MAJOR ANIRUDDHA SUBBA
DRDO Complex, CV Raman Nagar PO, Bangalore 560 093
REPAIRS AND MAINTENANCE OF HT LT UNDERGROUND CABLES EARTHINGS AVR SUBSTATION HT PRIMARY PROTECTION RELAYS HT VCBs RMUs TRANSFORMERS CAPACITOR BANK VOLTAGE STABILIZERS OF VARIOUS CAPACITIES AND PREVENTIVE ALLIED WORKS AT GTRE BANGALORE
2026_MES_791301_1
8768/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE I R AND D EAST BANGALORE
CLASS D CATEGORY b(ii)
8 documents required · 8 mandatory
₹500
Yes
GE I R AND D EAST BANGALORE
₹84,000
Yes
6 Oct 2026
6 Oct 2026
28 Oct 2026
6 Oct 2026
26 Oct 2026
20 Oct 2026
6 Oct 2026 - 19 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and fixing HT digital display voltmeter suitable for HT OCBs, HT VCBs at various substation suitable for HT panel 1100 / 100 volts (auxiliary volts) including necessary connections and taking out old unserviceable complete all as specified and as directed. | 5 | EACH | - | - |
| 2 | Supply and fixing HT digital type ammeter suitable for CT ratio 50 / 100 / 200 amps including necessary connections and taking out unserviceable ammeter complete all as specified and as directed. | 50 | EACH | - | - |
| 3 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for laying cables / poles foundation / stay assembly and getting out in hard / dense soil complete all as specified and as directed. | 80 | CUBIC METRE | - | - |
| 4 | Removing excavated material to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed. | 43 | CUBIC METRE | - | - |
| 5 | Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm complete all as specified and as directed by Engineerr-in-Charge. | 37 | CUBIC METRE | - | - |
| 6 | Material and labour for sand cushioning to under ground cable providing with a layer 8cm thick before laying the cable and 15 cm thick after laying the cable complete all as specified and as directed
NOTE :- Punned thickness only will be measured for the purpose of payment. | 13 | CUBIC METRE | - | - |
| 7 | Material and labour for unreinforced pre cast concrete covers class HV type 300mm x 180mm x 40mm size factory made for cable protection complete all as specified and as directed. | 320 | EACH | - | - |
| 8 | Material and labour for unreinforced pre cast concrete covers class LV type 250mm x 150mm x 40mm size factory made for cable protection complete all as specified and as directed. | 250 | EACH | - | - |
| 9 | Material and labour for filtration / dehydration of transformer oil including checking di-electric strength of oil before and after filtration for transformers located in GTRE area with suitable machine having filtration, heating and pumping facility to improve the dielectric strength / insulation value of oil complete all as specified and as directed. | 24,000 | LITRE | - | - |
| 10 | Supply and filling new transformer oil for topping up the transformers duly filtered with filtration plant having dielectric strength not less than 60 KV complete all as specified and as directed.
MAKE : POWEROIL / ELECTROL / SERVO. | 1,800 | LITRE | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
BOQ_888791.xls
BOQ • 1.65 MB
8768Tender.pdf
Tender Documents • 0.87 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .