Construction of mult-istoried building at Tertiary Cancer Care Centre (TCCC) at Burdwan Medical College and Hospital, Purba Bardhaman- SITC of UPS.
2023_WBPWD_447536_1
WBPWD/SEWEC /BED /NIQ-137/2022-23
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Bardhaman
Please refer Tender documents.
5 documents required · 5 mandatory
₹50,400
Office of the Superintending Engineer, Western Ele
7 Feb 2023
17 Jan 2023
3 Feb 2023
17 Jan 2023
1 Feb 2023
20 Jan 2023
17 Jan 2023 - 19 Jan 2023
19 Jan 2023
Amount
SITC of 40 KVA UPS including Battery Bank of 57600 VAH (SMF Battery) 12 Volt 3ph Input / 3ph Output, inbuilt Isolation Transformer, static by pass arrangement, compitable with D.G. Set, DSP controlled IGBT based rectifire with minimum 90% efficincy on 100% Load. The UPS shall be provided with active input P.F. Correction system to obtain 0.9 lag at 100% resistive Load, Wave form - Pure Sine wave. It Should be capable of operating in 50"c above ambient temprature, Built in Solid State float cum boost charger with automatic boost / trickel charge mode with current Limiting features. The charger should be designed for at least 15% of the total battery current. The UPS Should have current limiting protection, built in over load /Short circuit protection with snubber circuits for current limit. Soft start arrangement, Over voltage/ under voltage protection, mains ON, Inverter ON/ OFF/ FAULTY/ TRIP (Reason), Charger ON/ FAULTY or TRIP, Battery Low,Static by-pass ON, Over temperature. Battery set Complete with self-standing cubicle or cabinet.
Regulated Sealed Lead Acid Battery, Construction type : AGM or VRSLAB in ABS Flame Retardant Rating, 57600 VAH (12V, SMF Battery) (Battery Make : Amararaja Quntra/ Exide Power Safe. Back up time : 60 Min at full load.Warranty : One Year on UPS and two Years on SMF Battery on site against any manufacturing defects. Certificate : ISO 9001:2015, ISO 14001:2015, IOS 18001,OHSAS 18001. CE Certification: IEC/EN 62040-1-1, 1ЕС/ EN50091- 1,IEC/EN 60950(Safety), IEC/EN 50091-2,IEC/EN 62040-2(EMC Emmission), IEC/EN 62040-3 (Performance & Design), IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design 8s Manufacture) (Make: APC-Schneider Electric/ NUMERIC/ Power One/ VERTIV/ Switching AVO/ Powersafe/ Dell)
SITC of 10 KVA UPS including Battery bank of 14400 VAH (SMF Battery) 12 Volt 3ph Input / 3ph output, inbuilt isolation transformer, static by pass arrangement, compitable with D.G. Set DSP controlled IGBT based rectifire with minimum 90% efficiency on 100% Load. The UPS shall be provided with active input P.F. Correction system to obtain 0 .9 lag at 100% resistive Load, Wave form Pure Sine wave. It Should be operated 50’ с above ambient temprature built in solid state float cum boost charger with automatic boost / trickel charge mode with current Limiting features. The charger should be designed for at least ,15% of the total battery current. The UPS Should have current limiting protection, built in over load /Short circuit protection with snubbcr circuits for current limit. Soft start arrangement, Over voltage/ under voltage protection , mains ON, Inverter ON/OFF / FAULTY/ TRIP (Reason), Charger ON/ FAULTY or TRIP, Battery Low, Static by-pass ON, Over temperature. Battery set Complete with self standing cubicle or cabinet.
Regulated Sealed Lead Acid Battery, Construction type : AGM or VRSLAB in ABS Flame Retardant Rating, 14400 VAH (12V, SMF Battery) (Battery Make : Amararaja Quntra/ Exide Power Safe. Back up time : 60 Min at full load. Warranty : One Year on UPS and two Years on SMF Battery on site against any manufacturing defects. Certificate : ISO 9001:2015, ISO 14001:2015, IOS 18001,OHSAS 18001. CE Certification: IEC/EN 62040-1-1, 1ЕС/ EN50091- 1,IEC/EN 60950(Safety), IEC/EN 50091-2,IEC/EN 62040-2(EMC Emmission), IEC/EN 62040-3 (Performance & Design), IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design 8s Manufacture) (Make: APC-Schneider Electric/ NUMERIC/ Power One/ VERTIV/ Switching AVO/ Powersafe/ Dell)
IRP Enterprise
Hipotronics Engineers
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .