Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹3,500
Closing Date
4 Jan 2020, 2:00 pmClosed
Executive Engineer
Electricity Construction and Works Division, Near Urja Bhawan, P.V.V.N.L., Victoria Park, Meerut
Construction of 33 KV Underground line for 33 KV Substation Kazipur, Meerut from Four Pole Structure of 33 KV Substation Lohiyanagar to 33 KV Line of Manat Steel (Unused Line) feeding from 132 KV Substation Lohiyanagar Distt. Meerut
2019_PVVNL_407055_2
01/ECWD/MRT/Works/2019-20
Open Tender
Electrical Works
Lump-sum
60 days
Meerut
Please refer tender doucments
3 documents required · 3 mandatory
₹1,180
Payable to Ex.En., E.C.W.D., Meerut
₹3,500
7 Jan 2020
23 Dec 2019
4 Jan 2020
23 Dec 2019
4 Jan 2020
23 Dec 2019
1. Safe carriage of Poles from Store Center to Site Store with loading & unloading at both ends respectively distance about 20 Km. (a) 11 M Long STP, SP-55 Round Pole
2. Loading, Safe carriage & unloading of heavy stock material (other than pole) from store center to site store with proper stacking of material distance about 20 Km.
3. A) Excavation of foundation pit in mix soil/normal soil/soft & hard rock and its back filling and leveling etc. The size of the pit will be (900×600)mm and having depth of 1/6th of the full length of the support & Erection of support. The work includes carriage and handling of supports from site store to pit site. (i) 11 M Long STP, SP-55 Round Pole
3. B) Fixing of all clamps, Cross Bracing Sets 3.5 Mtr. from M.S. Angle 65×65×6mm/50×50×6mm & other accessories on the supports as per drawing. Work includes cutting of holes and providing M.S. Bolts of 16×40mm size in the middle of cross bracing with 1 no. spring washer. The work also includes carriage & handling of accessories from sectional store to pit site as well as any fabrication work if required. (i) Double Pole Structures (a) 11 M Long STP, SP-55 Round Pole (Riser)
4. Grouting of supports in CC 1:4:8 (Cement, sand & 40 mm brick ballast) Grouting will be done in the block of size (450×450)mm ×1/6th of full length of the support, up to ground level, 300 mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grit) with muffing as per drawing, work includes back filling and proper ramming. (i) 11 M Long STP, SP-55 Round Pole
5. Grouting of stay rods (20×1800)mm including all work of excavation, cement concrete in size (0.60 × 0.60 × 0.30)m in ratio 1:4:8 cement, sand, 40mm brick ballast) as per drg. including back filling, proper ramming etc and fixing tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing.
6. Earthing of supports with MS earth Rod of (20×2500)mm long including excavation of pit and driving M.S. Rod 3.0 M apart from support and 0.5m below the ground level and connecting below the earth electrodes with the help of G.I. wire no. 8 SWG and earthing lugs.
7. Laying, spreading, lifting and final sagging of 3 phases of ACSR Dog conductor in accordance with profile and sag chart including binding, Jumpering and fixing of P.G. Clamp as per requirement in 03 Nos. conductor in parallel.
8. Providing & fixing of danger board at each location as per specification of the drawing with clamps etc.
9. Painting of following supports/structures with 2 coats of synthetic enamel paint after one coat of ready mix primer including cost of all material, as well as rubbing/cleaning of surface as required for proper completion of work. Painting will be done by post office red paint from top to cross arm and remaining by Aluminium paint. i) 11 Mtr, SP-55 Poles including all channels/X-Arms/Clamps etc. a) Double supports
10. Making H.T. Connections of the proposed line, on to the existing 33 KV bay/line from where line is eminating and another at the end of line to the terminal gantry at proposed 33 KV Sub-station. The work consists of fixing of tension fitting, insulators, jumpering, clamping and binding etc. at the end as per site conditions.
11. Wrapping of barbed wire on 33 KV PCC Poles/SP-55/SP-72 ST Poles as anti-climbing device for a length of 0.9 Mtr., wire pitch/gap 13mm and fixing upper and lower end keeping lower end at a height of 2.75 Mtr. from the ground complete with supply and fixing of lower end & upper end clamps made of M.S. Flat 40×5mm complete with nuts & bolts & all other required material.
12. Numbering of each supports by preparing background with dark yellow paint in the size of 150mm dia and writing support number 100mm high with black paint.
13. Laying of 33KV XLPE cable of size 3x300mm2 details as given below. a) Safe carriage of 3x300mm2 XLPE Cable from store centre Meerut to site store distance upto 20 Km including loading,unloading and both ends.
b) Digging of trench of size 900x1050 mm for laying of 33KV 3×300mm2 Cable & back filling of earth including Supply & Laying of Ist Class bricks work for making chulla and sand work for cushin.
c) Safely laying of 33KV 3×300mm² XLPE cable alongwith spare cable into trench including loop
d) Safe laying of 33KV XLPE cable in Air on Double on D/P/Riser
e) Supply & Fixing of cable rout marker along the rout of 33KV cable.
f) Making of 33KV Outdoor type Heat shrink XLPE Cable Box of size 3×300mm2 and crimping of proper size Aluminium lugs. Work includes providing insulating tapes etc.
g) Providing and fixing 150mm dia 3 mtr long G.I pipe over 33KV 3x300 mm2 XLPE cable before mounting the cable on double pole structure. This work includes supply & fixing of clamps, Nut bolt, sealing of top and bottom of pipe and one end of pipe is to be buried under earth about 500mm including laying of cable in Pipe.
M/S KUMAR TRADERS KAKA NAGAR
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .