Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹9.8 LAccepted-AOC | 1 | Accepted-AOC 1 | |
| 2 | 2₹17.2 L+₹7.4 L (75.1%)Rejected-Finance B 46 INDUSTRIAL AREA SECTOR 59 NOIDA UP 201301 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | 2 | Rejected-Finance 2 |
Tender Value
Refer Docs
EMD Value
₹18,000
Closing Date
25 Jun 2021, 3:00 pmClosed
EE PHED No. 1 Kaithal
Near Govt ITI Kaithal
Providing, fixing , commissioning and testing of online COD, BOD and TSS sensor and data connectivity of existing EQMS to CPCB/HSPCB and PHED servers at Manas Road STP (MBBR TTP) and all other works contingent thereto
2021_HRY_176236_1
SE Kaithal Memo No. 3469 dated 04.06.2021
Open Tender
Civil Works
Works
30 days
Various Villages
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
₹18,000
Yes
6 Aug 2021
18 Jun 2021
25 Jun 2021
18 Jun 2021
25 Jun 2021
18 Jun 2021
Amount
Supplying fixing of 1 No. Multi-parameter measuring converter, for connecting up to 18 intelligent sensors scope including 8 analog inputs/outputs (4 inputs & 4 outputs) (0/4-20Ma) wide range power supply Optical COD/BOD and TSS probe withspectral processing of the UV-VIS range, for measurement in the outlet/effluent/ of Sewerage treatment plant at 10.00 MLD STP (MBBR) Manas Raod Kaithal town with integrated with automatic cleaning on existing online Analyzer System with 5 years warranty complete description as per NS Items Specifications:- Measuring principle :- UV-VIS Spectrophotometer Measuring principle detail : xenon flash lamp, 256 photo diodes Automatic compensation instrument : Two beam measurement, complete spectrum. Measuring range : COD:0-3750 mg/L BOD:0-2000 mg/L TSS: 0-3000 mg/L Reference standard : distilled water Onboard memory : 656 KB Integrated temperature sensor :-10..50 C Resolution temperature sensor : 0.1 C Integration via : Con::cube Power supply : 11::15 VDC Power consumption (typical) : 4.2 W Power consumption (max) : 20 W Interface connection to S::can terminals : MIL connector (IP67), RS 485 Cable length : 7.5 m fixed cable Housing material : stainless steel 1.4404 Weight(min) : 3.4 kg(incl.cable) Dimensions (diameter x length) :44 mm x 547 mm /591 mm Operating temperature : 0…45 C Storage temperature : -10…50 C Operating pressure : 0…3 bar Installation /mounting : submersed Flow rate : 3m/s(max) Mechanical stability : 30 Nm Ingress protection class : IP68 Automatic cleaning : media: compressed air permissible pressure: 4… 6 bar cleaning interval: depending on application. Conformity –EMC : EN61326-1,EN61326-2-3 Conformity – safety : EN61010-1 Including all other items for above mentioned system successful running.
Data connectivity charges of existing Effluent quality monitoring system to CPCB, HSPCB & PHED server including maestro make Lan Modem
Aaxis Nano Technologies Pvt. Ltd.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .