EE (ELECT-I) JDA JAIPUR
EE (ELECT-I) JDA JAIPUR
SITC of ductable Airconditioning units in GIS Sub Station Building at Cardiology, JDA, Jaipur
2026_JDAJP_571229_1
EE (ELECT-I)/07/2026-27
Open Tender
Electrical Works
Percentage
60 days
JDA AREA
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
ONLINE JDA WEBSITE
₹39,700
Yes
13 Jul 2026
25 Jun 2026
13 Jul 2026
29 Jun 2026
8 Jul 2026
29 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying, installing, testing and balancing of double louvered of extruded Aluminium Powder coated supply/return air grills of various sizes, Each grill shall be with fixed aerofoil shaped horizontal front bar at 0 deflection and back adjustable vertical louvers, air distribution grid for straightening the air flow through the collar and register including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | |||||
| 1.1 | Supply air grill with key operated volume control damper | - | Sqm. | 10,530 | - |
| 1.2 | Return air grill without volume control damper | - | Sqm. | 8,438 | - |
| 2SITC of air cooled ducted split type air conditioning machine with each having a capacity and details as mentioned below suitable for operation on factory charged R-32/R-410A Green refrigerant comprising of Scroll /rotary type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system, Suitable capacity squirrel cage induction motor with class 'B' insulation suitable for operation on sigle / three phase supply, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers, Microprocessor based control panel complete with accessories, machine isolation / disconnect switch, valves and accessories to inter connect compressor and condender including pressure testing, vacuum. Necessary starters suitable for Indoor & outdoor unit complete with O/L , U/V, phase reversal protection, single phase preventors etc complete as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | |||||
| 2.1 | 11 TR | - | Each | 2,89,571 | - |
| 3 | SITC of Interconnecting refrigerant copper pipe for split/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizes as per OEM requirement & specifications including class 'O' Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | - | Kg | 1,987 | - |
| 3.1 | Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- | - | - | - | - |
| 3.2 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole | - | - | - | - |
| 3.3 | (b) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts | - | - | - | - |
| 3.4 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt | - | - | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.90 MB
BOQ_1016293.xls
BOQ • 0.37 MB
07TDGISSubStation.pdf
Tender Documents • 7.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .