Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 108 BADA CHAKA NAINI ALLAHABAD | ALLAHABAD | PRAYAGRAJ | UTTAR PRADESH | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹46.9 L
EMD Value
₹46,000
Closing Date
1 Oct 2020, 12:00 pmClosed
SE EUCC(V) LESA LUCKNOW
Lesa Bhawan Near Residency kaiserbagh Lucknow
Construction of 33 KV Single Circuit O/H feeder from 132/33 KV Khujehta to Khujauli Chauraha for 33/11 KV S/S Mohanlal ganj and re-coundoctoring of existing 33 KV Interlinking line (from Khujauli chouraha to 33/11 KV S/S Mohanlalganj) Route Len
2020_MVVNL_514081_1
15/EUCC(V)/LESA/2020-21
Open Tender
Electrical Works
180 days
Khujauli chouraha to 33/11 KV S/S Mohanlalganj
As per tender documents
2 documents required · 2 mandatory
₹3,540
A/c. No. 10101985364,IFSC CODE No. SBIN0003347,SBI
₹46,000
10 Nov 2020
23 Sept 2020
1 Oct 2020
23 Sept 2020
1 Oct 2020
23 Sept 2020
Amount
Safe loading & carriage including unloading & proper stacking of following store materials from ESC Daliganj/JE store to site of work.
ACSR PANTHER CONDUCTOR
33 KV V-TYPE X-ARM CHANNEL 100X50MM
ST POLE 11 MTR LONG
MS EARTHING ROD 20X2500 MM
DISC FITTING FOR PANTHER
STAY WIRE 7/8 SWG
TOP CHANNEL 125X65 MM
MS ANGLE 65X65X6
GI WIRE 6 SWG
MS CHANNEL 100X50 MM
STAY SET 20X1800 MM
33KV 3X300 SQ MM XLPE CABLE
33KV END TERMINATION O/DOOR 3X300 SQ MM
33 KV ST/TH C/J KIT 3X300 SQ MM
MS CHANNEL 125X65 MM 13.10KG/MTR
33 KV PIN WITH NUT
33 KV PIN INSULATOR
11 KV DISC INSULATOR B&S 70 KN
Fabrication & erection of single pole for 33 KV line on 11 M long ST Pole with fixing of necessary clamp & other acessories like 1 no. Channel cross arm, Danger board, No Plate, barbed wire etc. contractor shall provide, necessary clamps, F-Bracket etc. as per RESPO norms.
Fabrication & erection of 33 KV cable exposure type double pole with the provission of separate bus bar for each cable with fixing of necesory clamps and other acessories like danger board,number plate,barbed wire, 9 no. pin insulators with pins,2 no. channels 125x65 mm (1600mm each),1 no.MS channel 125x65mm(3200mm in length) and 2 no.MS angle 65x65x6 mm (each 3200mm in length ) for supporting the hoisting of cable & poles.its jumpering by single core PVC aluminium cable with proper size of lug. (all material arranged by contractor except steel,pole,PVC aluminium cable & insulator).as per RESPO norms.
End Type Double Pole- Fabrication, erection, of double pole of end terminations with one side cable exposure for 33 KV line on 11 M long ST pole with fixing of necessary clamps & other accessories like disc insulator, 1 no. top chennel 125×65 mm - 3.20M & 1 no. gaurding angle and 1 no. X bracing,disc fittingits,33kv pin with pin insulator ,danger board,number plate,barbed wire,jumpering by PG clamp 4 no stay complete work (all material arranged by contractor except steel,insulator,disc insulator with fitting & pole).as per RESPO norms.
Sectional Double Pole-Fabrication, erection, of double pole for 33 KV line on 11 M long ST pole with fixing of necessary clamps & other accessories like ,disc insulator, 1 no. top chennel 125×65 mm - 3.20M & 1 no. gaurding angle and X bracing,disc fittingits,33kv pin with pin insulator ,danger board,number plate,barbed wire,jumpering by PG clamp 8 no Stay set etc.(all material arranged by contractor except steel,insulator,disc insulator GI Pin, Disc Fitting & pole).as per RESPO norms.
Fabrication, erection, of Tri pole for 33 KV line on 11 M long ST pole with fixing of necessary clamps & other accessories like ,disc insulator, 3 no. top chennel 125×65 mm - 3.20M & 2 no. gaurding angle and 3 side X bracing,disc fittingits,33kv pin with pin insulator ,danger board,number plate,barbed wire,jumpering by PG clamp 8 no stay set etc. (all material arranged by contractor except steel,insulator,disc insulator GI Pin, Disc Fitting & pole).as per RESPO norms.
Conversion of existing single pole support into Double Pole-Fabrication, erection, of single pole in alignmnet of existing single pole to convert into double pole pole for 33 KV line on 11 M long ST pole with fixing of necessary clamps & other accessories like ,disc insulator, 1 no. top chennel 125×65 mm - 3.20M & 1 no. gaurding angle and X bracing,disc fittingits,33kv pin with pin insulator ,danger board,number plate,barbed wire,jumpering by PG clamp etc. (all material arranged by contractor except steel,insulator,disc insulator GI Pin, Disc Fitting & pole).as per RESPO norms.Dismantling of accessories of existing pole like X-arm 33 KV pin insulators and pins etc also include in this work,
Making Section & Holding of exsting 33 KV overhead line on exsting D/P or S/P for enabling removal of conductor on one side of 33 KV overhead line ,its stringging on D/P .(agency also to provide temporary stay at the time of dismantaling of overhead line)
Erection of single stud pole support one ST pole 11 M long with fixing of necessary clamps and other accessories required for erection.
Dismantling of ACSR Raccoon conductor of existing 33 KV line its rerolling and proper stacking at site
Dismantling of accessories from 33 KV Single pole support/double poles/ end type double poles of existing 33 KV line
33 KV V-type X-Arm
33 KV GI Pin
33 KV Pin Insulator
33 KV Disc Fitting
11 KV Disc Insulators 70 KN
Top Channel
E-clamp
Fixing of following accessories in place of above dismatled accessories(only x-arm pin and insulator provided by deptt.)
33 KV V- Type X-Arm Channel 100x50 mm
33 KV Pin Insulator
33 KV PIN WITH NUT
F-bracket
11 KV disc Insulator
33 KV Disc Fitting for Panther(provided by contractor)
Top Channel 125x65 mm 3.2 M long
GI barbed wire on poles
E-clamp
Regrouting and replinthing of existing pole
Laying of 33 KV XLPE Cable.
Tagging of 33 KV cable(i.e Name of feeder and S/S)
D/C Cable laying in normal soil by digging of trench 1050 mm deep, 750 mm wide including supply of required material as fine sand, 1st class bricks, stone slab. Inter axial spacing between the two cable should be in between 0.25 m to 0.40m. the two cables should be seprated by a partition of single bricks (All the material required for laying will be supplied by the contractor except 33 KV XLPE cable)
Laying of 33 KV Single cable in normal Soil
Cable laying By dirll method Single circuit
Cable laying By dirll method Single circuit with MS pipe
In RCC pipe single circuit.
In MS pipe single circuit.
In HDPE Pipe 160 mm Dia
Laying in already existing trench S/C
Fixing of cable marker
Hoisting of 33KV XLPE cable on double pole with MS pipe of size 5/6" dia 3 M long including its jumpering complete with clamps, nuts and bolts(all material arranged by contractor).
Hoisting of 33 KV Cable on cable stand
Stringing & Sagging of three phase 33 kv line on ACSR Panther conductor as per RESPO Norms.
Stringing and sagging of three nos. Earth/GI wire withh caddle guarding of above 33 kv line as per RESPO Norms. Including provision of all necessary clamps and hooks. Shifting of existing line conductor of 11 Kv/LT lines to maintain proper clearence in between both lines.
Guarding of O/H Line (40-50 Mtr span)- Fabrication and fixing of gaurding angle on single/double Poles.Stringing & sagging of three nos ,Earth/G.I. wire with cradle gaurding of above 33 KV Line as per Resspo norms includingprovision of all necessary clamps and hooks.Shifting of existing line conductor of 11 KV/LT lines to maintain proper clearence in between both Lines.(all the material arranged by contractor except steel and GI wire 6 swg)
Ordinary Earthing of pole by M.S. Earthing Rod 20x2500 mm as per Resspo Norms (only MS earthing rod shall be provided by Deptt)
Ordinary Earthing of pole by M.S. Earthing Rod 20x2500 mm as per Resspo Norms( all the material arranged by contractor)
Extra Stay Set - Nozzillling & grouting of stay set .(all the material except stay set will be arranged by the contractor )
Fabrication erection grouting plinthing & painting of cable stand on MS channel 100x50 mm (Only MS channel provided by deptt)
Grouting,Plinting and Painting of new erected 11M long ST poles of single pole support,double pole cable exposures and end type poles of 33 KV lines
Digging of Pit in kachcha/Pakka land in depth upto 1/6 length of Pole, Dragging of STP from near by place/Dump, Erection of Single pole along with stone pad in bottom with proper alignment of line for 33 KV line on 11 M long ST Pole and refilling with ramming of earth.
Grouting of pole in depth of 1/6 the length of pole in ratio 1:4:8 in cement sand and brick balast as per RESPO norms.
Construction of pole plinth 300mm x 450 mm above ground level in 1:2:4 in cement, coarse sand and stone gritt as per RESPO norms.
Painting of new erected ST pole with two coat of red oxide paint,PO red paint at top of pole 2 M & balance by two coats of best quality aluminium paint ISI of Burger/Nerolac/Asian mark as per norms.
Painting of old existing RS Joist/Rail Poles/ST Pole of 33 KV Line
Painting of Old existing RS Joist/Rail Poles/ST Pole with two coat of red oxide paint,PO red paint at top of pole 2 M & balance by two coats of best quality aluminium paint ISI of Burger/Nerolac/Asian mark as per norms.
High Pressure Testing of 33 KV cable as per Norms
Safe loading/unloading/weighing carriage of dismantled material from dump/work site to je"s store/ESC daliganj .
RS Joist Scrap
ACSR Raccooon conductor
Steel material(Topchannel/x-arm and other steel material)
Tree branches cutting and chopping where required aprox 2 KM .
RAJ ENTERPRISES
CHAUHAN ELECTRICALS
M/S INDIA ELECTRICALS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid