Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 LAccepted-AOC 14 SURI LANE KOLKATA 700 014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | ₹3.4 L | L1 | Accepted-AOC AOC |
| 2 | L2₹3.5 LRejected-Finance 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | ₹3.5 L | L2 | Rejected-Finance Not L1 Bidder |
| 3 | L3₹3.5 LRejected-Finance 24 C GOABAGAN LANE KOLKATA 700006 WEST BENGAL | KOLKATA | KOLKATA | WEST BENGAL | 700006 | ₹3.5 L | L3 | Rejected-Finance Not L1 Bidder |
Tender Value
Refer Docs
EMD Value
₹6,200
Closing Date
10 Dec 2025, 11:00 amClosed
The Assistant Engineer, Dhanadhanya Elec
Office of the Assistant Engineer, P.W.Dte. Dhana Dhanya Electrical Sub-Division PWD Office Building (2ndFloor), 32, Belvedere Road, Alipore,Kolkata-27
Repairing and renovation of power and earthing connections of AC pump motors and installation of Arc Chute and Metering system in LT panel and allied electrical installation Works at Madhusudhan Mancha, Dhakuria
2025_WBPWD_948973_1
56 /Q/AE/DDESD/PWD/2025 - 26
Open Tender
ELECTRICAL WORKS ORG
10 days
Madhusudan Mancha. Dhakuria
Please refer Tender documents.
9 documents required · 9 mandatory
₹6,200
Yes
office of the Assistant Engineer, Dhanadhanya Elec
20 Feb 2026
14 Nov 2025
12 Dec 2025
15 Nov 2025
10 Dec 2025
21 Nov 2025
19 Nov 2025
Amount
ACB Replacement & Retrofitting Works
Supplying, retrofitting, installation & testing of New 800A 4P 50KA MDO ACB in place of existing 800A ACB in the existing Incomer Cubicle. Rettrofitting of the ACB along with supply, fixing & commissioning is in scope of entrusted supplier/contractor for one to one replacement with existing Circuit Breaker. The Contractor/ Supplier should have authorization from the OEM/manufacturer of related switchgear items & also produce Test Certificate from OEM.
New Incomer Details :-
i) SITC of 415 V, 800A, 50 kA 4(four) pole Manually draw- out type A.C.B. with Microprocessor-based protection release. (Make – L & T, Cat no.- SL96062 or equivalent model of Siemens / Legrand) ------1 no.
Metering Panel :-
b) S & F LED VAF + PF Meters, Accuracy Class 0.5 (Make L& T, Cat no.-WL411020OOOO or equivalent model of Siemens / Legrand) - 1 No.
c) S & F 1 phase LED Ammeter, Accuracy Class 0.5 [L&T cat no.-WL111010OOOO or equivalent model of Siemens / ABB) ---3 Nos.
e) S & F Indicating LED Lamp with colour glasses showing (Red/Yellow/Blue/Green) (Make- Siemens, Cat No.- 3SB5285-6HC03, 3SB5285-6HD03, 3SB5285-6HF03 or equivalent model of L&T / ABB) - 30 Set.
Disconnection & dismantling existing old Electrical installation, wiring, etc with owns tools & takles incl. mending good damages and clearing/removing from the site as directed by EIC.
Supplying and fixing 415V, TPN SFU with sheet steel enclosure on flat iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per following rating (Make: Siemens/ L&T as approved by E.I.C) [D-3/4(a)]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment
a) 6 Way Make - Legrand, Enclosure (607716 ) or equivalent model of Siemens/L&T as approved by E.I.C. [14/ D- 10 ]
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. (Make: Legrand /Siemens/ L&T as approved by E.I.C) [D-5/6]
(a) 63Amp FP Isolator
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection.(Make: Legrand /Siemens/L&T/ABB as approved by E.I.C) [D-6/7]
(a) 6-32 Amps SP MCB [D-6/7]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-18/9(b)]
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene/Rigid pipe and by the prelaid GI fish wire and making necy. connection as required
(a) 2 x 22/0.3 (1.5 sqmm) [E-9/1(a)]
(b) 3 x 22/0.3 (1.5 sqmm) [E-9/1(b)]
(c) 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC [E-9/1(s)]
(d) 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC [E-9/1(y)]
(e) 4x126/0.4 (16 sqmm) + 2x80/0.4 (10 sqmm) as ECC [E-9/1(g1)]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes [F-5/9]
(i) 1.5 sqmm
(ii) 2.5 sqmm [F-5/9(i)]
(iii) 4 sqmm [F-5/9(ii)]
(iv) 6 sqmm [F-5/9(iii)]
(v) 10 sqmm [F-5/9(iv)]
(vi) 16 sqmm [F-5/9(v)]
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works [E-16/7]
a) 20mm size [E-16/7(a)]
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required [F-6/11 ]
(a) 50 mm dia [F-6/11(d)]
Supply and fixing 415 V (1.6 A - 2.5 A) Motor Protection Circuit Breaker of Breaking capacity 100kA (Make L& T, Cat no.- ST41895OOOO or equivalent model of Siemens / Legrand) [required for 450 mm sweep exhaust fan (1 no Existing + 1 no New)]
Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB,concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachmen [D-9/11]
Supply of heavy duty Exhaust fan (Make-EPC]
(i) 18 INCH (920 rpm)
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter:
(i) 45 cm (18") [C-4/28(d)]
Supply & Fixing GI louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) [C-4/32]
(i) For 45 cm (18") Exhaust fan [C-4/[32(b)]
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:-By TATA-Medium GI pipe [G-1/2(a)]
Excavation of soil for installation of Earth Electrode and filling & ramming (for Morrum soil). (G-1/1(b)]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. [G-2/3(a)]
Extra for treatment of soil by using salt & charcoal or coke for plate electrode [G-2/3(b)]
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. [G-2/4(b)]
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. (i) No. 4 SWG Solid GI wire [G-2/5(a)-(i)]
Connecting the equipments body to earth busbar including S&F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. [G-3/5]
S. A. ENTERPRISE (BID ID -7582203)
T.D.K. ENTERPRISE (BID ID -7590385)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Document
1.29 MB
BOQ
BOQ • 0.31 MB
Tender Documents
Tender Documents • 1.86 MB
Download all tender documents and submit your bid