Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹43.5 LAccepted-AOC NO 1A 1 SHALOM VALLUVAR STREET SIVANANDHA COLONY COIMBATORE TAMIL NADU 641 012 | COIMBATORE | TAMIL NADU | 641012 | L1 | Accepted-AOC L1 Accepted | |
| 2 | L2₹44.9 L+₹1.4 L (3.22%)Rejected-Finance DOOR NO IV 400 NEAR RAMANTHALI GHSS RAMANTHALI PO KANNUR 670308 | KANNUR | KERALA | 670308 | L2 | Rejected-Finance Being not the Lowest Tenderer | |
| 3 | L3₹48.4 L+₹4.9 L (11.2%)Rejected-Finance 138A STANLEY PARK OTTUPATTARAI POST COONOOR 643 105 THE NILGIRIS TAMIL NADU | THE NILGIRIS | TAMIL NADU | 643105 | L3 | Rejected-Finance Being not the Lowest Tenderer | |
| 4 | L4₹48.6 L+₹5.1 L (11.6%)Rejected-Finance D 235 ADG P CHENNAI | CHENNAI | TAMIL NADU | 600001 | L4 | Rejected-Finance Being not the Lowest Tenderer |
| Sl No | Description | Qty | Unit | shalom constructions L1 | SREEKRUPA ENTERPRISES L2 | JOE ENTERPRISES L3 | T C KARUNANITHI L4 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings and base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement including taking out old unserviceable panel board with accessories such as MCCBs complete with following cables all as specified and directed. (9 Mal lake view sub station & Lake view near High Mast light)
(a) INCOMING:-
(i) MCCB thermal magnetic release, adjustable over load, 80-100% 4 Pole, 36 KA, 250 Amps 415 Volt - 1 No
(b) OUTGOING
(i) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 200 Amps 415 Volt - 1 Nos
(ii) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 160 Amps 415 Volt - 1 Nos
(iii) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 100 Amps 415 Volt - 2 Nos
(iv) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 63 Amps 415 Volt - 2 Nos
(v) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 25 KA, 40 Amps 415 Volt - 2 Nos
(vi) Astronomical time switch for 24 Hrs setting-1 Nos.
(vii) 2 Pole power contactor AC 3 rating 25 Amps AC1 rating 45 Amps MNX 25-2P type-1 Nos.
(c) 500 Amps aluminium busbar for phase and 300 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulators in separate compartment - 01 Set
(d) Digital multi function panel meter for measuring voltage, Amps and Frequency with suitable CTs and back up protection - 1 Nos
(e) LED type Indication lamp 415 Volts Set of three - 1 Set
(f) danger notice board of size 200 mm x 150 mm x 1.6 mm thick of mild steel sheet printed with vitreous enabled white paint and letter figure and convention skull and bones of signal red colour and fixed / rivetted with panel -02 Nos
Note:- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work.
(ii) Panels shall be placed above 0.6 mtr from ground level.
(iii) Outgoing MCCBs shall be fed with solid busbar connectors.
(iv) Cables shall be terminated using gun metal /SS glands. | 6 | JOB | 1,65,000 ₹9,90,000 Lowest | 1,69,000 ₹10,14,000 | 1,75,000 ₹10,50,000 | 1,80,000 ₹10,80,000 |
| 2.00 | MCCB 4 pole, 415V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as specified and directed. | 3 | EACH | 6,000 ₹18,000 Lowest | 7,500 ₹22,500 | 9,500 ₹28,500 | 9,000 ₹27,000 |
| 3.00 | MCCB 4 pole, 415V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified and directed. | 5 | EACH | 9,000 ₹45,000 Lowest | 12,000 ₹60,000 | 14,500 ₹72,500 | 13,000 ₹65,000 |
| 4.00 | MCCB 4 pole, 415V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as specified and directed. | 6 | EACH | 10,000 ₹60,000 Lowest | 13,000 ₹78,000 | 17,300 ₹1,03,800 | 14,000 ₹84,000 |
| 5.00 | MCCB 4 pole, 415V, Adjustable type, 400 Amps with breaking capacity 36 KA complete all as specified and directed. | 2 | EACH | 17,000 ₹34,000 Lowest | 19,000 ₹38,000 | 28,000 ₹56,000 | 20,000 ₹40,000 |
| 6.00 | MCCB 4 pole, 415V, Adjustable type, 630 Amps with breaking capacity 36 KA complete all as specified and directed. | 1 | EACH | 22,000 ₹22,000 Lowest | 23,000 ₹23,000 | 42,000 ₹42,000 | 25,000 ₹25,000 |
| 7.00 | MCCB 3 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as specified and directed. | 3 | EACH | 5,000 ₹15,000 Lowest | 7,000 ₹21,000 | 7,500 ₹22,500 | 9,000 ₹27,000 |
| 8.00 | MCCB 3 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified and directed. | 2 | EACH | 8,000 ₹16,000 Lowest | 9,000 ₹18,000 | 12,000 ₹24,000 | 12,000 ₹24,000 |
| 9.00 | MCCB 3 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as specified and directed. | 2 | EACH | 9,000 ₹18,000 Lowest | 10,000 ₹20,000 | 14,200 ₹28,400 | 13,000 ₹26,000 |
| 10.00 | Repair of LT cable faults shall include identification of fault location using suitable methods, excavation for underground cables, removal of damaged portion, jointing using approved heat shrink or straight-through kits, proper insulation and sealing of joint, testing of cable after repair, and restoration of site to original condition.
Excavation , joining kits shall be measured separately | 18 | Each Job | 4,000 ₹72,000 | 3,000 ₹54,000 | 800 ₹14,400 Lowest | 9,000 ₹1,62,000 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
26 May 2026, 6:00 pmClosed
GE WELLINGTON
Garrison Engineer Wellington Barrack Post The Nilgiris Pin code-643231
REPAIRS/ REPLACEMENT LT PANEL, UG CABLES AND CONNECTED ITEMS WELLINGTON STATION UNDER GE WELLINGTON
2026_MES_763154_1
8245/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
WELLINGTON
As Per Tender Documents
8 documents required · 8 mandatory
₹500
GE WELLINGTON
₹90,000
Yes
11 Aug 2026
2 May 2026
6 Jun 2026
3 May 2026
26 May 2026
19 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings and base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement including taking out old unserviceable panel board with accessories such as MCCBs complete with following cables all as specified and directed. (9 Mal lake view sub station & Lake view near High Mast light)
(a) INCOMING:-
(i) MCCB thermal magnetic release, adjustable over load, 80-100% 4 Pole, 36 KA, 250 Amps 415 Volt - 1 No
(b) OUTGOING
(i) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 200 Amps 415 Volt - 1 Nos
(ii) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 160 Amps 415 Volt - 1 Nos
(iii) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 100 Amps 415 Volt - 2 Nos
(iv) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 63 Amps 415 Volt - 2 Nos
(v) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 25 KA, 40 Amps 415 Volt - 2 Nos
(vi) Astronomical time switch for 24 Hrs setting-1 Nos.
(vii) 2 Pole power contactor AC 3 rating 25 Amps AC1 rating 45 Amps MNX 25-2P type-1 Nos.
(c) 500 Amps aluminium busbar for phase and 300 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulators in separate compartment - 01 Set
(d) Digital multi function panel meter for measuring voltage, Amps and Frequency with suitable CTs and back up protection - 1 Nos
(e) LED type Indication lamp 415 Volts Set of three - 1 Set
(f) danger notice board of size 200 mm x 150 mm x 1.6 mm thick of mild steel sheet printed with vitreous enabled white paint and letter figure and convention skull and bones of signal red colour and fixed / rivetted with panel -02 Nos
Note:- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work.
(ii) Panels shall be placed above 0.6 mtr from ground level.
(iii) Outgoing MCCBs shall be fed with solid busbar connectors.
(iv) Cables shall be terminated using gun metal /SS glands. | 6 | JOB | - | - |
| 2 | MCCB 4 pole, 415V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as specified and directed. | 3 | EACH | - | - |
| 3 | MCCB 4 pole, 415V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified and directed. | 5 | EACH | - | - |
| 4 | MCCB 4 pole, 415V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as specified and directed. | 6 | EACH | - | - |
| 5 | MCCB 4 pole, 415V, Adjustable type, 400 Amps with breaking capacity 36 KA complete all as specified and directed. | 2 | EACH | - | - |
| 6 | MCCB 4 pole, 415V, Adjustable type, 630 Amps with breaking capacity 36 KA complete all as specified and directed. | 1 | EACH | - | - |
| 7 | MCCB 3 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as specified and directed. | 3 | EACH | - | - |
| 8 | MCCB 3 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified and directed. | 2 | EACH | - | - |
| 9 | MCCB 3 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as specified and directed. | 2 | EACH | - | - |
| 10 | Repair of LT cable faults shall include identification of fault location using suitable methods, excavation for underground cables, removal of damaged portion, jointing using approved heat shrink or straight-through kits, proper insulation and sealing of joint, testing of cable after repair, and restoration of site to original condition.
Excavation , joining kits shall be measured separately | 18 | Each Job | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
BOQ_854826.xls
BOQ • 0.30 MB
Tenderdocuments8245.pdf
Tender Documents • 0.78 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .