| 1 | L1₹44.6 LAccepted-AOC M S RRK PROJECTS D 306 ADG P CHENNAI 11 3RD CROSS SIR MV LAYOUT VIDHYARANYAPURA POST BANGALORE 560097 | BENGALURU URBAN | KARNATAKA | 560097 | ₹44.6 L Quoted ₹45.5 L | L1 | Accepted-AOC AWARD OF CONTRACT |
| 2 | L2₹47.8 L+₹2.3 L (5.10%)Rejected-Finance | ₹47.8 L+₹2.3 L (5.10%) | L2 | Rejected-Finance Not being lowest |
| 3 | L3₹49.0 L+₹3.4 L (7.52%)Rejected-Finance | ₹49.0 L+₹3.4 L (7.52%) | L3 | Rejected-Finance Not being lowest |
| 4 | L4₹50.3 L+₹4.8 L (10.5%)Rejected-Finance | ₹50.3 L+₹4.8 L (10.5%) | L4 | Rejected-Finance Not being lowest |
| 5 | L5₹52.2 L+₹6.7 L (14.7%)Rejected-Finance | ₹52.2 L+₹6.7 L (14.7%) | L5 | Rejected-Finance Not being lowest |
Tender Value
₹44 L
EMD Value
₹88,000
Closing Date
26 Sept 2022, 6:00 pmClosed
GE I R nd D West Bengaluru
GARRISON ENGINEER I R nd D WEST BANGALORE DRDO COMPLEX CV RAMAN NAGAR BANGALORE
REPAIR AND REPLACEMENT WORKS TO EXTERNAL ELECTRIFICATION INFRASTRUCTURE, LT FEEDER PILLAR, LT CABLES, LT PANELS, APFC PANELS, LT SWITCHGEAR AND CONNECTED ITEMS AT LRDE AND CAIR UNDER GE (I) RndD (WEST) BENGALURU.
2022_MES_548189_1
GE(I)/R ND D/BAN/TOKEN/45 OF 2022-2023 8100/E8
Open Tender
Civil Works
Item Rate
270 days
Bengaluru
Class and Category as per NIT
8 documents required · 8 mandatory
₹500
GE I R nd D West Bengaluru
₹88,000
Yes
4 Jan 2023
30 Aug 2022
1 Oct 2022
31 Aug 2022
26 Sept 2022
14 Sept 2022
31 Aug 2022 - 13 Sept 2022
Amount
Excavation in trenches not exceeding 1.5 m deep and not exceeding 1.5 m wide and getting out in soft / loose soil all as directed.
Returning and filling in, soils, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick all as directed.
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as directed.
Demolition of plain cement concrete as in foundation base of transformers, poles, panels, sign boards, coping, etc including providing necessary supports to ensure that existing installation / poles / panels do not fall while demolition, removing of debris outside MD land complete all as directed by Engineer-in-Charge.
Material and labour for plain cement concrete 1:4:8, type D2 (using 40 mm graded stone aggregate as in mass concrete foundations of transformers, poles, panels, sign boards, etc., including necessary formwork, complete all as specified and as directed.
Material and labour for plain cement concrete 1:3:6, type C1 (using 20 mm graded stone aggregate as in coping to poles, panels, etc., including necessary formwork, complete all as specified and as directed.
Screening excavated earth (passing through 12 mm square mesh), laying riddled earth in trenches for cable protection, under and above Cable all as specified in SSR Part - I (Clause No 19.75) and as directed by Engineer-in-Charge. Note : Punned thickness of riddled earth of 18 cm will be measured and paid.
Material and labour for cushioning of river sand, for Cables in ducts of sub stations, complete all as directed and specified. Note : For the purpose of payment punned thickness will be measured.
Material and labour for laying of burnt bricks sub class `B’ bricks of size 230 x 115 x 75 mm, laid in trenches for cable protection all as directed and specified
Re-laying of burnt bricks sub class `B’ bricks in trenches for cable protection all as directed and specified Note : Serviceable brick covers obtained while excavating for replacement of unserviceable cables shall be reused under this item.
Taking out old unserviceable joints, Supplying, jointing new indoor termination, heat shrink type joint, suitable for 11 KV (earthed) grade XLPE armoured aluminium conductor cable of size 3 core 95 sq mm, testing, complete all as specified and as directed
Taking out old unserviceable joints, Supplying, jointing new indoor termination, heat shrink type joint, suitable for 11 KV (earthed) grade XLPE armoured aluminium conductor cable of size 3 core 120 to 185 sq mm, testing, complete all as specified and as directed
Supplying, jointing new Straight through cable jointing kit suitable for 11 K V, UG XLPE cable of size 3 core 95 sq mm, testing, complete all as specified and as directed
Supplying, jointing new Straight through cable jointing kit suitable for 11 K V, UG XLPE cable of size 3 core 120 to185 sq mm, testing, complete all as specified and as directed
Taking down unserviceable cable protection pipe, Supply and Fixing on walls / pole with clamps / laid in trenches, 50 mm bore Galvanized iron tubing, light grade, as cable protection, complete all as specified and as directed.
Taking down unserviceable cable protection pipe, Supply and Fixing on walls / pole with clamps / laid in trenches, 80 mm bore Galvanized iron tubing, light grade, as cable protection, complete all as specified and as directed.
Taking down unserviceable cable protection pipe, Supply and Fixing on walls / pole with clamps / laid in trenches, 150 mm bore Galvanized iron tubing, light grade, as cable protection, complete all as specified and as directed.
Material and labour for Painting to existing LT poles of any type upto 9.0 mtr long including bracket & other accessories as per site requitrement after preparing / scraping the metal surface with emery sheet in all respect for making smooth surface and painted with one coat coat of aluminium paint including writing pole No / feeder No on poles as per site requirement complete all as specified and as directed by Engr-in-charge. Note -: The bottom of Pole 1.5 mtr height above coping / ground level shall be painted with blue paint or other any colour as decided by Engineer-in-charge in consultation with LRDE / CAIR aluminium paint strips alternatively at an interval of 30 cm including writing the pole with white colour over black colour circle base all as per site complete all as specified and directed by Engr-in-charge .
Material and labour for writing letters of size up to 1.5 inch height, with exterior grade enamel water proof paint on panels / feeder pillar boxes, etc., including representing incoming and outgoing connections complete all as per directions of Engineer-in-Charge.
Material and labour for writing letters of size up to 2 inch height, with exterior grade enamel water proof paint on panels / feeder pillar boxes, etc., including representing incoming and outgoing connections complete all as per directions of Engineer-in-Charge.
Material and Labour for finding 11KV HT UG cable fault / defect of any size from the positions accurately using cable fault locator machine vehicle including finding of cable route as applicable on the ground, transportation, testing, restoring of the supply in all respects and commissioning etc complete all as specified and as directed by Engineer-in-charge. Note - 1) Earth work from cable fault position to nearest cable loop as per site and cable joints as per site requirement shall be measured and paid separately under relevant item of the schedule.
Taking out old unserviceable MCCB, Supply and fix, adjustable MCCB, 4 pole, 415 volts, 100 amps, 25 kA breaking capacity, making additions / alterations in MCCB panel compartment, complete all as specified and as directed.
Taking out old unserviceable MCCB, Supply and fix, adjustable MCCB, 4 pole, 415 volts, 160 amps, 25 kA breaking capacity, making additions / alterations in MCCB panel compartment, complete all as specified and as directed.
Taking out old unserviceable MCCB, Supply and fix, adjustable MCCB, 4 pole, 415 volts, 200 amps, 36 kA breaking capacity, making additions / alterations in MCCB panel compartment, complete all as specified and as directed.
Taking out old unserviceable MCCB, Supply and fix, adjustable MCCB, 4 pole, 415 volts, 400 amps, 36 kA breaking capacity, making additions / alterations in MCCB panel compartment, complete all as specified and as directed.
Taking out existing old or burnt or defective LT UG cable, including loop of under mentioned cable sizes from panels / ducts / trenches / loop etc., near the sub stations / poles / buildings / panels including disconnecting cables on both ends, tracing out the fault with the help of megger and other tests complete all as directed by Engineer-in-Charge. Note: i) Excavation and earthwork will be measured and paid for separately under respective items. ii) Serviceable brick covers shall be stacked aside for re-use.
All as per Serial Item No 26.00, but 1100 V grade XLPE Cable of size up to 4 Core, 25 Sq mm,
All as per Serial Item No 26.00, but 1100 V grade XLPE Cable of size 3.5 Core 35 Sq mm to 3.5 Core 50 Sq mm
All as per Serial Item No 26.00, but 1100 V grade, XLPE Cable of size 3.5 Core 70 Sq mm to 3.5 Core 95 Sq mm
All as per Serial Item No 26.00, but 1100 V grade, XLPE Cable of size 3.5 Core 120 Sq mm to 3.5 Core 185 Sq mm
All as per Serial Item No 26.00, but 1100 V grade, XLPE Cable of size 3.5 Core 240 Sq mm to 3.5 Core 300 Sq mm
All as per Serial Item No 26.00, but 1100 V grade, XLPE Cable of size 3.5 Core 400 Sq mm to 3.5 Core 630 Sq mm
Laying only serviceable cable of following sizes as per site requirement, connecting to existing cable with and including new lugs, complete all as specified and as directed by Engineer-in-Charge. Note : Serviceable cables obtained from Sl Item Nos 26.01 to 26.06 shall be reused under this item.
All as per Serial Item No 27.00, but 1100 V grade XLPE Cable of size up to 4 Core, 25 Sq mm,
All as per Serial Item No 27.00, but 1100 V grade XLPE Cable of size 3.5 Core 35 Sq mm to 3.5 Core 50 Sq mm
All as per Serial Item No 27.00, but 1100 V grade XLPE Cable of size 3.5 Core 70 Sq mm to 3.5 Core 95 Sq mm
All as per Serial Item No 27.00, but, 1100 V grade XLPE Cable of size 3.5 Core 120 Sq mm to 3.5 Core 185 Sq mm
All as per Serial Item No 27.00, but, 1100 V grade XLPE Cable of size 3.5 Core 240 Sq mm to 3.5 Core 300 Sq mm
All as per Serial Item No 27.00, but ,1100 V grade XLPE Cable of size 3.5 Core 400 Sq mm to 3.5 Core 630 Sq mm
Disconnecting Incoming cable and all out going cables of any sizes from the Indoor panel, taking out all cables carefully as per site conditions and kept aside for reuse and reconnections in the new panel and taking out the panel from the site carefully complete all as directed by Engineer-in-charge. Location - Admin bldg and Vajra bldg Note - Earth work and PCC work as applicable shall be measured and paid seprately
Disconnecting Incoming cable and all out going cables of any sizes from the Outdoor panel, taking out all cables carefully as per site conditions and kept aside for reuse and reconnections in the new panel and taking out the panel from the site carefully complete all as directed by Engineer-in-charge. Location - NFM Bldg and opposite new MED S/S, Note - Earth work and PCC work as applicable shall be measured and paid seprately
Supply and laying New 1100 V XLPE LT cable, insulated, screened, bedded galvanized steel strip armoured heavy duty with aluminum conductor, of cross sectional area 185 sq mm 3.5 core with cable protection works (as applicable) laid in trenches/ ducts/ fixed on pole/ wall/ laid under road/ path/ culvert/ drains/ encased in pipe, including necessary lugs, jointing and testing complete all as specified and as directed.
Supply and laying New 1100 V XLPE LT cable, insulated, screened, bedded galvanized steel strip armoured heavy duty with aluminum conductor, of cross sectional area 240 sq mm 3.5 core with cable protection works (as applicable) laid in trenches/ ducts/ fixed on pole/ wall/ laid under road/ path/ culvert/ drains/ encased in pipe, including necessary lugs, jointing and testing complete all as specified and as directed.
Supplying, jointing new Straight through cable jointing kit, epoxy type, suitable for 1100 V, LT UG XLPE cable of following sizes and testing, complete all as specified and as directed
All as per Serial Item No 36.00, but, 1100 V grade XLPE Cable of size up to 4 Core, 16 Sq mm,
All as per Serial Item No 36.00 but, 1100 V grade XLPE Cable of size 4 Core 25 Sq mm to 3.5 Core 50 Sq mm
All as per Serial Item No 36.00 but, 1100 V grade XLPE Cable of size 3.5 Core 70 Sq mm to 3.5 Core 95 Sq mm
All as per Serial Item No 36.00 but, 1100 V grade XLPE Cable of size 3.5 Core 120 Sq mm to 3.5 Core 185 Sq mm
All as per Serial Item No 36.00 but, 1100 V grade XLPE Cable of size 3.5 Core 240 Sq mm
All as per Serial Item No 36.00 but, 1100 V grade XLPE Cable of size 3.5 Core 300 Sq mm
Checking of old and existing out door LT feeder boxes of any size located at various locations, taking down old broken / corroded / damaged / dented LT Outdoor feeder box doors / sheets of any type and of area not exceeding 0.5 Sq m from existing positions carefully in and including addition / alterations to doors / hinges as per site requirement with repairing, denting, machining work, welding works, applying two coats of spray painting matching of existing colour to panel complete over a coat of primer as per panel site conditions, provision of pad locking arrangements, aldrops, pad lock with three keys, etc., for proper locking of doors / fixing of sheets complete all as per directions of Engineer-in-Charge. Note : i) The Contractor shall visit the site before quoting the rate in the tender. All spares required as per site requirement shall deemed to be included in quoted rate. ii) Cost of disconnecting, taking out cable from trench etc., reconnecting with new lugs as per site requirements shall deemed to be quoted in quoted rate, iii) PCC work shall be measured and paid separately under respective items.
Servicing and repairing of LT Air Circuit Breaker of any type and rating in and including replacement of non functional components, charging mechanism and all connected accessories, tightening of cable in / out connections all as per requirements complete all as specified and as directed by Engineer-in-Charge. Note : The quoted rate shall be inclusive of replacing of all spare parts for switching ON / OFF, functioning of charging mechanism and tripping mechanism in all respects and no extra amount will be paid in this regards.
Supply, install, test and commissioning of LT bus bar chamber (fabricated by CPRI certified and approved manufacturers), made out of 3 mm thick CRCA sheet steel enclosure outdoor cubical type (size 600 mm x 600 mm x 400 mm), double door with front and rear opening facility, tower bolt locking, pad locks - 2 Nos, Provn of earthing bolts and nuts with GI Strip, four side slanting canopy of roof top, dust, vermin, weather proof duly powder coated with seven tank process, IP-54, and all as per IE rules including mounted on MS angle iron frame of size 75 x 75 x 6 mm (1 m height 4 Nos) welded to shape, mild steel base frame with channels of size 75 x 75 x 6 mm, including necessary grouting with PCC 1:4:8 type D2 with 20 mm graded stone aggregate with legs 50 cm in ground and 40 cm above ground including necessary excavation and earth work complete with necessary compartments, fitted with TPN aluminium bus bar 600 Amps with colour code sleeves mounted on porcelain/SMC/DMC insulators, including provision of doors on front with neoprene gaskets, internal control wiring with PVC insulated copper wire. Note: The quoted rate shall deemed to be inclusive of connections of incoming & outgoing, UG cable, terminating with suitable cable end glands, aluminium lugs, excavation and earthwork, taking down old cable with LT switches complete all as specified and as directed.
Checking of copper / GI strip or GI wire earthing of any type near all E/M installations, by following all safety methods carefully, tightening of all earthing connections, pouring water in the earth pits through earth pit funnel, testing of earthing pit using earth tester after 24 Hours of water pouring. (The arrangement of earth tester is the responsibility of the Contractor), white washing to earth pit, marking & painting information of pit with exterior paint mentioning date of earth result checked, test results, to which equipment earthing pit pertains, complete all as directed by Engineer-in-Charge. Note : i) The job shall be paid twice in the contract period with interval of six month periodicity. ii) Earthwork, demolition of PCC, PCC new work, RCC earth pit cover and GI strip as applicable shall be measured and paid separately under relevant items.
Taking down broken RCC covers, providing material and labour, for Pre-cast Reinforced Cement Concrete, (1:2:4), type B1 using 20 mm graded stone aggregates as in cover slabs of earth pit, set in CM(1:4) complete all as specified and as directed. NOTE :- Steel for Reinforcement will be measured and paid separately.
Material and labour, for reinforcement of concrete with Mild steel TMT bars of 8 mm dia, cut to length, bent to shape required, including cranking, bending, spirally looping for columns, hooking ends & binding with and including mild steel annealed wire of not less than 0.9 mm dia or securing with clips complete all as specified
Material and labour for earthing Complete with GI earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground earth pit not less than 2.25 M deep below normal ground level and complete earth plate connected to GI strip of size 32 x 6 mm by brazing only earth strip protected with light grade GI Pipe 50 mm dia bore from earth plate electrode including 20mm bore water pipe medium grade GI Tubing including GI Funnel,wire mesh. alternate 5 layers of charcoal & salt crystal including excavation in strata, refiling and removal of the excavated soil and depositing at the place where directed,PCC Pit in PCC (1:3:6) type C1 using 20 mm graded stone aggregate , RCC (m) Cover 40 mm thick in RCC (1:2:4) type B 1 using 20 mm grade aggregate reinforced with 8 mm dia TMT bars @ 7.5 mm c/c both ways including suitable RCC Pit cover etc watering the earth pit to acheive earth resistance below 02 Ohm incl testing complete all as specified and directed by Engineer-in-Charge. Note :- GI strip 32 x 6 mm,GI Tubing 50 mm light grade upto 7.5 mtr deemed to be included in the rate quoted by the contractor. Note:(i) Quoted rate deemend to include necessary earth work PCC chamber, RCC cover, renforcement removal of surplus soil , site clearance etc. (ii) GI earth strip 32X6 mm , GI tubing light grade 50 mm dia upto 7.5m deemed to be included the rate quoted by the contractor.
Material and labour, Galvanized earth strip of size 32 x 6 mm earth continuity or main earthing lead fixed to Wall/ trenches /ducts / buried in ground (beyond 7.5 m through Galvanized iron pipe including necessary clamps, nuts, bolts, etc., and connecting up complete all as specified and as directed.
Fixing only, Galvanized earth strip of size 32 x 6 mm earth continuity or main earthing lead on Wall/ floors fixing with necessary clamps, nuts, bolts, etc., and connecting up complete all as specified and as directed.
Supply and fixing of synthetic Rubberized insulated mats, 2 mm thick, of size 2 m x 1 m, suitable to resist electric shock safety for voltage up to 3.3 KV as per IS 15652-2006 (superceding IS 5424), complete all as specified and as directed.
Supply and fixing of synthetic Rubberized insulated mats, 2.5 mm thick, of size 2 m x 1 m, suitable to resist electric shock safety for voltage of up to 11 KV as per IS 15652-2006 (super ceding IS 5424), complete all as specified and as directed.
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .