Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.5 LAccepted-AOC | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹27.3 L+₹3.3 L (14.0%)Rejected-Finance | L2 | Rejected-Finance Not being lowest |
Tender Value
Refer Docs
EMD Value
₹56,000
Closing Date
3 Mar 2021, 6:00 pmClosed
GE, Minniebay, Junglighat (PO), Port Blair -744103
GE, Minniebay, Junglighat (PO), Port Blair -744103
REPAIR MAINT OF EXTERNAL WATER SUPPLY DISTRIBUTION SYSTEM, PUMP SETS AND ALLIED WORKS CLEANING OF UG SUMPS SERVICEABLE TANKS AND CONNECTED WORKS AT NTS MARCOS AREA AND NAD, DAD AREA AND REPAIR AND MAINT OF DG SETS, ACBS AND APFC PANEL AND CONNECTE
2020_MES_406915_2
8906/E8
Open Tender
Civil Works - Water Works
Item Rate
180 days
GE, Minniebay, Junglighat (PO), Port Blair -744103
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE Minniebay
₹56,000
Yes
31 Mar 2021
17 Feb 2021
5 Mar 2021
17 Feb 2021
3 Mar 2021
17 Feb 2021
Amount
M&L for detecting and repairing leakage in CI/DI pipe lines of size 150mm / 100mm / 80mm bore, taking up unserviceable /serviceable CI/DI water main with spigot and socket ends (including fittings) of any type/grade and joints from trenches and laying new CI/DI pipe lines of size 150mm / 100mm / 80mm bore in trenches or placing on existing pillars / supports as directed and specified to including the following:-
Execution and earth work in soil / mud by using machinery / labour to suitable length (Appx 10 mtrs) and forming bund with excavated soil to avoid sea / raw water entering into the working area including pumping / bailing out water by using portable disel engine driven pump set.
Cutting of CI / DI pipe of size 150mm / 100mm / 80mm bore after through inspection for the damaged pipe line including disconnecting / dismantling.
Taking out CI/DI pipe with CI/DI specials after removing from joints/burning out joints and removing lead at both ends with the help of hydraulic crane / other machinery and keeping aside for further disposal.
Cutting of new pipe into pieces as per requirement and laying using machinery.
Alinging the pipe line as per site condition, in setting the CI Collar suitable for 150mm / 100mm / 80mm CI/DI pipe.
Attending repair work within the minimum time frame/period as specified by Engr-in-charge.
Notes for Items No 01 above :- (a) The unit rate is deemed to include cost of tools and plants and transprtation required for attending the repair work. (b) Supply only CI/DI pipe shall be measured & paid for seperately under relevant item of this schedule. (c) Extra soil required for refilling / making bunds to prevent water entering into the work place shall be deemed to include in the unit rate. (d) Specials / rubber or fiber/ lead joints shall be measured and paid seperately under relevent items of this schedule. (e) Old unsv CI/DI pipes, fittings, lead, nuts, bolts, washer, gaskets etc. shall become contractors property and necessary recovery as per schedule of credit shall be deducted from contractor.
M&L for attending of water supply complaints for any leakage/blockage in GI pipe lines of size 20mm/25mm bore taking up serviceable / unserviceable GI water pipe lines with all fitings/fixtures from trench including supply and laying GI tubing 20mm/25mm bore up to 1 mtr length (max) including necessary cutting, treading and replacement of unserviceablel GI fittings such as GI socket /Nipple/union socket, Tee, Tee reducer etc. of size 20mm/25mm including necessary exevation and earth work upto 1 mtr length to repair the leakage/clearing the blockage in the pipe line and testing on completion complete all as specified and as directed.
All as per item No 2 above but of size 40/50mm bore GI pipe line complete all as specified and directed
All as per item No 2 above but of size 80/100mm bore GI pipe line complete all as specified and directed
All as per item No 2 above but of size 20/25mm bore GI pipe lines on wall/floor/roof complete all as specified and directed
All as per item No 2 above but of size 40/50mm bore GI pipe lines on wall/floor/roof complete all as specified and directed
All as per item No 2 above but of size 80/100mm bore GI pipe lines on wall/floor/roof complete all as specified and directed.
Note for item No. 2 to 7:- (a) The break down complaint shall be attended within 2 hours after the intimation of Engr-in-charge or concern JE E/M by telephonically / verbally / by writing. (b) Not attending of complaint within two hours after intimation shall lead to recovery from subsequent payment in the following manner :- (i) Attending within 2 to 4 Hours - Rs. 2000.00. (ii) Attending within 4 to 6 Hours- Rs. 4000.00 (iii) Attending within 6 to 8 Hours- Rs. 8000.00. (iv) Attending after 8 Hours - Rs. 10,000.00 (v) The maximum recovery will be Rs. 50,000.00 plus the expenditure incurred for rectification of the same by any other means.
Excavating in trenches in soft / loose soil, n.exc 1.5m wide and n.exc 1.5m in depth: for foundation, etc. or for shafts, wells, cessapits, manholes, pier holes, etc. n.exc 10 Sq.m on plan and in.exc 1.5m in depth and getting in soft/dense soil out all as specified and directed.
Returning, filling in, using excavated soil including spreading, levelling watering and well ramming in layers n.exc. 25cm as specified and as directed.
Removing the surplus excavated material to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above starting point.
S&F in replacement tubes medium grade galvanized with all fittings, laid in trenches/fixed on wall/on roof etc of the following sizes all as specified as directed :-
20mm dia
25mm dia
40mm dia
50mm dia
80mm dia
100mm dia
M&L for Ductile Iron pipes with spigot and socket ends centrifugally cast class K-7 of any length, laid in trenches of following sizes all as specified and directed :-
80mm bore
100mm bore
150mm bore
Supply and fixing in replacement Gun Metal, globe or gate valves with iron wheel head, screwed both ends for iron pipe and fixed of the following sizes all as specified and directed :-
20 mm bore
25 mm bore
40 mm bore
50 mm bore
80 mm / 100 mm bore
Supply and fix in replacement of flanged type Sluice valve hand wheel operated CI Body with SS spindle PN-1.0 rating, IS-14846 of following sizes all as specified and directed :-
80mm bore
100mm bore
150mm bore
S&F in replacement of CI/DI Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot or flanged) collars, caps and plugs upto 150mm bore all as specified and directed
S&F in replacement joint with rubber or fiber board gasket (flange joints) suitable for flanged pipes and fittings of the following sizes :-
80mm bore
100mm bore
150mm bore
S&F Gland packing 10/12.5mm dia / thick for sluice valve / pumps all as specified and as directed
Taking down UNSV sluice valves and Re-fixing the same in its original position/location with flanged ends including necessary cleaning, resetting & minor repairs for its smooth functioning , any pattern of following sizes :-
Repacking stuffixing box of sluice valve spindle including taking apart and reassembling of the following sizes:-
S&F in replacement rubber gasket joint suitable for spigot and socket pipes and fittings for the following size as specified and directed.
S&F in replacement Run lead joint suitable for CI / DI spigot and socket pipes and fittings for the following size as specified and directed
Taking down UNSV/rusted MS ladders of any size / type from site and transporting to store yard for further disposal complete all as specifid and as directed.
M&L for fabrication of mild steel (MS) Ladder at local civil work shop made out of angle iron of size 65X65X6mm for main member, 50X50X6mm for steps and 40X40X5mm for support to existing wall of the building including necessary cutting, welding, grainding etc, the distance between two concecutive steps shall be 0.30 mtr, the distance between 1st step and ground level shall be 1mtr and over all width of the ladder shall be 0.68 mtr,total length of the ladder shall be suitable for multi storey bldgs viz G+1 , G+2 and G+3 / under ground sump as required & transporting to site in Minniebay Area, grouting the ladder in ground (at various locations of Ajay Baugh and Srinagar area) and grouting the supporting angle iron member with existing wall of the bldg with PCC 1:2:4 and top of the ladder shall be supported with parapet wall/top slab of the bldg including painting with two coats of synthetic enamel paint black/smoke grey colour/shade over a coat of red oxide primer all as specified and directed
Supply only tyton joint suitable for spigot and socket pipes and fittings for the following size complete all as specified and as directed.
80 mm dia
100 mm dia
150 mm dia
S&F in replacement Ball valves high pressure of PTMT with epoxy coated Aluminium rod & high density plastic ball screwed for iron pipe and fixed (minimum weight 20mm - 210 gms/25mm - 455 gm ) all as specified and directed
20mm bore
25mm bore
S&F in replacement of Rotational moulded polyetheylene (HDPE) Water Tanks, Cylindrical & Vertical Type, double layered, ISI marked, hoisted and fixed in position including provision of 40mm / 25mm dia spouts for connecting inlet, outlet, over flow and washout pipes complete including taking down old tanks and removing to store complete all as specified and as directed of following capacities :-
500 Ltr capacity
1000 Ltr capacity
5000 Ltr capacity
Cleaning of service tanks installed on roofs of multistoryed buildings at various places by emptying the tanks, removing scale, dirt and all other foreign materials deposited inside nipples, on side of walls and bottom of the tanks by scrapping and brushing with wire brush , and pressure pump, cleaning with bleaching powder slurry and allowed to dry and then washing the tank with fresh water, Checking and removing Airlock if any on next day after cleaning of the tank, cleaning of vegetation, etc, on surrounding RCC slab where the tank is resting and writing on the tank the date of cleaning, capacity of tank, etc, with synthetic enamel paint of 10 cm high and 6 cm width letters in white color, over a black background of size 450mm x 300mm complete all as specified and directed for the service tanks of capacity as shown below :- Notes :- Rate quoted is deemed to be including the following :- (a) Maintenance of Register with details of tanks cleaned with building No, and provisions of signature of Users, JE, AGE, Contractor & Remarks. (b) Sample testing by NABL Accredited Laboratory for Microbial parameters of water of two tanks for each Area / Location as decided by GE before and after cleaning of tank.
Tanks of capacity exc 500 Ltrs and not exc 750 Ltrs
Tanks of capacity exc 750 Ltrs and not exc 2000 Ltrs
Tanks of capacity exc 2000 Ltrs and not exc 5000 Ltrs
Dismantle the broken valve chamber of size 1.50 x 1.50 x 1 mtr and made new valve chamber with brick in cement mortar 1:6 , with PCC 1:3:6 type C2 (using 40mm graded aggregate) for sub-base, plaster internally and exposed external surface in cement mortar 1:4 (15 mm thick and provision of valve chamber cover made out of MS sheet 3.15 mm thick welded on angle iron frames 40 x 40 x 5 mm made out to size 1.50 x 1.50 in double door type with hinges with locking arrangement duly painted with 2 coat of synthetic enamel paint over a coat of red oxide primer all as directed including removing u/s chamber cover complete all as specified and as directed.
All as per item No 28 above but valve chamber of size 0.90 mtr x 0.90 mtr x 1mtr complete all as specified and as directed.
M&L for providing cement cocrete Type B1, 1:2:4 (using 20mm graded aggregate) as in coping, bed plates, etc. all as specified and directed.
Cleaning and replacement of filter media in filteration by removing old filter media with bleaching powder slurry and clear water incuding discarding of unusable filter media and disposing off same to a distance exc 500m and n exc 1km, scraping the internal surfaces of filter tank with wire brush, cleaning with bleaching powder slurry, cleaning with fresh water and refilling up of cleaned filter media alongwith new filter media as described in this schedule item here -in-after in layers as per existing filter bed complete all as specified and directed. Note:- Supply of new filter media shall be measured and paid separately under relevant item of this schedule.
Supply only filter media of size 1/8 to 1/6 to 1/32 inch complete in layers as per existing filteration plant for balancing the retrived media complete all as specified and as directed. Note:- The filter media shall be provided to match with the existing one of each filtertank and as per sample available at NAD Filter plant
M&L for Painting to external surface of Pressure Filter Plant unit including connected pipes (size of 150mm dia), valves etc. (size 1.5 Mtr Dia & 3. Mtr Height) with two coat of synthetic enamel paint of sky blue colour / shade duly preparing the existing painted surface all as per the direction of Engineer-in-charge / GE.
Cleaning of RCC Semi under ground sump / suction gallery of following capacity by emptying the reservoirs, taking down the scale/sludge/mud/algae formed including and other foreign materials got deposited on side of walls and bottom of the tanks by scrapping and brushing with wire brush, cleaning with pressure pump, washing with bleaching powder slurry and allowing to dry and then washing and cleaning the tank with fresh water including applying one coat of white wash on internal surface of reservoirs/sumps and written details on tanks like date of cleaning, capacity of tanks etc on the out side of the tank with synthetic enamel paint with letter size 20cm high, 10cm width in white colour, over a black background of size 100 x 60cm all as specified and directed for the following capacity. Note :- (i) The photographs before and after cleaning be submitted to Engineer-in-charge for records. (ii) Sample testing of every UG sumps water before and after cleaning from auth Govt agency.
Semi underground sump of capacity 20000 gallons
Semi underground sump of capacity 15000 gallons
Over Head reservoir of capacity 6600 gallons
S&F of CI foot valve heavy duty both end flanged confirming to relevant IS fixing with provn of new rubber flange gasket, nut, bolt, double washer etc. complete of size 80 mm dia and all as specified & directed
All as per item No 35 above but Cast iron foot valve heavy duty of size 100mm bore both ends flanged rating PN-1.6 all as specified and as directed
S&F in replacement cable PVC insulated sheathed, unarmoured, flat submersible water proof with stranded copper conductor 1100 V grade of size 3 core 16 Sq mm complete all as specified and as directed.
Repair/Maint of centrifugal pump of capacity 30 HP by dicpnnecting electrical connection and taking out complete assembly with electric motor, transporting to workshop and testing the complete and refixing with new, nuts, bolts & washers and fitting the same after repairs all as specified and directed.
All as per item No 38 above but capacity of 10/15 HP
All as per item No 38 above but capacity of 5/7.5HP
M&L for re-winding of unserviceable / burnt Centrifugal pump set motor of capacity 30 HP, removing all burnt out coils, cleaning the slots and rewinding the same with supper enameled copper winding wire of same as existing gauge and reassembling , testing and commissioning of electric motor on full load for 4-6 hours of continuous running complete in all respects to the entire satisfaction of Engr-in-Charge / GE.
All as per item No 41 above but capacity of 15/10 HP 3 phase AC 415 volt.
All as per item No 41 above but capacity of 05/7.5 HP 3 phase AC 415 volt.
Supply only electric terminal block/connector suitable for 30 HP electric motor AC 3 phase 415 Volts.
Supply only electric terminal block/connector suitable for 10/7.5/5 HP electric motor AC 3 phase 415 Volts
M&L in replacement of rubber jaw coupling as per sample suitable for 15/10/7.5/5 HP pump sets complete all as specified and as directed.
M&L in replacement of MS coupling along with rubber star coupling complete with proper alignment for 10/15/7.5/5 HP pump set complete all as specified and directed.
M&L in replacement of MS coupling along with rubber star coupling complete with proper alignment for 30 HP pump set complete all as specified and directed.
S&F of Power Contactor 3 pole 3 phase 415 Volt suitable for starter ML-2 type 3 phase 415 V AC 50 HZ complete all as specified and as directed.
S&F of Single phase preventor VSP3 complete all as specified and as directed.
S&F of motor starter Relay 10 to 50 Amps complete all as specified and as directed.
S & F in repair for DOL startor of capacity 7.5/10HP motor fully automatic type includung timer,conductor,O/L relay etc complete all as specified and as directed.
Supply only Stainless steel shaft suitable for 30 HP pump set (as per sample) all as specified and as directed
Supply only Stainless steel shaft suitable for 15/10/7.5 HP pump set (as per sample) all as specified and as directed
Supply only ball bearing set of 2 suitable for monoblock electrical motor of capacity 7.5/10/15 HP as per sample
Supply only ball bearing for centrifugal pump of capacity 20/30 HP complete all as specified and as directed.
Repair /Maint of Non Clog submersible pump set of capacity 5/10/15HP disconnecting electrical connection at filtration plant NAD,NTS and DAD area and taking out from the Sump well by using chain pulley block/ by crane complete assembly with column pipe, electric motor, pump set, transporting to workshop and testing the complete and refixing with new, nuts, bolts & washers and lowering the same in UG sump well after the following repairs as mentioned here in after all as directed.
Re-winding of Non clog submersible electric motor by opening the motor , removing all burnt out coils, cleaning the slots and rewinding the same with PVC insulated copper winding wire of same as existing gauge,including replacement of bearing suitable size and reassembling , testing and commissioning of electric motor on full load for 4-6 hours continuous running of the capacity 15/10 HP complete all as specified and as directed.
All as per item No 58 above but capacity of 5 HP all as specified and as directed
S&F of Micro filter for RO plant of any capacity all as specified and as directed
Supply and fix in replacement of Multigranted sand filter (MSF) of capacity 13" x 54", operating pressure 3.0 Kg/cm2, type of media Dual-sand and anthracite, FRP type including suitable filter media complete all as specified and as directed.
Supply and fix in replacement of Activated carbon filter (ACF) of capacity 13" x 54", operating pressure 2.5 Kg/cm2, type of media Activated Carbon 900IV, Micron rating-10/5 Micron FRP type including suitable filter media complete all as specified and as directed.
S&F in replacement of Membrane of capacity 1000ltrs/hr (2 No. of 500 lit/hr each) as per existing filter in RO Plant along with rubber ring all as specified and as directed.
M&L to carry out periodical repair / maint of RO filtration plant of capacity 1000 ltrs per hour for its smooth functioning comprising the following equipments / plants including replacement of following unserviceable parts / items and cleaning of 04 Nos PVC service tanks of 5000 ltr capacity each, and testing on completion to the entire satisfaction of Engr-in-Charge all as specified and directed Note:- (a) The cost of parts / items to be replaced shall be measured and paid for separately under relevant items of this schedule. (b) Cost of fixing charges including replacement of small parts such as screws, nut bolt and washers etc. are deemed to be included in this item.
M&L for B check maintenance in 500 KVA DG Cummins / Greaves set incl change of lub oil & fuel filters all as specified by the OEM complete all as specified and as directed.
M&L for C check maintenance in 500 KVA DG Cummins / Greaves set incl change of lub oil & fuel filters all as specified by the OEM complete all as specified and as directed
Attending complaints / repairs of any capacity and any make DG set and bring to normal working condition as per OEM instructions incl checking of cable lungs, connections, insulations and residual voltage etc all as specified and directed.
Note:- (a) The break down complaint should be attended within 2 hours with the intimation of Engr-in-charge or concern JE E/M by telephonically / verbally. (b) Not attending of complaint within two hours will lead to recovery from subsequent payment in the following manner :- (i) Not attending within 2 to 4 Hours - Rs. 2000.00 (ii) Not attending within 4 to 6 Hours- Rs. 4000.00 (iii) Not attending within 6 to 8 Hours- Rs. 8000.00 (iv) Not attending after 8 Hours - Rs. 10,000.00 (v) The maximum recovery will be Rs. 50,000.00 plus the expenditure incurred for rectification of the same by any other means.
M&L for fixing in replacement of Air filter of 500 KVA DG set complete all as specified and directed.
M&L for fixing in replacement of fan belt (set) in 500 KVA DG set complete all as specified and directed.
Supply only coolant for radiator suitable for DG set 500 KVA all as per OEM instructions compete all as specified and as directed.
Supply and replace engine oil from engine oil sump with suitable grade oil SAE-20W40 complete all as specified and as directed.
Supply and fill distilled water for battery 12V complete all as specified and as directed.
SHUSHANT ASSOCIATES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .