Type only)
500/1 A, 3C (Live Tank Type only)
C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
New Substation
Control Panel for 220 kV Transformer (220 kV Side) Type: SAS-THCB
Relay Panel for 220 kV Transformer (for both HV & MV) Type: SAS-THRB
Control Panel for 220 kV Bus Reactor (220 kV Side) Type: SAS-RCB
Relay Panel for 220 kV Bus reactor (for both HV & MV) Type: SAS-RRB
Control Panel for 220 kV Feeder Type: SAS-FCB
Relay Panel for 220 kV Feeder Type: SAS-FRB
Control Panel for 220 kV Bus Coupler Type: SAS-BCCB
Relay Panel for 220 kV Bus Coupler Type: SAS-BCRB
220 kV Busbar Protection Relay Panel Type: SAS-BBRB
Control Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLCB
Relay Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLRB
Control and Relay Panel for 1x 50/31.5/25 MVA, 132/33 kV Power Transformer Type SAS-TCRA
Control Panel for 132 kV Feeder Type SAS-FCA
Relay Panel for 132 kV Feeder Type SAS-FRA
Control and Relay Panel for 132 kV Bus-Coupler Type SAS-BCRA
Control and Protection Panel for 33 kV Feeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD
Station HMI [Industrial grade Computer with 21"TFT monitor as per specification requirements]
Station HMI (Hot Standby)[Industrial grade Computer with 21"TFT monitor as per specification requirements]
HMI View Node[Industrial grad Computer with 21"TFT monitor as per specification requirements]
A3 Size B&W Laser Printer
Substation Automation System Network Panel Type SAS-NW
Modems (both sending and Receiving End) for communication to RCC & Sub SLDC for PLCC]
Data Concentrator Unit (DCU) at Substation for RAS mounted in suitable enclosure & fully wired
Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.
Substation Auxiliary Monitoring Panel Type SAS-SAMP
Other Items:
Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
Surge Arresters
Substation LT Transformer
33/ 0.433 kV, 250 kVA LT transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil
Batteries & Battery Charger
Batteries (Sizing shall be as per requirement of technical specification)
220 V [Min. 600 AH]
48 V [Min. 600 AH]
Battery Charger System
220 V Float and Boost
50 V Float and Boost
Lighting System
Outdoor Lighting & other Works
Lighting Fixture Type FL-1
Lighting Fixture Type FL-2
Outdoor Receptacle
Type-RP
Type-RO
Substation Premises Lighting
Lighting poles
Type-L1
Type-D1
Street Lighting Type-SL-L1 for mounting on poles
Street Lighting Type-SL-D1 for mounting on Poles
Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast and Other Loaction as designated complete with all controgears and accessories, items etc.
Lighting Panel Type ACP-2 as per technical specification
Lighting Panel Type ACP-3 as per technical specification
Indoor Lighting & Other Works
Electrification
Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, Hall and administrative office building as per the requirements of the specifications
Illumiation
Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements)
Indoor Lignting Panels
Lighting Panel (Indoor) Type ACP-1 as per technical specification
Lighting Panel (Indoor) Type DCP as per technical specification
Wall mounted fans Approx. 400 mm sweep
Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator
Exhaust Fans
Fire Fighting System
Nitrogen Injection Fire Protection System for Auto Transformer (160 MVA ) complete in all respects.
Nitrogen Injection Fire Protection System for 220 kV 25 MVAR Bus reactor (25MVAr ) complete in all respects.
Nitrogen Injection Fire Protection System for Power Transformer (31.5 MVA ) complete in all respects.
DCP Type
Carbon di oxide type – 6 Liters.
Foam Type- 9 Liters
Sand type
i) GI Buckets 9 liters capacity
ii) Steel Stands for four buckets
Air Conditioning System
Air Conditioning for the Rooms specified in the specifications
1.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
Power Cables(XLPE)
3.5Cx300 sq.mm
Power Cable(PVC)
1Cx150 sq.mm
3.5Cx70 sq.mm
3.5Cx35 sq.mm
4Cx16 sq.mm
4C x 6 Sq. mm
2C x 6 Sq. mm
Control Cable (PVC)
4 CX4 Sq. mm
3Cx2.5 sq.mm
4Cx2.5 sq.mm
14Cx2.5 sq.mm
19Cx2.5 sq.mm
Substation Structures
Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
Non-Standard type Pipe Support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe Support structure as per specification requirements]
Isolators
220 kV (3-Phase) (Horizontal DOUBLE BREAK)
1600A, 50KA, isolator with one E/S
Post insulators for above Isolator
1600A, 50KA, isolator with two E/S
Post insulators for above Isolator
1600A, 50KA, isolator without E/S
Post insulators for above Isolator
1600A, 50KA, isolator without E/S (TANDEM Type)
Post insulators for above Isolator
132 kV (3-Phase) (Horizontal DOUBLE BREAK)
1250A, isolator with one E/S
Post insulators for above Isolator
1250A isolator without E/S
Post insulators for above Isolator
33 kV (3-Phase) (Horizontal DOUBLE BREAK)
1250A, isolator without E/S
Post insulators for above Isolator
800 A isolator without E/S
Post insulators for above Isolator
800A isolator withE/S
Post insulators for above Isolator
Switchyard Erection
Busbar & Interconnections
New Substation/ Switchyard
220 kV Switchyard Works:
Main-I Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/Porcelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
Main-II Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Pocelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
Aux Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string(DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
220 kV Overhead Jack Bus (for DMT Layout) on Twin ACSR Zebra(Bus-Coupler Bay)/ Single ACSR Zebra (Transformer/ Line on ACSR Zebra) with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Twin ACSR Zebra
Single ACSR Zebra
Equipment Interconnections to Main Bus, Overhead Bus including Single ACSR Zebra (for Line), Twin ACSR Zebra (forTransformer bay & B/C Bay), bus-bar materials, clamps, connectors, spacers, corona shields, including equipment connectors, Junction box including of all accessories etc. for the following:
220 kV DMT-type layout
Line bay
Transformer bay
Bus-Coupler
Bus CVT Interconnections to Main Buses including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
132 kV Switchyard Works:
Main Bus: 132 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulator, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
Aux Bus: 132 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay), Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Twin ACSR Zebra
Single ACSR Zebra
Single Panther
Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV Transformer Bay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
132 kV Main & Aux-type layout
Line bay
Transformer bay /Reactor Bay
Bus-Coupler
Bus Sectionalizer
Bus CVT Interconnections to Main Bus including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
33 kV Switchyard Works:
Main Bus: 33 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]
Aux Bus: 33 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]]
33 kV Overhead Jack Bus for Transformer Incomer (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
33 kV Main & Aux-type layout
Line bay
Transformer bay
Bus-Coupler
LT Transformer connection with ACSR Panther conductor, 33 kV DO Fuse Set alongwith required Clamp/connectors
Bus PT Interconnections to Main Bus including Single ACSR Panther , clamps, connectors, junction box including of all accessories etc.
Bus Post Insulators (BPI)
Earthing & Lightning Protection System
Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
40 mm Dia MS Rod
40mm Dia, 3.2 M Long MS Rod Earth Electrodes Directly Driven.
40mm Dia, 8 M Long MS Rod Earth Electrodes Directly Driven.
40mm Dia, 3.2M Long MS Rod Earth Electrode in untreated pit with test link
40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works
75X12 mm GS Flat
50X6 mm GS Flat
Earth Enhancing Compound for treated pits as above and other requirement as per specification
Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
Earth Wire for Shielding Protection of Switchyard
7/3.15 Galvenized Steel Wire
Earthwire tension clamps with D Shackle assembly
PG calmp to suit 7/3.15 mm GS earth wire
Cleat clamp on structure to suit 7/3.15 mm GS earth wire/ 50 X 12 mm GS Flat
Pad clamp on structure to suit 7/3.15 mm earth wire and 75 x 12 GS flat
Lug to suit 7/3.15 mm earth wire
Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
Bay Marshalling KIOSK
200 way (Stud Type Connectors)
AC Distribution Boxes (Outdoor Type)
Outdoor AC Distbibution Box (Double Front type)
Outdoor AC Distbibution Box (Single Front type)
Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
LT Switchgear
LT AC Main Panel
LT AC Distribution Board
Main Lighting Distribution Board
Emergency Lighting Distribution Board
220V DCDB
48V DCDB
PLCC EQUIPMENTS
220 kV Wave trap (2000A, 0.5 mH, 40 kA)
132 kV wave trap (1250A, 0.5 mH, 40 kA)
SSB single Channel Carrier Set (40 W) suitable for transmitting Data and super imposed channels along with Remote subscriber facility and emergency calling set.
A.F. Protection coupler microprocessor based suitable for Four commands.
Coupling Devices for Phase to Phase coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
Coupling Devices for Phase to Ground coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
HF Armoured Coaxial cable having 75 Ohms unbalanced impendance.
Microprocessor based 32/16 line Electronic Private Automatic Exchange (EPAX) with PLCC interphasing facility
Telephone Sets (Push Button Type)
20 pair Jelly Filled and armoured telephone cable with copper conductor of 0.63 mm
5 Pair jelly filled armoured telephone cable having copper conductor of Dia. 0.5 mm
5 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm
CIVIL WORKS
TOWER/ EQUIPMENT FOUNDATIONS :
LATTICE / PIPE STRUCTURE
220 kV tower type AT1/AT3
220 kV tower type AT4
220 kV tower type AT6/AT7/AT8
220 kV ,LA support structures
220 kV CT, support structures
220 kV CVT support structures
220 kV Tendom Isolator (including associated PIs)
220 kV Isolator
220 kV PI Structure
220 kV Circuit Breaker
132 kV PI Structure
132 KV tower type BT1/BT3
132 KV tower type BT4
132 kV tower type BT6/BT7
132 kV CT, support structures
132 kV LA support structures
132 kV CVT support structures
132 kV Isolator
33 KV PI Structure
33 kV structure Y type with stub
33 kV structure Z type
33 kV CT/PT structure
33 kV isolator
145 kV SF6 Circuit Breaker
36 kV Vacuum Circuit Breaker
Marshalling Kiosk
Isolator handle mechanism
Lighting Mast
FOUNDATION FOR160 MVA, 220/132 kV TRANSFORMER:-
Civil works for MS Tank including Excavation, Laying of 75 mm PCC, Constructing brick wall jacket around the tank, laying of 200 mm RCC raft, leveling and alignment of MS Tank, backfilling with excavated sand, Top leveling by laying of PCC, as per site requirement and Technical specifications (complete job).As per specification for 160 MVA Transformer
FOUNDATION FOR 25 MVAr, 220 kV Bus Reactor:-
Civil works for MS Tank including Excavation, Laying of 75 mm PCC, Constructing brick wall jacket around the tank, laying of 200 mm RCC raft, leveling and alignment of MS Tank, backfilling with excavated sand, Top leveling by laying of PCC, as per site requirement and Technical specifications (complete job). As per specification for 40/50 MVA Transformer
FOUNDATION FOR 31.5 MVA, 132/33 kV TRANSFORMER:-
Civil works for MS Tank including Excavation, Laying of 75 mm PCC, Constructing brick wall jacket around the tank, laying of 200 mm RCC raft, leveling and alignment of MS Tank, backfilling with excavated sand, Top leveling by laying of PCC, as per site requirement and Technical specifications (complete job). As per specification for 40/50 MVA Transformer
FOUNDATION FOR 33/0.415 kV, 250 kVA, LT three phase station transformer
CABLE TRENCH
Type A Cable trench
Type C Cable trench
Construction of RCC sump having capacity 10000 Liters with provision of automatic dewatering mud pump with disposal arrangement upto outside RVPN premises as directed by Engineeer In-charge with provision of a stand by pump.
CABLE TRENCH CROSSING
Road crossing for 'A' type cable trenches
Road crossing for 'C' type cable trenches
Grading of yard including all cutting and filling:-
Supply and stacking earth material obtained from borrow pits with all leads and lifts, transporting to site, spreading, grading to required slope & compacting by vibratory roller 8-10 Ton to meet requirement of table 300-2 including cost of compensation for earth taken from private land with all lead as per MORTH specification clause no. 305.
Construction of retaining wall at level difference with stone /brick masonry/RCC-M20 walls of required section including all finishings required as per direction of Engineer-in charge
ANTI WEED TREATMENT AND BASE LAYER OF INTERLOCKING TILES
Providing and fixing of precast concrete interlocking blocks of M 30 grade 60mm thick manufactured from fully computerised automatic stationery hydraullic vibropressed machine and fully computerised automatic batching plant of class A1/A2 as per BS 6717:2001. The CC interlocking paving blocks be laid on average 50mm. thick bed of coarse sand and the joint is to be filled with fine sand. Laying procedure on compacted sub-base as defined. Complete job is to be executed as per the instruction of Engineer incharge. The rates to be inclusive of all lead, Lifts and taxes. General specification of blocks: ( 1) Shape as defined by Engineer incharge 2) Tensile splitting strength and braking load as per BS 6717:2001 3) Color: Grey cement natural colour 4) Variation in dimension: Less than 1.6mm. 5) Variation in thickness: Less than 3.2mm 6) Abrasion: As per BS: 6717:2001
JELLY SPREADING (Gravelling)
Providing and laying 100mm thick layer of granite/basalt/trap jelly(gravel) of 40mm single size shall be spread over the entire switchyard area as per drawing and directions of engineer incharge of the work. The whole switchyard area (excluding buildings pathway road, drainages, cable trenches, equipments/ structures/ plinths etc.) shall be covered with jelly spreading. The jelly used shall be free from dirt, organic materials and flakes.
Supply & Fixing Barricades to confine Jelly (gravel), which include Supply and fixing cement concrete solid blocks of size 60x(20+25)/2x30 cms (l, b, h) jointed with CM 1:4, made from precast M-20 concrete and laid over 100 mm thick base of PCC 1:4:8 including necessary curing etc. complete. The top of concrete block shall be 100 mm above gravel top with provision of suitable openings for drainage of rain water. The exposed surface of barricades shall be applied with two coat of water proof cement paint.
ROAD WORK
Construction of unreinforced, dowel jointed plain cement cocrete pavement in 150 mm thickness over and including sub-base of 150 mm thick quarry rubbish and 100 thick PCC 1:4:8 with M 30 grade cement concrete laid in approved side form work(steel channels , laying and fixing 125 micron thick polythene film wedged, steel plates including leveling the form work as per drawing, spreading using shovels, rakes, compacted using needdle, plate and screed vibrator finished in continuous operation including provision of expansion and contraction and construction joints, applying debonding strips, primer, sealant, dowel bars at expansion & construction joints only, curing etc complete including dewatering process with all equipments. work also includes providing and fixing precast cement concrete solid blocks on outer edges of both sides shoulder of size 60x(20+25)/2x30 cms (l, b, h) jointed with CM 1:4, made from precast M-20 concrete and laid over 100 mm thick base of PCC 1:4:8 including necessary curing etc. complete. The concrete block top shall be 100 mm above road top, with provision of suitable openings for drainage of rain water. The exposed surface of concrete blocks shall be applied with two coat of enamel paint, painted black and yellow alternately, and Providing and laying 80 mm thick M 30 interlocking tiles Category A Denated units to key into each other on four faces zig zag shape over 100 mm PCC 1:4:8, complete as per IRC SP 63:2004 specification on shoulders as per approved drawing, specification and direction of engineer incharge(payment shall be made as per actual length).
4.0 Mtr. Wide Road with shoulders of 1 m on both side of CC road
3.0 Mtr. Wide Road. with shoulders of 0.60 m on both side of CC road
RAIN WATER HARVESTING
CONTROL ROOM BUILDING
Construction of control room building as per drawing and specification including internal electricafication with Energy Efficient Lights , Tube light fixtures etc, 15 lit storage geyser, earthing, sanitary system including septic tanks, soakage pits and rain water harvesting system as per drawing approved by owner/GWD etc., water supply system including making connection with distribution system, false ceiling (In Hall, PLCC room and XEN chamber), fans,water cooler of cooling capacity 80 lits/hour and storage capacity of 120 lits, RO system withpurification capacity of 25 lits/hour and duty cycle of 170-250 lits/day with PVC tank of 200 lits capacity, internal cable trenches covered with 6 mm thick MS chequred plates, plinth protection works with chequred tiles etc (plinth area approximately 600 sqm, with out roof projections, plinth protection and porch)
WATER SUPPLY :-Supply and installation of water supply system with construction of GLR, submersible cables, pump room with pump and one stand- by pump for the sub-station, required electrifcation cables from control room and panels, providing and laying GI pipe line from GLR to control room, yard, guard room,store, for plantation etc including making connection , landscaping,construction and development of park as per the drawing & plantation as per specification & approved drawings and directions of engineer incharge.
Construction of Tube-well from ground levels and upto required depth & dia (as per hydrogelogist report) to accommodate housing and assembly pipe of required sizes in all types of alluvium /rocky strata by percussion/ rotary drilling method and with gravel as per IS:4097-1967 and packing as per IS:2800 (part I & II) 1979 as amended upto date (the work includes the cost of gravel & its primary packing and packing during developement, lowering of housing & strainer assembly pipes, with supply & wrapping of coir-rope, whenever necessary, for arresting fine sand particles, including cost of housing pipe and strainer pipe assembly and developement work. Work would be completed after obtaing sand free water) work also includes supplying and installation of submersible pumping motor pump sets I.S.I. marked (IS:8034-1989) and one stand- by pump of approved make like K.S.B., Kirloskar, calama etc. or equivalent, making connection suitable for T.W. The job includes supplying and welding of flanges on G.I. riser pipes, pipe line of required dia up to GLR, required cables from control room to panel and subersible pump, installation of complete fitting & accessories, with riser pipes, jointing of electrical cables and other connections making switch board electrical connections, panels etc as per design and specification, all labour for testing of submersible pump set and supply of water to water mains, complete in all respect as directed by engineer incharge. Note:- Tubewell shall be constructed as per feasibility report received from hydrogeologist.
Providing, Laying & Jointing R.C.C. class NP-2 Non-Pressure pipes (IS : 458 mark) of approved make with collars, jointed with C.M. 1:2 or having Spigot and socket ends with flexible rubber rings joints including testing of joints etc. complete for 300 mm dia internal dia pipe including Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40mm nominal size) upto haunches of S.W. pipes including bed concrete as per standard design and Excavating trenches of required width for pipes cables etc. including excavation for sockets, depth up to required depth including taking out the excavated materials, refilling the soil as required in layers not exceeding 20 cm in depth including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, with all lead and lifts in all types of soil, rocks etc complete in all respect.
Add: Any other item bidder may require to complete the Civil works as per specification requirements
Description of Work / Item(s)
Amount
Tower: Fabrication, galvanising and supply of various types of towers (including special towers), & its body / leg (equal & unequal) extensions (complete) including stubs and hangers, D-shackles, Bird Guard, U-Bolt, Pack washer, Anticlimbing devices etc.
High Tensile Steel
Mild Steel
Supply of Bolts & Nuts for towers and stubs (including step bolts & nuts and anti theft bolts & nuts, Spring Washers Etc. )
Supply of Earthing material of Towers
Pipe Type Set
Counter Poise type
Supply of following Tower Accessories
Danger Plate
Number Plate
Phase Plate (Set of three)
Design, manufacture and supply of following line material. **
(i) Disc Insulator - 70 kN
(ii) Porcelain Long Rod Insulator - 70 kN
(i) Disc Insulator - 120 kN
(ii) Porcelain Long Rod Insulator - 120 kN
ACSR Panther Conductor
Hardware Fittings for ACSR Panther Conductor
Single Suspension H/W fittings for ACSR Panther Conductor
Single Tension H/W fittings for ACSR Panther Conductor
Double Suspension H/W fittings for ACSR Panther Conductor
Double Tension H/W fittings for ACSR Panther Conductor
Accessories for ACSR Panther Conductor
Mid Span Compression Joint for ACSR Panther Conductor
Repair Sleeve for ACSR Panther Conductor
Preformed Armour Rod for ACSR Panther Conductor
Vibration Damper for ACSR Panther Conductor
OPGW Cable
24 Fibre (DWSM) OPGW fibre optic cable
Installation Hardware set for 24 Fibre OPGW Fibre Optic cabling including all cable fittings & accessories except joint box
Joint box (24 Fibre)
FODP 48F Indoor Type rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
48 Fibre (DWSM)
Installation Hardware set for 48 Fibre OPGW Fibre Optic approach cable
Any Other item required for successful completion of work
Note: *One set of installation hardware shall contain all installation hardware fittings as may be required for 1 km of OPGW. ** Quantity indiacted is for evaluation purpose. Actual quantity to be supplied after getting approval from owner. *** Bidder will quote either for Disc or Long Rod or Composit Long Rod insualtors. In case of bidder quote for more than one types of insulators, then in evaluation heighest cost of insulators will be considered.
Description of Work / Item(s)
Amount
Detail Survey as per tentative route- Which includes the following major activities-Pegging of line route, providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of line, marking of side clearance for hills, sand dunes etc, as per specification and tower scheduling.
Check survey as per approved route of line which includes- Re-checking of the line route as per approved profile, chainage, tower center marking, pit marking, bisection of angle tower as required at site.
Excavation-Excavation, excluding back filling, including shoring,shuttering, dewatering, etc. upto the required depth as per foundation specification/drawings.
(i) Any soil, soft rock other than hard rock
(ii) Hard Rock (with blasting subject to permission or without blasting)
SETTING OF TEMPLATE & STUB/ANCHOR BOLT:- Setting of template & stub/ anchor bolt & removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead & lift) in layers with ramming andwatering as per specification.
(i) Tower including extension upto 9 Meter
CONCRETING: Providing and laying cement concrete for all types of foundation as per latest ISS:456 including cement, sand, stone aggregate 20mm nominal size,water etc., preparing surfaces, shuttering, mixing, placing, ramming, curing, finishing as per specification and drawings.
(ii) 1:1.5:3 Mix
STEEL REINFORCEMENT: Cutting, bending, welding of joints if required,fixing and placing of steel reinforcement as per specification and drawings including material.
EARTHING:
(A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats &connectors, but including coke/charcoal, etc.,excavation,augering and backfilling in all types of soil.
(B) Earthing of towers legs with counterpoise typeearthings excluding supply of materialsbut including excavation and backfilling in all types of soil. (i)each set by laying 4 wires each 15m long at a depth of 600mm l.
ERECTION OF TOWERS: Erection of super structures including D-shackles,ACD, Hangers, U-Bolts, step bolts, danger plate, phase plate, number plate etc. Also including tack welding of bolts & nuts upto bottom cross arm/beam level including application of Zinc Rich paint
Erection of tower (with extension upto 9 Meters)
CONDUCTOR STRINGING: Stringing of ACSR Panther including hoisting of insulator string, laying, jointing & tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line.
(i) Single Conductor
RIVETMENT OF TOWERS
(A) Providing and laying cement concrete including curing, compaction etc. complete using stone aggregate 40 mm nominal size (crusher broken) in foundation plinth, using 1 Cement: 5 Sand: 10 aggregate mix.
(B) Random rubble stone masonary for rivetment in 1:5 cement sand mortar including providing and fixing 100mm dia PCC drain pipe & raised and cut-pointing on stone masonary in 1:3 cement sand mortar excluding excavation but including Back filling inside rivetment using excavated/ borrowed earth (with all lead & lift) in layers not exceeding 20cm in depth & consolidating each deposited layer by ramming and watering.
(C )Random rubble dry stone pitching including preparing surface etc. complete with raised & cut pointing in cement sand mortar 1:3, curing etc.
(D) Cement concrete coping grade 1:2:4 (1cement: 2coarse sand :4 graded stone aggregate) rounding off edges etc. but excluding the cost of nosing of steps etc. complete for 75mm thick with 20mm thick nominal size aggregate
Installation of OPGW Cable
Stringing of 24 Fiber (DWSM) OPGW FIBRE OPTIC CABLE
Installation Hardware set for above 24 Fibre OPGW cabling including of al cable fittings and accessories exept joint Box
JOINT BOX (24 FIBER) OPGW CABLE
FODP 48 F-Indoor type, rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
24 fibre (DWSM)
Installation Hardware set for above 24 Fibre approach cable
Any Other Item
Description of Work / Item(s)
Amount
Tower: Fabrication, galvanising and supply of various types of towers (including special towers), & its body / leg (equal & unequal) extensions (complete) including stubs and hangers, D-shackles, Bird Guard, U-Bolt, Pack washer, Anticlimbing devices etc.
High Tensile Steel
Mild Steel
Supply of Bolts & Nuts for towers and stubs (including step bolts & nuts and anti theft bolts & nuts, Spring Washers Etc. )
Supply of Earthing material of Towers
Pipe Type Set
Counter Poise type
Supply of following Tower Accessories
Danger Plate
Number Plate
Phase Plate (Set of three)
Design, manufacture and supply of following line material. **
(i) Disc Insulator - 70 kN
(ii) Porcelain Long Rod Insulator - 70 kN
(i) Disc Insulator - 120 kN
(ii) Porcelain Long Rod Insulator - 120 kN
ACSR Zebra Conductor
Hardware Fittings for ACSR Zebra Conductor
Single Suspension H/W fittings for ACSR Zebra Conductor
Single Tension H/W fittings for ACSR Zebra Conductor
Double Suspension H/W fittings for ACSR Zebra Conductor
Double Tension H/W fittings for ACSR Zebra Conductor
Accessories for ACSR Zebra Conductor
Mid Span Compression Joint for ACSR Zebra Conductor
Repair Sleeve for ACSR Zebra Conductor
Preformed Armour Rod for ACSR Zebra Conductor
Vibration Damper for ACSR Zebra Conductor
Accessories for7/4 mm Earth Wire
G.I. Earth wire 7/3.15mm
Strin Assembly for Earth wire 7/3.15 mm with copper Earth Bond
Suspension Assembly for Earth wire 7/3.15 mm with copper Earth Bond
Vibration Damper for Earth wire7/3.15 mm
Mid Span Compression Joint for Earth wire 7/3.15 mm
Repair Sleeve for for Earth wire 7/3.15 mm
Any Other item required for successful completion of work
Note: *One set of installation hardware shall contain all installation hardware fittings as may be required for 1 km of OPGW. ** Quantity indiacted is for evaluation purpose. Actual quantity to be supplied after getting approval from owner. *** Bidder will quote either for Disc or Long Rod or Composit Long Rod insualtors. In case of bidder quote for more than one types of insulators, then in evaluation heighest cost of insulators will be considered.
Description of Work / Item(s)
Amount
Detail Survey as per tentative route- Which includes the following major activities-Pegging of line route, providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of line, marking of side clearance for hills, sand dunes etc, as per specification and tower scheduling.
Check survey as per approved route of line which includes- Re-checking of the line route as per approved profile, chainage, tower center marking, pit marking, bisection of angle tower as required at site.
Excavation-Excavation, excluding back filling, including shoring,shuttering, dewatering, etc. upto the required depth as per foundation specification/drawings.
(i) Any soil, soft rock other than hard rock
(ii) Hard Rock (with blasting subject to permission or without blasting)
SETTING OF TEMPLATE & STUB/ANCHOR BOLT:- Setting of template & stub/ anchor bolt & removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead & lift) in layers with ramming andwatering as per specification.
(i) Tower including extension upto 9 Meter
CONCRETING: Providing and laying cement concrete for all types of foundation as per latest ISS:456 including cement, sand, stone aggregate 20mm nominal size,water etc., preparing surfaces, shuttering, mixing, placing, ramming, curing, finishing as per specification and drawings.
(i) 1:3:6 Mix (M-10)
(ii) 1:1.5:3 Mix (M-20)
STEEL REINFORCEMENT: Cutting, bending, welding of joints if required,fixing and placing of steel reinforcement as per specification and drawings including material.
EARTHING:
(A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats &connectors, but including coke/charcoal, etc.,excavation,augering and backfilling in all types of soil.
(B) Earthing of towers legs with counterpoise typeearthings excluding supply of materialsbut including excavation and backfilling in all types of soil. (i)each set by laying 4 wires each 15m long at a depth of 600mm l.
ERECTION OF TOWERS: Erection of super structures including D-shackles,ACD, Hangers, U-Bolts, step bolts, danger plate, phase plate, number plate etc. Also including tack welding of bolts & nuts upto bottom cross arm/beam level including application of Zinc Rich paint
Erection of tower (with extension upto 9 Meters)
CONDUCTOR STRINGING: Stringing of ACSR Zebra including hoisting of insulator string, laying, jointing & tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line.
(i) Single Conductor
EarthwireStringing :- (A) Stringing of galvanised steel stranded wire including laying,jointing & tensioning, clamping,clipping and fixing vibration damper and earth bond etc.
(i)One No. 7/3.15 mm galvanised wire
RIVETMENT OF TOWERS
(A) Providing and laying cement concrete including curing, compaction etc. complete using stone aggregate 40 mm nominal size (crusher broken) in foundation plinth, using 1 Cement: 5 Sand: 10 aggregate mix.
(B) Random rubble stone masonary for rivetment in 1:5 cement sand mortar including providing and fixing 100mm dia PCC drain pipe & raised and cut-pointing on stone masonary in 1:3 cement sand mortar excluding excavation but including Back filling inside rivetment using excavated/ borrowed earth (with all lead & lift) in layers not exceeding 20cm in depth & consolidating each deposited layer by ramming and watering.
(C )Random rubble dry stone pitching including preparing surface etc. complete with raised & cut pointing in cement sand mortar 1:3, curing etc.
(D) Cement concrete coping grade 1:2:4 (1cement: 2coarse sand :4 graded stone aggregate) rounding off edges etc. but excluding the cost of nosing of steps etc. complete for 75mm thick with 20mm thick nominal size aggregate
Any Other Item
Description of Work / Item(s)
Amount
Tower: Fabrication, galvanising and supply of various types of towers (including special towers), & its body / leg (equal & unequal) extensions (complete) including stubs and hangers, D-shackles, Bird Guard, U-Bolt, Pack washer, Anticlimbing devices etc.
High Tensile Steel
Mild Steel
Supply of Bolts & Nuts for towers and stubs (including step bolts & nuts and anti theft bolts & nuts, Spring Washers Etc. )
Supply of Earthing material of Towers
Pipe Type Set
Supply of following Tower Accessories
Danger Plate
Number Plate
Phase Plate (Set of three)
Design, manufacture and supply of following line material. **
(i) Disc Insulator - 70 kN
(ii) Porcelain Long Rod Insulator - 70 kN
(i) Disc Insulator - 120 kN
(ii) Porcelain Long Rod Insulator - 120 kN
ACSR Panther Conductor
Hardware Fittings for ACSR Panther Conductor
Single Tension H/W fittings for ACSR Panther Conductor
Double Tension H/W fittings for ACSR Panther Conductor
Accessories for ACSR Panther Conductor
Mid Span Compression Joint for ACSR Panther Conductor
Repair Sleeve for ACSR Panther Conductor
Vibration Damper for ACSR Panther Conductor
Accessories for7/4 mm Earth Wire
OPGW Cable
24 Fibre (DWSM) OPGW fibre optic cable
Installation Hardware set for 24 Fibre OPGW Fibre Optic cabling including all cable fittings & accessories except joint box
Joint box (24Fibre)
FODP 48F Indoor Type rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
24 Fibre (DWSM)
Installation Hardware set for 24 Fibre OPGW Fibre Optic approach cable
Any Other item required for successful completion of work
Note: *One set of installation hardware shall contain all installation hardware fittings as may be required for 1 km of OPGW. ** Quantity indiacted is for evaluation purpose. Actual quantity to be supplied after getting approval from owner. *** Bidder will quote either for Disc or Long Rod or Composit Long Rod insualtors. In case of bidder quote for more than one types of insulators, then in evaluation heighest cost of insulators will be considered.
Description of Work / Item(s)
Amount
Detail Survey as per tentative route- Which includes the following major activities-Pegging of line route, providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of line, marking of side clearance for hills, sand dunes etc, as per specification and tower scheduling.
Check survey as per approved route of line which includes- Re-checking of the line route as per approved profile, chainage, tower center marking, pit marking, bisection of angle tower as required at site.
Excavation-Excavation, excluding back filling, including shoring,shuttering, dewatering, etc. upto the required depth as per foundation specification/drawings.
(i) Any soil, soft rock other than hard rock
(ii) Hard Rock (with blasting subject to permission or without blasting)
SETTING OF TEMPLATE & STUB/ANCHOR BOLT:- Setting of template & stub/ anchor bolt & removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead & lift) in layers with ramming andwatering as per specification.
(i) Tower including extension upto 9 Meter
CONCRETING: Providing and laying cement concrete for all types of foundation as per latest ISS:456 including cement, sand, stone aggregate 20mm nominal size,water etc., preparing surfaces, shuttering, mixing, placing, ramming, curing, finishing as per specification and drawings.
(ii) 1:1.5:3 Mix
STEEL REINFORCEMENT: Cutting, bending, welding of joints if required,fixing and placing of steel reinforcement as per specification and drawings including material.
EARTHING:
(A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats &connectors, but including coke/charcoal, etc.,excavation,augering and backfilling in all types of soil.
ERECTION OF TOWERS: Erection of super structures including D-shackles,ACD, Hangers, U-Bolts, step bolts, danger plate, phase plate, number plate etc. Also including tack welding of bolts & nuts upto bottom cross arm/beam level including application of Zinc Rich paint
Erection of tower (with extension upto 9 Meters)
CONDUCTOR STRINGING: Stringing of ACSR Panther including hoisting of insulator string, laying, jointing & tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line.
(i) Single Conductor
OPGW cable & Accessories
Stringing of 24 Fibre (DWSM) OPGW fibre optic cable
Installation Hardware set for 24 Fibre OPGW Fibre Optic cabling including all cable fittings & accessories except joint box
Joint box (24 Fibre)
FODP 48 F-Indoor type, rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
24 fibre (DWSM)
Installation Hardware set for above 24 Fibre approach cable
Any Other Item
Description of Work / Item(s)
Amount
Tower: Fabrication, galvanising and supply of various types of towers (including special towers), & its body / leg (equal & unequal) extensions (complete) including stubs and hangers, D-shackles, Bird Guard, U-Bolt, Pack washer, Anticlimbing devices etc.
High Tensile Steel
Mild Steel
Supply of Bolts & Nuts for towers and stubs (including step bolts & nuts and anti theft bolts & nuts, Spring Washers Etc. )
Supply of Earthing material of Towers
Pipe Type Set
Counter Poise Earthing set
Supply of following Tower Accessories
Danger Plate
Number Plate
Phase Plate (Set of three)
Design, manufacture and supply of following line material. **
Disc Insulator - 70 kN
(ii) Porcelain Long Rod Insulator - 70 kN
(i) Disc Insulator - 120 kN
(ii) Porcelain Long Rod Insulator - 120 kN
ACSR Zebra Conductor
Hardware Fittings for ACSR Zebra Conductor
Single Suspension H/W fittings for ACSR Zebra Conductor
Single Tension H/W fittings for ACSR Zebra Conductor
Double Suspension H/W fittings for ACSR Zebra Conductor
Double Tension H/W fittings for ACSR Zebra Conductor
Accessories for ACSR Zebra Conductor
Mid Span Compression Joint for ACSR Zebra Conductor
Repair Sleeve for ACSR Zebra Conductor
Preformed Armour Rod for ACSR Zebra Conductor
Vibration Damper for ACSR Zebra Conductor
G.I. Earth wire 7/3.15mm
Strin Assembly for Earth wire 7/3.15 mm with copper Earth Bond
Suspension Assembly for Earth wire 7/3.15 mm with copper Earth Bond
Vibration Damper for Earth wire7/3.15 mm
Mid Span Compression Joint for Earth wire 7/3.15 mm
Repair Sleeve for for Earth wire 7/3.15 mm
Bird Flight Diverters
Non LED Type
Solar Powered LED Type
Any Other item required for successful completion of work
Note: *One set of installation hardware shall contain all installation hardware fittings as may be required for 1 km of OPGW. ** Quantity indiacted is for evaluation purpose. Actual quantity to be supplied after getting approval from owner. *** Bidder will quote either for Disc or Long Rod or Composit Long Rod insualtors. In case of bidder quote for more than one types of insulators, then in evaluation heighest cost of insulators will be considered.
Description of Work / Item(s)
Amount
Detail Survey as per tentative route- Which includes the following major activities-Pegging of line route, providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of line, marking of side clearance for hills, sand dunes etc, as per specification and tower scheduling.
Check survey as per approved route of line which includes- Re-checking of the line route as per approved profile, chainage, tower center marking, pit marking, bisection of angle tower as required at site.
Excavation-Excavation, excluding back filling, including shoring,shuttering, dewatering, etc. upto the required depth as per foundation specification/drawings.
(i) Any soil, soft rock other than hard rock
(ii) Hard Rock (with blasting subject to permission or without blasting)
SETTING OF TEMPLATE & STUB/ANCHOR BOLT:- Setting of template & stub/ anchor bolt & removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead & lift) in layers with ramming andwatering as per specification.
(i) Tower including extension upto 9 Meter
CONCRETING: Providing and laying cement concrete for all types of foundation as per latest ISS:456 including cement, sand, stone aggregate 20mm nominal size,water etc., preparing surfaces, shuttering, mixing, placing, ramming, curing, finishing as per specification and drawings.
(iii) 1:1.5:3 Mix
STEEL REINFORCEMENT: Cutting, bending, welding of joints if required,fixing and placing of steel reinforcement as per specification and drawings including material.
EARTHING:
(A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats &connectors, but including coke/charcoal, etc.,excavation,augering and backfilling in all types of soil.
(B) Earthing of towers legs with counterpoise typeearthings excluding supply of materialsbut including excavation and backfilling in all types of soil. (i)each set by laying 4 wires each 15m long at a depth of 600mm l.
ERECTION OF TOWERS: Erection of super structures including D-shackles,ACD, Hangers, U-Bolts, step bolts, danger plate, phase plate, number plate etc. Also including tack welding of bolts & nuts upto bottom cross arm/beam level including application of Zinc Rich paint
Erection of tower (with extension upto 9 Meters)
Erection of substation structures including leveling, setting of stub & Tighting,Punching of Nuts& Bolts and tack welding upto beam level as per specification.
CONDUCTOR STRINGING: Stringing of ACSR Zebra including hoisting of insulator string, laying, jointing & tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line.
(i) Single Conductor
EarthwireStringing :- (A) Stringing of galvanised steel stranded wire including laying,jointing & tensioning, clamping,clipping and fixing vibration damper and earth bond etc.
(i)One No. 7/3.15 mm galvanised wire
Installation of Bird Flight Diverter
Non LED Type
Solar Powered LED Type
Revitment work
(A) Providing & laying cement concrete including curing compaction etc. complete using stone aggregate 40 mm nominal size (Crusher broken) in foundation plinth using 1 cement : 5 sand : 10 Aggregate mix
(B) Random rubble stone massonary for rivetment in 1:5 cement sand mortat including providing and fixing 100 mm dia PCC drain pipe and raised and cut pointing on stone masonary in 1:3 cement sand mortar excluding excavation but including Back filling inside rivetment using excavated/ borrowed earth (with all lead & lift) in layers not exceeding 20cm in depth & consolidating each depositing layer by ramming and watering.
(C) Random rubble dry stone pitching including preparing surface etc. complete with raised & cut pointing in cement sand mortar 1:3 curing etc.
(D)Cement concrete coping grade 1:2:4 (1 Cement:2 Coarse sand:4 Graded stone aggregate) rounding off edges etc. but excluding the cost of nosing of step etc. complete for 50mm thik with 20mm thik nominal size aggregate
Any Other Item
Description of Work / Item(s)
Amount
Service- ETC+ Civil
Auto Transformer:
220/132 kV, 160 MVA Auto Transformer with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 160 MVA 220/132 kV Auto Transformer as per S-I , (1) above
Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers at S-I (1) above
Bus Reactor:
220 kV, 25 MVAR Bus Reactor with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 220 kV, 25 MVAR Bus Reactor above
Power Transformer:
132/33 kV, 31.5 MVA Power Transformer with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 31.5 MVA 132/33 kV Power Transformer S-II (4) above
Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers S-II, (4) above
Circuit Breakers
220 kV Circuit Breakers
220kV circuit breakers (3 Ph.) Along with support Structure
132 kV Circuit Breakers
132 kV circuit breakers (3 Ph.) Along with support Structure
33 kV Circuit Breakers
33 kV circuit breakers (3 Ph.) Along with support Structure
Instrument Transformers
Capacitor Voltage Transformer
Single-Phase, 220 kV, 4400 pf CVT
Single Phase 132 kV , 4400 pf CVT
33 kV Potential Transformer
Current Transformer (1-Phase)
C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
New Substation
Control Panel for 220 kV Transformer (220 kV Side) Type: SAS-THCB
Relay Panel for 220 kV Transformer (for both HV & MV) Type: SAS-THRB
Control Panel for 220 kV Bus Reactor (220 kV Side) Type: SAS-RCB
Relay Panel for 220 kV Bus Reactor (for both HV & MV) Type: SAS-RRB
Control Panel for 220 kV Feeder Type: SAS-FCB
Relay Panel for 220 kV Feeder Type: SAS-FRB
Control Panel for 220 kV Bus Coupler Type: SAS-BCCB
Relay Panel for 220 kV Bus Coupler Type: SAS-BCRB
220 kV Busbar Protection Relay Panel Type: SAS-BBRB
Control Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLCB
Relay Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLRB
Control and Relay Panel for 1x 50/31.5/25 MVA, 132/33 kV Power Transformer Type SAS-TCRA
Control Panel for 132 kV Feeder Type SAS-FCA
Relay Panel for 132 kV Feeder Type SAS-FRA
Control and Relay Panel for 132 kV Bus-Coupler Type SAS-BCRA
Control and Protection Panel for 33 kV Feeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD
Station HMI [Industrial grade Computer with 21"TFT monitor as per specification requirements]
Station HMI (Hot Standby)[Industrial grade Computer with 21"TFT monitor as per specification requirements]
HMI View Node[Industrial grad Computer with 21"TFT monitor as per specification requirements]
A3 Size B&W Laser Printer
Substation Automation System Network Panel Type SAS-NW
Modems (both sending and Receiving End) for communication to RCC & Sub SLDC for PLCC]
Data Concentrator Unit (DCU) at Substation for RAS mounted in suitable enclosure & fully wired
Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.
Substation Auxiliary Monitoring Panel Type SAS-SAMP
Other Items:
Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
Surge Arresters
Substation LT Transformer
33/ 0.433 kV, 250 kVA LT transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil
Batteries & Battery Charger
Batteries (Sizing shall be as per requirement of technical specification)
220 V [Min. 600 AH]
48 V [Min. 600 AH]
Battery Charger System
220 V Float and Boost
50 V Float and Boost
Lighting System
Outdoor Lighting & other Works
Lighting Fixture Type FL-1
Lighting Fixture Type FL-2
Outdoor Receptacle
Type-RP
Type-RO
Substation Premises Lighting
Lighting poles
Type-L1
Type-D1
Street Lighting Type-SL-L1 for mounting on poles
Street Lighting Type-SL-D1 for mounting on Poles
Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast and Other Loaction as designated complete with all controgears and accessories, items etc.
Lighting Panel Type ACP-2 as per technical specification
Lighting Panel Type ACP-3 as per technical specification
Indoor Lighting & Other Works
Electrification
Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, Hall and administrative office building as per the requirements of the specifications
Illumiation
Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements)
Indoor Lignting Panels
Lighting Panel (Indoor) Type ACP-1 as per technical specification
Lighting Panel (Indoor) Type DCP as per technical specification
Wall mounted fans Approx. 400 mm sweep
Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator
Exhaust Fans
Fire Fighting System
Nitrogen Injection Fire Protection System for Auto Transformer (160 MVA ) complete in all respects.
Nitrogen Injection Fire Protection System for Power Transformer (31.5 MVA ) complete in all respects.
DCP Type
Carbon di oxide type – 6 Liters.
Foam Type- 9 Liters
Sand type
i) GI Buckets 9 liters capacity
ii) Steel Stands for four buckets
Air Conditioning System
Air Conditioning for the Rooms specified in the specifications
1.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
Power Cables(XLPE)
1Cx630 sq.mm
3.5Cx300 sq.mm
Power Cable(PVC)
1Cx150 sq.mm
3.5Cx70 sq.mm
3.5Cx35 sq.mm
4Cx16 sq.mm
4C x 6 Sq. mm
2C x 6 Sq. mm
Control Cable (PVC)
4 CX4 Sq. mm
3Cx2.5 sq.mm
5Cx2.5 sq.mm
7Cx2.5 sq.mm
10Cx2.5 sq.mm
14Cx2.5 sq.mm
19Cx2.5 sq.mm
Substation Structures
Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
Non-Standard type Pipe Support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe Support structure as per specification requirements]
Isolators
220 kV (3-Phase) (Horizontal DOUBLE BREAK)
1600A, 50KA, isolator with one E/S
Post insulators for above Isolator
1600A, 50KA, isolator with two E/S
Post insulators for above Isolator
1600A, 50KA, isolator without E/S
Post insulators for above Isolator
1600A, 50KA, isolator without E/S (TANDEM Type)
Post insulators for above Isolator
132 kV (3-Phase) (Horizontal DOUBLE BREAK)
1250A, isolator with one E/S
Post insulators for above Isolator
1250A isolator without E/S
Post insulators for above Isolator
33 kV (3-Phase) (Horizontal DOUBLE BREAK)
1250A, isolator without E/S
Post insulators for above Isolator
800 A isolator without E/S
Post insulators for above Isolator
800A isolator withE/S
Post insulators for above Isolator
Switchyard Erection
Busbar & Interconnections
New Substation/ Switchyard
220 kV Switchyard Works:
Main-I Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/Porcelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
Main-II Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Pocelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
Aux Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string(DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
220 kV Overhead Jack Bus (for DMT Layout) on Twin ACSR Zebra(Bus-Coupler Bay)/ Single ACSR Zebra (Transformer/ Line on ACSR Zebra) with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Twin ACSR Zebra
Single ACSR Zebra
Equipment Interconnections to Main Bus, Overhead Bus including Single ACSR Zebra (for Line), Twin ACSR Zebra (forTransformer bay & B/C Bay), bus-bar materials, clamps, connectors, spacers, corona shields, including equipment connectors, Junction box including of all accessories etc. for the following:
220 kV DMT-type layout
Line bay
Transformer bay
Reactor bay
Bus-Coupler
Bus CVT Interconnections to Main Buses including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
132 kV Switchyard Works:
Main Bus: 132 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulator, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
Aux Bus: 132 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay), Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Twin ACSR Zebra
Single ACSR Zebra
Single Panther
Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV Transformer Bay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
132 kV Main & Aux-type layout
Line bay
Transformer bay
Bus-Coupler
Bus CVT Interconnections to Main Bus including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
33 kV Switchyard Works:
Main Bus: 33 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]
Aux Bus: 33 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]]
33 kV Overhead Jack Bus for Transformer Incomer (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
33 kV Main & Aux-type layout
Line bay
Transformer bay
Bus-Coupler
LT Transformer connection with ACSR Panther conductor, 33 kV DO Fuse Set alongwith required Clamp/connectors
Bus PT Interconnections to Main Bus including Single ACSR Panther , clamps, connectors, junction box including of all accessories etc.
Bus Post Insulators (BPI)
Earthing & Lightning Protection System
Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
40 mm Dia MS Rod
40mm Dia, 3.2 M Long MS Rod Earth Electrodes Directly Driven.
40mm Dia, 8 M Long MS Rod Earth Electrodes Directly Driven.
40mm Dia, 3.2M Long MS Rod Earth Electrode in untreated pit with test link
40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works
75X12 mm GS Flat
50X6 mm GS Flat
Earth Enhancing Compound for treated pits as above and other requirement as per specification
Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
Earth Wire for Shielding Protection of Switchyard
7/3.15 Galvenized Steel Wire
Earthwire tension clamps with D Shackle assembly
PG calmp to suit 7/3.15 mm GS earth wire
Cleat clamp on structure to suit 7/3.15 mm GS earth wire/ 50 X 12 mm GS Flat
Pad clamp on structure to suit 7/3.15 mm earth wire and 75 x 12 GS flat
Lug to suit 7/3.15 mm earth wire
Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
Bay Marshalling KIOSK
200 way (Stud Type Connectors)
AC Distribution Boxes (Outdoor Type)
Outdoor AC Distbibution Box (Double Front type)
Outdoor AC Distbibution Box (Single Front type)
Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
LT Switchgear
LT AC Main Panel
LT AC Distribution Board
Main Lighting Distribution Board
Emergency Lighting Distribution Board
220V DCDB
48V DCDB
PLCC EQUIPMENTS
220 kV Wave trap (2000A, 0.5 mH, 40 kA)
132 kV wave trap (1250A, 0.5 mH, 40 kA)
SSB single Channel Carrier Set (40 W) suitable for transmitting Data and super imposed channels along with Remote subscriber facility and emergency calling set.
A.F. Protection coupler microprocessor based suitable for Four commands.
Coupling Devices for Phase to Phase coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
HF Armoured Coaxial cable having 75 Ohms unbalanced impendance.
Microprocessor based 32/16 line Electronic Private Automatic Exchange (EPAX) with PLCC interphasing facility
Telephone Sets (Push Button Type)
20 pair Jelly Filled and armoured telephone cable with copper conductor of 0.63 mm
5 Pair jelly filled armoured telephone cable having copper conductor of Dia. 0.5 mm
5 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm
CIVIL WORKS
TOWER/ EQUIPMENT FOUNDATIONS :
LATTICE / PIPE STRUCTURE
Marshalling Kiosk
Isolator handle mechanism
220 kV Equipment Structure
220 kVISO (3-Phase)
220 kVISO (3-Phase) - Tandem
220 kV BPI
220 kV CVT
132 kV Equipment Structure
132 kVISO (3-Phase)
132 kV BPI
132 kV CVT
33 kV Equipment Structure
33 kVISO (3-Phase)
33 kV BPI
FOUNDATION FOR 160 MVA, 220/132 kV TRANSFORMER:-
Civil works for MS Tank including Excavation, Laying of 75 mm PCC, Constructing brick wall jacket around the tank, laying of 200 mm RCC raft, leveling and alignment of MS Tank, backfilling with excavated sand, Top leveling by laying of PCC, as per site requirement and Technical specifications (complete job).As per specification for 160 MVA, 220/132 kV Transformer
FOUNDATION FOR 25 MVAR, 220 kV BUS REACTOR:-
Civil works for MS Tank including Excavation, Laying of 75 mm PCC, Constructing brick wall jacket around the tank, laying of 200 mm RCC raft, leveling and alignment of MS Tank, backfilling with excavated sand, Top leveling by laying of PCC, as per site requirement and Technical specifications (complete job).As per specification for 25 MVAR, 220 kV BUS REACTOR
FOUNDATION FOR 31.5 MVA, 132/33 kV TRANSFORMER:-
Civil works for MS Tank including Excavation, Laying of 75 mm PCC, Constructing brick wall jacket around the tank, laying of 200 mm RCC raft, leveling and alignment of MS Tank, backfilling with excavated sand, Top leveling by laying of PCC, as per site requirement and Technical specifications (complete job).As per specification for 31.5 MVA, 132/33 kV Transformer
FOUNDATION FOR 33/0.415 kV, 250 kVA, LT three phase station transformer
CABLE TRENCH
Type A Cable trench
Type C Cable trench
Construction of RCC sump having capacity 10000 Liters with provision of automatic dewatering mud pump with disposal arrangement upto outside RVPN premises as directed by Engineeer In-charge with provision of a stand by pump.
CABLE TRENCH CROSSING
Road crossing for 'A' type cable trenches
Road crossing for 'C' type cable trenches
Grading of yard including all cutting and filling:-
Supply and stacking earth material obtained from borrow pits with all leads and lifts, transporting to site, spreading, grading to required slope & compacting by vibratory roller 8-10 Ton to meet requirement of table 300-2 including cost of compensation for earth taken from private land with all lead as per MORTH specification clause no. 305.
Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas including filling available excavated earth (excluding rock) in trenches, plinth side of foundation etc. in layers not exceeding 20 cm. in depth, consolidating each deposited layer by ramming and watering including with all lead and lift. All kinds of soil.
Construction of retaining wall at level difference with stone /brick masonry/RCC-M20 walls of required section including all finishings required as per direction of Engineer-in charge
ANTI WEED TREATMENT AND BASE LAYER OF INTERLOCKING TILES
Providing and fixing of precast concrete interlocking blocks of M 30 grade 60mm thick manufactured from fully computerised automatic stationery hydraullic vibropressed machine and fully computerised automatic batching plant of class A1/A2 as per BS 6717:2001. The CC interlocking paving blocks be laid on average 50mm. thick bed of coarse sand and the joint is to be filled with fine sand. Laying procedure on compacted sub-base as defined. Complete job is to be executed as per the instruction of Engineer incharge. The rates to be inclusive of all lead, Lifts and taxes. General specification of blocks: 1) Shape as defined by Engineer incharge 2) Tensile splitting strength and braking load as per BS 6717:2001 3) Color: Grey cement natural colour 4) Variation in dimension: Less than 1.6mm. 5) Variation in thickness: Less than 3.2mm 6) Abrasion: As per BS: 6717:2001
JELLY SPREADING (Gravelling)
Providing and laying 100mm thick layer of granite/basalt/trap jelly(gravel) of 40mm single size shall be spread over the entire switchyard area as per drawing and directions of engineer incharge of the work. The whole switchyard area (excluding buildings pathway road, drainages, cable trenches, equipments/ structures/ plinths etc.) shall be covered with jelly spreading. The jelly used shall be free from dirt, organic materials and flakes.
Supply & Fixing Barricades to confine Jelly (gravel), which include Supply and fixing cement concrete solid blocks of size 60x(20+25)/2x30 cms (l, b, h) jointed with CM 1:4, made from precast M-20 concrete and laid over 100 mm thick base of PCC 1:4:8 including necessary curing etc. complete. The top of concrete block shall be 100 mm above gravel top with provision of suitable openings for drainage of rain water. The exposed surface of barricades shall be applied with two coat of water proof cement paint.
ROAD WORK
Construction of unreinforced, dowel jointed plain cement cocrete pavement in 150 mm thickness over and including sub-base of 150 mm thick quarry rubbish and 100 thick PCC 1:4:8 with M 30 grade cement concrete laid in approved side form work(steel channels , laying and fixing 125 micron thick polythene film wedged, steel plates including leveling the form work as per drawing, spreading using shovels, rakes, compacted using needdle, plate and screed vibrator finished in continuous operation including provision of expansion and contraction and construction joints, applying debonding strips, primer, sealant, dowel bars at expansion & construction joints only, curing etc complete including dewatering process with all equipments. work also includes providing and fixing precast cement concrete solid blocks on outer edges of both sides shoulder of size 60x(20+25)/2x30 cms (l, b, h) jointed with CM 1:4, made from precast M-20 concrete and laid over 100 mm thick base of PCC 1:4:8 including necessary curing etc. complete. The concrete block top shall be 100 mm above road top, with provision of suitable openings for drainage of rain water. The exposed surface of concrete blocks shall be applied with two coat of enamel paint, painted black and yellow alternately, and Providing and laying 80 mm thick M 30 interlocking tiles Category A Denated units to key into each other on four faces zig zag shape over 100 mm PCC 1:4:8, complete as per IRC SP 63:2004 specification on shoulders as per approved drawing, specification and direction of engineer incharge(payment shall be made as per actual length).
4.0 Mtr. Wide Road with shoulders of 0.60 m on both side of CC road
3.0 Mtr. Wide Road. with shoulders of 0.60 m on both side of CC road
CONTROL ROOM BUILDING
Construction of control room building as per drawing and specification including internal electricafication with Energy Efficient Lights , Tube light fixtures etc, 15 lit storage geyser, earthing, sanitary system including septic tanks, soakage pits and rain water harvesting system as per drawing approved by owner/GWD etc., water supply system including making connection with distribution system, false ceiling (In Hall, PLCC room and XEN chamber), fans,, internal cable trenches covered with 6 mm thick MS chequred plates, plinth protection works with chequred tiles etc (plinth area approximately 600 sqm, with out roof projections, plinth protection and porch)
WATER SUPPLY :-Supply and installation of water supply system with construction of GLR, submersible cables, pump room with pump and one stand- by pump for the sub-station, required electrifcation cables from control room and panels, providing and laying GI pipe line from GLR to control room, yard, guard room,store, for plantation etc including making connection , landscaping,construction and development of park as per the drawing & plantation as per specification & approved drawings and directions of engineer incharge.
Construction of Tube-well from ground levels and upto required depth & dia (as per hydrogelogist report) to accommodate housing and assembly pipe of required sizes in all types of alluvium /rocky strata by percussion/ rotary drilling method and with gravel as per IS:4097-1967 and packing as per IS:2800 (part I & II) 1979 as amended upto date (the work includes the cost of gravel & its primary packing and packing during developement, lowering of housing & strainer assembly pipes, with supply & wrapping of coir-rope, whenever necessary, for arresting fine sand particles, including cost of housing pipe and strainer pipe assembly and developement work. Work would be completed after obtaing sand free water) work also includes supplying and installation of submersible pumping motor pump sets I.S.I. marked (IS:8034-1989) and one stand- by pump of approved make like K.S.B., Kirloskar, calama etc. or equivalent, making connection suitable for T.W. The job includes supplying and welding of flanges on G.I. riser pipes, pipe line of required dia up to GLR, required cables from control room to panel and subersible pump, installation of complete fitting & accessories, with riser pipes, jointing of electrical cables and other connections making switch board electrical connections, panels etc as per design and specification, all labour for testing of submersible pump set and supply of water to water mains, complete in all respect as directed by engineer incharge. Note:- Tubewell shall be constructed as per feasibility report received from hydrogeologist.
Providing, Laying & Jointing R.C.C. class NP-2 Non-Pressure pipes (IS : 458 mark) of approved make with collars, jointed with C.M. 1:2 or having Spigot and socket ends with flexible rubber rings joints including testing of joints etc. complete for 300 mm dia internal dia pipe including Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40mm nominal size) upto haunches of S.W. pipes including bed concrete as per standard design and Excavating trenches of required width for pipes cables etc. including excavation for sockets, depth up to required depth including taking out the excavated materials, refilling the soil as required in layers not exceeding 20 cm in depth including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, with all lead and lifts in all types of soil, rocks etc complete in all respect.
RAIN WATER HARVESTING: Designing and providing storm water drainage along with Rainwater harvesting by providing two numbers recharge structures with bore wells as per technical specifications.
Add: Any other item bidder may require to complete the Civil works as per specification requirements
Description of Work / Item(s)
Amount
Tower: Fabrication, galvanising and supply of various types of towers (including special towers), & its body / leg (equal & unequal) extensions (complete) including stubs and hangers, D-shackles, Bird Guard, U-Bolt, Pack washer, Anticlimbing devices etc.
High Tensile Steel
Mild Steel
Supply of Bolts & Nuts for towers and stubs (including step bolts & nuts and anti theft bolts & nuts, Spring Washers Etc. )
Supply of Earthing material of Towers
Pipe Type
Counter Poise Type
Supply of following Tower Accessories
Danger Plate
Number Plate
Phase Plate (Set of three)
Design, manufacture and supply of following line material. **
Porcelein Long Rod Insulators 70 kN
Porcelein Long Rod Insulators 120 kN
ACSR Zebra Conductor (54/3.18MM AL+7/3.18MM Steel)
Hardware Fittings for ACSR Zebra Conductor
Single Suspension H/W fittings for ACSR Zebra Conductor
Single Tension H/W fittings for ACSR Zebra Conductor
Double Suspension H/W fittings for ACSR Zebra Conductor
Double Tension H/W fittings for ACSR Zebra Conductor
Accessories for ACSR Zebra Conductor
Mid Span Compression Joint for ACSR Zebra Conductor
Repair Sleeve for ACSR Zebra Conductor
Preformed Armour Rod for ACSR Zebra Conductor
Vibration Damper for ACSR Zebra Conductor
OPGW Cable
48 Fibre (DWSM) OPGW fibre optic cable
Installation Hardware set for 48 Fibre OPGW Fibre Optic cabling including all cable fittings & accessories except joint box
Joint box (48Fibre)
FODP 96F Indoor Type rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
48 Fibre (DWSM)
Installation Hardware set for 48 Fibre OPGW Fibre Optic approach cable
BIRD FLIGHT DIVERTER
NON-LED TYPE BIRD FLIGHT DIVERTER(BFD)
LED TYPE BIRD FLIGHT DIVERTER(BFD)
Accessories for7/4 mm Earth Wire
Any Other item required for successful completion of work
Description of Work / Item(s)
Amount
Detail Survey as per tentative route- Which includes the following major activities-Pegging of line route, providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of line, marking of side clearance for hills, sand dunes etc, as per specification and tower scheduling.
Check survey as per approved route of line which includes- Re-checking of the line route as per approved profile, chainage, tower center marking, pit marking, bisection of angle tower as required at site.
Excavation-Excavation, excluding back filling, including shoring,shuttering, dewatering, etc. upto the required depth as per foundation specification/drawings.
(i) Any soil, soft rock other than hard rock
SETTING OF TEMPLATE & STUB/ANCHOR BOLT:- Setting of template & stub/ anchor bolt & removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead & lift) in layers with ramming andwatering as per specification.
(i) Tower including extension upto 9 Meter
CONCRETING: Providing and laying cement concrete for all types of foundation as per latest ISS:456 including cement, sand, stone aggregate 20mm nominal size,water etc., preparing surfaces, shuttering, mixing, placing, ramming, curing, finishing as per specification and drawings.
(i) 1:3:6 Mix (M-10)
(iii) 1:1.5:3 Mix (M-20)
STEEL REINFORCEMENT: Cutting, bending, welding of joints if required,fixing and placing of steel reinforcement as per specification and drawings including material.
EARTHING:
(A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats &connectors, but including coke/charcoal, etc.,excavation,augering and backfilling in all types of soil.
(B) Earthing of towers legs with counterpoise typeearthings excluding supply of materialsbut including excavation and backfilling in all types of soil. (i)each set by laying 4 wires each 15m long at a depth of 600mm
ERECTION OF TOWERS: Erection of super structures including D-shackles,ACD, Hangers, U-Bolts, step bolts, danger plate, phase plate, number plate etc. Also including tack welding of bolts & nuts upto bottom cross arm/beam level including application of Zinc Rich paint
Erection of tower (with extension upto 9 Meters)
CONDUCTOR STRINGING: Stringing of ACSR Zebra including hoisting of insulator string, laying, jointing & tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line.
(i) Single Conductor
OPGW cable & Accessories
48 Fibre (DWSM) OPGW fibre optic cable
Installation Hardware set for 48 Fibre OPGW Fibre Optic cabling including all cable fittings & accessories except joint box
Joint box (48Fibre)
Revitment work
(A) Providing & laying cement concrete including curing compaction etc. complete using stone aggregate 40 mm nominal size (Crusher broken) in foundation plinth using 1 cement : 5 sand : 10 Aggregate mix
(B) Random rubble stone massonary for rivetment in 1:5 cement sand mortat including providing and fixing 100 mm dia PCC drain pipe and raised and cut pointing on stone masonary in 1:3 cement sand mortar excluding excavation but including Back filling inside rivetment using excavated/ borrowed earth (with all lead & lift) in layers not exceeding 20cm in depth & consolidating each depositing layer by ramming and watering.
(D)Cement concrete coping grade 1:2:4 (1 Cement:2 Coarse sand:4 Graded stone aggregate) rounding off edges etc. but excluding the cost of nosing of step etc. complete for 50mm thik with 20mm thik nominal size aggregate
FODP 96F Indoor Type rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
48 Fibre (DWSM)
Installation Hardware set for 48 Fibre OPGW Fibre Optic approach cable
Installation of Bird Flight Diverter (BFD) (Falling under GIB arc area)
Installation of Non - LED Type Bird Flight Diverter
Installation of LED Type Bird Flight Diverter
Any Other Item
Description of Work / Item(s)
Amount
Tower: Fabrication, galvanising and supply of various types of towers (including special towers), & its body / leg (equal & unequal) extensions (complete) including stubs and hangers, D-shackles, Bird Guard, U-Bolt, Pack washer, Anticlimbing devices etc.
High Tensile Steel
Mild Steel
Supply of Bolts & Nuts for towers and stubs (including step bolts & nuts and anti theft bolts & nuts, Spring Washers Etc. )
Supply of Earthing material of Towers
Pipe Type
Counter Poise Type
Supply of following Tower Accessories
Danger Plate
Number Plate
Phase Plate (Set of three)
Design, manufacture and supply of following line material. **
Porcelein Long Rod Insulators 70 kN
Porcelein Long Rod Insulators 120 kN
ACSR Zebra Conductor (54/3.18MM AL+7/3.18MM Steel)
Hardware Fittings for ACSR Zebra Conductor
Single Suspension H/W fittings for ACSR Zebra Conductor
Single Tension H/W fittings for ACSR Zebra Conductor
Double Suspension H/W fittings for ACSR Zebra Conductor
Double Tension H/W fittings for ACSR Zebra Conductor
Accessories for ACSR Zebra Conductor
Mid Span Compression Joint for ACSR Zebra Conductor
Repair Sleeve for ACSR Zebra Conductor
Preformed Armour Rod for ACSR Zebra Conductor
Vibration Damper for ACSR Zebra Conductor
OPGW Cable
48 Fibre (DWSM) OPGW fibre optic cable
Installation Hardware set for 48 Fibre OPGW Fibre Optic cabling including all cable fittings & accessories except joint box
Joint box (48Fibre)
FODP 96F Indoor Type rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
48 Fibre (DWSM)
Installation Hardware set for 48 Fibre OPGW Fibre Optic approach cable
BIRD FLIGHT DIVERTER
NON-LED TYPE BIRD FLIGHT DIVERTER(BFD)
LED TYPE BIRD FLIGHT DIVERTER(BFD)
Accessories for7/4 mm Earth Wire
Any Other item required for successful completion of work
Description of Work / Item(s)
Amount
Detail Survey as per tentative route- Which includes the following major activities-Pegging of line route, providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of line, marking of side clearance for hills, sand dunes etc, as per specification and tower scheduling.
Check survey as per approved route of line which includes- Re-checking of the line route as per approved profile, chainage, tower center marking, pit marking, bisection of angle tower as required at site.
Excavation-Excavation, excluding back filling, including shoring,shuttering, dewatering, etc. upto the required depth as per foundation specification/drawings.
(i) Any soil, soft rock other than hard rock
SETTING OF TEMPLATE & STUB/ANCHOR BOLT:- Setting of template & stub/ anchor bolt & removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead & lift) in layers with ramming andwatering as per specification.
(i) Tower including extension upto 9 Meter
CONCRETING: Providing and laying cement concrete for all types of foundation as per latest ISS:456 including cement, sand, stone aggregate 20mm nominal size,water etc., preparing surfaces, shuttering, mixing, placing, ramming, curing, finishing as per specification and drawings.
(i) 1:3:6 Mix (M-10)
(iii) 1:1.5:3 Mix (M-20)
STEEL REINFORCEMENT: Cutting, bending, welding of joints if required,fixing and placing of steel reinforcement as per specification and drawings including material.
EARTHING:
(A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats &connectors, but including coke/charcoal, etc.,excavation,augering and backfilling in all types of soil.
(B) Earthing of towers legs with counterpoise typeearthings excluding supply of materialsbut including excavation and backfilling in all types of soil. (i)each set by laying 4 wires each 15m long at a depth of 600mm
ERECTION OF TOWERS: Erection of super structures including D-shackles,ACD, Hangers, U-Bolts, step bolts, danger plate, phase plate, number plate etc. Also including tack welding of bolts & nuts upto bottom cross arm/beam level including application of Zinc Rich paint
Erection of tower (with extension upto 9 Meters)
CONDUCTOR STRINGING: Stringing of ACSR Zebra including hoisting of insulator string, laying, jointing & tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line.
(i) Single Conductor
OPGW cable & Accessories
48 Fibre (DWSM) OPGW fibre optic cable
Installation Hardware set for 48 Fibre OPGW Fibre Optic cabling including all cable fittings & accessories except joint box
Joint box (48Fibre)
Revitment work
(A) Providing & laying cement concrete including curing compaction etc. complete using stone aggregate 40 mm nominal size (Crusher broken) in foundation plinth using 1 cement : 5 sand : 10 Aggregate mix
(B) Random rubble stone massonary for rivetment in 1:5 cement sand mortat including providing and fixing 100 mm dia PCC drain pipe and raised and cut pointing on stone masonary in 1:3 cement sand mortar excluding excavation but including Back filling inside rivetment using excavated/ borrowed earth (with all lead & lift) in layers not exceeding 20cm in depth & consolidating each depositing layer by ramming and watering.
(D)Cement concrete coping grade 1:2:4 (1 Cement:2 Coarse sand:4 Graded stone aggregate) rounding off edges etc. but excluding the cost of nosing of step etc. complete for 50mm thik with 20mm thik nominal size aggregate
FODP 96F Indoor Type rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
48 Fibre (DWSM)
Installation Hardware set for 48 Fibre OPGW Fibre Optic approach cable
Installation of Bird Flight Diverter (BFD) (Falling under GIB arc area)
Installation of Non - LED Type Bird Flight Diverter
Installation of LED Type Bird Flight Diverter
Any Other Item
Description of Work / Item(s)
Amount
Tower: Fabrication, galvanising and supply of various types of towers (including special towers), & its body / leg (equal & unequal) extensions (complete) including stubs and hangers, D-shackles, Bird Guard, U-Bolt, Pack washer, Anticlimbing devices etc.
High Tensile Steel
Mild Steel
Supply of Bolts & Nuts for towers and stubs (including step bolts & nuts and anti theft bolts & nuts, Spring Washers Etc. )
Supply of Earthing material of Towers
Pipe Type
CounterPoise
Supply of following Tower Accessories
Danger Plate
Number Plate
Phase Plate (Set of three)
Design, manufacture and supply of following line material. **
Disc Insulator - 70 kN
Disc Insulator - 120 kN
ACSR Panther Conductor
Hardware Fittings for ACSR Panther Conductor
Single Suspension H/W fittings for ACSR Panther Conductor
Single Tension H/W fittings for ACSR Panther Conductor
Double Suspension H/W fittings for ACSR Panther Conductor
Double Tension H/W fittings for ACSR Panther Conductor
Accessories for ACSR Panther Conductor
Mid Span Compression Joint for ACSR Panther Conductor
Repair Sleeve for ACSR Panther Conductor
Preformed Armour Rod for ACSR Panther Conductor
Vibration Damper for ACSR Panther Conductor
Accessories for7/4 mm Earth Wire
BIRD FLIGHT DIVERTER
NON-LED TYPE BIRD FLIGHT DIVERTER(BFD)
LED TYPE BIRD FLIGHT DIVERTER(BFD)
FODP 96F Indoor Type rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
48 Fibre (DWSM)
Installation Hardware set for 48 Fibre OPGW Fibre Optic approach cable
OPGW Cable
48 Fibre (DWSM) OPGW fibre optic cable
Installation Hardware set for 48 Fibre OPGW Fibre Optic cabling including all cable fittings & accessories except joint box
Joint box (48Fibre)
Any Other item required for successful completion of work
Description of Work / Item(s)
Amount
Detail Survey as per tentative route- Which includes the following major activities-Pegging of line route, providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of line, marking of side clearance for hills, sand dunes etc, as per specification and tower scheduling.
Check survey as per approved route of line which includes- Re-checking of the line route as per approved profile, chainage, tower center marking, pit marking, bisection of angle tower as required at site.
Excavation-Excavation, excluding back filling, including shoring,shuttering, dewatering, etc. upto the required depth as per foundation specification/drawings.
(i) Any soil, soft rock other than hard rock
SETTING OF TEMPLATE & STUB/ANCHOR BOLT:- Setting of template & stub/ anchor bolt & removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead & lift) in layers with ramming andwatering as per specification.
(i) Tower including extension upto 9 Meter
CONCRETING: Providing and laying cement concrete for all types of foundation as per latest ISS:456 including cement, sand, stone aggregate 20mm nominal size,water etc., preparing surfaces, shuttering, mixing, placing, ramming, curing, finishing as per specification and drawings.
(i) 1:3:6 Mix (M-10)
(iii) 1:1.5:3 Mix (M-20)
STEEL REINFORCEMENT: Cutting, bending, welding of joints if required,fixing and placing of steel reinforcement as per specification and drawings including material.
EARTHING:
(A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats &connectors, but including coke/charcoal, etc.,excavation,augering and backfilling in all types of soil.
ERECTION OF TOWERS: Erection of super structures including D-shackles,ACD, Hangers, U-Bolts, step bolts, danger plate, phase plate, number plate etc. Also including tack welding of bolts & nuts upto bottom cross arm/beam level including application of Zinc Rich paint
Erection of tower (with extension upto 9 Meters)
CONDUCTOR STRINGING: Stringing of ACSR Panther including hoisting of insulator string, laying, jointing & tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line.
(i) Single Conductor
OPGW cable & Accessories
48 Fibre (DWSM) OPGW fibre optic cable
Installation Hardware set for 48 Fibre OPGW Fibre Optic cabling including all cable fittings & accessories except joint box
Joint box (48Fibre)
Revitment work
(A) Providing & laying cement concrete including curing compaction etc. complete using stone aggregate 40 mm nominal size (Crusher broken) in foundation plinth using 1 cement : 5 sand : 10 Aggregate mix
(B) Random rubble stone massonary for rivetment in 1:5 cement sand mortat including providing and fixing 100 mm dia PCC drain pipe and raised and cut pointing on stone masonary in 1:3 cement sand mortar excluding excavation but including Back filling inside rivetment using excavated/ borrowed earth (with all lead & lift) in layers not exceeding 20cm in depth & consolidating each depositing layer by ramming and watering.
(D)Cement concrete coping grade 1:2:4 (1 Cement:2 Coarse sand:4 Graded stone aggregate) rounding off edges etc. but excluding the cost of nosing of step etc. complete for 50mm thik with 20mm thik nominal size aggregate
(E) Brick Masonary in founadtion & plinth with bricks of class designation 75 in cement mortar 1 : 5 (1 cement : 5 Coarse sand)
(F) Brick on edge flooring with bricks of class designation 75designation 75 including pointing in cement mortar (1:3) complete laid on 12mmthick bed of cement sand mortar 1:6.
FODP 96F Indoor Type rack mounted with FCPC coupling and pigtails
Fiber Optic Approach Cable
48 Fibre (DWSM)
Installation Hardware set for 48 Fibre OPGW Fibre Optic approach cable
Installation of Bird Flight Diverter (BFD) (Falling under GIB arc area)
Installation of Non - LED Type Bird Flight Diverter
Installation of LED Type Bird Flight Diverter
Any Other Item
Description of Work / Item(s)
Amount
MAIN MATERIAL/ ITEMS
Auto Transformer:
220/132/11 kV, 160 MVA Auto Transformer with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 160 MVA 220/132/11 kV Auto Transformer as per S-I , (1) above
Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers at S-I (1) above
Bus reactor
220 kV, 25 MVAr Bus reactor with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 220 kV, 25 MVAr Bus reactor above
Power Transformer:
132/33 kV, 31.5 MVA Power Transformer with all accessories (excluding transformer Oil) as per technical specification
Insulating Oil for 31.5 MVA 132/33 kV Power Transformer S-II (4) above
Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers S-II, (4) above
Circuit Breakers
220 kV Circuit Breakers
220kV circuit breakers (3 Ph.) Along with support Structure
132 kV Circuit Breakers
132 kV circuit breakers (3 Ph.) Along with support Structure
33 kV Circuit Breakers
33 kV circuit breakers (3 Ph.) Along with support Structure
Instrument Transformers
Capacitor Voltage Transformer
Single-Phase, 220 kV, 4400 pf CVT
Single Phase 132 kV , 4400 pf CVT
33 kV Potential Transformer
Current Transformer (1-Phase)
1000/1 A, 5C (Live Tank Type only)
1000/1 A, 3C (Live Tank Type only)
500/1 A, 3C (Live Tank Type only)
C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
New Substation
Control Panel for 220 kV Transformer (220 kV Side) Type: SAS-THCB
Relay Panel for 220 kV Transformer (for both HV & MV) Type: SAS-THRB
Control Panel for 220 kV Bus Reactor (220 kV Side) Type: SAS-RCB
Relay Panel for 220 kV Bus reactor (for both HV & MV) Type: SAS-RRB
Control Panel for 220 kV Feeder Type: SAS-FCB
Relay Panel for 220 kV Feeder Type: SAS-FRB
Control Panel for 220 kV Bus Coupler Type: SAS-BCCB
Relay Panel for 220 kV Bus Coupler Type: SAS-BCRB
220 kV Busbar Protection Relay Panel Type: SAS-BBRB
Control Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLCB
Relay Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLRB
Control and Relay Panel for 1x 50/31.5/25 MVA, 132/33 kV Power Transformer Type SAS-TCRA
Control Panel for 132 kV Feeder Type SAS-FCA
Relay Panel for 132 kV Feeder Type SAS-FRA
Control and Relay Panel for 132 kV Bus-Coupler Type SAS-BCRA
Control and Protection Panel for 33 kV Feeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD
Station HMI [Industrial grade Computer with 21"TFT monitor as per specification requirements]
Station HMI (Hot Standby)[Industrial grade Computer with 21"TFT monitor as per specification requirements]
HMI View Node[Industrial grad Computer with 21"TFT monitor as per specification requirements]
A3 Size B&W Laser Printer
Substation Automation System Network Panel Type SAS-NW
Modems (both sending and Receiving End) for communication to RCC & Sub SLDC for PLCC]
Data Concentrator Unit (DCU) at Substation for RAS mounted in suitable enclosure & fully wired
Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.
Substation Auxiliary Monitoring Panel Type SAS-SAMP
Other Items:
Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
Surge Arresters
Substation LT Transformer
33/ 0.433 kV, 250 kVA LT transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil
Batteries & Battery Charger
Batteries (Sizing shall be as per requirement of technical specification)
220 V [Min. 600 AH]
48 V [Min. 600 AH]
Battery Charger System
220 V Float and Boost
50 V Float and Boost
Lighting System
Outdoor Lighting & other Works
Lighting Fixture Type FL-1
Lighting Fixture Type FL-2
Outdoor Receptacle
Type-RP
Type-RO
Substation Premises Lighting
Lighting poles
Type-L1
Type-D1
Street Lighting Type-SL-L1 for mounting on poles
Street Lighting Type-SL-D1 for mounting on Poles
Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast and Other Loaction as designated complete with all controgears and accessories, items etc.
Lighting Panel Type ACP-2 as per technical specification
Lighting Panel Type ACP-3 as per technical specification
Indoor Lighting & Other Works
Electrification
Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, Hall and administrative office building as per the requirements of the specifications
Illumiation
Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements)
Indoor Lignting Panels
Lighting Panel (Indoor) Type ACP-1 as per technical specification
Lighting Panel (Indoor) Type DCP as per technical specification
Wall mounted fans Approx. 400 mm sweep
Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator
Exhaust Fans
Fire Fighting System
Nitrogen Injection Fire Protection System for Auto Transformer (160 MVA ) complete in all respects.
Nitrogen Injection Fire Protection System for 220 kV 25 MVAR Bus reactor (25MVAr ) complete in all respects.
Nitrogen Injection Fire Protection System for Power Transformer (31.5 MVA ) complete in all respects.
DCP Type
Carbon di oxide type – 6 Liters.
Foam Type- 9 Liters
Sand type
i) GI Buckets 9 liters capacity
ii) Steel Stands for four buckets
Air Conditioning System
Air Conditioning for the Rooms specified in the specifications
1.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
Power Cables(XLPE)
3.5Cx300 sq.mm
Power Cable(PVC)
1Cx150 sq.mm
3.5Cx70 sq.mm
3.5Cx35 sq.mm
4Cx16 sq.mm
4C x 6 Sq. mm
2C x 6 Sq. mm
Control Cable (PVC)
4 CX4 Sq. mm
3Cx2.5 sq.mm
4Cx2.5 sq.mm
14Cx2.5 sq.mm
19Cx2.5 sq.mm
Substation Structures
Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
Non-Standard type Pipe Support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe Support structure as per specification requirements]
Isolators
220 kV (3-Phase) (Horizontal DOUBLE BREAK)
1600A, 50KA, isolator with one E/S
Post insulators for above Isolator
1600A, 50KA, isolator with two E/S
Post insulators for above Isolator
1600A, 50KA, isolator without E/S
Post insulators for above Isolator
1600A, 50KA, isolator without E/S (TANDEM Type)
Post insulators for above Isolator
132 kV (3-Phase) (Horizontal DOUBLE BREAK)
1250A, isolator with one E/S
Post insulators for above Isolator
1250A isolator without E/S
Post insulators for above Isolator
33 kV (3-Phase) (Horizontal DOUBLE BREAK)
1250A, isolator without E/S
Post insulators for above Isolator
800 A isolator without E/S
Post insulators for above Isolator
800A isolator withE/S
Post insulators for above Isolator
Switchyard Erection
Busbar & Interconnections
New Substation/ Switchyard
220 kV Switchyard Works:
Main-I Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/Porcelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
Main-II Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Pocelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
Aux Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string(DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
220 kV Overhead Jack Bus (for DMT Layout) on Twin ACSR Zebra(Bus-Coupler Bay)/ Single ACSR Zebra (Transformer/ Line on ACSR Zebra) with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Twin ACSR Zebra
Single ACSR Zebra
Equipment Interconnections to Main Bus, Overhead Bus including Single ACSR Zebra (for Line), Twin ACSR Zebra (forTransformer bay & B/C Bay), bus-bar materials, clamps, connectors, spacers, corona shields, including equipment connectors, Junction box including of all accessories etc. for the following:
220 kV DMT-type layout
Line bay
Transformer bay /Reactor Bay
Bus-Coupler
Bus CVT Interconnections to Main Buses including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
132 kV Switchyard Works:
Main Bus: 132 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulator, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
Aux Bus: 132 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay), Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Twin ACSR Zebra
Single ACSR Zebra
Single Panther
Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV Transformer Bay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
132 kV Main & Aux-type layout
Line bay
Transformer bay
Bus-Coupler
Bus Sectionalizer
Bus CVT Interconnections to Main Bus including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
33 kV Switchyard Works:
Main Bus: 33 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]
Aux Bus: 33 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]]
33 kV Overhead Jack Bus for Transformer Incomer (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
33 kV Main & Aux-type layout
Line bay
Transformer bay
Bus-Coupler
LT Transformer connection with ACSR Panther conductor, 33 kV DO Fuse Set alongwith required Clamp/connectors
Bus PT Interconnections to Main Bus including Single ACSR Panther , clamps, connectors, junction box including of all accessories etc.
Bus Post Insulators (BPI)
Earthing & Lightning Protection System
Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
40 mm Dia MS Rod
40mm Dia, 3.2 M Long MS Rod Earth Electrodes Directly Driven.
40mm Dia, 8 M Long MS Rod Earth Electrodes Directly Driven.
40mm Dia, 3.2M Long MS Rod Earth Electrode in untreated pit with test link
40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works
75X12 mm GS Flat
50X6 mm GS Flat
Earth Enhancing Compound for treated pits as above and other requirement as per specification
Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
Earth Wire for Shielding Protection of Switchyard
7/3.15 Galvenized Steel Wire
Earthwire tension clamps with D Shackle assembly
PG calmp to suit 7/3.15 mm GS earth wire
Cleat clamp on structure to suit 7/3.15 mm GS earth wire/ 50 X 12 mm GS Flat
Pad clamp on structure to suit 7/3.15 mm earth wire and 75 x 12 GS flat
Lug to suit 7/3.15 mm earth wire
Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
Bay Marshalling KIOSK
200 way (Stud Type Connectors)
AC Distribution Boxes (Outdoor Type)
Outdoor AC Distbibution Box (Double Front type)
Outdoor AC Distbibution Box (Single Front type)
Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
LT Switchgear
LT AC Main Panel
LT AC Distribution Board
Main Lighting Distribution Board
Emergency Lighting Distribution Board
220V DCDB
48V DCDB
PLCC EQUIPMENTS
220 kV Wave trap (2000A, 0.5 mH, 40 kA)
132 kV wave trap (1250A, 0.5 mH, 40 kA)
SSB single Channel Carrier Set (40 W) suitable for transmitting Data and super imposed channels along with Remote subscriber facility and emergency calling set.
A.F. Protection coupler microprocessor based suitable for Four commands.
Coupling Devices for Phase to Phase coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
Coupling Devices for Phase to Ground coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
HF Armoured Coaxial cable having 75 Ohms unbalanced impendance.
Microprocessor based 32/16 line Electronic Private Automatic Exchange (EPAX) with PLCC interphasing facility
Telephone Sets (Push Button Type)
20 pair Jelly Filled and armoured telephone cable with copper conductor of 0.63 mm
5 Pair jelly filled armoured telephone cable having copper conductor of Dia. 0.5 mm
5 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm
TESTING & MEASURING INSTRUMENTS, TOOLS & TACKLES AND MISCELLANEOUS ITEMS
(A) TESTING EQUIPMENT/ INSTRUMENTS [This shall consist of all the standard accessories, cables, software etc. required for satisfactory operation of equipment meeting functional requirements]
Insulation Tester (5000 Volts, Digital)
SF6 Leakage Detector
Digital Multimeter
Digital Clamp Meter
PLCC Maintenance/Testing Equipments:
Level generator with a range at 50Hz to 620kHz including facility for synchronization with SLM
8 digit time interval & frequency counter with the frequency range of 10 Hz to 10MHz & timer range of 1 microsec to 1 sec in decade steps.
Dual range 15 MHz oscilloscope with a display screen 8x10 sq.cm and the input impedance of 1 M ohm/25 pF with a deflection coefficient of 5Mv/div to 20 V/div.
4-1/2 digit LCD Multimeter with input impedance of 10Mohm & with a range of 0.1 mV to 1000 V DC, 0.1mV to 600v AC, 0-10 AMP AC,(40hz to 10KHz) & 0-20 Mohm With builtin power –supply.
Print testing Kit for PLCC terminal, protection coupler, EPAX , As per specifications appended at Annexure- V2-P3-S19-2, Volume-II, Part 3, Section-XIX
(B) Maintenance Tools& Tackles
Oil Sampling Bottle (1 Liter Capacity)
Vaccum Cleaner
Telescopic ladder aluminium 6 meter height
Ring spanner set
Tube spanner set
Pipe wrench 24 inch
Pipe wrench 18 inch
Hydraulic crimping tools up to 630 sq.mm
Threading die set for pipe threading
Welding machine (arc welding) 10kVA
Heavy duty drilling machine
Bench Vice
Insulated cuttingplier 12 inch
Insulated cuttingplier 8 inch
Screw driver 18 inch
Screw driver 12 inch
Hammer 8 lbs
Hammer 2 lbs
Chain pulley block 5 ton
Pipe derrick
Allen Keys
Box Spanners
(C ) Office and Miscellaneous Equipments / Items
Insulation Rubber mat (1mX2mX 12 mm)
Isulation Rubber Gloves (15 kV Tested)
Furniture for Control Room Building:
SCADA Room Furniture (Control Desk for specified consoles and Revolving Chair) matching with the overall interiors as per specification
Executive Desk bulit in wood and steel with lockable drawings on both side (6 feetX2 ½ feetx 2 ½ feet)
Junior executive table with three drawings on right side One Cup board left side with prelaminated decolam top 20mm thick over painted M.S. Frame ( 4 ½ feet x 2 ½ feetx 2 ½ feet).
Library Shelf with Glass Door (min 4 Shelf)
Steel tubular “S” type with continuous and one feet dia 14guage pipe, cane seat backing, teak wood with quality cane.
Archival Storage 4 Drive Type
Lateral Filing Cabinets
3 Drawer Unit
4 Drawer Unit
Steel Almirah of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system.
Steel Almirah (with Glass doors) of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system.
Minor Almirah of size 4 ½ feet x30 inch x 17 inch with three shelves making four compartments in 22 guage or better with two waylocking system.
Steel rack of size 5 feet x 3 feet x 16 inches with six shelves making five compartments (22 guage).
Steel file trays of size 16 inches x11 inches x 3 inches of guage 14 SWG.
Steel stools of size 15 inch x15 inch x 18 inch square pipe 16 guage
Steel waste paper baskets of size 12 inch (H) and Approx. 10 inch Dia Round.
Key board (wooden) with Glass door
First Aid Box
Shock Treatment Chart [Laminated with Frame]
Safety Instruction Boards [ Laminated with Frame]
(D) Drinking Water Arrangement
Water Cooler (Storage type, Storage Capacity 40 Ltr, Cooling Capcity 20 Ltr./hr)
RO/ Water Purifier
Refrigirator (380 Lt.)
Substation Name Board [1 No. Glow Type & 1 No. Painted Type] [Size and Color etc. be got approved from owner]
Danger Plate [Size and Color etc. be got approved from owner]
MANDATORY SPARES
(A) 220/132 kV TRANSFORMER
Bushing with metal parts & gaskets of each rating including Neutral bushing
Local and remote winding temperature indicator complete with sensing device & contacts
Oil temperature indicator with contacts & sensing device
Oil cooler pump with motor
Cooler fan with motor
Set of starter, contactor, relays and switch for electrical control panels (1 set of each type and range)
Buchholz relay complete with floats & contacts
(B) 132/33 kV Power Transformer
HV bushing with metal parts and gaskets
LV bushing with metal parts and gaskets
Neutral bushing with metal parts and gaskets
Magnetic oil level gauge with low oil level alarm contacts
Winding temperature Hot indicator
Cooler fans
Buchlotz Relay
(B-1) 220 kV, 25 MVAr Bus reactor
Local and remote WTI complete with sensing device and contacts
Local and remote OTI complete with sensing device and contacts
Pressure release device
Buchholz relay complete with assembly
Magnetic oil level gauge
Set of Valves (Complete set for one reactor)
Breather assembly
(C )Circuit Breakers
(One pole of circuit breaker with grading capacitor complete with pole column and interrupter with M.B. but without support structure and operating mechanism.
Rubber gaskets, ‘O’ rings and seals
Fixed Contacts
Moving Contacts
Terminal pads and connectors
Closing Assembly Valve
Trip Assembly Valve
Auxiliary Switch Assembly
Operation Counter
Closing Coils
Tripping coils
Support insulator complete for one pole of breaker
One pole of circuit breaker without support structure and operating mechanism.
Rubber gaskets, ‘O’ rings and seals
Fixed Contacts
Moving Contacts
Terminal pads and connectors
Closing assembly valve
Trip assembly valve
Auxiliary switch assembly
Operation counter
Closing Coils
Tripping coils
Support insulator (set complete for one pole of breaker)
Instrument Transformer
Spare of 245kV Capacitive Voltage Transformer
(i) Complete CVT
Spare of 145kV Capacitive Voltage Transformer
(i) Complete CVT
Spare of 245kV Current Transformer
(i) Complete CT [1 No. each type supplied)
Spare of 145kV Current Transformer
(i) Complete CT (1 No. each type supplied)
Spare of 33 kV Current Transformer
(i) Complete CT (1 No. each type supplied)
(E) C&R panels (similar items as used in the quoted panels)
Bay Control Unit (220 kV Side of offered type)
Bay Control Unit (132 kV Side of offered type)
Bay Control & Protection Unit (33 kV Side of offered type)
Bay Unit (For 220 kV Busbar Protection of offered type)
Bay Protection Unit (Distance for 220 kV Feeders of offered type)
Bay Protection Unit (Line Distance cum Differential for 220 kV Feeders of offered type)
Bay Protection Unit (Distance for 132 kV Feeders of offered type)
Bay Protection Unit (Differential for 220 kV Transformers of offered type Main-I)
Bay Protection Unit (Differential for 220 kV Transformers of offered type-Main-II)
Bay Protection Unit (Differential for 132 kV Transformers of offered type)
Bay Protection Unit (Back-up Overcurrent & E/F of offered type)
Breaker failure relay (numerical type)
Trip circuit supervision relay
Self reset trip relay
Hand reset trip relay
Timer relay
DC supervision relays
Flag relays
Auxiliary relays
Multifunction Panel Meter
Fiber Optic Cable with Connectors
Transducers (Each Type used in the autoamtion system)
Ethernet Switch (of offered type)
(F) Station Transformer
10% of total Transformer Oil quantity in non-returnable drums
HV bushing
LV bushing
Pressure relief device
Tap charger contact
Set of valves
Set of gasket
Silica gel required for five replacements
(G) Surge Arrester
220kV class 198 kV rating LA complete as specified.
132kV class 120 kV rating LA complete as specified.
33 kV Class of 30kV rating LA Complete as specified
2 Nos. Terminal connector of each type as spare
(H) Battery & Battery Charger
220 V & 48 V Type Battery
Spare battery cell without electrolyte
Terminal connectors with bolts & Nuts
Float level indicators
Vent Plugs
220V/ 50V Battery Chargers
Set of Control Cards
Set of relays
Set of contactor
Micro-switches
Filter Capacitors
Thyristor/ Diode
Set of switches
Set of wound resistors
Potentiometers
Fuses of Thyristor with indicators
(I) L.T. SWITCHGEAR :
Relays
CTs AND PTs
Switches/Push buttons and Meters
TPN Switches/MCB
L.T. Breaker spares
a) Spring charging motor
b) Aux. Contact sets
c) Busbar Seal off insulators
d) Arc-chutes
e) Moving contacts
f) Arcing contacts (Fixed/Moving)
g) Springs (Closing/Opening)
h) Closing coil
i) Tripping coil
j) Aux. finger contact
k) Limit switches
l) Jaw contacts
Busbar
a) Busbar insulators
b) Interphase barrier
c) Busbar strip 1mm (Aluminium)
(J) LIGHTING SYSTEM
Single Pole MCB
Triple pole MCB
Fluorescent tube & Starter
a) Choke
b) Bottom Strips
c) Top covers & reflector (if applicable)
d) Holders
e) Complete fittings
Sodium vapour/Mercury vapour Lamps a) Lamp
b) Ballast
c) Condenser/ Igniter
d) Lamp holder
e) Lamp holder
f) Complete fittings
Incandescent lamp
a) Bulbs
b) Holders
c) Complete fittings
Switches and sockets
Junction box
Celing Fan
(K) Clamps & Connectors Set
(L) Fire Protection System
NIFPES System
Fitted Nitrogen Cylinder [48 Lit Water Capacity]
Hose Pipe with Fittings
Heat Sensor Assembly
Fire Survival Cable [sufficient for 1 system]
Limit Switches for Fire Detector
Fire Detector (for NIFPES System)
Thermostat
Heating Element
(M) Isolators
Solid core Insulator Stacks (Requirement of one Isolator)
Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key interlock for electrical control circuit as per approved schematic --- Each set containing one number of each type and rating as offered.
Limit switches & aux.switches--Each Set containing one no. of each type and rating as offered
Motor with gear assembly and bevel gear assembly.
Bearings (Requirement of one Isolator)
Current carrying assembly total (Requirement of one Isolator)
Solid core Insulator Stacks (Requirement of one Isolator)
Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key interlock for electrical control circuit as per approved schematic --- Each set containing one number of each type and rating as offered.
Limit switches & aux.switches--Each Set containing one no. of each type and rating as offered
Motor with gear assembly and bevel gear assembly.
Bearings (Requirement of one Isolator)
Current carrying assembly total (Requirement of one Isolator)
Solid core insulator Stacks ( Requirement of one Isolator)
Limit switches and auxiliary switches ---Each Set containing one no. of each type and rating as offered
Bearings (requirement of one isolator)
Current carrying assembly 2000A total (requirement of one isolator)
Motor with gear assembly and bevel gear assembly.
Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key inter lock for electrical control circuit as per approved schematic-- Each Set containing one no. of each type and rating as offered
Add: Any other supply item, if any, bidder may require completing the substation as per specification requirements.
R S INFRAPROJECTS PVT LTD
R S INFRAPROJECTS PVT LTD
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
R S INFRAPROJECTS PVT LTD
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
Montecarlo Limited
R S INFRAPROJECTS PVT LTD
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid