Loading…
Loading…
Tender Value
₹2.4 Cr
EMD Value
₹4.8 L
Closing Date
6 Jul 2026, 3:00 pm
Similar tender results from the same govt authority in the past 3 years.
Electrical work in c/w augmentation of PF shelter at 13 Nos. NSG-5 stations (Keshrisinghpur, Lunkaransar, Mahajan, Napasar, Nohar, Rajaldesar, Raman, Sadulsahar, Sangaria, Satnali, Sri Dungargarh, Sri Karanpur, Tehsil Bhadra) of Bikaner Division (Total 64 Bays at 22 PFs).
04-EL-BKN-E-Tender-26-27
04-EL-BKN-E-Tender-26-27
Open
6 Months
Bikaner, Rajasthan
₹0
₹4.8 L
12 Jun 2026
12 Jun 2026
22 Jun 2026
85/90 GSM showing over all electrical installation of Railway station / Service building, etc. as per site requirement.
Description:- Supply of material and wiring of LP/TP/FP/Ex.Fan point with 1.5sqmm PVC single core
conduit with 1.5sqmm PVC wire insulated copper for earth wire 1-way/2-way switch 5/6A as required and good quality ceiling rose including connection. This item includes modular switch, ceiling rose, PVC conduit and required chase as per site requirement.
modular board and connection as per spec.
with modular board and connection as per spec.
-plug with sheet metal box of good quality concealed fixing of MS / PVC as per site requirement and specification.
-plug with sheet metal box of good quality concealed fixing of MS / PVC as per site requirement and specification. BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
-plug with sheet metal box of good quality concealed fixing of MS / PVC as per site requirement and specification.
-plug with sheet metal box of good quality concealed fixing of MS / PVC as per site requirement and specification.
switches -plug with sheet metal box of good quality concealed fixing of MS / PVC as per site requirement and specification.
Description:- Wiring of sub-main with 2x2.5 sqmm PVC insulated, single core, multi-stranded
copper wire for earth wire as per spec. This item includes PVC conduit (25 mm) and chase as per requirement.
wire in PVC conduit concealed and 4.0 sqmm PVC insulated, single core, multi-stranded copper wire for earth wire as per spec. This item includes PVC conduit (25 mm) and chase as per requirement.
wire in PVC conduit concealed and 6.0 sqmm PVC insulated, single core, multi-stranded copper wire for earth wire as per spec. This item includes PVC conduit (25 mm) and chase as per requirement.
Description:- Supply, laying, connection and commissioning of sub-main 2x10 Sqmm with PVC
earthing wire in ISI marked PVC conduit in recessed / on surface as per site requirement. This item includes PVC conduit (25 mm) and chase as per requirement.
PVC insulated, single core wire in PVC 19/20 mm ISI PVC conduit pipe mounted on structure/ shed with ceiling rose 5 Amp. mounted on wooden block/PVC junction box as per site requirement.
Description:- Supplying and drawing 4.0 sq. mm PVC insulated multistrand copper conductor cable
earthing wire conforming to IS: 694-1990 in existing conduit/casing caping. Wire should be of reputed make.
Contractor is responsible for falling of fan within a period of 12 month.
complete with required necessary fixing accessories as per spec & site requirement. Minimum 5 years warranty.
and necessary fixing arrangements as per site requirement.
Description:- Supply & fixing of battery-enabled emergency LED tube light fitting, 18-20 W, batten
load, including all accessories as per requirement. Reputed Make like Orient, Crompton, Phillips, Surya, Havells, Jaguar, Halonix, Bajaj, Wipro and Eveready with warranty of minimum 02 years.
20 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY 20 Description:- Fabrication, supply, fixing, testing and commissioning of OFF delay timer panel comprising of analogue multifunction timer with OFF delay/Signal OFF delay function with timing range adjustable upto 30 minutes minimum for OFF delay (L&T GIC model no. Micon 175 - 1CMDT0 or similar of reputed make), 3 Pole power contactor AC3-40A / AC1-55A, 240 VAC coil, 2 nos. LED based illuminated flush type push switch with 2 NC/NO contact for ON/OFF, SP MCB 6A, 10 kA 'C' series for control wiring, four terminal connecting strip 63 A min. for incoming and outgoing and other accessories including power (min. 10 sqmm copper wire) and control(min. 1.0 sqmm copper wire) wiring. Panel should have good finishing in all respect to the satisfaction of Railway authority. Panel should be as per tech spec. and should be got approved by competent authority prior to supply and commissioning.
side particle board for mobile with hanging clip as per requirement.
Description:- SETC of wall mounting mobile charging unit consisting of 6 Way Modular box with 10 A SP Mini MCB with i) 2.1 A USB Charging point - 4 Nos ii) 2.1 A (TYPE-C) Charging point - 1 No, Rack
Unit should include inbuilt MS stand/tray to hold min 5 numbers of mobile phones under charge. Enclosure material made of mild steel and powder coated including internal wiring by 2.5 sq.mm multistrand copper in an approved manner as directed by Engineer incharge at site.
Description:- Supply & erection of 5Mtr high octagonal pole with double arm model no. BOP-5030 of Bajaj or similar, pole shaft material S355J0 or equivalent as per IS, hot dip galvanized steel
stud terminals (for mounting inside the base compartment of pole), foundation bolt size 4x16mm dia. 600 mm in length including excavation and making foundation as per spec. and drawing. It shall be galvanized internally and externally by single dipping method. The pole and foundation shall be made as per specification and attached drawing.
accessories and integral electronic driver. Reputed make like Orient, Crompton, Phillips, Surya, Havells, Jaguar Halonix, Bajaj, Wipro and Eveready. Minimum 5 years warranty.
Reputed make like Orient, Crompton, Phillips, Surya, Havells, Jaguar, Halonix, Bajaj, Wipro & Eveready. Minimum 5 years warranty.
requirement and Engineer in charge of railway.
suitable bore as per fitting, clamps, nuts, bolts, cable, etc. as per instruction of site engineer.
pole with cement concrete ratio 1:2:4 as per technical specification and satisfaction to site engineer. (Supply of Octagonal Poles are not included in this NS)
instructed by site engineer including labour charges and other expenditure.
octagonal pole as per site.
by suitable cement concrete and transportation of pole and all accessories with fitting etc. complete from the site to place located at the station as advised by concern SSE/Elect.
Description:- Removal of existing Rail/Swage poles with overhead wire and all accessories from
suitable cement concrete and transportation of rail pole and all accessories with fitting etc. complete from site to place located at that station by concern SSE/Elect.
33 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY 33 Description:- Supplying and drawing FR PVC insulated & unsheathed flexible 3 Core X 1.5sqmm PVC Unarmoured copper cable ISI marked (IS:694) of 1.1 kV grade and approved make in existing surface or recessed conduit/casing capping including making connections etc. as required.
accessories as per site requirements. Fan should be of reputed make.
junction point in poles (5 / 7 mtr.) as per site requirement.
Description:- Supply and fixing of Double Door MCB TPN DB SP (8+12 module), neutral and earth
no. SP MCB 32/25/16/10/6 amp. 'C' series. Breaking capacity not less than 10 kA. MCB, RCCB and DB should be as per tech spec. and of same make.
Description:- Supply, installation, testing and commissioning of SPN DB 12 Way with suitable IP
Nos. 10-32 Amp. SP MCB, 10 kA, 'C' curve, as required with bus bar, neutral bar and necessary wire sets. MCB, RCBO and DB should be of same make.
ventilation fan of 300 mm. sweep with louver shutters. Fan should be of reputed make and as per tech. spec.
aluminium conductor armoured cable confirming IS: 7098 (Part-1) and as per tech spec. Reputed make like KEI, Polycab, Finolex, Havells or similar.
aluminium conductor armoured cable confirming IS: 7098 (Part-1) and as per tech spec. Reputed make like KEI, Polycab, Finolex, Havells or similar.
Trench / wall / cable tray etc. with complete lugs / glands & clamping arrangement including transportation of cable as per site requirement.
kachha/pakka land and all type of soil as per site requirement and without protective layer of brick) Surface of trench shall be made good in all respect and satisfaction of site engineer.
Description:- Cutting of cement concrete floors (PCC / RCC), any type / depth as required for laying of UG cables in trenches and disposing off the excavated material as directed including refilling the
barricading and danger lighting around the excavated areas safety precaution is a mandatory requirement and cost of this provision, wherever required, is deemed to be included in the quoted rate of this item.
6, PE-80 as per requirement.
under the road. The work involves laying of HDPE pipe along with transportation.
Description:- Supply and fixing of junction box size 390x305x170mm comprising of SMP/FRP
model no. GSJB 3525 or similar with 4 no. aluminium busbar cap 200 Amp., suitable for 415 volt supply requirement. The box shall be fixed robustly with clamps at pole/ wall as per requirement. All the material should be of good quality.
47 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY 47 Description:- Supply and fixing of junction box size 500x450x100mm comprising of sheet steel 2mm thick, 60 micron powder coating/two coats of primer and finished by enamel paint - grey shade, gland plates, neoprene EDPM/rubber gasket, padlock arrangement, zinc passivated earth bolt, canopy etc. 4 no. aluminium busbar cap 200 Amp., suitable for 415 volt supply requirement. The box shall be robust clamps at pole/ wall as per requirement.
1.5mm thick size 150X100mm welded with 12mm dia MS rod 85 cm long. The lower end of rod should be turned in hooks shape and attached with the cable at the time of laying.
part-I for passing incoming and outgoing cable from ground through it size 38 mm dia. Pipe should be of reputed make.
refilling with charcoal & salt. (As per specification)
mm thick with CI/RCC earth pit cover 300 x 300 x 25 mm with lifting hooked in center.
Description:- Supply, laying and fixing of 25 x 5 mm GI earth strip at 0.5 metre below ground level
required (jointing shall be done by overlapping and with 2 sets of GI nut bolt & spring washer spaced at 50 mm). Note:- Suitable GI saddles with screws shall be provided to secure earth strips run on walls / floors etc.
Description:- Supply & Fixing of GRP / FRP cable tray made of glass fiber reinforced polyester
horizontal and vertical reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with GI suspenders, etc. as per site requirement.
with cover and all fixing arrangements as per specification and as per site requirement.
GI hot dip perforated cable tray with cover and all required mounting accessories as per site requirement & technical spec.
GI hot dip perforated cable tray with cover and all required mounting accessories as per site requirement & technical spec.
made of MS sheet 1.6 mm thick size 600mmX300mmX600mm with suitable MS stand copper bus bar of 200 Amp. capacity and 2X63 Amp MCB four pole as per technical specification.
Description:- Drilling of horizontal bore below Track/Road by pushing method (trenchless
Railway representative taking all necessary safety precautions related track and movement of trains. Horizontal boring will be done at minimum 1.5 Mtr. Below from ground level at railway track portion.
IS, PN-6, PE-80 as per requirement.
water connection, angle valve, etc. as per site requirement.
cooler of required height as per site requirement and as per instructions of site supervisor of railway.
BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
fixed on base angle frame on 50 x 50 x 6mm and 40 x 6mm MS flat in centre to support the jaali. The whole structure including the framed jaali painted with one coat of red oxide and two coats of enamel paint. Providing roofing on rail/iron structure by MS/GI sheets with support of 50 x 50 x 6mm angle, nut-bolt and washer as per requirement.
leakage, overload and short circuit protection as per spec.
leakage, overload and short circuit protection as per spec.
flush mounting and surface mounting with door for IP-54, similar to Legrand model no. 5077 91/93 of reputed make.
capacity not less than 10 kA.
magnetic adjustable as per relevant IS / IEC.
magnetic adjustable as per relevant IS / IEC.
MCCBs of 100A and 63A. Square
sign / direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than 160 deg. as per tender specs. Square
direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than
Railway yard / below track / Road.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
UpdatedGCCwithACS.pdf
ATTACHMENT
JPOforprotectionofSTCables.pdf JPO for Protection of Cables
ATTACHMENT
RBSIGNAGESPOLICYPART-1.pdf RB Signage Policy Part 1
ATTACHMENT
RBSIGNAGESPOLICYPART-2.pdf RB Signage Policy Part 2
ATTACHMENT
TenderSpecsT-04-2026-27.pdf Tender Specifications
ATTACHMENT
JPOforprotectionofSTCables.pdf
ATTACHMENT
RBSIGNAGESPOLICYPART-1.pdf
ATTACHMENT
RBSIGNAGESPOLICYPART-2.pdf
ATTACHMENT
TenderSpecsT-04-2026-27.pdf
ATTACHMENT
Download all tender documents and submit your bid