Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.8 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹17.0 L+₹20,690 (1.23%)Rejected-Finance | L2 | Rejected-Finance Being other than L1 | |
| 3 | L3₹18.6 L+₹1.9 L (11.1%)Rejected-Finance | L3 | Rejected-Finance Being other than L1 | |
| 4 | L4₹18.7 L+₹1.9 L (11.5%)Rejected-Finance | L4 | Rejected-Finance Being other than L1 | |
| 5 | L5₹18.7 L+₹2.0 L (11.6%)Rejected-Finance | L5 | Rejected-Finance Being other than L1 |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
6 Oct 2022, 6:00 pmClosed
GE (AF) E/M CHAKERI
GE (AF) E/M CHAKERI KANPUR 208008
REWIRING OF OLD UNSERVICEABLE / DETERIORATED WIRING AT VARIOUS HANGERS IN TECH AREA AT AF STN KANPUR
2022_MES_550775_1
8590/E8
Open Tender
Electrical and Maintenance Works
Item Rate
274 days
GE (AF) E/M CHAKERI KANPUR
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE (AF) E/M CHAKERI
₹50,000
Yes
2 Nov 2022
8 Sept 2022
8 Oct 2022
8 Sept 2022
6 Oct 2022
23 Sept 2022
Amount
Taking down old unserviceable/deteriorated batten/PVC conduit /MS conduit point wiring from existing place i.e. light, fan, socket or power points complete with all unserviceable fittings such as switches, sockets, ceiling rose, pendants, Holders, etc complete all as specified and directed.
M&L for concealed point wiring on wall and surface wiring on ceiling/roof/trusses with necessary fixing arrangements with stranded PVC-FRLS insulated and unsheathed copper stranded conductor of size 1.5 Sqmm, 1100 volts grade drawn in and including 16 gauge stove enameled rigid steel conduit (metallic) not less than 19 mm dia with all conduit accessories / fittings such as junction boxes, bends, tee, elbow etc including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.0 mm with earth dolly and Bakelite laminated sheet 3mm thick ISI marked for fixing of switches / sockets, fan regulators with brass screw and cup washers including PVC-FRLS insulated and unsheathed copper stranded conductor of size 1.5 Sqmm, 1100 volts grade for continuous earthing including cutting the chases and making good the surface by cement mortar (1:3) and for matching / finishing of new surfaces either by means of plaster of peris / Putti or distemper / colour wash with same existing colour surfaces complete all as specified and directed. For one light, fan, call bell point controlled by one switch.
All as per item No. 3.00 above but 5 Amp independent socket point controlled by one switch.
All as per item No 3.00 above but for one socket point controlled by one switch on same board.
All as per item No 3.00 above but for power point wiring with 2.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable and 2.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable as continuous earth lead complete all as specified and directed.
M&L for concealed point wiring on wall and surface wiring on ceiling/roof/coloum with necessary fixing arrangements with PVC-FRLS insulated and unsheathed copper stranded conductor of size 1.5 Sqmm, 1100 volts grade drawn in and including rigid non metallic white / ivory PVC conduit medium grade ISI marked not less than 19 mm dia with all conduit accessories/ fittings such as junction boxes, bends, tee, elbow etc including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and Bakelite laminated sheet 3mm thick ISI marked for fixing of switches / sockets, fan regulators with brass screw and cup washers including PVC-FRLS insulated and unsheathed copper stranded conductor of size 1.5 Sqmm, 1100 volts grade for continuous earthing including cutting the chases and making good the surface by cement mortar (1:3) and for matching / finishing of new surfaces either by means of plaster of peris/ Putti or distemper / colour wash with same existing colour surfaces complete all as specified and directed. For one light, fan, call bell controlled by one switch.
All as per item No. 7.00 above but 5 Amp independent socket point controlled by one switch.
All as per item No.7.00 above but for one socket point controlled by one switch on same board.
All as per item No 7.00 above but for power point wiring with 2.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable and 2.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable as continuous earth lead complete all as specified and directed.
M&L for surface point wiring on wall and surface on ceiling/roof with necessary fixing arrangements with PVC-FRLS insulated and unsheathed copper multi-stranded conductor of size 1.5 Sqmm, 1100 volts grade drawn in and including casing caping/conduit (as per site requirement) 20 / 25 mm white / ivory with all accessories/ fittings such as junction boxes, bends, tee, elbow etc including PVC / Polycarbonate gang box of appropriate size for fixing of switches / sockets, fan regulators, door bell & bulkhead etc with MS screw and cup washers including PVC-FRLS insulated and unsheathed copper multi-stranded conductor of size 1.5 Sqmm, 1100 volts grade for continuous earthing complete all as specified and directed. For one light, fan, call bell controlled by one switch.
All as per item No 11.00 above but for one socket point controlled by one switch on independent board.
All as per item No 11.00 above but for one socket point controlled by one switch on same board.
All as per item No 11.00 above but for power point wiring (15 Amp socket point controlled by one switch ) with 2.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable and 2.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable as continuous earth lead complete all as specified and directed.
All as per item No 11.00 above but for one light point controlled by two, two way switch.
S&F switch flush type single pole one way 5 Amps, 240 volts, white finish complete all as specified and directed.
S&F switch flush type 15 Amps, 240 Volts single pole white finish complete all as specified and directed.
S&F socket outlet 5 pin, 5 Amps flush type white finish complete all as specified and directed.
S&F socket outlet 2 in 1, 3 pin, 5/15 A, flush type universal, 240 V white finish complete all as specified and directed.
S&F in replacement electronic socket size, rotary, 5 speed step type regulator, 120-230 V white finish complete all as specified and directed.
S&F ceiling rose, surface backlite, 65 x 20 mm three terminal complete all as specified and directed.
S&F in replacement lamp holder insulated body with back plate suitable for angle / batten fitting conforming/ ISI Marked complete all as specified and directed.
S&F in replacement double door metallic sheet metal enclosure having IP43-IK09 for DB when MCBs to be used SPN 8 ways, 240 V with 200Amps rated bus bar complete fixed properly on in concealed position on wall and suface position on trusses and to provide required sizes of flexible conduit at any open surfaces near DBs of cables/wires including providing of suitable size of lugs and blanking plate complete all as specified and directed. Note : MCBs will be measured and paid separately.
All as per item No 23.00 above above but 4 way.
All as per item No. 23.00 but 2 ways without busbar.
S&F in replacement double door metallic sheet metal enclosure for DB when MCBs to be used TPNL, 4 ways, 415Volts (horizontal type) with 200 Amps rated bus bar suitable for TPN MCB/ 4 pole Isolator fixed properly on in concealed position on wall and surface position on trusses and to provide required sizes of flexible conduit at any open surfaces near DBs for cables/wires complete all as specified and directed.
S&F in replacement sheet metal enclosure double door type for DB when MCBs & MCCB 125 Amp (as incomer) & MCB SP/TP (as outgoing) to be used, VTPN, 4 ways, 415 V with bus bar fixed properly on in concealed position and to provide required sizes of flexible conduit at any open surfaces near DBs of cables/wires complete all as specified and directed.
S&F (in replacement) testing and commissioning of MCB SP 240 volt 6 Amp to 32 amp 10 KA capacity having C-curve characteristics connected with suitable lugs complete all as specified and directed.
All as per item No 28.00 above but SP 40-63 Amps.
All as per item No 28.00 above but SPN 16-32 Amps.
All as per item No 28.00 above but SPN 40-63 Amps.
All as per item No 28.00 above but TP 40-63 Amps, 415V.
All as per item No 28.00 above but TPN 40-63 Amps, 415V.
S&F in replacement MCCB 125 Amps, 4 Pole, 415V, 25KA complete all as specified and directed.
S&F in replacement MCCB 160 Amps, 4 Pole, 415V, 36KA complete all as specified and directed.
S&F in replacement sheet metal enclosure, 20A, 230 Volts single pole and neutral with a two pin and earth plug and socket complete in metal clad board (Industrial type) with one single pole MCB 20 Amp fixed properly on / in concealed position on wall and surface position on trusses complete all as specified and directed.
S&F in replacement sheet metal enclosure, 32A, 415 Volts triple pole neutral & earth with a three pin and earth plug and socket complete in metal clad board (Industrial type) with one TP MCB 32 Amp fixed properly on / in concealed position complete all as specified and directed.
S&F in replacement sheet metal enclosure, 63A, 415 Volts triple pole neutral & earth with a three pin and earth plug and socket complete in metal clad board (Industrial type) with one TPN MCB 63 Amp fixed properly on / in concealed position complete all as specified and directed.
M&L sub main wiring (in replacement) on surface with two single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 4 sqmm drawn in MS/PVC conduit with 4 Sqmm PVC-FRLS insulated unsheathed multi stranded copper conductor as a continuous earth wire complete in rigid stove enameled steel conduit/PVC conduit ISI marked of size not less than 25 mm dia in concealed/surface wiring and all fixing accessories such as couplers lock, nuts, sadles, pipe hooks etc fixed properly including taking down old unserviceable sub main wiring complete all as specified and directed. Note : (i) Two run single core PVC-FRLS cable and one run single core PVC-FRLS cable of earth copper conductor will be measured and paid as one unit length. (ii) Steel Conduit / PVC Conduit and cutting, cheaseling and making good will be measured and paid separately.
M&L sub main wiring (in replacement) on surface with two single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 6 sqmm drawn in MS/PVC conduit with 6 Sqmm PVC-FRLS insulated unsheathed multi stranded copper conductor as a continuous earth wire complete in rigid stove enameled steel conduit/PVC conduit ISI marked of size not less than 32 mm dia in concealed/surface wiring and all fixing accessories such as couplers lock, nuts, sadles, pipe hooks etc fixed properly including taking down old unserviceable sub main wiring complete all as specified and directed. Note : (i) Two run single core PVC-FRLS cable and one run single core PVC-FRLS cable of earth copper conductor will be measured and paid as one unit length. (ii) Steel Conduit / PVC Conduit and cutting, cheaseling and making good will be measured and paid separately.
M&L sub main wiring with four single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 6 sqmm drawn in MS/PVC conduit with 2 run of 6 Sqmm PVC-FRLS insulated unsheathed multi stranded copper conductor as a continuous earth wire complete in rigid stove enameled steel conduit/PVC conduit ISI marked of size not less than 25 mm dia in concealed/surface wiring and all fixing accessories such as couplers lock, nuts, sadles, pipe hooks etc fixed properly including taking down old unserviceable sub main wiring complete all as specified and directed. Note : (i) Four run single core PVC-FRLS cable and two run single core PVC-FRLS cable of earth copper conductor will be measured and paid as one unit length. (ii) Steel Conduit / PVC Conduit and cutting, cheaseling and making good will be measured and paid separately.
M&L sub main wiring on surface with four single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 10 sqmm drawn in MS/PVC conduit with 2 run of 10 Sqmm PVC-FRLS insulated unsheathed multi stranded copper conductor as a continuous earth wire complete in rigid stove enameled steel conduit/PVC conduit ISI marked of size not less than 32 mm dia in concealed/surface wiring and all fixing accessories such as couplers lock, nuts, sadles, pipe hooks etc fixed properly including taking down old unserviceable sub main wiring complete all as specified and directed. Note : (i) Four run single core PVC-FRLS cable and two run single core PVC-FRLS cable of earth copper conductor will be measured and paid as one unit length. (ii) Steel Conduit / PVC Conduit and cutting, cheaseling and making good will be measured and paid separately.
S&F in replacement rigid metallic medium 20mm dia stove enameled steel conduit ISI marked in concealed position inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddlers, pipe hooks etc fixed properly on as in concealed position complete all as specified and directed.
All as per item No. 43.00 above but metallic medium 25 mm dia stove enameled steel conduit ISI marked complete all as specified and directed.
All as per item No. 43.00 above but metallic medium 32 mm dia stove enameled steel conduit ISI marked complete all as specified and directed.
S&F in replacement rigid non-metallic medium 20mm dia PVC conduit ISI marked in concealed position inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddlers, pipe hooks etc fixed properly on as in concealed/Surface position complete all as specified and directed.
All as per item No. 46.00 above but non-metallic medium 25 mm dia PVC conduit ISI marked complete all as specified and directed.
Cutting chases in brick walls, pinning exceeding 10cm but not exceeding 30cm girth and depth of 30 mm and making good to facings where required and pointing in cement mortar 1:3 cutting chases for concealed conduit wiring,submain wiring etc and making good and palstering the surface with cement or plaster of peris and matching with same colour scheme complete all as specified and directed.
M&L for earthing complete (in replacement) with MS galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25m deep below normal GL) with top edge of the earth plate not less than 1.5m below normal GL, connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1(using 20mm graded crushed stone aggreagte) chamber with RCC cover (1:2:4) type B0(using 12.5mm graded crushed stone aggreagte), 40 mm thick reinforced with 6 mm dia bar, 3 Nos. both way, 15 mm dia light grade GI protection pipe, funnel with wire mesh, watering pipe of size 20 mm dia medium grade, lugs, main Earthing lead upto 7.5 m including Charcoal dust, salt etc. all as shown in electrical plate No. 3 of SSR Pt-I, 2009 specification complete all as specified and directed.
M&L for cutting / boring of PCC/hard standing at a depth not more than 15 cm deep and 15 cm in breadth for passing earthing conductor and making good the disturbed surfaces with PCC (1:2:4) type B-0(using 12.5mm graded crushed stone aggreagte) or cement mortar (1:3) complete all as specified and directed.
S&F in replacement GI pipe light grade (ISI marked) of size 15 mm bore for laying in trenches/floors or walls including all fittings for fixing as required complete all as specified and directed.
M&L in replacement for earth continuity conductor or main earthing lead 4 mm dia GI or steel wire fixed to wall on batten or recessed or buried in ground or drawn in conduit/pipe all as required at site complete all as specified and directed.
S&F in replacement for energy saver LED light fitting 20/21 watt, 230 Volts, single tube mounting including LED Tube/ LED blocks 20/21 Watt, Lumen OUTPUT NOT LESS THEN 115 lM /WATT with 50000 burning Hours, PF = 0.95 complete with electronic driver LED Printed board, end cover, connector box etc and accessories, prewired, LED including required fixing arrangements and electrical connection three core copper cable from ceiling rose to led light fitting including taking down of old unserviceable fitting complete all as specified and directed. Make: CROMPTON / HAVELLS / BAJAJ / PHILIPS / WIPRO
S&F in replacement Master LED Tube 1200mm 20 Watt complete all as specified and directed. Make: CROMPTON / HAVELLS / BAJAJ / PHILIPS / WIPRO
S&F in replacement for energy saver LED Smart Batten fitting 10 watt, 230 Volts, Box type etc and accessories, including required fixing arrangements and electrical connection three core copper cable from ceiling rose to light fitting old unserviceable bracket with sketch fitting complete all as specified and directed. Make: Philips Cat Part No: BN021LED 10S-6500 PSU GRS1 / Wipro Cat No LL20-111-XXX-65-NE / Havells Cat No: ENDURALINEARNEOBS 10WLED 865SPCWH
S&F in replacement Recess LED 600x600mm fitting made of CRCA powder quoted finish with Fully Covered by PMMA Acrylic Lumio Diffuser, LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, Life of fixture 50000hrs@L70% Lumen maintenance, CCT up to 6500, CRI >80, PF >0.95, an operating Voltage Range of 140 - 270 V, Minimum Internal Surge Protection 2.5KV The fixture should comply with the parameters as per IS10322 and IEC60598, EMC / EMI compliance, Maximum Wattages 37W, Minimum system Lumens 3400 complete all as specified and directed. Make: Philips Models RC-380B LED 36S-6500G4L60W60 PSD / WIPRO LM24-392-XXX-57-DD / BAJAJ BZR SQL-36WG21WH
S&F in replacement energy saver LED Full Glow fitting 40 watt , 230 Volts, Box type. etc and accessories, including required fixing arrangements and electrical connection three core copper cable from ceiling rose to light fitting old unserviceable bracket with sketch fitting complete all as specified and directed. Make: CROMPTON / HAVELLS / BAJAJ / PHILIPS / WIPRO
S&F in replacement LED Street Light/Building security light 72 Watt Single Piece Pressure Die Cast Aluminium Housing (LM6 Alloy), Minimum 7000-7500lumens with maximum system wattage 70W-75W, With PMMA Lenses, External built proper heat sinks and Toughen Glass/PC ensuring IP66 & IK >05 protection, LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) 100lumens/watt, Life of System should be 50000hrs@L70 along with inbuilt Potted Driver, CCT >5000, CRI 70, PF >0.9 complete all as specified and directed. Make: CROMPTON / HAVELLS / BAJAJ / PHILIPS / WIPRO
S&F in replacement for LED Building Security Light 110 watt orf alumenium PDC housing glass cover with IP 66 protection inlcuding taking down old/unserviceable fitting complete all as specified and directed. Make: CROMPTON / HAVELLS / BAJAJ / PHILIPS / WIPRO
Supply and laying or fixing or passing through pipe, commissioning and testing 1100 volts grade XLPE insulated armoured heavy duty cable with aluminum conductor of cross sectional area 25 sqmm 3.5 core using stranded conductor complete all as specified and directed. Make: POLYCAB / HAVELLS / FINOLEX / GLOSTER/ GRANDLAY
S&F in replacement LED aviation obstruction light fitting red painted die-cast aluminium alloy having red coloured polycarbonate dome and accessories complete all as specified and directed. Make: CROMPTON / HAVELLS / BAJAJ / PHILIPS / WIPRO
S&F in replacement LED 4 FT Batten 40 watt with a nominal system lumen output of 4000 lumens and a minimum syestem efficiency of 105 Lm/w, system lifetime of luminaries 40,000 burning Hours at L70, Colour temparature of 6500 K and CRI not less then 80 IP -20 Protection CRCA WITH a glossy diffuser power factor 0.95, Total power comsumption should not exceed 38 watt (including driver) complete with hanging arrangements including taking down old unsrviceable fitting complete all as specified and directed. Make: CROMPTON / HAVELLS / BAJAJ / PHILIPS / WIPRO
M/s Sohanil Construction
SAKSHAM SUPPLIERS BUILDERS
M/S Husna Electrical Works
PAWAN COOL CORPORATION
M/s CHAUHAN BUILDERS & ENGINEERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .