Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.4 CrAccepted-AOC 21 PASCHIM VIHAR EXTENSION NEW DELHI 110 063 | NEW DELHI | WEST DELHI | DELHI | 110063 | ₹4.4 Cr | L1 | Accepted-AOC Being lowest and reasonable |
| 2 | L2₹5.2 Cr+₹83.6 L (19.0%)Rejected-Finance | ₹5.2 Cr+₹83.6 L (19.0%) | L2 | Rejected-Finance Not being lowest |
| 3 | L3₹5.3 Cr+₹87.8 L (19.9%)Rejected-Finance | ₹5.3 Cr+₹87.8 L (19.9%) | L3 | Rejected-Finance Not being lowest |
| 4 | L4₹5.3 Cr+₹93.1 L (21.1%)Rejected-Finance | ₹5.3 Cr+₹93.1 L (21.1%) | L4 | Rejected-Finance Not being lowest |
| 5 | L5₹5.4 Cr+₹1.0 Cr (23.3%)Rejected-Finance 208 2ND FLOOR EXPRESS MARKET AMBEDKAR ROAD GHAZIABAD 201001 UP | GHAZIABAD | UTTAR PRADESH | 201001 | ₹5.4 Cr+₹1.0 Cr (23.3%) | L5 | Rejected-Finance Not being lowest |
Tender Value
₹5.1 Cr
EMD Value
₹5.8 L
Closing Date
11 Feb 2022, 6:00 pmClosed
Chief Engineer Delhi Zone
HQ Chief Engineer Delhi Zone Delhi Cantt
PROVN OF PACKAGE TYPE STP (INCL CONNECTED WKS) FOR MANEKSHAW MARG URBAN VILLAGE AND ADJOINING AREA AND MANNING OPERATION IN DELHI CANTT-10
2021_MES_492833_1
CEDZ-35 OF 202I-22
Open Tender
Civil Works
Lump-sum
365 days
GE U Water Supply
As per NIT
7 documents required · 7 mandatory
₹3,000
GE U Water Supply
₹5.8 L
Yes
16 Mar 2022
6 Dec 2021
14 Feb 2022
6 Dec 2021
11 Feb 2022
28 Jan 2022
Amount
Total amount of Sch 'A' Part - 1 (Construction of Pump House Building complete all as specified shown on drawing.)
Total amount of Sch 'A' Part-III (Internal Electric Supply) (Ref pre priced Schedule attached seperately)
Total amount of Sch 'A' Part-IV (Internal Water Supply) (Ref pre priced Schedule attached seperately)
Total amount of Sch 'A'Part-V (External Electric Supply) (Ref pre priced Schedule attached seperately)
Total amount of Sch 'A'Part-VI (External Water Supply) (Ref pre priced Schedule attached seperately)
Total amount of Sch 'A'Part-VII (Excavation and Earth work) (Ref pre priced Schedule attached seperately)
Total amount of Sch 'A'Part-VIII (Boundary Wall and Gate/ Fencing) (Ref pre priced Schedule attached seperately)
Total amount of Sch 'A'Part-IX (Road Path and Culvert) (Ref pre priced Schedule attached seperately)
Description of Work / Item(s)
Amount
Sch 'A' PART-II (STP)
Design, supply, installation, testing & commissioning of sewage treatment plant based on non clogging moving bed bio reactor (MBBR) aerobic attached growth process sewage treatment plant having capacity of 300 cum/day at Manekshaw marg including all civil works for STP inlcuding all civil work electrical, mechnaical, control and instrumentation works including tapping of existing sewage passing nearby to site of STP, laying of sewage line and sewage sump well with raw sewage pumps and other allied equipments as under for STP as per OEM to achive the parameter as mentioned in Appendix-I to BOQ. Please note the that Appendix 'A' to BOQ Annexure-I & Anneuxre-II is part of BOQ for all purpose
All as per item No 1 (here-in-before) but at Urban Village in Delhi Cantt
Supply and fixing surface Decorative ultra Slim Round Profile LED Lighting fixture and Extruded Policarbonate, Environmental friendly , Energy Efficient 18 Watt connection complete all as specified.
Supply and fixing of Decorative wall light fixture made of Policarbonate, Suitable for 12Watt Spiral CFL B-22 Base connection complete all as specified.
Supply and fixing of energy efficient (5 star rating) ventilation Air fan 200 mm sweep SP 230V , 50Hz, PVC body including louvre and making hole on wall and grouting the same connection complete all as specified
Supply and fixing of energy efficient (5 star rating) exhaust fan 450 mm sweep SP 230V , 50Hz,1400 RPM heavy duty including louvre and making hole on wall and grouting the same connection complete all as specified
Supply and fixing energy efficient (5 star rating) ceilling fan 1200 mm sweep Single pole 230V , 50Hz complete with fan regulator and down rod connection complete all as specified
Supply, Installalation and testing of water cooled Diesel Engine driven Prime duty Generating Set of net capacity after all derating factors net of not less than 62.5 KVA/50 KWe ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg, 84 hp minimum Required Power for Rated kVA (hp) along with AMF system with Acoustic Enclosure exhaust silencer-residential in line , as per the noise emmission standards liad down by MoEF / CPCB Norms.
A) Engine comprising of the following: Rugged engine natural liquid cooled (EG Compleat 50:50) with radiator as secondary media with world class OEM such as Cummins/Perkins/Kohler/Greaves/Ashok Leyland Engines for powered diesel generator set along with these specifications of Advanced in-cylinder technology turbo charged , air cooled aspriated to meet latest emission norms without any after-treatment device. Class defining technology engine is designed to meet stringent exhaust emission tests as per revised MoEF norms, thus offering environment friendly powe Compact in size with optimum power to weight ratio, 4 cylinder, In-line 4 stroke, radiator cooled engine Well designed air handling system with Dry type, heavy duty, replaceable paper element aircleaner with restriction indicator, Air to air aftercooling, Optimised turbocharger for increased altitude capabilities, Best in class fuel economy with Inline fuel pump with A1 class mechanical governing, Spin on fuel filter, Standard integral set-mounted radiator system, designedand tested for 50°C ambient temperature,Full flow spin on lube oil filte,First fill of lube oil and coolant, Electrical starter motor with soft start engagement feature, Battery charging alternator,1 x 12 V DC battery/Alternator
b) Alternator PMG type comprising of the following: Stamford UC/jyothi/crompton alternator frames from Technologies Brushless type, Screen protected, Revolving field, Self excited alternator conforming to IS/IEC 60034-13 Phase reconnectable winding with 12 terminals brought out for connection Dedicated winding specially designed for 1 phase and 3 phase operation Better motor starting capability Best in class efficiency Compact design with sealed bearings for longer life and lesser maintenance Impregnation on all wound components for better mechanical strength with Alternator of IP 23, Voltage regulation (Max.)±1%, Class of Insulation H Class, Winding Pitch 2/3,Stator Winding Double layer lap Rotor Dynamically Balanced, Waveform distortion/ Total Harmonic Distortion No load < 1.5 %, Non distorting balanced linear load < 5 %,Maximum Unbalanced Load across phases# less than or equal to 25%, Telephonic Harmonic factor < 2% alternator capacity output shall not be less than 62.5 KVA / 50KWe ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg. 87 Amp / phase
Control Panel comprising of the following: c) AMF / Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish.The control panel consists of the following parts of makes as per OEM recomendation: microprocessor based generator set monitoring and control system. along with AMF Functionality is inbuilt and this control includes an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration, and diagnostics, Copper bus bars with suitable capacity with incoming/outgoing terminals, Indicating lamps for ‘Load ON’ and ‘Set Running’,Instrument fuses / MCBs duly wired and ferruled, Circuit breakers of suitable rating with overload and shortcircuit protections. with motorised change overs /on load power contactors with copper busbars, cables and protective acessories with load / bypass arrangements
Resednetial type silencer Critical grade silencer suitably optimized to meet stringentnoise emission standards laid down by MoEF / CPCBalong with MS supporting structures .along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gauge aluminium cladding (12")
d) Controller should be compatable to the following specifications: (i)AMF Functionality controllers of Makes from the OEM : Deep Sea/ Cummins/ Wood Ward/ Com Amp (II) Intuitive operator interface which includes LED backlit128X64 pixel graphic display with tactile feel soft-switches.Indications - Generator set, Utility Status Lamp. (iii)Remote start-stop with Engine Metering: Oil pressure, Engine temperature, Startingbattery voltage, Engine running hours (iv)AC Alternator Metering: L-L Voltage and L-N Voltage,Current (phase and total), kVA (phase and total) andFrequency. kwh, Total & per phase (kw & kVA), PF, UtilityVoltage and Freq. (v)Engine Protection: Low lube oil pressure, High/Low coolanttemperature, Battery Over/Under/Weak Volts, Fail to Crank/Start, Sensor failure, Cranking lockout, Low fuel level. (vi)AC Alternator Protection: Over/Under Voltage, Over/UnderFrequency, Loss of AC sensing. Overspeed, Over Current. (vii)Data Logging: Engine hours, Control hours and upto 5 recent fault codes (viii)Configurable glow plug control, Cycle Cranking (ix)12/24 Volt DC operation,Sleep mode,Modbus interface (RS485 RTU),InPower compatible (PC based service tool),Certifications - meets the requirement of relevant ISO, EN,Mil Std. and CE standards (e)Maintenance due alarm based on Engine Run Time and duedate,Exercisor scheduler (f) Remote HMI, Digital electronic governor with temperture compensation and smooth starting, digital AVR for shunt of PMG excitor with Torque monitoring
(e) All pipe line connections, valves etc.required for the lube oils, fuel and cooling system
(f) Battery & Battery charger of rated capacity as per the alternator/ Engine compatability
(g) Mounting Arrangement shall be of the following: (i) Engine and alternator are mounted on a common MSfabricated base frame with AVM pads. (ii) Base frame with integral fuel tank is provided with drainplug, air vent, inlet and outlet connection, level indicator andprovision for cleaning
(h) Fuel Tank of capacity 12 hrs running capacity along with Fuel pipe MS c class 25mm ID with bends , flanges , valves, tees and bends.
(I) Residnetial type silencer with MS pipe as designed by the OEM horizontal Exhaust pipe complete with bends and flanges of adeeaquate length not less than 10 Mtr.along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gauge aluminium cladding (12")
(j) Controll / service cables shall be of 4cx 2.5 sqmm, 24 c x 2.5 sqmm , 2 c x 2.5 sqmm, and 8c x 0.75 sqmm shielded control cables ,pvc insulated copper armoured, controll panel for auxilaries with starters for pumps,heaters etc
(k) RCC foundation with necessary earth work ,PCC 1:4:8 type D-2 (40mm graded stone aggregate) as in foundation, filling and mass concrete / RCC M-30 (20 mm graded aggregate) as in foundations, Plinth beam along with necessary form work / TMT bars of 10mm dia and over cut to length bend to shape required including cranking, bending, spirally for hooping for columns, hooking ends and bidning with and including MS wire (annealed) not less than 0.9mm dia securing with clips / 10 mm thick plastering on fair faces of brick work or concrete surface in CM (1:6),even and smooth without using extra cement / Sand filling in layers around the foundation including watering and consolidation as per OEM dimensions
(l) Acoustic Enclosure shall comprise of the following (i) Specially designed to meet stringent MoEF/ CPCB norms of75 dBA @ 1mtr at 75% load under free field conditions (ii) The Acoustic Enclosure as per CPCB Norms is made of CRCA sheets in Munselgreen shade and a structural/ sheet metal base frame painted in black. or any other standard colour as specified by the OEM (iii) High quality noise absorbant and fire-retardant gradeacoustic insulation material (P.U. Foam) complying to IS8183 designed to have optimum serviceability (iv) Air inlet louvers specially designed to operate at rated load, Made on special purpose CNC machines for consistency inquality and workmanship (v) 11 tank pretreatment process and UV resistant powdercoating of all parts to withstand extreme environment, Use of special hardware for longer life, Flush styling - no projections, Fluid drains for lube oil and fuel,Fuel filling arrangement inside the enclosure
Supply & fixing in replacement of SMC Junction box for street light having side hinged, outside dimention 333x233x120mm and inside dimention 300x200x105mm including 4 Nos aluminium bus bar of 40 Amps rating and 1 No 5 A MCB SP connecting of existing LT power cable complete all as directed
Labour for drilling hole under the road with the help of bocki / by manual or by machine for crossing GI tubing of any size for cable protection all as specified and directed by EIC.
Supply , fixing and commissioning of LT Panel Out door LT Panel / LT Pillar Box of comprising of the following all as directed
Fabrication Details : Main frame 3 mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom for installation, seperate chambers for Main Bus Bars, MCCBs /ACB and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for doors and locking arrangements with Aldrops at front and Back Bus bar details : Material shall be alluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for phase 1.5 times the Rating of incommer MCCB /ACB and out going shall be of rated capacity and bus bar shall be support of epoxy type insulators , earthing of 40x6 mm GI Flat.
Painting Detais : Painting shall be 7 tank processed powder coated shall be a dry finishing process that uses finely ground particles of pigment and resin based polymer that are electrostatically charged and sprayed onto electrically grounded parts
Wiring : Pannel wiring shall be of 2.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps
Accessories for Pillar Box : Digital Multifunctional Meters CT/PT programmable with RS 485 communicatio port CL 0.5 with direct acess to basic power and Energy parameters and Indication Lamps (LED) - 03 No. make: L&T cat no WL440531OOOO or equivalent in Secure /Elmeasure
Switch Gears: (a) Incommer:- 200A Onload Change over Switch,MCCB 160 A, 4 pole,36 KA-1No along with sprader terminals Make: HPL /or equivalent in Schnider/Simens
(b) Outgoing:-(i)125A,MCCB 3 pole 25 KA MCCB along with sprader terminals along with sprader terminals-1 no,s Make: HPL/or equivalent in Schnider/Simens (ii) MCB 3 Pole 25 A -05 Nos,,MCCB are along with sprader terminals along with sprader terminals-4 no,s Make:HPL / or equivalent in Schnider(iii) MCB SP 10 A -01 No (iv) DOL Starter 7.5 HP-02 Nos
Note : Rate quoted includes for necessary PCC foundation of LT pannel and includes the cost of all Accessories and switch gears
Supply and fix highly efficient high power 45 W LED street light fitting with pressure die cast aluminium housing reflector and enclosed with heat resistant toughened glass IP65 protection AC 240 Volts 50 HZ refractive lens with suitable electronic drive PF > 0.9 complete including taking exiting unserviceable street light fitting. Make: CG cat No. LSTO-45-CDL/ Halonix Cat part No HLSLD-09-45-CWL/ Surya Cat Part No SLEUL45WIP66LXN
Supply and fixing Automatic Light Timer switch with Nature switch Cat No. SWADEEP-02EC12KW3P, infra ray sensor with pre sawn switching off timer, 4-8 hrs, of Maximum load capacity of 4KW per phase. Degree of protection conforms to IP 65 complete all as specified and directed.
M & L for 2 coat of aluminium painting over a coat of red oxide to steel surfaces of HT/LT pcc pole or MS 2/4pole sturcture (Angle Iron/MS channel /MS clamp etc) including preparation of old surface complete all as specified.
Supply and fixing of new generation energy saving& enviroment friendly aluminium pressure die cast high power LED flood light luminare of wattage 150 Watts of IP66,class I portection integral driver operation at 170-270VAC 50Hz supply inclding , brackets for fixing on the pole/buildings/walls complete all as specified and directed.
M&L for MS pipe header 200mm dia size 6.3mm thick 3 mtr length with flanged ends closed with end plates not less than 20 mm thick fixed with and including provision of 1 incoming and 5 outgoing upto 150mm dia borebore with flanged end including painting with two coat of red oxide primer all as specified and as directed by Engr-In-Charge.
Supply and fix pipe ERW steel including specails, nominal dia. 100 mm as per IS 3589 (1981) thickness 6.0mm complete all as specified and as directed by the Engr-In-charge.
Supplying and fixing, MS flanges of size 100 mm bore bore not less than 16 mm thick duly welded on ends of MS pipe all as specified and directed by Engr-in-Charge.
M&L for Flanged Joints of size 100 mm dia with rubber or fibre board gasket including nuts, bolts and double washers complete all as specified and directed by Engr-in-Charge.
Supply and laying of 3 layers (inner animicrobial),outer UV stabilized ) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fitting in trenches/walls/cellings or laying in floors inluding fittings and jointing material with standard euipment complete of size 25 mm.
Making bore hole under the road, pavement, hard standing any type of soil through trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 MPA working pressure complete all as specified and as directed by the Engr-In-charge)
Making bore hole under the road, pavement, hard standing any type of soil through trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 200 mm dia suitable for 0.4 MPA working pressure complete all as specified and as directed by the Engr-In-charge)
Supply and fixing CI 100mm foot valve rating PN 0.2 flanged ends, swing type opration with rubber sheet, as per IS:4038 including taking out unsv foot valve all as specified and directed by Engr-in-Charge. Note:- Flanged joints complete with jointing material shall deemed to be included in the unit rate of this item.
Supply, fixing, jointing and testing non clogging three phase submersible pump set of 7.5 HP capacity having mtr 10-21 mtr head, 400-600 LPM,sucion X delivery (100 X100), sand holiding capacity 30mm. Including starter & cable connection complete all as specified and directed. Make:KSB/Crompton/Kirloskar)
Supply fixing commisioning and testing of three phase, electric driven 4 WHP centrifugal monoblock pump set having having 10-16 mtr head with 3000 rpm ,suction X delivery (100 X100),600-800 LPM inclusive of starter,cable,pressure gauge,one working and one stand by each location (4 WHP x 4) complete all as specified and as directed at site by the Engineer-in-Charge. (Make:KSB/Crompton/Kirloskar)
Supply & fixing for mild steel work of MS angle /flats/channels etc including cutting of top and botttom to shape as directed,drilling holes & welding work etc and similar works confirming Fe-290,Gde E-165 complete all as specified and as directed.
Cutting of road /Hard standing to a size of 30 cm in width and not exceeding 90cm in depth for laying of pipes including spreading, leveling, watering and well ramming in layers and providing PCC in 1:2:4 type B1 using 20mm graded stone aggregate, for the top 100mm layer, complete all as specified and directed.
Supply, installation and testing flanged ends strainer/dirt box for non clogging submersible pump set of 100mm dia bore with stainless steel mesh suitable for cold water meter to avoid foreign material entering into meter and making good connection with flanged ends, with gasket rubber sheet and nut & bolts fixing in horizontal/inclind/vertical position, including taking out unsv strainer/dirt box complete all as directed at site by the Engr-in-Charge. Note :- Flange joints including jointing materials shall deemed to be included in the unit rate of this item.
Description of Work / Item(s)
Amount
Manning and Operation of Sewage treatment plant(Manekshaw area) having capacity 300 Cubic meter/day at Manekshaw Marg installed under item No 1.00 under Sch 'A' BOQ-2 during defect liability peroid for the duration of 24 hours in 03 (Three) shifts ie. For Ist Shift from 0600 Hrs to 1400 Hrs, IInd shift from 1400 Hrs to 2200 Hrs and IIIrd shift from 2200 Hrs to 0600 Hrs per day (with deploying one well experienced operator in each shift) for Ist year from next date of certified date of completion of phase-II, complete all as specified and directed .
All as per item No 1 above but for STP installed at urban Village against item No 2 of BOQ-2
All as per item No. 1 above but for 2nd year
All as per item No. 2 above but for 2nd year
All as per item No. 1 above but for 3rd year including comprehensive maintenance after defect liability peroid.
All as per item No. 2 above but for 3rd year including comprehensive maintenance after defect liability peroid.
All as per item No. 1 above but for 4th year including comprehensive maintenance after defect liability peroid.
All as per item No. 2 above but for 4th year including comprehensive maintenance after defect liability peroid.
All as per item No. 1 above but for 5th year including comprehensive maintenance after defect liability peroid.
All as per item No. 2 above but for 5th year including comprehensive maintenance after defect liability peroid.
Note for item No 1 to 10 above : (i) Water and Electric required for operation of plant shall be provided free of cost by the Department. (ii) All Consumable such as Sodium Hypochlorite and any other chemical required, compressure oil and grease etc required for operation of plant shall be provided by contractor at his own cost as per the manufacturer's instruction and direction of GE during the period of manning & Operation, cost of the same shall be deemed included in the unit rates quoted by contractor. (iii) Please ensure that all trade men engaged in subject work covered in EPF scheme. Proper doc should be maintained in this regard and submitted alongwith each payment. (iv) The expense incurred due to insurance and EPF scheme for the staff deployed by the contractor for manning & operation shall also be deemed included in the quoted rates of BoQ. Nothing extra shall be admissible in this account. (v) Contractor’s quoted rate shall be deemed to include removal of dried sludge and its disposal outside MD land during the M&O period as directed by Engineer-in-Charge. (vi) Testing of of incoming sewage and treated sewage shall be done by the contractor from any Govt. approved lab as approved by GE on a monthly basis during the M&O period and test report shall be submitted to GE. Contractor’s quoted rate shall be deemed to include for the same. (vii) In case contractor fails to employ the duty personnel in any of the shift, he shall be liable to bear the recovery @ Rs 1500/- per shift and No payment shall be made for that shift.
M/s R. K. Bhambri
United Sales Corporation
Chauhan Associates
AMIT ASSOCIATES
M/s JAIMAA ASSOCIATES
AMIT ASSOCIATES
Chauhan Associates
M/s JAIMAA ASSOCIATES
VADERAS INTERIORS AND EXTERIORS
United Sales Corporation
M/s R. K. Bhambri
Chauhan Associates
AMIT ASSOCIATES
VADERAS INTERIORS AND EXTERIORS
United Sales Corporation
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .