Loading…
Loading…
Tender Value
₹4.0 Cr
EMD Value
₹3.5 L
Closing Date
20 Jan 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
SRDSTECSIG
14 conditions · 2 needing a document upload
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Form-2, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
Technical Eligibility Criteria: The Tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i)Three similar works costing not less than the amount equal to 30% of advertised value of the tender, or (ii)Two similar works costing not less than the amount equal to 40% of advertised value of the tender, or (iii)One similar work costing not less than the amount equal to 60% of advertised value of the tender.
Defination of Similar Work :- Any work of Provision of Maintenance Free earthing or Conventional earthing arrangements. OR Any Signaling or Telecom work which includes Maintenance Free earthing and/or Conventional earthing arrangements. Note 1: Tenderer may be required to submit the schedule of those works, Completion/Performance Certificates of which have been submitted by him/her in support of 30% / 40% / 60% (as the case may be) criterion of similar nature of work.
14 conditions · 11 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
PAN Number must be attached.
Detail of Bid Security paid, through only payment modes available on IREPS portal like net banking, debit card, credit card etc.
Registered Office Address with contact no.
Mandatory undertaking regarding Employment/Partnership of Retired Railway Employees as per Clause No. 12 of Chapter-I as per Annexure- E.
Mandatory certificate to be submitted by tenderer along with tender documents as per Annexure- A.
GST Number must be attached.
Mandatory Power of Attorney to be submitted by tenderer along with tender documents as per Annexure- B.
MOA & AOA, Resolution of Board and POA, Sole Proprietorship, Notarized partnership deed with POA and latest certificate of registration with Registrar of the firms must be attached. Year of Formation / Incorporation. (As per Clause-10 of Tender Document)
Upload duly filled and signed Cover Letter (Tender Form 1).
Mandatory Document Tenderer uploaded Annexure-A (1) {This certificate is to be given by attorney/authorized signatory/each member of Partnership firm/Joint Venture (JV)/Hindu Undivided Family (HUF)/Limited Liability Partnership (LLP) etc.)}of tender documents.
An undertaking by the tenderer shall be provide at the time of tender submission that the equipment shall be procured from RDSO/TEC/OEM covering supply, installation, testing, commissioning of system including after sales support required during the warranty period.
Signalling work in connection with improvement of earthing of signalling equipments over Delhi Division.
558-Sig-16-M-Tender-1468~NR
558-Sig-16-M-Tender-1468
Open
Works - General
12 Months
Delhi, Delhi
₹0
₹3.5 L
20 Jan 2026
29 Dec 2025
6 Jan 2026
39 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 3,99,17,072.7 | ||
| — | 800.00 | — | — | ||
| Supply, Installation & Commissioning of maintenance free earth suitable kit as per RDSO Specification no. RDSO/SPN/197/2008 and Drg No.SDO/. /E&B/001 dated: - 19.09.2008 and Drg No. RDSO/SDO/. /E&B/002 dated: - 19.09.2008. Earthing kit consisting of earthing electrode of 17mm dia as 3m long -01 no 2 MEEB (300mmx25mmx6mm) -o1 no. 3. SEEB (150mmx25mmx6mm) -01 no 4. Earth enhancing compound - 30 kg (minimum). This includes: - Provision of earth connection from MEEB to S&T equipment i.e. cable sheath, apparatus case, BPAC, Axle counter, IPS, Data Logger etc. with PVC earth wire of size 25/35 sq.mm through copper lugs of suitable size PVC earth wire shall be supplied by contractor. Note: At certain locations, it may not be possible to achieve earth resistance of less than 1.0 ohm with one earth electrode /pit due to soil resistivity. In such cases, provision of loop earth consisting of more than one earth pit shall be done, for interconnection of two earth pits copper tape of size 25x2 sq.mm shall be provided by the contractor. The number of pits required shall be decided based on the resistance achieved for the earth pits already installed. The procedure mentioned above for one earth pit shall be repeated for other earth pits. The other earth so installed for the purpose of loop earthing arrangement shall be counted as separate earth. Inspection: RDSO for supply portion, Execution: Site Engineer. | — | — | — | 2,06,98,296 | |
| — | 500.00 | — | — | ||
| Supply and installation of earth electrodes as per std. practice. The item includes digging of pit in earth, 3 Mtrs. deep and fixing earth electrode pipe. Casting of cement concrete enclosures as per drg. No. (NR/S&T/CON/6.4/97). The soil treatment shall be done as per std. practice. The item includes provision. of mild steel flat of size 35mm x 6mm (as per IRSEM) and nut bolted connection of MS flat with earth electrode. The other end of mild steel flat to be connected to block instrument, cable sheath of power equipment, signal base, apparatus case, CT rack / relay racks, other equipment's as per the instruction of Engr. at site & IRSEM. Earthing connection location to location shall be done through cable which shall be provided by Railway. Complete materials such as earth electrodes as per drg. No. (NR/S&T/CON/6. 3/97), cement, wiring material, nut bolt for connection & mild steel flat of size 35mm x 6mm or 210 sqm as per SEM etc. to be supplied by the contractor. Inspection: Rites for supply portion, Execution: Site Engineer. | — | — | — | 15,35,205 | |
| — | 200.00 | — | — | ||
| Supply of Main Equip-potential earth bus bar (MEEB) Copper of size-300x25x6 mm. Inspection by consignee. | — | — | — | 85,414 | |
| — | 200.00 | — | — | ||
| Supply of Sub equip-potential earth bus bar (SEEB) Copper of size-150x25x6 mm. Inspection by consignee. | — | — | — | 48,024 | |
| — | 400.00 | — | — | ||
| Supply of Exothermic welding for connecting the existing ring earth with new earth maintenance free earth. Inspection by RITES. | — | — | — | 6,60,000 | |
| — | 400.00 | — | — | ||
| Carrying out exothermic welding for various conductors as per requirement Materials required for the work like, Lug, Nut screw, bolt, welding martials and other misc. materials (excluding cable) required for the inter connection works to be supplied by contractor. Inspection by Site Engineer. | — | — | — | 2,02,120 | |
| — | 6000.00 | — | — | ||
| Supply of 35 Sq. mm PVC insulated Single core Multistrands copper conductor (Red/Black/Green) as per IS:694/2010 or latest, as per Specification No. IRS:S-76/89 or latest. Colour of the wire which is required will be specified by the Engineer-in-charge. Inspection: RDSO. | — | — | — | 21,17,760 | |
| — | 6000.00 | — | — | ||
| Digging a trench to a depth of at least 0.5 meter and run the two 35 sq mm earth conductor (procured against supply item) from Earth pit to MEEB. (b) Routing and termination of two 35 sqmm earth conductors in trench from earth pits to300x25x6 mm MEEB, which is to be fixed inside the equipment room with two insulation studs. Inspection by consignee. | — | — | — | 4,47,840 | |
| — | 6000.00 | — | — | ||
| Supply of 16 Sq. mm PVC insulated Single core Multistrands copper conductor (Red/Black/Green) as per IS:694/2010 or latest, as per Specification No. IRS:S-76/89 or latest. Colour of the wire which is required will be specified by the Engineer-in-Charge. Inspection: RDSO. | — | — | — | 10,06,500 | |
| — | 6000.00 | — | — | ||
| Routing and connecting of all the SPDs in the equipment room to MEEB/SEEB to MEEB with 16 sq. mm copper cable using copper lugs with stainless steel nut and bolts. The work includes laying and routing the copper cable in PVC / conduits and fixing them on wall. The PVC/conduit pipe to be supplied by Railway. Note-1: MEEB shall be installed not more than 0.5 metres from LPD /SPD box and preferably near SMR rack of IPS (Annexure-V) as per RDSO TAN No.STS/E/TAN/3006, Ver.3.1, Dated: 25.06.2025 or latest. if required SPD to be shifted from Relay rack/Power Rack/CTR to wall mounted position such way distance from MEEB to SPD not more than 0.5 mtrs. Note-2: all the equipment shall be connected to the nearest point on the BRC using bonding wires routed through the floor of the room. Routing through the floor ensures the shortest path and prevents the earth wire from running parallel to any power/data cables. The cutting to be filled and finished with cement/concrete, and plastering. The wire will be laid in suitable PVC pipe and this work is to be executed as per directions of Railway Engineer at site. Inspection: Site Engineer. | — | — | — | 3,42,180 | |
| — | 5000.00 | — | — | ||
| Supply of 10 Sq. mm PVC insulated Single core Multistrands copper conductor (Red/Black/Green) as per IS:694/2010 or latest, as per Specification No. IRS:S-76/89 or latest. Colour of the wire which is required will be specified by the Engineer-in-Charge. Inspection: RDSO. | — | — | — | 5,29,900 | |
| — | 5000.00 | — | — | ||
| Routing and connecting all the equipment in the equipment/relay room to SEEB with 10 sq. mm copper cable using copper lugs with stainless steel nut and bolts and fixtures. The work includes laying and routing the copper cable in PVC / conduits and fixing them on wall. Inspection by consignee. | — | — | — | 2,85,150 | |
| — | 5000.00 | — | — | ||
| Supply of 50x6 mm GI Tape for interconnecting earth electrodes. Inspection by Consignee. | — | — | — | 20,49,100 | |
| — | 5000.00 | — | — | ||
| Digging a trench to a depth of at least 0.5 meter for laying of 50x6mm bar galvanlised steel tape connecting all earth pits. Inspection by consignee. | — | — | — | 4,05,200 | |
| — | 6000.00 | — | — | ||
| Supply of 25mm x 2 mm bare copper strips BRC (Bonding Ring conductor) in the equipment room. Inspection: RITES. | — | — | — | 77,83,440 | |
| — | 6000.00 | — | — | ||
| Routing and termination of 25 mm X 2 mm copper tape (BRC)/8mm solid copper round conductor which is to be fixed inside the equipment room with 60 mm,6KVA insulation studs including supply of insulation studs. The separation of the two successive insulation studs should be 600mm apart. Note: BRC to be fixed 0.5 mtrs from Room floor as per RDSO/SPN/197 Para 8.5.1(b), all the equipment shall be connected to the nearest point on the BRC using bonding wires routed through the floor of the room. Routing through the floor ensures the shortest path and prevents the earth wire from running parallel to any power/data cables. it is mandatory that a complete close loop has to be formed for BRC. Inspection by consignee. | — | — | — | 5,12,400 | |
| — | 600.00 | — | — | ||
| Supply of Fiber/ SMC/FRP/RCC Earth Chamber as per instructions of Engineer In charge as per site requirement as per STS/E/TAN/3006 ver 3.0. Inspection by consignee. | — | — | — | 3,37,302 | |
| — | 600.00 | — | — | ||
| Supply of 25 mm (1 inch) PVC conduit pipe rigid plain ended conduit size IS:9537 (part-3) or latest and 9537 (Part-1) 1980 with latest amendment ISI marked with minimum 1.2 mm wall thickness & minimum one socket at every 3 meter pipe. Inspection by consignee. | — | — | — | 15,960 | |
| — | 21.00 | — | — | ||
| Supply of Earth Tester clamp on meter as per specification in annexure technical specification of tender document: Makes: Meco/Fluke/ Motwana or similar or better. Inspection by RITES. | — | — | — | 8,55,281.7 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Tender-doc-1468.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .