| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-Finance | ₹1.3 Cr | L1 | Accepted-Finance 1st lowest |
| 2 | L2₹1.4 Cr+₹1.7 L (1.26%)Rejected-Finance | ₹1.4 Cr+₹1.7 L (1.26%) | L2 | Rejected-Finance 3rd lowest |
| 3 | L3₹1.4 Cr+₹3.0 L (2.24%)Rejected-Finance 401 501 HARSH ANAND YEOLEKAR MALA COLLEGE ROAD NASHIK 422005 | NASHIK | NASHIK | MAHARASHTRA | 422005 | ₹1.4 Cr+₹3.0 L (2.24%) | L3 | Rejected-Finance 2nd lowest |
| 4 | L4₹1.4 Cr+₹4 L (2.97%)Rejected-Finance A 602 SARITA GARDEN CHS LTD OPPOSITE SBI BANK VAKOLA PIPELINE SANTACRUZ EAST MUMBAI 400055 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400055 | ₹1.4 Cr+₹4 L (2.97%) | L4 | Rejected-Finance 4th lowest |
| Sl No | Description | Qty | Unit | Super Electric And Co. L1 | Harsh Constructions Pvt Ltd L3 | Ramsangam Projects Pvt Ltd L4 | K H Construction L2 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supplying and erecting 350 kVAr, 3 phase, 50 Hz., Power contactors Derated for microprocessor APFC controller with MPP / APP type capacitor with 525 V and having minimum overcurrent capacity of 1.8 In, peak inrush current capacity 300 In and minimum life 150000 hours with , consisting of suitable steps of MPP / APP type capacitor units with detuned aluminium filter 7% reactors with circuit breaker as main incomer and MCCB for each branch protection, as per specification no CP-ED/APFC | 1 | Each | 14,50,000 ₹14,50,000 Lowest | 15,63,000 ₹15,63,000 | 15,50,000 ₹15,50,000 | 14,80,000 ₹14,80,000 |
| 2.00 | Supplying, erecting, testing and commissioning of diesel generating set conforming CPCB-IV plus Emission Norms with alternator of 500 kVA output continuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C supply, a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %, with performance class G2 and maximum fuel consumption 81.90 Ltr/hr @75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level up to 75 dB at 1.0 m, provided with first filling of oil, diesel not less than 690 Ltr etc. on provided M20 Grade CC Foundation and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG | 2 | Each | 60,00,000 ₹1,20,00,000 Lowest | 60,94,000 ₹1,21,88,000 | 61,50,000 ₹1,23,00,000 | 60,70,000 ₹1,21,40,000 |
Tender Value
Refer Docs
Closing Date
12 Aug 2026, 10:00 amClosed
Sambhaji Ghorpade
Office of the Executive Engineer South Mumbai Electrical Division P.W.D. Bandhakam Bhavan 1st floor Marzban Road Fort Mumbai 400 001
Est.No. OW/MESD/MS/ 1329/2024-25 Supplying, Installation, Testing and Comissioing of Complete Electrical Installation including all services with necessary allied work for proposed New Mantralaya Building ( G7 Upper floors), Mantralaya,Mumbai.
2026_PWDM_1324937_1
Est.No. OW/MESD/MS/ 1329/2024-25-2
Open Tender
Electrical Works
Percentage
60 days
Mantralaya
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
14 Aug 2026
5 Aug 2026
13 Aug 2026
5 Aug 2026
12 Aug 2026
5 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying and erecting 350 kVAr, 3 phase, 50 Hz., Power contactors Derated for microprocessor APFC controller with MPP / APP type capacitor with 525 V and having minimum overcurrent capacity of 1.8 In, peak inrush current capacity 300 In and minimum life 150000 hours with , consisting of suitable steps of MPP / APP type capacitor units with detuned aluminium filter 7% reactors with circuit breaker as main incomer and MCCB for each branch protection, as per specification no CP-ED/APFC | - | Each | - | - |
| 2 | Supplying, erecting, testing and commissioning of diesel generating set conforming CPCB-IV plus Emission Norms with alternator of 500 kVA output continuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C supply, a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %, with performance class G2 and maximum fuel consumption 81.90 Ltr/hr @75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level up to 75 dB at 1.0 m, provided with first filling of oil, diesel not less than 690 Ltr etc. on provided M20 Grade CC Foundation and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG | - | Each | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.17 MB
1329dtp.pdf
Tender Documents • 1.15 MB
BOQ_2269278.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .