| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹183.7 CrAdmitted-Finance 14 BILASIPARA P O P S BILASIPARA DIST DHUBRI ASSAM PIN 783348 | DHUBRI | ASSAM | 783348 | ₹183.7 Cr | L1 | Admitted-Finance |
| 2 | L2₹193.9 CrAdmitted-Finance 4B TOWN SQUARE CHINAR PARK RAJARHAT KOLKATA 700 136 | ₹193.9 Cr | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Shree Gautam Construction Co. Ltd. L1 | Tribeni Constructions Limited L2 |
|---|---|---|---|---|---|
| 1.00 | CIVIL | 1 | Nos | 63,52,86,101.12 ₹63.5 Cr | 61,54,02,541.04 ₹61.5 Cr |
| 2.00 | ELECTRICAL | 1 | Nos | 13,31,62,274.96 ₹13.3 Cr | 14,87,46,588.26 ₹14.9 Cr |
| 3.00 | HVAC | 1 | Nos | 13,01,90,150 ₹13.0 Cr | 18,16,58,575 ₹18.2 Cr |
| 4.00 | FIRE FIGHTING | 1 | Nos | 1,99,81,883.67 ₹2.0 Cr | 2,34,88,216.3 ₹2.3 Cr |
Tender Value
₹85 Cr
EMD Value
₹95 L
Closing Date
27 Jan 2023, 6:55 pmClosed
IncahrgeEngineeringDeptonbehalfofDirectorTMC
In Charge Engineering Dept, BBCI on behalf of Director, TMC
ConstructionofAncillaryBuildingatthecampusofDrBBCI
2022_TMC_725492_2
BBCIENGeNITAncillary48612022
Open Tender
Civil Works - Buildings
630 days
Dr B Borooah Cancer Institute, Guwahati
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹95 L
21 Jun 2023
19 Jan 2023
30 Jan 2023
19 Jan 2023
27 Jan 2023
21 Jan 2023
19 Jan 2023 - 20 Jan 2023
Amount
CIVIL
ELECTRICAL
FIRE FIGHTING
Description of Work / Item(s)
Amount
EARTH WORK Disposal of moorum/building rubbish/ malba/ similar unserviceable, dismantled or waste material by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 10 km for all lifts, complete as per directions of Engineer-in-charge. Note - item to be applicable in urban areas having directions for restricted hours for movement/ plying of load carrying motor vehicle of 3.5 cum or more.
Extra for Item as above: lead beyond 5 km upto 10 km
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.
All kinds of soil
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.
All kinds of soil
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.
Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials.
All kinds of soil.
Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete.
Supplying chemical emulsion in sealed containers including delivery as specified.
Chlorpyriphos/ Lindane emulsifiable concentrate of 20%
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :
Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor:
With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
CONCRETE WORK Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone - III) : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing:
1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
REINFORCED CEMENT CONCRETE Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete
Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Suspended floors, roofs, landings, balconies and access platform.
Shelves (cast in situ)
Lintels, beams, plinth beams, griders, bressumers and cantilevers
Columns, pillars, piers, abutments, posts and struts
Stairs, (excluding landings), except spiral staircase
Edges of slabs and breaks in floors and walls i) Under 20 cm wide
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured).
Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.
Thermo-Mechanically Treated bars of grade Fe-500D or more.
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level.
Thermo-Mechanically Treated bars of grade Fe-500D or more. Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.
Concrete of M25 grade with minimum cement content of 330 kg /cum
All works up to Plinth level: Concrete of M30 grade with minimum cement content of 350 kg /cum
All works upto plinth level: Concrete of M40 grade with minimum cement content of 390 kg/cum
All works above plinth & up to floor V level.: Concrete of M25 grade with minimum cement content of 350 kg /cum
All works above plinth & up to floor V level.: Concrete of M30 grade with minimum cement content of 350 kg /cum
All works above plinth & up to floor V level.: Concrete of M40 grade with minimum cement content of 390 kg /cum
Extra for R.C.C/ B.M.C/ R.M.C. work above floor V level for each four floors or part thereof.
Providing and fixing parallel threaded couplers conforming to IS code on “Reinforcement Couplers for Mechanical Splices of Bars for Concrete Reinforcement - Specification”, to reinforcement bars including threading, enlargement at connection by forging, protecting the preparedreinforcement bars and related operations as required to complete the works per direction of Engineer- in-Charge.
Coupler for 16 mm diameter reinforcement bar
Coupler for 20 mm diameter reinforcement bar
Coupler for 25 mm diameter reinforcement bar
Coupler for 28 mm diameter reinforcement bar
Coupler for 32 mm diameter reinforcement bar
Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system at it provides floor to floor /floor to wall expansion control system for various vertical localtion in load application areas that accommodates multi directional seismic movement without stress toit's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self- centering arrangement that freely rotates / moves in all directions. The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in- Charge. (Material shall confirm to ASTM 6063). Floor Joint of 100 mm gap
Providing and fixing of expansion joint system related with wall joint (internal/external) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall confirm to ASTM 6063). Wall Joint of 100 mm gap
Providing and fixing of expansion joint system of approved make and manufactures for various roof locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members with, self aligning and self centering arragement support plates asper ASTM B221-02. The system shall be such that it provides watertight roof to roof/roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminum base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063). Roof Joint of 100 mm gap
BRICK/ BLOCK WORK or PARTITION WORKS Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: i) Cement mortar 1:6 (1 cement : 6 coarse sand).
Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300 mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge.
Half brick masonry with non modular fly ash bricks of class designation 10, conformingio IS :12894, in super structure above plinth and upto floor V level. Cement mortar 1 : 4 (1 cement : 4 coarse sand)
Extra for half brick masonry in superstructure, above floor V level for every four floors or part thereof by mechanical means.
Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry.
Providing and fixing factory made 18 mm thick single extruded WPC (Wood Polymer composite) solid plain white colour board Jali, CNC (Computer numeric control) routed of approved design by Engineer in -charge which are machine cut for duct/shaft covering, partitions and facades comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium corbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives(maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with properties of being termite/borer proof, water/moisture proof and fire retardant and fixing on M.S (mild steel) frame made of 25 x 25 x 1.5 mm square hollow box section including applying a priming coat of approved steel primer, placed at grid made at 1.0 x 1.0 m or as per requirement at site with necessary stainless steel fasteners and SS screws etc., all complete as per direction of Engineer-In- Charge. (Note: M.S (mild steel) framework with priming coat and necessary SS fasteners and SS screws shall be paid separately.
Providing and fixing at all height wall panelling with phenol bonded Bamboo Mat board conforming to IS:13958-1994 including providing and fixing to frame work made of 50mm x 50mm hardwood plugs including cutting brick work and fixing in cement mortar and making good the wall etc. and also providing and fixing wooden moulded corner beading of triangular shape to the junction of panelling etc. with iron screws all complete as per direction of Engineer-in-Charge.
12mm thickness
Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with zinc coating of 120 gms/sqm(both side inclusive), consisting of floor and ceiling channel 50mm wide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with joints staggered to avoid through cracks, M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corners (25 mm x 25 mm x 0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture's specification and direction of engineer in charge all complete.
75 mm overall thickness partition with 12.5 mm thick double skin fire rated Glass Reinforced Gypsum (GRG) plaster board conforming to IS: 2095: part 3 (Board with BIS certification marks)
GRANITE WORK Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.
Granite of any colour and shade: Area of slab over 0.50 sqm
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.
Granite work
Extra for fixing marble /granite stone, over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive, including cleaning etc. complete.
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
WOOD WORK Providing and fixing factory made single extruded WPC (WoodPolymer Composite) solid door/window/Ceosetory windows & other Frames/Chowkhat comprising of virgin PVC polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximumtoxicity index of 12 for 100 gms) fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 750 kg/ cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge),minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold fast/lugs/SS dash fasteners of required dia and length complete as per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash fasteners shall be paid for separately). Note: For WPC solid door/window frames, minus 5mm tolerance in dimensions i.e depth and width of profile shall be acceptable. Variation in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made.
Frame size 65 x 100 mm
Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid plain flush door shutter of required size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge.
35 mm thick
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length . i) Second class teak wood
Providing and fixing ISI marked flush door shutters conforming to IS :2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters i) 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).
Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured):
Rectangular or square
Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block 30x10x15cm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size).
Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete i) 100X58X1.90 mm
Providing and fixing IS : 12817 marked stainless steel butt hinges (heavy weight) with stainless steel screws etc. complete : size- 125x64x2.50 mm
Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete i) 300x16 mm
Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : size- 300x10 mm
Providing and fixing 50 cm long aluminium kicking plate of size 100x3.15mm, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete.
Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories and screws etc. complete.
Providing and fixing aluminium hanging floor door stopper, ISI marked,anodised (anodic coating not less than grade AC 10 as per IS : 1868)transparent or dyed to required colour and shade, with necessary screws etc. complete. i)Twin rubber stopper
Providing and fixing bright finished brass 100 mm mortice latch and lock, ISI marked, with six levers and a pair of anodised (anodic coating not less than grade AC 10 as per IS : 1868) aluminium lever handles of approved quality with necessary screws etc. complete.
Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality.
1.0 mm thick
Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete.
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing factory made uPVC white colour fixed glazed windows/ventilators comprising of uPVC multi-chambered frame and mullion (where ever required) extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately). Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable. Variation in profile dimension in higher side shall be accepted but no extra payment on this account shall be made.
Fixed window / ventilator made of (small series) frame 47 x 50 mm & mullion 47 x 68 mm both having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. (Area upto 0.75 sqm.)
Float glass panes; 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm).
Extra for providing frosted glass panes 4 mm thick instead of ordinary float glass panes 4 mm thick in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured).
Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontal side & 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mm thick GI sheet ( Zinc coating not less than 120gm/ m²) suitable for mounting 120 min Fire Rated Glazed Door Shutters. The frame shall be filled with Mineral wool Insulation having density min 96Kg/m³ . The frame will have a provision of G.I. Anchor fastners 14 nos ( 5 each on vertical style & 4 on horizontal style of size M10 x 80 ) suitable for fixing in the opening along with Factory made Template for SS Ball Bearing Hinges of Size 100x89x3mm for fixing of fire rated glazed shutter . The frame shall be finished with a approved fire resistant primer or Powder coating of not less than 30 micron in desired shade as per the directions of Engineer - in- charge .
Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 min Fire Rating confirming to IS:3614 (Part II) or EN1634-1:1999, tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, top rail & side rail 60 mm x 60 mm wide and bottom rail of 110 mm x 60 mm made out of 1.6mm thick G.I. sheet (zinc coating not less than 120gm/m²) duly filled mineral wool insulation having density min 96 kg/ m³ and fixing with necessary stainless steel ball bearing hinges of size 100x89x3mm of approved make, including applying a coat of approved fire resistant primer or powder coating not less than 30 micron etc all complete as per direction of Engineer-in-charge.
Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/ powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and as per direction of Engineer-incharge with glass of required thickness having 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested in approved NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The maximum glazing size shall not be more than 1100x2200 mm (w x h) or 2.42 sqm.
Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete.
Providing and fixing PVC Door Frame of size 50x47 mm with a wall thickness of 5 mm (± 0.2 mm), made out of single piece extruded PVC profile, with mitred cut joints and joint with 2 nos of PVC bracket of size 190 mm x 100 mm long arms of cross section size 35 x 15 mm & self driven self taping screws, the vertical door profiles to be reinforced with 40x20 mm M.S. rectangular tube of 0.8 mm , including providing EPDM rubber gasket weather seal throughout the frame, including jointing 5 mm PVC frame strip with PVC solvent cement on the back of the profile. The door frame to be fixed to the wall using 8 x100 mm long anchor fasteners complete, all as per manufacturer's specification and direction of Engineer -in- charge.
35 mm thick factory made Solid panel PVC Door shutter, made out of single piece extruded soild PVC profiles, 5 mm (± 0.2 mm) thick, having styles & rails (except lock rail) of size 95 mmx 35 mm x 5 mm, out of which 75 mm shall be flat and 20 mm shall be tapered (on both side), having one side thickness of 15 mm integrally extruded on the hinge side of the profile for better screw holding power, including reinforcing with MS tube of size 40 mm X 20 mm x 1 mm, joints of styles & rails to be mitered cut & joint with the help of PVC solvent cement, self driven self tapping screws & M.S. rectangular pipes bracket of size 190 mm X 100 mm of cross section size 35 mm x 17 mm x 1 mm at each corner. Single piece extruded 5 mm thick solid PVC Lock rail of size 115 mm x 35 mm, out of which 75 mm to be flat and 20 mm to be tapered at both ends, having 15 mm solid core in middle of rail section integrally extruded, fixing the styles & rails with the help of solvent and self driven self tapping screws of 125 mm x 11 mm, including providing 5 mm Single piece solid PVC extruded sheet inserted in the door as panel, all complete as per manufacturer's specification and direction of Engineerin- charge. Non decorative finish (matt finish)
STEEL WORK Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover
Providing and fixing ball bearing for rolling shutters.
Extra for providing mechanical device chain and crank operation for operating rolling shutters. Exceeding 10.00 sqm and upto 16.80 sqm in the area
Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by Engineer-in- charge, (area of grill to be measured).
Providing and fixing factory made ISI marked steel glazed doors, windows and ventilators, side /top /centre hung, with beading and all members such as F7D,F4B, K11 B and K12 B etc. complete of standard rolled steel sections, joints mitred and flash butt welded and sash bars tenoned and riveted, including providing and fixing of hinges, pivots, including priming coat of approved steel primer, but excluding the cost of other fittings, complete all as per approved design, (sectional weight of only steel members shall be measured for payment).
Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.
Hot finished welded type tubes
Steel work welded in built up sections/framed worK including cutting hoisting, rixing in position andapplying a priming coat of approved steel primer using structural steel, etc. as required.
In gratings, frames, guard bar, ladders, railings, brackts. Gates & similar works.
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
Providing and erecting 2.00 metre high temporary barricading at site; each panel of size 2.50mx3.00m made of 40x40x6mm angle iron or 50x50x3mm hollow MS tube posts/horizontal members/ bracings covered with 1.63mm thick MS sheet. The sheet shall be fixed with 30x5mm MS flat by suitable welding/riveting. The panels shall be made so that gap of 50cm above the ground is available making overall height as 3.5m. MS channel ISLC 75 @ 5.70 kg/m, 50cm long shall be provided at the bottom having oval shaped holes of size 50x25mm at both ends with 50cm long MS angle 40x40x6mm bracing. Suitable arrangement shall be made to fix the barricading to avoid from overturning by providing 250mm long expansion fasteners at both ends. The work shall be executed as per drawing/direction of Engineer-in-Charge which includes writing and painting, arrangement for traffic diversion such as traffic signals during construction at site for day and night, glow lamps, reflective signs, marking, flags, caution tape as directed by the Engineer-in-Charge. The barricading provided shall be retained in position at site continuously i/c shifting of barricading from one location to another location as many times as required during the execution of the entire work till its completion. Rate include its maintenance for damages, painting, all incidentals, labour materials, equipments and works required to execute the job. The barricading shall not be removed without prior approval of Engineer-in-Charge. (Note :- One time payment shall be made for providing barricading from start of work till completion of work i/c shifting. The barricading provided shall remain to be the property of the contractor on completion of the work).
Providing and fixing roofing consist of 0.8 mm thick galvanized steel deck sheet confirming to IS 277:1992 used as permanent shuttering over which MS wire mesh 3mm laid at 100x100 mm grid including edge trim covered with concrete. This metal deck will be supported on structural steel beam with shear studs. (Structural steel like Beam, column, joists etc. & concrete of different grade as per design will be paid separately).
FLOORING WORK Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge :
Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.
Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25mm thick
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.
62 mm thick cement concrete flooring with concrete hardener topping, under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) and top layer 12mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate, 6mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacture’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Stone tile (polished) work for wall lining over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and cement slurry @ 3.3 kg/sqm including pointing in white cement complete. 8mm thick; Granite of any colour and shade
Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Glazed Vitrified tiles Matt/Antiskid finish of size; Size of Tile 600 x 600 mm
Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.
Double charge vitrified tile polished finish of size; Size of Tile 600 x 600 mm
Providing and laying Vitrified double charged tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete.
Size of Tile 600x600 mm
Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 (1 cement :4 coarse sand) : Medium shade pigment using 50% white cement, 50% ordinary cement
Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS:15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.
ROOFING WORKS Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design :
In 75x75 mm deep chase
In 75x75 mm deep chase
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with :
Fully Perforated Gypsum Plaster Board of size 1200 x 2400x12.5 mm having approx. 15 % perforated area with perforation size and pattern as approved by the Engineerin- charge and as per manufacturer's specification, with all 4 side tapered and backed by acoustical tissue with NRC value not less than 0.60
12.5 mm thick tapered edge Glass Reinforced Gypsum(GRG) board conforming to IS: 2095- (Part 3):1996 (Boards with BIS certification marks)
Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge.
GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece.
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner.
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner.
FINISHING WORK CEMENT PLASTER (IN COARSE SAND) 12 mm cement plaster :
1:6 (1 cement: 6 fine sand)
15 mm cement plaster on the rough side of single or half brick wall of mix :
1:6 (1 cement: 6 fine sand)
18 mm cement plaster in two coats under layer 12 mm thick cementplaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand).
6 mm cement plaster of mix :
1:3 (1 cement : 3 fine sand)
Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
White washing with lime to give an even shade :
New work (three or more coats)
Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives.
New work (Two or more coats applied @ 1.43 litre/ 10 sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm.
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :
Two or more coats on new work
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Distempering with 1st quality acrylic distemper, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour.
Two coats
Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applyingadditional coats wherever required to achieve even shade and colour.
Two coats
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade i) New work (two or more coats) over and including water thinnable priming coat with cement primer
Finishing walls with textured exterior paint of required shade i) New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm
Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade i) Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture
Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour. i) Two coats
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content.
With ready mixed pink or grey primer on wood work (hard and soft wood) having VOC content less than 50 grams/ litre
With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre
Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres.
Extra for compaction of earth work in embankment under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density).
Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge.
With material conforming to Grade-I (size range 75 mm to 0.075 mm) having CBR Value-30
Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 40 mm nominal size in appropriate proportions as per approved & specified design criteria, providing dowel bars with sleeve/ tie bars wherever required, laying at site, spreading and compacting mechanically by using needle and surface vibrators, levelling to required slope/ camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints (10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in-charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars to be paid separately). Note:- Cement content considered in M-30 is @ 340 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately.
Cement concrete manufactured in automatic batching plant (RMC plant) i/c transportation to site in transit mixer
Providing and fixing pre-moulded joint filler in expansion joints of RCC roads / CC pavements after making the joints dust free with high pressure air jet cleaners, all complete as per direction of the Engineer-in-Charge. (Pre-moulded joint fillers shall be made of bitumen hot sealing compound impregnated fibre board having impregnation more than 35%, conforming to IS:1838 for fibre board and IS: 1834 for hot sealing bitumen compound grade A.)
Providing and filling in position rubberized bitumen hot sealing compound for sealing of expansion joints in roads / pavements all complete as per direction of the Engineer-in-Charge.
Using grade 'A' sealing compound conforming to IS: 1834.
Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.
60mm thick cement concrete paver block of M-35 grade with approved colour, design & pattern.
Painting runway/taxi track/apron marking with adequate nos of coats to give uniform finish with road marking paint of superior make as approved by the Engineer-in-charge, i/c cleaning the surface of ail dirt, scales, oil, grease and other foreign material etc. and lining out complete.
New work (Two or more coats)
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).
ALUMINIUM WORK Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :
For fixed portion: Powder coated aluminium (minimum thickness of powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineerin- charge. Pre-laminated particle board with decorative lamination on both sides
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 5 mm thickness weight not less than 12.50 kg/sqm)
Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness
Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg., for doors, including cost of cutting floors ,embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. i) With brass cover plate minimum 1.25 mm thickness.
Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0 mm thick & 2100 mm long with SS screws etc .complete as per direction of Engineer-in-Charge. Powder coated minimum thickness 50 micron aluminium tubular handle bar
Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.
Filling the gap in between aluminium/ stone/ wood frame and adjacent RCC/Brick/ Stone/ wood/ Ceramic/ Gypsum work by providing weather/structural non sag elastomeric PU sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete, complying to ASTM C920, DIN 18540- F & ISO 11600. Upto 10 mm depth and 10 mm width
Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor. (Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.25.2) For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. (i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement.
Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all accessories and hardwares for the openable panels as specified and of the approved make such as heavy duty stainless steel friction hinges, min 4 -point cremone locking sets with stainless steel plates, handles, buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all complete as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineerin-Charge.
WATER PROOFING Laying of membrane: Providing & installing pre applied 3.5mm SBS membrane with top granular finish, from the positive side waterproofing treatment for “Raft Slab” by using flexible, SBS sheet membrane before casting of the base RCC slab over the laid uniform substrate. Membrane should be supplied with original manufacturer's Material Test Certificate (MTC) & CE marking & membrane should be installed in strict accordance with original manufacturer's instructions and contractor should produce method statement from original product manufacturer (private label supplier are not acceptable).The manufacturer shall provide the certificate of origin(COO). The system should be fully bonded to the RCC and consists of highly resilient SBS membrane layer and a trafficable granular grey slate layer. The SBS Membrane is multi-layer composite system reinforced with polyester and does not require protection screed protection also & steel reinforcement laid directly over the robust membrane allowing faster construction. The membrane conforming the following properties of the specified membrane 1) Tear Resistance (L/T), > 500±150 (N) as per ASTM D 5147, 2) Tensile Strength (L/T), ≥ 600 N as per ASTM D5147, 3) Elongation (L/T), 40±20/40±20 (%) as per ASTM D5147, 4) Puncture Resistance: - > 1050 (N) as per ASTM E 154, 5) Peel Adhesion strength to the poured Concrete: > 3200 ±150(N/m) ASTM D903-1998 The layer of membrane shall be overlapped by sealing all joints with Butane / LPG torch with minimum 75 mm side laps & 100mm end laps to form a monolithic system. The laying of membrane shall be got done through the authorized applicator of the manufacturer of membrane.
Grouting of Pile Heads: Firstly, rust, floating pulp and stones on the side wall of pile head and pile core can be cleaned with steel wire brush. Secondly, Providing and laying a proper smooth surface on top of pile head with 40mm thick micro concrete after suitable temporary shuttering around the pile periphery upto required level upto 75mm (shuttering shall be in client scope) of Sika/TN to achieve the desired dimension and level followed by the removal of form work after one day. After PCC, the waterproofing SBS membrane shall be laid and terminated in pile head with the help of joint sealing by installing the stainless-steel metal hose hoop at the closing position and tighten it. all complete as per the instruction of manufacturer (for pile dia 500-800mm)
Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of: (i) Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofing compound conforming to IS 2645 in recommended proportions including rounding off junction of vertical and horizontal surface. (ii) IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface. (iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg. per sqm of area. (iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 kg/sqm).
Providing and laying APP (Atactic Polypropylene Polymer) modified prefabricated five layer 3 mm thick water proofing membrane, black finished reinforced with non-woven polyester matt consisting of a coat of bitumen primer for bitumen membrane @ 0.40 litre/sqm by the same membrane manufacture of density at 25°C, 0.87-0.89 kg/ litre and viscocity 70-160 cps. Over the primer coat the layer of membrane shall be laid using Butane Torch and sealing all joints etc, and preparing the surface complete. The vital physical and chemical parameters of the membrane shall be as under : Joint strength in longitudinal and transverse direction at 23°C as 650/ 450N/ 5cm. Tear strength in longitudinal and transverse direction as 300/ 250N. Softening point of membrane not less than 150°C. Cold flexibility shall be upto -2°C when tested in accordance with ASTM, D - 5147. The laying of membrane shall be got done through the authorised applicator of the manufacturer of membrane : 3 mm thick
Extra for covering top of membrane with Geotextile, 120 gsm non woven, 100% polyester of thickness 1 to 1.25 mm bonded to the membrane with intermittent touch by heating the membrane by Butane Torch as per manufactures recommendation.
Providing and laying six courses water proofing treatment with bitumen felt over roofs consisting of first, third and fifth courses of blown or / and residual bitumen applied hot at 1.45, 1.20 and 1.70 kg per square metre of area respectively, second and fourth courses of roofing felt type 2 grade I (fibre base self finished bitumen felt) six and final courses of stone grit 6 mm and down size or pea sized gravel spread at 6 cubic decimeter per sqm including preparation of surface, excluding grading, compete.
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage.
For vertical surface two coats @ 0.70 kg per sqm
For horizontal surface one coat @1.10 kg per sqm.
Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size)
MISS. WORK Providing & fixing Chicken wire mesh on joints of RCC & Brick work before plastering complete in the direction of Engineer-in-charge.
Providing and fixing Brand S.S. 316 Grade Mortice Handle Ø22mm with euro profile escutcheons [Finish : Satin] [Mechanically BSEN 1906 : 2010 Certified] AND Brand Lock Body - 9'' [With Stainless Steel main and strike plate] [Fire Rated – BSEN 1634 : 1 : 2000 Certified] complete as direction of Engineer-in-charge.
Providing and fixing Toughened glass 12 mm thickness in partion/ walls with required framing and accessories as per specifications to complete as direction of Engineer-in-charge.
Lead lined doors Providing & fixing of Hollow metal lead lined door from ISO 9001-2008 certified Manufacturer Pressed Galvanized steel Single /Double leaf to required sizes of approved make which consists of frame, shutter, infill and finish as detailed below. Door frame shall be Single rebate profile of size 120 x 62 mm made out of 1.60mm (16gauge) thick galvanized steel sheet. Frames shall be Butt jointed and field assembled with self tabs. The Shutter & Frame Shall be fully lead lined of min of 2 MM lead Sheet with 99% purity and as defined by AERB. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Rubber door silencers should be provided on the striking jamb. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening.
Lead lined doors shutters; Door leaf shall be 44 mm thick fully flush double skin door without vision lite.incase vision lite is required it shall be only Lead Glass as recomomnded by AERB/DRC Door leaf shall be manufactured from 1.0mm (18guage) thick galvanised steel sheet. The internal construction of the door should be rigid with lead line of 2mm thick all across the inside of the exposed surface. In addition the door should have a basic infill ROCK WOOL with necessary reinforcement both on top and bottom. All doors should be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers as per ANSI Standard .The edges should be interlocked with a bending radius of 1.4mm. All doors and frames shall be finished with Powder coating, approved RAL colour. The door Leaf & Frame shall be in a position so that Lead Line should overlap. including following fixtures & fittings a. Supply & fixing of SS Ball Bearing Hinges of size 100 x 89 x 3mm complet with SS Screws b. Supply & fixing of anchor fastners of HILTI/ FISHER/ Equvalent of M10X120mm length. c. Supply & fixing of door closers of BLC-604 Becker Fire Solutions/ TS-89 DORMA / GEZE TS 2000 Series d. Supply & fixing of Stainless Tower Bolt 300mm Long for Double leaf door of height upto 2100mm of Becker Fire Solutions. / Dorset Make with necessary screws as required. e. Supply and Filling the gap between wall & Door frame by using silicone sealant and Wool insulaion on both side of the door f. Supply & fixing of Mortise Dead Lock DL7260K Becker Fire Solutions / 288A DORMA / GEZE Make with Half Cylinder on Pull/Outside of the door. g. Supply & fixing of SS D Type SS Pull Handle B2B of size 300mm mm Long of PHD2230 Becker Fire Solutions/ TGDI30022 DORMA / GEZE Make on Pull Side with 400x200mmx1.0mm thick SS Push Plate on Push Side.
Barrium Plaster: Providing and applying the Barium plastering on the brick walls and columns of rooms that needed radiation shielded with consistency of 2mm Pb equivalent imply to all walls. The plaster is 20-25mm thick with the mixture of 25% : 65% : 10% ratio of barium, sand and cement respectively. composition of barium sulphate as follows: Barium Sulphate BA2SO4 95.0 + 2.0% Silica SiO2 2.15% Alumina AI2O3 0.4% Iron Oxide Fe2O3 0.9% Calcium Oxide CaO 0.15%max
Roller Blinds - Screen fabric : Providing and fixing of roller blind should have sturdy aluminium top tube of 38mm diameter, powder coated bottom bar, with suitable roller clutch mechanism and plastic ball chain. The roller blind fabric should possess the mentioned specifications: a) Composition – 36% Fiberglass & 64% Vinyl b) Openness factor - 3% - 5% c) Fabric thickness – 0.43 mm +-5% & Weight - 393 gsm (± 5%) d) Width - 300 cm e) Color fastness - Grade 6 f) UV blockage – Approximately 90% - 99% g) Flame retardancy – NFPA 701 h) Anti-fungal / Anti-bacterial – ASTM E 2180 product protection i) Environmental certification – GREENGUARD Gold certified j) Acoustical value - NRC 0.50, SAA 0.50. Aluminium profile should have temper WP consisting of alloy 63400 along with anodizing of 10 micron and powder coating of 60 micron. The tensile strength of profile should be 9.10 Kg/mm square and elongation 18.The control clutch drive unit engineered heavy duty chain drive pulley operating system consisting of gear clutch housing and locking plug containing minimum 6 ribs and inserted at minimum of 38mm into roller tube. It is self-lubricating exclusive clutch with safety pins for secure bracket installation and unlocking pin for quick manual removal. Universal clutch is most convenient for large windows down to the smallest windows. It shall be driven by a ball chain pulley with ball chain and can be positioned at right hand or left hand side of the shade. Clutch gear ratio of 1.75:1 for reduced operating force on larger blinds. Mounting hardware brackets universal brackets including end plug bracket with lock down retainer device. Brackets finish of powder coated metal installation brackets made of stamped and hardened steel. Roller tube circular-shaped aluminium tube extruded from alloy 63400 and temper WP. Bottom rail flat-shaped extruded aluminium from alloy 63400 and temper WP. Ball chain shall be 2mm diameter cord with plastic balls moulded to form an endless ball chain. It is used for raising or lowering action of the shades. Plastic parts all plastic components are UV-stable compounds available white.
Roller Blinds - Blackout fabric : Providing and fixing of roller blind of sturdy aluminium top tube of 38mm diameter, powder coated bottom bar, with suitable roller clutch mechanism and plastic ball chain. The roller blind fabric should possess the mentioned specifications: a) Composition - 100% Polyester b) Openness factor - Opaque c) Fabric thickness - 0.5 mm +-5% & Weight - 450 gsm +-5% d) Width - 250 cm e) Fire rating - AS1530.3-1999 f) Water/Stain resistance - Protected by TEFLON fabric protector g) Environmental certification - OEKO-TEX Standard 100. Aluminium profile should have temper WP consisting of alloy 63400 along with anodizing of 10 micron and powder coating of 60 micron. The tensile strength of profile should be 9.10 Kg/mm square and elongation 18.The control clutch drive unit engineered heavy duty chain drive pulley operating system consisting of gear clutch housing and locking plug containing minimum 6 ribs and inserted at minimum of 38mm into roller tube. It is self-lubricating exclusive clutch with safety pins for secure bracket installation and unlocking pin for quick manual removal. Universal clutch is most convenient for large windows down to the smallest windows. It shall be driven by a ball chain pulley with ball chain and can be positioned at right hand or left hand side of the shade. Clutch gear ratio of 1.75:1 for reduced operating force on larger blinds. Mounting hardware brackets universal brackets including end plug bracket with lock down retainer device. Brackets finish of powder coated metal installation brackets made of stamped and hardened steel. Roller tube circular-shaped aluminium tube extruded from alloy 63400 and temper WP. Bottom rail flat-shaped extruded aluminium from alloy 63400 and temper WP. Ball chain shall be 2mm diameter cord with plastic balls moulded to form an endless ball chain. It is used for raising or lowering action of the shades. Plastic parts all plastic components are UV-stable compounds available white.
Rest room Cubicles : Providing and installing in required position, approved Toilet / Restroom Cubicles in "L" shape and of approved brand, series, colour & quality in sizes as specified below and made out of 12mm thick solid grade high pressure laminate (of approved colour & conforming to EN 438-4) including supporting arrangements for top rail on existing back wall, end finishing, all accessories etc. complete as per approved shop drawings, manufacturer's specifications and all as per directions and to the satisfaction of the Engineer-in-charge and comprising of the following : SS “U” Channel - 304 Grade SS “F” Channel - 304 Grade SS Box Top Rail - 304 Grade SS Coat Hook with door stopper- 304 Grade SS Gravity Hinges (right / left)- 304 Grade SS Privacy Thumb turn c/w Occupancy Indicator- 304 Grade SS Door Knob - 304 Grade SS Hinges with Cover - 304 Grade SS Adjustable Foot - 316 Grade Rubber Lining for Groove- 304 Grade S.S.Screws of 304 Grade & PVC Wall Plugs- 304 Grade a) Size: Toilet / Restroom Cubicles of 1200mm (W) x 1500mm (L) x 2100mm (H) Door Size : 600mm X 1925mm (excluding Top & bottom gap 150mm) Divider Height : 1945mm (excluding Top & bottom gap 150mm)
URINAL PARTITION : Providing and installing in required position, approved Urinal partitions of approved brand, series, colour & quality in sizes as specified below and made out of 12mm thick solid grade high pressure laminate (of approved colour & conforming to EN 438-4) including supporting arrangements wall, end finishing, all fixing and fitting accessories of grade SS 304, etc. complete as per approved shop drawings, manufacturer's specifications and all as per directions and to the satisfaction of the Engineer-in-charge : size of partition: 900mm x 450mm
PILING WORK Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap).
500 mm dia piles
Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Note: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing. Note: 2. Testing agency shall submit the design of loading platform for the approval of Engineer-in-charge.
Single pile upto 50 tonne Safe capacity; Initial test (Test Load 2.5 times the Safe capacity)
Single pile above 50 tonne and upto 100 tonne Safe capacity; Initial test (Test Load 2.5 times the Safe capacity)
Group of two or more piles upto 50 tonne Safe capacity; Initial test (Test Load 2.5 times the Safe capacity)
Cyclic vertical load testing of pile in accordance with IS Code of practice IS:2911 (part IV) by Kentledge method including preparation of pile head etc for.
Single pile; Upto 50 tonne Safe capacity pile
Above 50 tonne and upto 100 tonne Safe capacity pile
Group of two or more piles; Upto 400 tonne Safe capacity of group
Lateral load testing of single pile in accordance with IS Code of practice IS : 2911 (Part IV) for determining safe allowable lateral load on pile :
Upto 50 tonne capacity pile
Supplying and stacking of good earth at site including royalty and carriage nupto 5 km complete (earth measured in stacks will be reduced by 20% for payment).
Supplying and stacking at site dump manure from approved source, including carriage upto 5 km complete (manure measured in stacks will be reduced by 8% for payment) :
Screened through sieve of I.S. designation 20 mm
Mixing earth and sludge or manure in the required proportion specified or directed by the Officer-in-charge
In rows 5 cm apart in both directions
Preparation of beds for hedging and shrubbery by excavating 60 cm deep and trenching the excavated base to a further depth of 30 cm, refilling the excavated earth after breaking clods and mixing with sludge or manure in the ratio of 8:1 (8 parts of stacked volume of earth after reduction by 20% : one part of stacked volume of sludge or manure after reduction by 8%), flooding with water, filling with earth if necessary, watering and finally fine dressing, leveling etc. including stacking and disposal of materials declared unserviceable and surplus earth by spreading and leveling as directed, within a lead of 50 m, lift up to 1.5 m complete.
Felling trees of the girth (measured at a height of 1 m above ground level), including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.
Beyond 60 cm girth upto and including 120 cm girth
Beyond 120 cm girth upto and including 240 cm girth
Above 240 cm girth
Providing and displaying of Areca Palm having ht. 2.40 m to 2.70 m with 12 to 14 suckers, well developed, fresh and healthy with lush green foliage in 35 cm size of Bucket type cement pots & as per direction of the officer-in-charge.
Providing and Displaying plants Chrysenthemum single named variety in different colour well developed, having 45 to 60 cm ht., minimum 150 and above half bloom flowers well stacked with bamboo stick having three layer tiding by thread fresh and healthy foliage in 30 cm Earthen Pot and as per direction of the officer-in-charge.
Providing and Displaying plants Salvia ht. 45 to 60 cm multi branches stacking with bamboo stick specimen plants type with full bloom well developed in 30 cm Earthen Pot/Plastic Pot and as per direction of the officer-in-charge.
Providing and Displaying plants Cockscomb well developed fresh & healthy 20 to 25 cm ht. attractive colours fully bloomed in 20 cm Earthen Pot/ Plastic Pot and as per direction of the officer-in-charge.
Providing and Displaying plants Sunflower single well developed 8 to 10 half bloom buds multi branched in fresh & healthy full stacked with green painted bamboo stick stacking in 25 cm Earthen Pot/Plastic Pot and as per direction of the officer-in-charge.
Providing and Displaying Topiary plant of Ficus Panda well developed with fresh & healthy foliage with 3 to 4 Ball and 60 to 75 cm spread each Ball, 135 to 150 cm ht., in 35 cm Cement Tray /Cement Pot as per direction of the officer-in-charge.
Repairs to plaster of thickness 12 mm to 20 mm in patches of area 2.5 sq.meters and under, including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete, including disposal of rubbish to the dumping ground, all complete as per direction of Engineer-in-Charge. With cement mortar 1:4 (1cement: 4 coarse sand)
Repairs & Dismantling Works ( Dismantling of existing Building and Shifting of existing service (underground/ overhead as electrical, plumbing, etc) comes in construction area.
PLUMBING & SANITARY WORKS Sanitary Installations & Internal Water Supply Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :
W.C. pan with ISI marked white solid plastic seat and lid
Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:
White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm including painting of fittings and brackets, cutting and making good the walls wherever required :
510x1040 mm bowl depth 250 mm
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing P.V.C. Waste pipe for sink or wash basin including P.V.C. waste fittings complete.
Semi rigid pipe: 40 mm dia.
Providing and fixing CP Brass 32mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge.
Providing and fixing CP Brass Single lever telephonic wall mixer of quality & make as approved by Engineer in charge.
15 mm nominal dia
Providing and fixing toilet paper holder :
C.P. brass
Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/ 6 litre (adjustable to 4 litre/ 8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete.
Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge.
Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :
15 mm nominal bore
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.
15 mm nominal bore
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931
15 mm nominal bore
Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet :
150 mm dia.
Providing and fixing C.P. Brass extension nipple (size 15mmx50mm) of approved make and quality as per direction of Engineer-in-charge.
Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:-
a) White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer.
Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings.
Providing and fixing 15mm C.P brass Single Lever Basin Mixer approved equivalent for Wash Basin Including cutting and making good the walls wherever required.(For Hostel and Residential Block)
Providing and fixing uplasticised PVC connection pipe with brass unions : 45 cm length
15 mm nominal bore
Providing and fixing C.P. brass 15 mm nominal bore two way bib cock
Providing and fixing C.P. cast brass twin coat hooks fixed to PVC rawl plug with SS screws approved equivalent.
Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean type W.C. of quality and make as approved by Engineer - in -charge.
Providing and fixing 15mm C.P brass Sink Mixer approved equivalent.) for kitchen sink with swinging spout complete. Including cutting and making good the walls wherever required .
Providing and fixing of C.P. brass 600 mm size towel rail fixed with C.P. brass screws complete in all respects.
Providing and fixing of C.P. brass Soap Dish fixed with C.P. brass screws complete in all respects.
Providing and fixing white vitreous china laboratory sink with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required :
Size 450x300x150 mm
Providing & fixing chrome plated brass battery based infrared sensor operated pillar cock, having foam flow technology. 15 mm nominal bore
Supply, Installation, Testing and commissioning of wall hanging drinking online water cooler With cooling capacity of 60 LPH, with one drinking station and one swan neck tap for bottle filler , with MDCU29 Antimicrobial touch pad amd made by stainless steel top and heavy duty galvanized steel frame. With cooling capacity, ADA Compliant, size 472 mm Depth X 447mm width, flexible bubbler guard , Model- PG8AC ,operated between 50 to 120 PSI, Chiller unit Suitable to R134a Refrigerant, Adjustable thermostat control, uitable for 220-230v/50-60 hz A/C Supply Complete with all ccessories which include MD-CU29, which is an EPA egistered antimicrobial copper that fights off icroorganisms which include MRSA and e-coli. The water Fountain shall possess NSF-USA, Green building, energy star saving certification, and to be placed at different location of buidling. for proper functioning and aesthetic view as directed by the engineer-in-charge without any extra cost. Certified By NSF, GRIHA, TUV, UL, WATER QUALITY Asso.,UL, Stare rating Energy saver. Mechanical operation.
Soil, Waste, Vent & Rain Water Pipes Providing and laying cement concrete in 1:2:4 ( 1cement : 2 Coarse sand : 4 graded stone aggregate 20 mm nominal size ) and curing complete, including cost of form work.
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1mx1mx400micron, finished with 12mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams.
Providing and fixing sound-insulated mineral reinforced 3 layer polypropylene pipe & fitting drainage system. Conforming to BS EN1451 standard. Density of pipe is greater than 1.20g/cm³ and the pipe connections are leak-proof up to an internal excess water pressureof 1.0 bar.Offering sound levels of not more than 20dB as per DIN 4109 at a flow rate of 4ltr/Sec.Marking on pipe and fittings are as per EN1451 standard. All necessary fittings fitted with factory fitted lip ring including painting with ordinary cement based paint for external installation.
160 mm dia
110 mm dia
50 mm dia
40 mm dia
Providing and fixing PP 110mm P Trap with minimum 50mm water seal with rubber seal on inlet to push fit hopper for indirect waste connections.
Providing, fixing, testing and commissioning of pipe inlet fittings fabricated with Polyproplene Pipe with maximum 3 inlets 40, 50 & 75 mm OD size Polyproplene pipe, fixed to 'P' traps including Dripseal/Pipe seal/solvent /rubber ring joint complete .
Providing and fixing floor drain with 50mm outlet and 100 mm inlet having 50mm seal for indirect floor drain /balcony Drain.
Providing and fixing heavy duty square tainless steel grating with hinged cockroach trap.
Providing and fixing end cap (door piece) of pp for cleaning.
110 mm dia
Providing and fixing vent cowl.
110 mm dia
Water Supply Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.
Internal Work - Exposed on Wall 25 mm nominal outer dia .Pipes.
32 mm nominal outer dia .Pipes.
40 mm nominal outer dia .Pipes.
50 mm nominal outer dia .Pipes.
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work including cutting chases and making good the walls etc.
20 mm nominal outer dia .Pipes.
25 mm nominal outer dia .Pipes.
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc. Internal work - Exposed on Wall For Roof
25 mm dia nominal bore
32 mm dia nominal bore
40 mm dia nominal bore
50 mm dia nominal bore
65 mm dia nominal bore
80 mm dia nominal bore
100 mm dia nominal bore
150 mm dia nominal bore
Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :
With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :
25 mm dia nominal bore
32 mm dia nominal bore
40 mm dia nominal bore
50 mm dia nominal bore
Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) :
20 mm dia nominal bore
25 mm dia nominal bore
32 mm dia nominal bore
40 mm dia nominal bore
50 mm dia nominal bore
65 mm dia. nominal bore
80 mm dia. nominal bore
Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof.
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required.
65 mm dia
80 mm dia
100 mm dia
150 mm dia
Providing and fixing forged brass ball valve of brass body with hard chrome plated steel ball inside PTFE (Teflon) seat & ring with chrome plated centre handle with female BSP threads complete in all respects.
15 mm nominal bore
20 mm nominal bore
25 mm nominal bore
32 mm nominal bore
40 mm nominal bore
50 mm nominal bore
Providing and fixing forged brass single acting air release valve with screwed inlet 25 mm dia.
Providing and fixing of Single phase electrical actuator operated wafer type rubber lined butterfly valve with by pass arrangement as per drawing attached including level controller, 3 nos. normal butter fly valves,necessary control and Power cables ( Maximum 10 M. Length of each type) and control panel installed on OH tank filling line near the tanks complete in all respects.
50 mm dia.
"Hot Water Tank : Cylindrical - vertical / horizontal, Stainless steel 304 grade with 100 mm thick Rock Wool insulation including 22 SWG aluminium cladding. " The entire system should be complete with internal piping in SS(304) with 50 mm rock wool insulation of density 48 kg/m3 with 26 SWG Al cladding, necessary isolation valves, Y type CI strainer, hardwares, temperature gauge of range 0 - 120oC, water meter, MS angle iron structure of min thickness 3 mm duly painted etc as required to complete the system in all respects. The entire system should be approved by BIS as per IS : 12933 and as per local regulations.
System Capacity : 5000 liters ( storage tank of 5000 (SS304) litres ) per day (LPD) having 50 collectors.
RO WATER SUPPLY PIPE Providing and fixing Stainless Steel pipes confirming to corrosion resistant ausenitic steel, chrome-nickel- molybdenum X2CrNiMO17-12-2, no.14401 acordance to DIN-EN10088, according to AISI 316L with press type fitings with V profile for Hot and cold-water supply, capable to withstand temperature upto 135C and 16 bar pressure with length of 6 meters in accordance with dvgw regulation GW 41 such as tees, coupling, elbow, male adapter, connectors etc with Black grooved O-rings of EPDM material can withstand temperature upto 135C including suitable connection as per site requirement. Direct contact of stainless steel pipes and fittings to galvanized iron should be vaoided by inserting approved typeof filler material as per project managers/consultant requirement. Flanges, clamps with hanger as a spacing of 2 m centre to centre min or as required, necessary adapters for GI/copper and CP fittings, jointing, sundries, cutting holes in walls/floors/slabs & making good complete. ( For Domestic hot and cold water supply as well for external water supply covered with insulation ).
15 mm nominal outer dia pipes
22 mm nominal outer dia pipes
28 mm nominal outer dia pipes
35 mm nominal outer dia pipes
42 mm nominal outer dia pipes
54 mm nominal outer dia pipes
76.1 mm nominal outer dia pipes
88.9 mm nominal outer dia pipes
RO PLANT Supplying, installing, testing & commissioning of R.O. Plant including filters, pumps, dosing units, control panel, piping and valves and 1,000 litres SS 304 stainless steel tank complete as per specifcation and drawings. For Drinking Feed Flow - 1000 LPH Product Flow - 500 LPH Reject Flow - 500 LPH Recovery - 50% Mode of operation - Manual Operating Pressure - 10 to 12 Kg/cm2
External Sewerage & Storm System Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.
All kinds of soil.
Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
Extra for excavating trenches for pipes, cables etc. in all kinds of soil for depth exceeding 1.5 m, but not exceeding 3 m. (Rate is over corresponding basic item for depth upto 1.5 metre).
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth,consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Extra for every additional lift of 1.5 m or part thereof in excavation /banking excavated or stacked materials.
All kinds of soil
1:5:10 (1 cement : 5 coarse sand (zone-III) derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design:
180x150 mm size P type: With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg)
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS : 1786 having minimum cross section as 23 mmx25mm and over all minimum length 263 mm and width as 165mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.
Providing and laying non-pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete. (for storm drainage)
150 mm dia RCC pipe
250 mm dia RCC pipe
Providing and laying non-pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete. (for storm drainage)
150 mm dia RCC pipe
250 mm dia RCC pipe
Constructing bricks masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design :
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Extra for depth beyond 45 cm of brick masonry chamber For 455x610 mm size
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
"Water Supply, Drainage Pumps & Water Treatment Equipments Raw Water Treatment Feed Pump set Providing, fixing, commissioing and testing package vertical raw water pumps, comprising of Electrical Driven inline pumping with all accessories, Pumps shall be with C.I. Base, S.S 304, impeller, shaft, mechanical seal, S.S. Shaft directly coupled to motor suitable for operation on 400/440 volts, 3 phase 2900 RPM. TEFC electronic motor mounted on a common channel baseplate 150mm dia pressure gauge, GM isolation cock and cement concrete foundation with plaster with dunlop cushy foot mountings with all accessories such as vibration eliminator, NRVs, valves, pressure guage bourden type, common suction and delivery header, bellows on sucton and delivery side complete in all repsects." Pumps shall be suitable for 415 ± 10% volts 3 phase 50 Hz A.C supply & shall be having the following requirement complete with foundation and associated civil works. Suction & Delivery Header - SS 304 Control Valve On suction and Delivery - Ball Valve Only (No Butterfly Valve Accepted). Flow Prevention - Only Check Valve Suction & delivery header including all pipes, suction & delivery sides valves, NRV, Pressure gauges & accessories complete. Flow Rate : 8.5 LPS (1 working + 1 stand by) Head : 35 M
Min. Motor HP : 8.0 H.P. (Each)
Domestic Water Transfer Pumps Supplying & supervision of testing & commissioning of Booster Pumpset (Hydropneumatic systems) as described below . Supplying & supervision of testing & commissioning of package vertical Hydropneumatic system, comprising of 3.0 nos. (2 duty + 1 stand by) Electrical Driven inline pumping sets each of 8.5 LPS to a head to 60 meter with all accessories, Pumps shall be with C.I. Base, S.S 304, impeller, shaft, mechanical seal, S.S. Shaft directly coupled to motor suitable for operation on 400/440 volts, 3 phase 2900 RPM. TEFC electronic motor mounted on a common channel baseplate 150mm dia pressure gauge, GM isolation cock and cement concrete foundation with plaster with dunlop cushy foot mountings with all accessories such as vibration eliminator, NRVs, valves, pressure switch, common suction and delivery header, bellows on sucton and delivery side complete in all repsects. Pump mounted or wall mounted microprocessor based controller, Electronic control panel with frequency inverter, logic controller relays, pressure sensor, pressure sensor transmitter, electrical wiring, cabling from panel to pumps, level controller, two lined LCD display, diodes to indicate pump ready, pump running and fault capable to communicate with toher RS 485 interface. with Power box equipped with fuses or isolators or circuit breakers as required. complete with all accessories as per manufacturer specifications. Suction & Delivery Header - SS 304 Control Valve On suction and Delivery - Ball Valve Only (No Butterfly Valve Accepted). Flow Prevention - Only Check Valve One Number Variable frequency Drive Impeller : Stainless Steel Shaft : Stainless Steel RPM : 2900. Mover : Electric Motor HP - As required. Necessary foundation with bolts Ball valve on suction & delivery NRV on delivery
Dust & vermin proof cubicle type motor control centre fabricated from powder coated 16 SWG MS sheet suitable to automatic working of above mentioned pumps.
Soft Water Transfer Pumps Providing, fixing, commissioing and testing package vertical soft water pumps, comprising of Electrical Driven inline pumping with all accessories, Pumps shall be with C.I. Base, S.S 304, impeller, shaft, mechanical seal, S.S. Shaft directly coupled to motor suitable for operation on 400/440 volts, 3 phase 2900 RPM. TEFC electronic motor mounted on a common channel baseplate 150mm dia pressure gauge, GM isolation cock and cement concrete foundation with plaster with dunlop cushy foot mountings with all accessories such as vibration eliminator, NRVs, valves, pressure guage bourden type, common suction and delivery header, bellows on sucton and delivery side complete in all repsects. Pumps shall be suitable for 415 ± 10% volts 3 phase 50 Hz A.C supply & shall be having the following requirement complete with foundation and associated civil works. Suction & Delivery Header - SS 304 Control Valve On suction and Delivery - Ball Valve Only (No Butterfly Valve Accepted). Flow Prevention - Only Check Valve Suction & delivery header including all pipes, suction & delivery sides valves, NRV, Pressure gauges & accessories complete. Flow Rate : 6.0 LPS (1 working + 1 stand by) Head : 60 M
Min. Motor HP : 10.0 H.P. (Each)
Supply, installing, testing and commissioning of submersible dewatering single stage single entry pumps with C.I.body and C.I. two vane enclosed type impeller, SS-304 shaft connected to TEFC submersible motor for 415 + 10% volts, 3 phase, 50 cycles A.C. power supply with mechanical seal, pump connector unit with rubber diaphragm and bend, vertical discharge pipe, guide pipe and chain in built level controller, sequence running controller, arrangement for both pumps running together in case of emenegency, audible hooter for failure or flooding, dry running Protection complete in all respects. (Pumps shall be installed in a set of two pumps One working and One standby) Pump Room Drainage Pumps (Pumps to be suitable to handle solids upto 30 mm size) Capacity - 4.0 LPS (Each) Head - 10 M
H.P. - 2.2 HP Approx.
Supply Installation,Testing & Commissioning of vertical self supporting Filter fabricated from MS sheet as per IS: 2825, (minimum thickness of shall 6 mm and dished end 8 mm)) pressure gauges, sample cock, GI class 'C' face piping, CI butterfly valves and all accessories , with initial charge of filter media including anthracite, painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testing and commissioning complete including CC foundation of suitable size. Dual Media Filter For Domestic Water Supply Capacity- 8.5 LPS Filter dia approx. - 1800 MM Working pressure: 5.0 Kg/sq cm.
Test pressure : 7.0 Kg/sq cm
Activated Carbon Filter For Domestic Water Supply Capacity- 8.5 LPS Filter dia approx. - 1800 MM Working pressure: 5.0 Kg/sq cm.
Test pressure : 7.0 Kg/sq cm
Supply Installation,Testing & Commissioning of Water Softener fabricated from MS plate as per IS: 2825 (minimum thickness of shall 6 mm and dished end 8 mm) complete with initial charge of resins , GI class 'C' face piping, CI butterfly valves, pressure gauge, hydraulic brine injector, accessories, painting inside with epoxy paint, including 500 liters capacity PVC / HDPE brine tank suitable for 2 regeneration capacity, testing and commissioning complete with resins of approved quality and make complete in all respects including CC foundation of suitable size. For Domestic Tower Water Supply in Water Supply Pump Room Hardness- Inlet- 500-600 PPM Outlet- Less than 50 PPM Capacity- 8.5 LPS Regeneration period 12 hrs. Working pressure: 5.0 Kg/sq cm.
Test pressure : 7.0 Kg/sq cm
Supply Installation,Testing & Commissioning of metering pump type chemical doser with 200 lits. HDPE chemical grade solution tank,injection fitting assembly,suction and delivery hose upto the point of injection, capacity 0-12 lph, complete in all respects.
Chlorination of Domestic Water
Design, manufacture, supplying, fixing in position, testing and commissioning of the following front operated cubicle type, front access 2mm thick mild steel sheet, free standing, dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors complete with interconnections, tinned copper crimping lugs, bonding to earth and painting, suitable for use at 415 volts, 3 phase 4 wire 50 Hz system and suitable for a fault level of 25 MVA symmetrical at 415 volts. All switchboards shall have provision for entry of cables from the top or bottom as required. All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders doors and switch handles shall be lockable in OFF position. Electric Panel For Water Supply Pumps at Water Supply Pump Room INCOMING 1 No. 200 amps TP + NL MCCB with the following accessories: 1 No. square flush mounting 0-500 volts scaled voltmeter with three way and OFF switch. Three phase indicating lights. Electrolytic high conductivity three phase and neutral tinned alluminium bus bar rated at 300 amps having a current density of 1 amp per Sqmm suitable to with stand symmetrical fault level of 25 MVA at 415 volts. The neutral bus bar is to be of 100% capacity.
The motor control panel shall be prewired with colour coded wires with identification labels complete in all respects as required.
Supplying, installing, testing and commissioning controllers with low voltage relays, stainless steel probes and PVC shroud wiring from tank top to probes. Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
50 mm dia
65 mm dia
80 mm dia
100 mm dia
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
50 mm dia
65 mm dia
80 mm dia
100 mm dia
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
50 mm dia
65 mm dia
80 mm dia
100 mm dia
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 6 sq. mm
3 x 4 sq. mm
3 x 4 sq. mm
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.
80 mm dia.
100 mm dia.
Description of Work / Item(s)
Amount
INTERNAL ELECTRICAL WORKS I : CIRCUIT CUM POINT WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit with modular switch modular plate suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc.as required.
Group C
Same as item above but Secondary point. i.e. Points to be looped with Primary point and Point wiring.
Wiring for the following light point with 2.5 sq.mm PVC insulated copper conductor 1100 volts grade stranded flexible FRLS wires of approved make in concealed or surface mounted 25mm dia 16 gauge MS conduit including provinding and controlled by SPMCB provided in the DB. (Cost of MCB not to be including here ) complete in all respect and as per direction of Engineer in charge.
Primary point controlled by one MCB.
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required.
Wiring for power plug points with 2 x 4 sq.mm. FRLS PVC insulated, Cu. Conductor, single core cable in surface/ recessed steel conduit along with 1 No. 4 sq.mm. FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for light plug points / power plug points with 4 x 4 sq.mm. FRLS PVC insulated, Cu. Conductor, single core cable in surface/ recessed steel conduit along with 2 Nos. 4 sq.mm. FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for the following light point with 2.5 sq.mm PVC insulated copper conductor 1100 volts grade stranded flexible FRLS wires of approved make in concealed or surface mounted 25mm dia 16 gauge MS conduit including provinding and controlled by SPMCB provided in the DB. (Cost of MCB not to be including here ) complete in all respect and as per direction of Engineer in charge.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
4x 10 sqmm+ 2x 6 sqmm earth wire
4x 16 sqmm+ 2x 6 sqmm earth wire
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required
Supply & fixing of following sizes of medium class PVC conduit along with accessories in surface / recessed including cutting the wall & making good the same in case of recessed conduit as required.
32 mm dia.
Supplying and fixing of Stepped type 2 module electronic fan regulator on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 Amp modular socket outlet and 5/6 A modular switch, connection etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 6 pin 5/6 & 15/16 Amp modular socket outlet and 15/16 A modular switch, connection etc. as required.
Supplying & fixing of 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
Supplying and fixing brass batten/angle holder including connection etc. as required.
Supplying and fixing extra conduit down rod of 20 cm lengthG.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
Upto 450 mm sweep
Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing
II : DISTRIBUTION BOARD
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
100 Amp, 30 KA,FP MCCB
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
12 way, Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator).
8 way (4 + 24), Double door
12 way (4 + 36), Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
12 way (4 + 36), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, double pole, 240 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A, 415 V “C” curve TP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A, “C” curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
III: LIGHTING FIXTURE & FAN
Installation, testing and commissioning of wall bracket / ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting complete with all accessories including connections etc. as required
Supply of Light fixture as given below
Supply of 36 W recess mounted LED back-lit 2’x2’ with high efficient LED’s, CCT 5700 - 6500 K,CRI≥80, System lumen 100lm/W, Lumens ≥ 3600, white powder coated CRCA with PMMA opal diffuser for glare free & uniform lighting, minimum burning hour life >50000 hours. Driver shall be of constant current type, operating temperature from -10 to +45 degree celcius, power factor>0.95, rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt 2.5KV. Complete in all respect with the entire satisfaction of Engineer-in-Charge.
Supply of 36 W recess mounted Clean room LED back-lit 2’x2’ (IP-65) with high efficient LED’s, CCT 5700 - 6500 K,CRI≥80, System lumen 100lm/W, Lumens ≥ 3600, white powder coated CRCA with PMMA opal diffuser for glare free & uniform lighting, minimum burning hour life >50000 hours. Driver shall be of constant current type, operating temperature from -10 to +45 degree celcius, power factor>0.95, rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt 2.5KV. Complete in all respect with the entire satisfaction of Engineer-in-Charge.
Supply of recess mounting 18 W LED down light with 50000 burning hours. high efficient LED’s, CCT-5700k -500 K,CRI >80, Lumens ≥ 1800, single piece pressure die cast powder coated housing with opal diffuser for glare free & uniform lighting, Driver shall be of constant current type, operating temperature from -10 to +45degree celcius, power factor>0.90, rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt 2.5KV. Complete in all respect with the entire satisfaction of Engineer-in-Charge.
Supply of surface mounting 15 W LED down light with 50000 burning hours. high efficient LED’s, CCT-5700k -500 K,CRI >80, Lumens ≥ 1500, single piece pressure die cast powder coated housing with opal diffuser for glare free & uniform lighting, Driver shall be of constant current type, operating temperature from -10 to +45degree celcius, power factor>0.90, rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt 2.5KV. Complete in all respect with the entire satisfaction of Engineer-in-Charge.
Supply of recess mounting 12 W LED down light with 50000 burning hours high efficient LED’s, CCT-5700-6500 K,CRI >80, Lumens ≥ 100lumen/watt, with aluminium die cast housing with opal diffuser for glare free & uniform lighting, Driver shall be of constant current type, operating temperature from -10 to +45degree celcius, power factor>0.90, rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt 2.5KV. Complete in all respect with the entire satisfaction of Engineer-in-Charge.
Supply & erection of 20 watt LED Betten Tube Light, 4' long suitable with 40000 burning hours for rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply with aluminium alloy base,, frosted polycarbonate diffusers with power factor >0.90, Total Harmonic Distortion (THD) < 20%, system current - 0.085A, system efficiency > 85% , with operating temp. -10° C to 45° C, Lumen output for LED tube should be > 2000 lumen and overall lumen/watt of luminaire should be greater than 80%, C.R.I. of LED>80% with correlated colour temperature (CCT) of 6500K , minimum burning hour life >40000 hours,LED viewing angle 120 Degree complete in all respect with the entire satisfaction of the Engineer-in-incharge. Supply of Industrial General Purpose 4' long tube fitting suitable to house 1x20w LED tube rod 4' long, Polycarbonate housing , rated voltage 240 V and Ingress protection IP-20 complete in all respect with the entire satisfaction of the Engineer-in-incharge.
Supply of LED Bulkhead with a nominal system lumen output of 700 lumens and a minimum system efficacy of 105 lm/W. The luminaire shall have a rated system lifetime of 25,000 burning hours at L70. The luminaire should have a color temperature of 5700K and CRI > 80. The luminaire shall meet IP65 rating and IK 08 rating with THD < 20% and PF > 0.9. The luminaire housing should made of pressure die cast Aluminium with polycarbonate front diffuser. The total power consumption should not exceed 6.5W (including driver).
Supply of 11 W mirror light with high efficient LED’s, CCT-6500 K,CRI >70, Lumens ≥900, with Ingress protection IP-20, with 50000 burning hours Driver shall be of constant current type, operating temperature from -10 to +45 degree celcius, power factor>0.90, rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt 2.5KV. Complete in all respect with the entire satisfaction of Engineer-in-Charge.
Supply of LED exit signage of Box size in mm 325x425x365
Supply of LED aviation light luminaire
Supplying of Plastic Body Ornamental Exhaust Fan heavy duty 230V A.C 50 cycles, 300 mm sweep, 1300 rpm, energy efficient, complete erected in position with all accessories.
Supplying of wall bracket fan 230V A.C 50 cycles, 400 mm sweep, energy efficient, complete erected in position with all accessories.
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Supplying,Installation,Testing and Commissioning of Passive Infrared(PIR) technology based occupancy sensor having high preformance, non regulating programmable type, suitable for connected load upto 10 Amp, for mounting height up to 2.8 meter and for 5 meter diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required.
IV : UPS WORK
Supply, installation, testing & commissioning of Set of 2 Nos. 120 KVA/108 KW UPS. Each UPS of 120KVA should have following specifications in addition to tender requirements : True online double conversions, IGBT Rectifier & inverter based UPS. Three phases Input/ three phase output with SMF batteries complete with MS Fabricated battery rack to accommodate the all battery system, Suitable for 30 Min backup on Full load at 0.8 Load P.f., with 72 nos. 120AH Battery with Each UPS, Input voltage operations on mains without switch over to battery : 340-478V at 100% load, 220-478 V @ 50% load. Input power factor 0.99 @ 100% linear load, input THDi less than 5% @ 100% linear load. Output THD is less than 3% for full linear load & Less than 5 % for nonlinear load. Crest factor 3:1, over load 125% for 10 min, 150% for 1 min, UPS should be able to operate continuously at 115% load on bypass mode. Battery Flexible design shall be available from 36 to 40 or better. Battery type should be Valve regulated lead-acid (VRLA). Inbuilt Delta - Star Input Isolation Transformer with each UPS Shall be provided, parallel communication port, RS232, USB, EPO and SNMP interface, BMS interface, Dust Filter at Air Inlet point are required.
LCD Display indicating all important parameters. To improve the UPS Security over LAN/WAN the SNMP card provided with UPS shall be having Cybersecurity enhancements for IEC / UL 2900-2-2 certification, including stronger encryption, configurable password policy. The card shall work on GIGABIT Speed and should support all major protocols. UPS shall be provided with Temperature Humidity Sensors to monitor Temperature and Humidity over LAN through SNMP card Software. Battery open rack with top cover, battery interlinks, battery breaker(MCCB), Battery breaker enclosure, battery to UPS cable as required should be provided with UPS systems. UPS system shall be parallelable upto 4 units in case required in future. Each UPS shall be compatible for working in parallel redundant mode with other and should be able to be used with Lithium Ion Batteries if required in future. Offered UPS Model shall be type tested in line with IEC 62040-3 standard from third party NABL Approved lab.
V: LAN NETWORKING
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
TV antenna socket outlet
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc.as required.
1 or 2 Module (75mmX75mm)
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
1 run of cable
Supplying & Fixing of Non- PCB based Information Outlet (I/O) RJ45, Tolless Termination TIA-568C Category-6, Termination of Catergory-6 UTP Cable, UL listed ,Shall conform to Category-6 as per the EIA/TIA-568C.2,Shall support network line speeds up to 1 Gbps, Shall have RJ-45 type connector with bend limiting and strain relief boot for securing IDC contacts from external forces and for maintaining the bend radius of the cable, Shall have minimum duraility of 950 or Above mating cycles and 200 termination cycles. Certified by independent labs like ETL/GHMT/3P for compliance to EIA/TIA-568C.2 complete in all respect.
Supplying & Fixing of UTP Jack Panel, loaded with 24 nos UTP ports for Non-PCB based IO Jacks (RJ45, TIA-568C Category-6, Shall have integrated bonding bar or other mechanism for grounding, Shall be loaded with individually replaceable 24 nos. Category-6 certification by Jacks complying with TIA-568.C.2 , Shall be having a 6 port module construction for better cable dressing at the rear, the jacks shall have RJ-45 type connector with bend limiting and strain relief boot for securing IDC contacts from external forces and for maintaining the bend radius of the cable complete in all respect.
Supplying & Fixing of Category 6, UTP patch cords shall be constructed of 24-27 AWG unshielded twisted pair stranded copper cable with an enhanced performance modular plug at each end. Patch cord cable shall be offered in multiple colored UTP cable for design flexibility with a clear strain relief boot on each modular plug. All patch cords shall be compatible with both T568A and T568B wiring schemes. UTP Cable will be 1.0 mtr. complete in all respect. Jacket - LSZH.
Supplying & Fixing of Category 6 UTP patch cords shall be constructed of 24-27 AWG unshielded twisted pair stranded copper cable with an enhanced performance modular plug at each end. Patch cord cable shall be offered in multiple colored UTP cable for design flexibility with a clear strain relief boot on each modular plug. All patch cords shall be compatible with both T568A and T568B wiring schemes. Blue UTP Cable, 2 Meter complete in all respect. Jacket -LSZH.
Supplying & Fixing of Fiber Optic LC style fully loaded Patch Panel (FOPP), 19" Rack Mount ,Shall have all accessories including coupler plates pre loaded with 24 Nos of LC couplers (OM3) with all accessories complete in all respect. Pigtails Should Complie to ITU-G657.B-Bend insestive fiber.
Supplying & Fixing of Fiber Optic Patch Cable (LC-LC), 3 Mtrs. Long, ISO/IEC-11801-OM3 50μ Duplex, LSZH,All patch cords shall conform to EIA/TIA-568C.3 and ISO/IEC-11801,Shall be Duplex Multi Mode Fiber Optic Patch Cords OM3 50μ,Shall support network line speeds up to 10 Gbps.Shall have LC-LC Connector connectors at the ends complete in all respect.
Supply & Fixing of OM3 50/125μ Type Pigtails of ISO/IEC-11801-OM3 Pigtails with LC Type Connectors,pigtails for terminating fibers on the FOPP complete in all respect.
Supply, Installation, Testing & Commissioning of Access Switch 24 Port POE+ Access Switches with switching capacity of 128 Gbps, forwarding performance 137 Mpps, having 24 x 10/100/1000BASE-T PoE-plus(RJ45) with minimum PoE budget of 380W and 2 x 1G SFP and 2 1/10 SFP+ uplink ports can be upgraded to 4 X 1/10G SFP+ ports, should have support for 4 switch Stacking with bandwidth of minimum 40 Gbps. Should support min 1GB internal DRAM, 1GB internal Flash memory, 16K MAC address and EAL2/NDcpp certified . Should have static Routing from day 1 with 1 year support. For Data
Supplying Installation testing and Commissioning of 24 port 10/100/1000BASE-X ports and four GbE/10GbE SFP/SFP+ and 4Nos. 1/10/25G uplink ports, layer 3 from day1 having static & RIP ,stackable upto 8 switches , should support SPB or MPLS with EAL2/NDcPP certification , should support external redundant power supply, certified , each switch should be provided with stacking port/cable complete in all respect. For Voice & Wifi
Supplying, Installation, Testing & Commissioning of 50μ, 6-core Multi mode OM3 metallic armored Fiber cable as per ISO/IEC-11801, Shall be able to meet Gigabit & 10 Gigabit Ethernet performance up to 300 meters requirement specified by IEEE 802.3z (1000 Base-X) & IEEE 802.3ae (10G Base-X) Tensile load should be 4000 Newton or higher and crush resistance should be 4000 Newton or higher ,The attenuation @ 850 nm should be ≤ 2.7 (Max) db/Km and @ 1300 nm should be ≤ 0.7 (Max) dB/Km, the fiber construction can be unitube or multitube, but tensile and crush resistance parameters should be matched, the jacket shall be FRLSZH complete in all respect.
Supplying Installation testing and Commissioning of SFP+ 10 Gigabit Ethernet Direct Attach Copper (twinax copper cable) 1m in length complete in all respect.
Supplying Installation testing and Commissioning of Small Form Factor Pluggable 1 Gigabit Ethernet (SFP+) SR Optics.
Supplying & Fixing of Floor Standing Network/Server Rack - 42U / 800w / 800d, with Heavy Duty Extruded Aluminium Frame for rigidity. Top cover with FHU provision. Top & Bottom cover with cable entry gland plates. Two pairs of 19” mounting angles with ‘U’ marking. Depth support channels - 3 pairs. With a Overall Weight Carrying Capicity of 500Kgs. Side Panels - 42U/800d Front MS Door Perforated honeycomb 42U/800w Rear MS Door Split Perforated honeycomb 42U/800wFan 90CFM 230V AC, 4” dia Castors with Brake (set of 4) Vertical Cable manager 80mmW 42U Shelf, Stationery 700mm N/W PDU 12Sockets 5/15Amps with MCB Mounting Hardware (Pkt. Of 20) earthing Kit 150mmH Cable manager 1U MS with Loops complete in all respect.
Supplying & Fixing of Floor Standing Network Rack - 17U / 600w / 800d, with Heavy Duty Extruded Aluminium Frame for rigidity. Top cover with FHU provision. Top & Bottom cover with cable entry gland plates. Two pairs of 19” mounting angles with ‘U’ marking. Depth support channels - 3 pairs. With a Overall Weight Carrying Capicity of 500Kgs. Side Panels - 17U/800d Front MS Door perforated honeycomb 17U/600w Rear MS Door (Fully Perforated - Mesh) 17U/600w Fan 90CFM 230V AC, 4” dia Castors with Brake (set of 4) Cable manager 1U MS with Loops Shelf, Stationery 475mm N/W PDU 7Sockets 5Amps with MCB Mounting Hardware (Pkt. Of 20) Vertical Cable Channel 50mmW 17U complete in all respect.
Supplying & Fixing of Floor Standing Network Rack - 15U / 600w / 800d, with Heavy Duty Extruded Aluminium Frame for rigidity. Top cover with FHU provision. Top & Bottom cover with cable entry gland plates. Two pairs of 19” mounting angles with ‘U’ marking. Depth support channels - 3 pairs. With a Overall Weight Carrying Capicity of 500Kgs. Side Panels - 15U/800d Front MS Door perforated honeycomb 15U/600w Rear MS Door (Fully Perforated - Mesh) 15U/600w Fan 90CFM 230V AC, 4” dia Castors with Brake (set of 4) Cable manager 1U MS with Loops Shelf, Stationery 475mm N/W PDU 7Sockets 5Amps with MCB Mounting Hardware (Pkt. Of 20) Vertical Cable Channel 50mmW 15U complete in all respect.
Supplying & Fixing of Floor Standing Network Rack - 12U / 600w / 800d, with Heavy Duty Extruded Aluminium Frame for rigidity. Top cover with FHU provision. Top & Bottom cover with cable entry gland plates. Two pairs of 19” mounting angles with ‘U’ marking. Depth support channels - 3 pairs. With a Overall Weight Carrying Capicity of 500Kgs. Side Panels - 12U/800d Front MS Door perforated honeycomb 12U/600w Rear MS Door (Fully Perforated - Mesh) 12U/600w Fan 90CFM 230V AC, 4” dia Castors with Brake (set of 4) Cable manager 1U MS with Loops Shelf, Stationery 475mm N/W PDU 7Sockets 5Amps with MCB Mounting Hardware (Pkt. Of 20) Vertical Cable Channel 50mmW 12U complete in all respect.
Supply, installation, testing & commissioning of Central Core Server Operation & Management Application at DC: Management server should be an enterprise-class server in a 1RU form factor, Should have Intel Xeon processor (Preferably E5-2600 family) with atleast 2.3GHz speed & with 6-core CPU, Should support atleast 4 Number of Hot-swappable SAS drive and Server should be populated with 8*10TB HDD from day 1, Dual Gigabit Ethernet Port, 2 ports (USB 3.0), 1 VGA video port, Should have RAID controller card, Dual-redundant fans and hot-swappable, redundant power supplies, Should have atleast 16GB DDR4 RAM, Server should be supplied with VSM licenses for Management & Operation license including one workstation with 21" TFT i7 processor, 8GB RAM and graphic card etc as complete as required.
Supply, installation, testing & commissioning of Router,Two GE ports RJ-45 connectors GE 0/1,USB ports—two USB 2.0 Type-A ports USB 0=Bottom,RJ-45 serial console port,HWIC slot 0 (EHWIC, HWIC, WIC, or VWIC11—single wide1,USB serial port—USB 5-pin mini USB Type-B,Auxiliary One auxiliary port RJ-45 connectors,complet in all respect.
Supply, Installation, Testing and comissioning of Firewall. The UTM solution should be Hardware based, Reliable, purpose-built security appliance with hardened operating system that eliminates the security risks associated with general-purpose operating systems. It Should have minimum 2 x 10G supporting SFP+ interfaces & 2 x 100/1000/10 BaseT RJ45 ports to cater to connectivity from multiple service providers and load balance them. The Firewall should have ultra-low latency (~ < 5 micro seconds). The Firewall should support IPSEC & SSL VPN, inbound and outbound both. The IPSEC VPN should deliver at least 20 Gbps throughput to ensure connectivity with Multiple colleges / University catering to Data / Voice traffic over IPSEC tunnel. The Firewall should be able to handle very high concurrent sessions like 20 Million or above and at least 400,000 of new sessions per second. The solution should support Virtualization with 10 Virtual contexts scalable to 250 to help University use the logical Firewalls for internal / student projects run isolated with each other. The proposed solution should have integrated IPS module with at least 10Gbps of throughput for deep pack inspection of traffic and also should be able to inspect encrypted SSL traffic. The solution should have at least 5 Gbps of Threat Protection throughput and the so that the entire traffic is scanned before reaching the end user. The antivirus engine should be able to inspect the encrypted traffic like HTTPS, SMTPS, POP3s , IMAPs, FTPs etc. The proposed system should have integrated Web Content Filtering solution which can be used to block any unwanted sites / category of sites to adhere to University IT guidelines. The Firewall & IPSEC VPN module shall belong to product family which minimally attain Internet Computer Security Association (ICSA) Certification or equivalent. The proposed system should have modules/Licenses for integrated Web Content Filtering along with IPS, Application Control, Antivirus / Malware Protection & Anti spam. Proposed solution should be an Appliance/Virtual Machine based solution. In case of Virtual Machine based, required server must be quoted by bidder. It Should have direct OEM TAC support.
Supply, Installation, Testing & Commissioning of Distribution Switch should support Supplying Installation testing and Commissioning of 24 port 10/100/1000BASE-X ports and four GbE/10GbE SFP/SFP+ and 4Nos. 1/10/25G uplink ports, layer 3 from day1 with switching capacity of 720 Gbps and throghput of 500 Mbps having static & RIP ,stackable upto 8 switches , should support SPB or MPLS with EAL2/NDcPP certification , should support external redundant power supply, certified , each switch should be provided with stacking port/cable complete in all respect. For Voice & Wifi.
Supply, Installation, Testing & Commissioning of Core Switch with 10Gigabit/100Gigabit Ethernet L3 fixed configuration chassis in a 1RU form factor with 40 1/10G SFP+ ports, 8 10/25G SFP28 ports and 4 40/100G QSFP28 ports. QSFP28 ports operate as single 40/100GE port or Quad- 10/25GE. Provides MACsec on all ports. Back-to?front cooling. The chassis includes two 650W AC power supplies. with switching capacity of 2 Tbps, forwarding performance of 1480Mpps dual hot swappable internal power supply. Should support advance layer 3 (RIPng, OSPF, BGP and SPB/MPLS) with 1 year support.
Supplying, installation, testing and commissioning of Wireless Indoor AP should be Dual band 802.11ac wave2 supporting the legacy 802.11b/g/n standards also in the 2.4 and in the 802.11a/n in 5 GHz with Dual bands concurrent operations, should support 4x4 MU-MIMO in 5Ghz to communicate 4 devices simultaneously.should support minimum 02nos of Gigabit ethernet port (10/100/1000Mbps) and one USB port for IOT,Location services , Should support More than 500 concurrent users , Should support Hotspot2.0 (Passpoint ) compliant , Support aggregate data rate more than 2.1 Gbps , Support Mac Authentication for upto 1000 Mac per SSID , including Poe Injector.
Supplying, installation, testing and commissioning of WLC should support 50 access points from Day 1 and scalable for upto 4000 AP's without Software/hardware change. Proposed WLC should be On-Prem/cloud based, and should be hosted in India.Controller shall support minimum 20000 concurrent sessions from a single account.WLC should provide Guest management system with Voucher based authentication, local SMS server integration for OTP, Google and Facebook authentication. Should support major SMS gateway provider. Same controller should manage & configure Wireless AP & Network Switch through single dashboard.
Supply, Installation, Testing and Comissioning of IP Based Central IPABX as per technical specifications to be supplied. It should be of initially capacity of 500 Telephones with 28 party conference, 2 PRI, & expandable up to 5000 telephones. EPABX should be supported with CPU/Server connected in active/standby mode with with All the Telephone in the Complex will be IP Based and will use the existing LAN Network for the communication within the complex as well as for outside the complex. All Rack Panels of Individual buildings shall be connected to Central EPABX system through Optical Fiber Cable and complience.
Supply, Installation, Testing and Comissioning of Type 4 IP Phone . Should be an integrated system with at least 7 inch 1280X720 LCD/TFT screen, 720P resolution (16:9), HD camera and with speakers for wide band audio output. The Codec should be a part of the unit. No separate Codec's are preferred. The LCD/TFT screen should be a touch screen to provide a touch interface to the user as per detail tender specification.
Supply, Installation, Testing and Comissioning of Type 3 IP Phone . The phone should support 2.8 inch screen Power over Ethernet IEEE 802.3af class 1/2/3 and should also have AC power adapter option The phone should have 2 x 1GE ports, one for the LAN connection, temperature range from -5 to 45 C and the other for connecting to PC/laptop as per detail tender specification.
Supply, Installation, Testing and Comissioning of Type 3 IP Phone . The phone should support 2.3 inch screen with Power over Ethernet IEEE 802.3af class 1/2/3 and should also have AC power adapter option with temperature range from -5 to 45 C. The phone should have, one for the LAN connection and the other for connecting to PC/laptop as per detail tender specification.
VI: CCTV
Supply, Installation, Testing & Commissioning of 4MP Indoor IP Dome camera with 1/3-inch CMOS, Sensor pixels supports 2592×1520, with built in IR upto 30m effective distance, with Sensitivity-0.01 lx (color) , Dynamic range > 120dB, day/night, Automatic Electronic Shutter, Video compression H.265; M-JPEG, White balance, BLC, H.265 dual-streaming, Motion/tamper/audio detection, Auto zoom Varifocal Lens 3 to 12 mm motorized lens, Built-in audio in/out capability, Two-way, full duplex Audio support, Audio compression G.711U, Memory card slot (support minimum 128GB), 3-axis adjustment (pan/tilt/ rotation), IP 66,IK 10, ONVIF Profile S & G/ CE/ UL/ FCC Certified.
Supply, Installation, Testing & Commissioning of 4MP Outdoor IP Bullet camera with 1/3-inch CMOS, Sensor pixels supports 2592×1520, with built in IR upto 50m effective distance, with Sensitivity-0.01 lx (color) , Dynamic range > 120dB, day/night, Automatic Electronic Shutter, Video compression H.265; M-JPEG, White balance, BLC, H.265 dual-streaming, Motion/tamper/audio detection, Auto zoom Varifocal Lens 3 to 12 mm motorized lens, Built-in audio in/out capability, Two-way, full duplex Audio support, Audio compression G.711U, Memory card slot (support minimum 128GB), IP 67,IK 10, ONVIF Profile S & G/ CE/ UL/ FCC Certified.
Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light PTZ Camera with auto tracking, 1/2.8" CMOS, 2 MP @ 25fps, triple stream, Min. Illumination required 0.001 lux @ F1.6 (color) & 0.0001 lux @ F 1.6(B/W) or better, 120dB True WDR or better, Min. Pixels 1920 × 1080, triple stream, 5mm –120 mm, 25x motorized focus & zoom lens, BLC, HLC, 3DNR, Defog, Electronic Image Stabilization, Privacy Mask, Internal / External Illumination range with upto 100m IR distance, 64GB SD card, Alarm: 2 In/ 1 out, PoE, H.264 High Profile and MJPEG, PoE Class 5 and 12V DC/24VAC, IP 66, Having Operating temp range : –10°C to 65° C. Certifications: ONVIF Profile S compliant, UL/CSA 60950-22/CE (EN 50130-4 & EN 55022) / FCC Part 15 & RoHS compliant.
Supply, Installation, Testing & Commissioning of 64 ch. Standalone NVR , Embedded Linux System, H.265 compression, 64 channel support , support 4K,6MP,5MP ,4MP,2MP Cameras , upto 400Mbps bandwidth support, 64 channel composite audio input, 4K recording support, 4 channel synchronous 1080p playback, dual HDMI with 4K supporton atleast one port, Split preview upto 32 channel, scalability models option to be made available with 8 port and 16 port HDD bays, RAID 5 support, each slot to support upto minimum 14TB HDD, Dual RJ45, Dual USB, 8 channel Alarm input and 4 channel alarm output as minimum, CE/FCC/UL Certified.
Supply, Installation ,Testing and Commissioning of Workstation CMS of same make as NVR with 22" LED colour Full HD TV monitor for Live View and Replay of Recorded View as per tender specs or as per NVR OEM requitmentation as per CMS software required
Supply, Installation ,Testing and Commissioning of 43 inch 4K industrial/commercial type display. Resolution 4K ,brightness minimum 570 nit, viewing angle 178:178, display colors 1 billion, built-in speakers (10W + 10W) ,embedded media player, video (HDMI1, HDMI2 except KR, NA; component CVBS common), audio (stereo mini jack), USB 2.0 x 4 as per tender specs.
Supplying Installation testing and Commissioning of 24 port 10/100/1000BASE-X ports and four GbE/10GbE SFP/SFP+ and 4Nos. 1/10/25G uplink ports, layer 3 from day1 having static & RIP ,stackable upto 8 switches , should support SPB or MPLS with EAL2/NDcPP certification , should support external redundant power supply, certified , each switch should be provided with stacking port/cable complete in all respect.
Supply, Installation, Testing & Commissioning of Access Switch 24 Port POE+ Access Switches with switching capacity of 128 Gbps, forwarding performance 137 Mpps, having 24 x 10/100/1000BASE-T PoE-plus(RJ45) with minimum PoE budget of 380W and 2 x 1G SFP and 2 1/10 SFP+ uplink ports can be upgraded to 4 X 1/10G SFP+ ports, should have support for 4 switch Stacking with bandwidth of minimum 40 Gbps. Should support min 1GB internal DRAM, 1GB internal Flash memory, 16K MAC address and EAL2/NDcpp certified . Should have static Routing from day 1 with 1 year support.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
1 run of cable
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
2 x 1.5 sq. mm
Supply & fixing of following sizes of medium class PVC conduit along with accessories in surface / recessed including cutting the wall & making good the same in case of recessed conduit as required.
25 mm dia.
Supply, installation, testing & commissioning of 12U Wall mount rack of Width (mm)-600, Depth (mm) - 500, Approx.Net Wt (kg) - 20, CRCA 'D' Grade thickness (mm) - 1.2, Powder Colour for Cabinet - RAL9002, Glass - 4mm Toughened Tinted Glass Door, Accessories:, Fan & with all required acessories as per tender specs
Supply, installation, testing and Comissioning of 3x3 Juncation box with face place complete for Camera including all accessoires & connection.
VII: FIRE ALARM & DETECTION SYSTEM & PA SYSTEM
Eight Loop Panel
Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required.
Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required.
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.
Supplying, installation, testing & commissioning of addressable fire control module complete as required.
Supplying, installation, testing & commissioning of addressable phone control module complete as required.
Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required.
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.
Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.
PUBLIC ADDRESS SYSTEM
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required.
Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.
Supply installation, Testing & Commissioning of RMS 480w Power amplifier, battery voltage 24Vdc (max. 10% deviation) Frequency response 60Hz to 15kHz (+1/-3dB) Inputs XLR & Phone Jack, SIN >85dB, as per detailed technical specification etc as required.
Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.
speaker cable Single pair, 2-core, 1.5 sqmm
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
SUB HEAD - VIII: ACCESS CONTROL SYSTEM Supply, Installation, testing and commissioning of Surface mounted Networkable multiprocessor controlled 4Door/4 reader controller capable of controlling multiple readers (IN/OUT) alongwith TCP/IP connectivity complete as per specifications. Control panel housed in MS Powder Coated Cabinet with Tamper Switch, Complete with power supply unit for Controllers & Magnetic Locks as per specification.
Supply, installation, testing and commissioning of Access Control Application Software for 128 Reader Capacity, and 4000 Card Holder Capacity, Basic GUI , TA Module with Alarm Module, T+ Module, 2-Nos Client Work Stations,Module for using SQL DB , -MULTI Site Module.
Supply , installation, testing & commissioning of smart card I class readers as per specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories.
Supply, testing and commissioning of Exit Push Button
Supply, testing and commissioning of iClass Smart card .
Supply, installation, testing and commissioning of Single Leaf Electro Magnetic Lock of Suitable Capacity(Min 600 lbs).
Supply, installation, testing and commissioning of Double Leaf Electro Magnetic Lock of Suitable Capacity(Min 1200 lbs).
Supply and Fixing of ''U'' Bracket with Accessories.
Supply, fixing & testing of Biomatric Reader along with communication and USB port suitable for external / Internal environment with Mounting complete as required.
Supply, Fixing and Laying of 8 Core multi strand, copper, unarmoured Cable (between the every readers & the access controllers).
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
2 x 1.5 sq. mm (between the controller and EM Lock/Request to exit button).
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
"SUB HEAD - IX: LIFT WORK Supply, errection, testing & commissioning of 26 passanger with machine Electric Traction Elevator, to be errected in accordance with followingTechnical Specification & as per latest IS Specifications. " Nos. of Lifts 1 Nos. Type & Capacity:Passanger Elevator App. 1768 kg. 26 person. Speed mps : 1.5 mtr per second Travelling (max.) in mtrs : Approx. 30.0 mtrs Serving : 8 stops, 8 opening (All opening on the same side). Power Supply : 415V, 3 phase, 50 HZ AC supply. Control : Simplex full collectivecontrol with or without attendant. Operation : Automatic Motor : A Synchronous motor Car Size : as per manufacturer design. Door Frame : Full Glass Door. Well Size- 3.0 M deep x 2.4 M wide Other Features : Battery operated emergency alarm and emergency light with rechargeable battery. Adjustable guide shoes. Combine Luminous hall buton and digital hall indicator/touch screen. Integral full height car opening panel with luminouscombined with direction arrows, overload warning indicacator & service cabinet.
Hand free press & speak intercom with EPABX for three way communication. Automatic rescue device to automatic bring the elevator to a landing in case of power / phase failure/ low voltage. Full height Infrared safety curtain & automatic floor announcer. Diffused Lighting in car. Blower (noiseless) Looking mirror in front side of lift car. Face Plate finish : Stainless stell in hairline. Face Plate : Rectangular. The Three feet high railing shall be provided on car top. The motor shall be high starting torque and low starting current and shall be arranged for self lubrication. Proper weight screen shall be provided at the hoist way. Fire retardant compound coated traveling cable shall be used. 2Phase Device Fire Man Drive & Fireman switch at ground floor. Load Weight device with overload bypass feature. Steel itels such as Door Frames Sill angles, Fascia Plates, Spring Buffers. Bralite Features, Lift announcement system, Pit ladder, Hand Rail & Additional Car Gate Lock. Three side Hand Rail in Stainless Steel Finish. System Capable of withstanding +10% to -10% Variation in Supply Voltage Fluctuations. Car Plateform constructed out of Cold Rolled Grain Oriented Formed Sheets of Steel. Fire Rated landing Doors for a period of two hours only. The whole machinery shall be mounted on appropriate anti vibration supports to minimize voice & vibration.
Supply, errection, testing & commissioning of 13 passanger with machine room Electric Traction Elevator, to be errected in accordance with followingTechnical Specification & as per latest IS Specifications. Nos. of Lifts 1 Nos. Type & Capacity:Passanger Elevator App. 884 kg. 13 person. Speed mps : 1.5 mtr per second Travelling (max.) in mtrs : Approx. 30.0 mtrs Serving : 8 stops, 8 opening (All opening on the same side). Power Supply : 415V, 3 phase, 50 HZ AC supply. Control : Simplex full collectivecontrol with or without attendant. Operation : Automatic Motor : A Synchronous motor Car Size : as per manufacturer design. Door Frame : Full Glass Door. Pit Size- 2.4 M deep x 1.75 M wide Other Features : Battery operated emergency alarm and emergency light with rechargeable battery. Adjustable guide shoes. Combine Luminous hall buton and digital hall indicator/touch screen. Integral full height car opening panel with luminouscombined with direction arrows, overload warning indicacator & service cabinet.
Hand free press & speak intercom with EPABX for three way communication. Automatic rescue device to automatic bring the elevator to a landing in case of power / phase failure/ low voltage. Full height Infrared safety curtain & automatic floor announcer. Diffused Lighting in car. Blower (noiseless) Looking mirror in front side of lift car. Face Plate finish : Stainless stell in hairline. Face Plate : Rectangular. The Three feet high railing shall be provided on car top. The motor shall be high starting torque and low starting current and shall be arranged for self lubrication. Proper weight screen shall be provided at the hoist way. Fire retardant compound coated traveling cable shall be used. 2Phase Device Fire Man Drive & Fireman switch at ground floor. Load Weight device with overload bypass feature. Steel itels such as Door Frames Sill angles, Fascia Plates, Spring Buffers. Bralite Features, Lift announcement system, Pit ladder, Hand Rail & Additional Car Gate Lock. Three side Hand Rail in Stainless Steel Finish. System Capable of withstanding +10% to -10% Variation in Supply Voltage Fluctuations. Car Plateform constructed out of Cold Rolled Grain Oriented Formed Sheets of Steel. Fire Rated landing Doors for a period of two hours only. The whole machinery shall be mounted on appropriate anti vibration supports to minimize voice & vibration.
Supply, errection, testing & commissioning of 1500 kg fraight lift with machine room, to be errected in accordance with followingTechnical Specification & as per latest IS Specifications. Nos. of Lifts 1 Nos. Type & Capacity:Passanger Elevator App. 1500 kg. Speed mps : 0.5 mtr per second Travelling (max.) in mtrs : Approx. 34.0 mtrs Serving : 9 stops, 9 opening (All opening on the same side). Power Supply : 415V, 3 phase, 50 HZ AC supply. Control : Simplex full collectivecontrol with or without attendant. Operation : Automatic Motor : A Synchronous motor Car Size : as per manufacturer design. Door Frame : Full Glass Door. Pit Size- 23.0 M deep x 2.45 M wide Other Features : Battery operated emergency alarm and emergency light with rechargeable battery. Adjustable guide shoes. Combine Luminous hall buton and digital hall indicator/touch screen. Integral full height car opening panel with luminouscombined with direction arrows, overload warning indicacator & service cabinet.
Hand free press & speak intercom with EPABX for three way communication. Automatic rescue device to automatic bring the elevator to a landing in case of power / phase failure/ low voltage. Full height Infrared safety curtain & automatic floor announcer. Diffused Lighting in car. Blower (noiseless) Face Plate finish : Stainless stell in hairline. Face Plate : Rectangular. The motor shall be high starting torque and low starting current and shall be arranged for self lubrication. Proper weight screen shall be provided at the hoist way. Fire retardant compound coated traveling cable shall be used. 2Phase Device Fire Man Drive & Fireman switch at ground floor. Load Weight device with overload bypass feature. Steel itels such as Door Frames Sill angles, Fascia Plates, Spring Buffers. Bralite Features, Lift announcement system, Pit ladder, Hand Rail & Additional Car Gate Lock. Three side Hand Rail in Stainless Steel Finish. System Capable of withstanding +10% to -10% Variation in Supply Voltage Fluctuations. Car Plateform constructed out of Cold Rolled Grain Oriented Formed Sheets of Steel. Fire Rated landing Doors for a period of two hours only. The whole machinery shall be mounted on appropriate anti vibration supports to minimize voice & vibration.
LIGHTNING PROTECTION SYSTEM Supply of Earthing termination made of copper-bonded rod of 10 feet length,14 mm dia. (Minimum copper bonding shall be 0.25mm) along with Rod-to-Conductor connectors, Earth enhancement material (25 KG resistivity each less than 0.12 ohm meter), Pit Cover and other accessories as required and as per r and other applicable codes.
Providing and fixing of lightning conductor finial, made of 25 mm dia 1200 mm long, copper tube, having single prong at top , with 85 mm dia 3 mm thick copper base plate including holes with insulation etc. complete as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run).
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
RACEWAY & CABLE TRAY Supports, bends, access boxes, tap off boxes and cross over as per site requirement. (overhead / wall mounted recovery & junction boxes shall be 2.0 mm thick). The pregalvenised sheet shall be as per IS 277 or BS 2989 having tensile strength of minimum 500 N/sq.m. and minimum zinc coating of 275 GSM. Supplying, installation, testing & commissioning of Race way made from minimum 2.0 mm thick GI raceway, factory fabricated, with internal partition of the following sizes including providing removable double folded cover of 2.0 mm thick , knock out holes and fixing accessories & coupling, earthing stud for terminating 8 SWG copper earth wire complete as required
100 mm wide x38 mm deep in ceiling/floor
150 mm wide x38 mm deep in ceiling/floor
225 mm wide x38 mm deep in ceiling/floor
300 mm wide x38 mm deep in ceiling/floor
JUNCTION BOX Supplying, installation, testing & commissioning of floor/ceiling recessed 2 mm thick pregavanised sheet outlet junction box including providing cover with provision to adjust overall height, knock outs on four sides to accept raceways of specified sizes and cutouts to fix required outlets for following size of race ways with painted GI plate ( Colour as approved Architect/Consultant).
Supplying and installing following size of perforated Hot DippedGalvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
600 mm width X 50 mm depth X 2 mm thickness
900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “bends” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
600 mm width X 50 mm depth X 2 mm thickness
900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Tee” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Cross member” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
50 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
900 mm width X 62.5 mm depth X 2.0 mm thickness
QUEUE MANAGEMENT SYSTEM Supply, Installation, Testing & Commissioning of Token Printer (Table Top). 3" Thermal paper size, Auto paper Cutter, USB or RS232 and TTL input. Bar code and Logo printing support as complete as required.
Display Supply, Installation, Testing & Commissioning of 14-15" LED Display / Monitor with controller for Token number at each counter as complete as required.
Display for Comun Area Supply, Installation, Testing & Commissioning of 40-42" LED TV with controller for Token number at each counter as complete as required.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
1 run of cable
NURSE CALLING SYSTEM NURSE Calling Station Supply, Installation & commisioning of Nurse Station Terminal : Nurse Station shall comprises of displaying all details , Querying receiver for speaking discretely, Microphone and loudspeaker for hands-free speech (incl. volume control), full duplex speaker phone in brilliant sound quality & inbuilt microphone . The Nurse station shall have access to patient information , in case of emergency shall have facility to jump as many calls to other Nurse station.. All call indications follow the priority and must display the exact location of the calls. The system shall be able to configure with N number of bed for nurse station. In case of limitation for configuration , the system or its combination of system unit shall be able to configure atleast 40bed in any scenerio . The system shall be self sufficient to share data to central Nurse management station.
OUT DOOR LIGHT Supply Installation Testing & Commissioning of LED Indicators Module at Outside of each ward with ecofriendly Leds . It shall warn with three main colour red , green , blue, and combinations of these depending on the call status of the room complete as required.
BED UNIT Bedside Call Cancel Button shall consist of: Supply Installation Testing & Commissioning of Bed side Call & Cancel Push Button , Call Reset, Call Indication in Nurse station for each Bed complete as required.
HAND SET Patient handset without speech shall consist of: Supply Installation Testing & Commissioning of Patient handset without sppech. The patient shall be able to inform to nurse complete along with cord & all accesories as required for installation.
PULL CORD STATIONS Pull cord for WC & Bathroom shall consist of: Supply Installation Testing & Commissioning of Toilet Call Push Button with LED indication and flexiable cord with button , Call Reset, Call Indication, station for each WC unit complete as required.
SERVER The Central Monitoring Unit shall monitored that shall observes all activities such as nurse calls, code blue (and any custom emergency codes), assist calls, and nurse presences throughout the hospital. It shall show picture IDs of personnel that are present in patient rooms. Different parameters (call type, department, and floor info) can be filtered based on needs. In this way, the focus of health personnel can be directed and reaction and intervention times can be minimized
NETWORK CABLE Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
1 run of cable
EXTERNAL ELECTRICAL WORKS SUB HEAD - I : HT EQUIPMENT & TRANSFORMER TWO POLE STRUCTURE (BEFORE METER ROOM) Supply, Installation, testing and commissioning of 11 KV DP structure as per SEB(state Electricity Board) norms & comprising of the following, but not limited to it for completion of works RSJ (Rolled Steel Joist) pole of 9.15 mt length of size 175 x 90 mm complete with suitable M.S. base plate welded at bottom base plate - 2 Nos. MS Channel of size 100 x 50 mm, length 4 mts (approx), 11 KV AB switch - 1 set, 11 KV Horn Gap fuse Unit - 1 set, 11 KV Lightning Arrestor , 11 KV Disc insulator , 11 KV Pin insulator , 6 SWG copper wire for jumpering, Supply and erection of Stay set complete with necessary foundation, excavation and refilling of earth etc. as required. Concrete foundation for RSJ poles burrioed upto a depth of 1830 mm in ground in a pit of size 450X450 mm in CC 1:3:6 along with 200 mm copping above ground inclusive of earth work. Necessary Nut, Bolts, clamps, operating handle for AB switch, clamping welding etc. complete as required. Painting the RSJ poles complete with two coat of Red Oxide and two coats of GI enamel paints complete as required. Transportation of all materials and accessories at site, Complete erection, testing and commissioning.
11 KV HT Metering Panel (SEB's) Supply, Receiving, Unloading, Storing, Shifting, Installation, Testing & Commissioning of indoor type floor mounted, dust, damp and vermin proof, cubicle HT. Metering Panel made out of 14 gauge CRCA sheet steel complete with 5 Amp electronic trivector meter, C.T.'s of 100/50/5 Amp, 0.5 Class, 15 VA Burden, and P.T's of 11 KV / √3, 110V / √3, 100 VA conforming to relevant IS Standards and complete as required. H.T. Metering cubicle along with C.T.'s, P.T.'s and trivector meter shall be got tested and approved from local electricity supply authority. The GA drawing shall be got approved from the local statutory authorities before fabrication. file charges
11 KV HT PANEL : Supplying, installation, testing & commissioning of indoor type floor mounted metal clad, 11KV VCB panel with 3 No. VCBs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50Hz A.C. supply with short circuit fault level of 350 MVa, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 630 Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories i/c connections suitable for 3x240 sq. mm. XLPE 11KV cable (cable entry from *bottom/ top/side) end termination with heat shrinkable jointing material etc. as required. The Panel Shall consisting of following:- a) Each Module shall have Front & Back Door Interlock b) Panel shall be Floor Rolled trolley Design. c) Short Circuit Rating shall be for 3 Seconds. d) Panel shall be Scada Compatible. e) Relays shall be Numeric Type. f) Panel should be Internal Arc Typed Test for 26.3kA for 1 sec. Panels shall be suitable for loss of service continuity LSC 2B. Safety shutters complying with IEC-62271-200.
11/.433 KV Transformer Supply, installation assembling, transporting, Loading, testing and commissioning of Outdoor oil type 630 kVA 11/0.433 KV, 3 Phase, 50Hz, Dyn11 vector group, copper wound, class A insulation level, associated with Oil and winding temperature indicator/ controller actuated by means of resistance temperature detector embedded in LV windings Associated buccholz protection arrangement, Oil conservator as per IS 2026 and losses as per IS 1180 Level-1, Outdoor type transformer with approximately 5% impedance maximum allowable losses as per IS 1180 LEVEL 1, with ON Load tap changer (OLTC) on HV side in steps of -15 to 5 % in steps of 1.25 %.The transformer shall be provided with winding temperature alarm & trip protection, having cable end boxes on HV side suitable for 3C x 240 Sqmm XLPE cable of 11KV grade and arrangement on LV side suitable for 3 nos. of 3.5C X 300 Sqmm XLPE LT cable and including all control wiring as per specification attached complete in all respects as required at site.). The transformer shall be provided with RTCC for automatic sensing of incoming voltage & AVR for automatic tap change.
DG SET INCLUDING ALL ACCESSORIES Supplying, loading, testing of Diesel Generating set having Prime Power Rating of 750 KVA, radiator cooled without cooling tower ,with acoustic enclosure with Hospital Type silencer, 415 volts at 1500 RPM, 0.8 lagging power factor suitable for 50 HZ, 3 phase system and as per Latest CPCB-II. The DG sets shall be suitable for being overloaded upto 10% of the rated capacity for 1 hour in every 12 hours and consisting of the followings: The DG set shall be suitable for above 0.85 loading factor with net output shall be 750 kVA as per site conditions.
A. DIESEL ENGINE: Diesel engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 50 Degree C, 50% RH & at 1000 MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories. Type: Water Cooled Fuel injection :As per manufacturer Engine Starting : Battery starting. Starting position : Universal. Auto/Manual "The Engines shall include: • Flywheel with guard. • Flexible connection. • Bellow / expansion joints • Air cleaner • Blower fan • Electronic governor with electronic fuel injection system • Fuel and lube oil filters and pumps • Day Fuel tank with visual level indicators etc. • Silencer as per latest amendments of MOEF/CPCB • Safety controls • Instrument panel • Exhaust piping to let out the exhaust at mandatory height above the canopy including support arrangement and insulation with cladding inside the canopy etc." B. ALTERNATOR;
B. ALTERNATOR; Synchronous alternator rated at 750 KVA, 415 volts at 1500 RPM, 3 phase 50 HZ, AC supply with 0.8 lagging power factor at 50 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self excited & self-regulated through AVR conforming to IS:4722/BS 2613 suitable for tropical condition and with class-H insulation. Type : Brushless. Actual Power 750 KVA at 40 deg C. Frequency : 50 Cycles/sec. Supply system :3 phases & neutral Connection : Star. Rated rpm. : 1500 rpm. Casing protection : As per IP-23 Insulation : Class `H/F'. Power factor : 0.8. Controller : The DG sets should be suitable for Auto Synchronization & Auto Load Sharing with micro process based Synchronization controllers like Woodward/PCC (Power Command Control) or equivalent including providing of Engine control panel
C. ACCESSORIES: The Diesel Engine shall be equipped with minimum following/ as indicated in the specifications, devices/ accessories built-in type including all standard fittings. Fuel supply pump with manual venting pump. Turbo charger with air filter (dry/oil bath type) and damper. Charge air cooler. Suction fuel filter Lube oil filter. Hour meter and RPM indicator. Battery Starting Mechanism. Instrument/Indication panel complete with the followings; a) Starting Switch with key. b) Lub. Oil Temp. gauge. c) Lub. Oil pressure gauge. d) Water Temp. gauge. Control devices for safety and monitoring along with indicators. Common base/foundation frame. Daily service fuel tank of 990 liters capacity(as per manufacturers) fabricated out of CRCA 2 mm thick MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS Class C pipe of suitable dia. complete with valves, level indication, flow switch & twin fuel filters with fuel injectors and accessories as required as per specifications. Anti vibration pads 24V DC Starting system comprising of starter motors: Voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (-nos. x, --Amp. Hour capacity maintenance free as per manufacturer standards ) for minimum 6 no. consecutive starts as required as per specifications. The cost of initial charge of lubricants, coolant etc. The DG sets shall include the cost of all accessories, fittings, protections, instruments, safety controls, alarms, indications etc. complete as per specifications, as required
Supply, installation, testing & commissioning of the following MS class ‘C’ pipes cut to required lengths and installed with all welded joints. Providing the necessary fittings like elbows, tees and reducers, sockets, hot dip galvanized supports and accessories including ceiling Hanger, Hardware complete as per site requirement.
25 mm dia MS pipes
25 mm dia. ball valves
Supplying & fixing exhaust gas piping of suitable dia. Welded black MS, B class pipe confirming to IS:3589 cut to required lengthsand installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/rockwool, 50mm thick wiremesh & aluminium clading etc, as required as per specification.
200 mm dia
Providing and fixing in position following size of heavy duty stainless steel flanged expansion bellows with G.I. nut bolt washers for DG fume piping complete with GI nut bolt washers etc. complete as required. (for DG Sets)
200 mm dia
Providing & fixing for MS support structure for exhaust fume pipes from DG Sets (Exhaust pipe to be measured and paid for separately) along horizontal and vertical runs upto the height (as per CPCB norms) including cutting, welding etc. and applying two coats of red oxide and two coats of synthetic enamelled paint of colour and shade as directed by engineer-in-charge. The design of the support structure shall be done by the contractor and shall be as per CPCB norms approved , also to get the approval from the client/ consultant before execution etc. as required.
LT PANELS & DISTRIBUTION BOARDS ALL LT PANELS SPECIFIC INCLUSIONS: The outgoing feeders as indicated in SLD shall have suitable range of followings (except capacitor feeders). All ACB's shall be suitable for minimum 50 kA as specified in the items (Icu=Ics=Icw for 1 sec.) All MCCB's shall be suitable for unless otherwise specified in the item (Icu=Ics= 1 sec=100%.) Wiring with space heater, thermostat and control MCB's shall be provided for all vertical sections of main LT panel. All incoming as well as outgoing feeders shall have pad locking facility. Suitable danger board shall be provided. All MCCB’s shall be provided with front rotary handle and operating mechanism for door interlock with Pad locking of MCCB’s handles in “OFF” Position. The Panel fabricator shall provide Al./ Copper Bus-bars link from Breakers wherever more than two nos. of cables are terminated in the breakers. All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation. All distribution sub panels shall be provided with class 1.0 accuracy meters as well as CTs. All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire. Panels shall be Powder Coated with Siemens grey paint shade no. RAL-7032 of IS-5. All motor feeders MCCBs shall be of motor duty. Supporting/Base rigid steel framework. 4P ACB’s / MCCB’s shall mean 4 pole ACB’s / MCCB’s with adequate size of neutral link. All MCCB above 250A shall be microprocessor base.
BUS BARS TPN aluminium bus bars of minimum of 1250 Amps capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section, size supports & their spacing etc. for withstanding faultcurrent of 36kA for 1 sec. BUS COUPLER:- 1 No. of 1000 A, 4P electrically operated Drawout type ACB with Ics=Ics=50KA having Mircroprocessor based releases for O/L, S/C & E/F protection. 1 Set of Breaker ON-OFF indication Lamps as required. Interlocking: Electrical through advance contacts in MCCB/ACB's (Incomer & bus couplers) & mechanical (castel key) interlocking should be provided to ensure that only one supply is available at a time on each section of bus & to eliminate any possibility of accidentlly approaching two supplies at one bus section.
OUTGOINGS-Bus Section-1 1 No. 800A 4P ACB (50 KA) 1 No. 630A TP MCCB (36KA) 2 No. 630A 4P MCCB (36KA) 1 No. 300A 4P MCCB (25 KA) 1 No. 160A 4P MCCB (25 KA) 2 No. 40A 4P MCCB (25 KA) OUTGOINGS-Bus Section-2 1 No. 800A 4P ACB (50 KA) 1 No. 630A TP MCCB (36KA) 1 No. 630A 4P MCCB (36KA) 1 No. 400A 4P MCCB (25 KA) 1 No. 250A 4P MCCB (25 KA) 1 No. 200A 4P MCCB (25 KA) 2 No. 63A 4P MCCB (25 KA) 1 No. 40A 4P MCCB (25 KA)
PLC PLC FEEDER- FOR AMF FOR AUTO ON/OFF THE DG, LOAD MANAGEMENT & E/M INTERLOCKING : "Hardware using PLCs for Monitoring of all Electrical Software and for operations, controlling and interlocking Parameters of 2 Nos. I/C from Transformer & 2 Nos. DG Set with Window based software & Engineering & Software Development. Required Aux. Relays, Push Buttons & Indication lamps, 1KVA UPS for Black start & maintenance free Batteries, Power monitors, Programmable Logic controller, Annunciator and status Fascia, MIMIC with LED circuit etc as required completing the system. " The Switchboard with Logic control panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required. Note: Incomer from LT Supply, D.G. set & Bus coupler shall be electrically & mechanically interlocked. Main LT Panel as described above
NOTE - i. The outgoing feeders as indicated in SLD shall have suitable range of followings (except capacitor feeders) Three phase indicating lamps protected by 2 amps SP MCBs. ii. All ACB's shall be suitable for minimum 25 kA ( Icu=Ics=Icw for 1 sec.) iii. 415/110V suitable rating control transformer and shall be provided for aux. control supply. iv. Wiring with space heater, thermostat and control MCB's shall be provided for all vertical sections of main LT panel. v. All breakers shall be interlocked as per schematic diagram through Mini PLC. vi. All incoming as well as outgoing feeders shall have pad locking facility. vii. Suitable danger board shall be provided. viii Incase of Fire, Fire pumps along with other ventilations and pressurization fans designed shall become operational. Interlocking with LT panel shall be carried out accordingly.
Capacitor Panel (230 kVAR) A INCOMER 1 No. 630A TP MCCB (36KA) B METERING & INDICATION i) 1 set of phase indicating lamps ii) 1 No. 9 step-Microprocessor APFC controller/Relay(Dual source purpose) shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel. Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor. C BUS-BAR TPN aluminium bus bars of minimum of 1000 Amps capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 sec. D OUTGOINGS i) 3 Nos.of 125A TP MCCB (25 KA) each with 3 Nos. 50 KVAR MPP Heavu Duty capacitor Bank each with capacitor duty contactor. ii) 2 Nos.of 80A TP MCCB (25 KA) each with 2 Nos. 25 KVAR MPP Heavu Duty capacitor Bank each with capacitor duty contactor. iii) 2 Nos. of 63A TP MCCB (25 KA) each with 2 Nos. 10 KVAR MPP Heavu Duty capacitor Bank each with capacitor duty contactor. iv) 2 No. of 32A TP MCB (10 KA) each with 2 No. 5KVAR MPP Heavu Duty capacitor Bank each with capacitor duty contactor.
Capacitor Panel (230 kVAR) - For Main LT Panel as described above
TYPICAL FLOOR PANEL A INCOMER 1 No. 100 amps 4P MCCB(25 KA) with thermal Magnetic release. "1 No. 100 amps 4P ATS. The ATS shall be complying to Standard IEC 60947-6-1 & 60947-3 with Third Party Test Certificate .The ATS should have four poles with fully rated neutral & controller with separate watchdog relay for both controller and motor." B METERING & INDICATION i) 1 set of R,Y,B phase indicating lamps ii) 1 No.- Multifunction Meter C BUS-BAR i) Electrolytic high conductivity Aluminium three phase and neutral busbars with earthing rated at 160 amps having a maximum current density of 1 amp per sq mm. The neutral busbar is to be of 50% capacity. D OUTGOINGS i) 1 Nos. 63A 4P MCCB(25KA) i) 1 Nos. 63A 4P MCB(10KA) ii) 1 Nos. 40A 4P MCB(10KA) iii) 1 Nos. 63A 4P MCB(10KA) For Spare iv) 2 Nos. 40A 4P MCB(10KA) For Spare
TYPICAL FLOOR PANEL as described above
MAIN LIFT PANEL-1 A INCOMER 1 No. 160 amps 4P ATS 1 No. 160 amps 4P MCCB(25 KA). B METERING & INDICATION i) 1 set of R,Y,B phase indicating lamps ii) 1 No.- Multifunction Meter C BUS-BAR i) Electrolytic high conductivity Aluminium three phase and neutral busbars with earthing rated at 200 amps having a maximum current density of 1 amp per sq mm. The neutral busbar is to be of 50% capacity. D OUTGOINGS i) 5 Nos. 40A 4P RCBO For Lifts ii) 2 No. 32A 4P MCB (10 KA)
Main Lift Panel- 1 as described above
MAIN LIFT PANEL-2 A INCOMER 1 No. 63 amps 4P ATS 1 No. 63 amps 4P MCCB(25 KA). B METERING & INDICATION i) 1 set of R,Y,B phase indicating lamps ii) 1 No.- Multifunction Meter C BUS-BAR i) Electrolytic high conductivity Aluminium three phase and neutral busbars with earthing rated at 100 amps having a maximum current density of 1 amp per sq mm. The neutral busbar is to be of 50% capacity. D OUTGOINGS i) 2 Nos. 40A 4P RCBO For Lifts ii) 1 No. 32A 4P MCB (10 KA)
Main Lift Panel- 2 as described above
UPS INPUT PANEL INCOMER 2 Nos. 300 amps 4P MCCB(25 KA) 2 Nos. 300 amps 4P Contactors for E/M interlocking. METERING & INDICATION 1 set of R,Y,B phase indicating lamps 1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB 1 No. (0-300A) Ammeter with ASS with 3 nos. 300/5A CT's BUS-BAR 1 Set of 400A TPN Aluminium Bus Bar with colour coded PVC Sleeves OUTGOINGS SECTION-1 2 No. 300A 4P MCCB (25 KA)
UPS INPUT PANEL as described above
UPS OUTPUT PANEL INCOMER 2 Nos. 300 amps 4P MCCB(25 KA) METERING & INDICATION 1 set of R,Y,B phase indicating lamps 1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB 1 No. (0-300A) Ammeter with ASS with 3 nos. 300/5A CT's BUS-BAR 1 Set of 400A TPN Aluminium Bus Bar with colour coded PVC Sleeves OUTGOINGS SECTION 16 Nos. 40A 4P MCB (10 KA) 4 Nos. 63A 4P MCB (10 KA) 2 Nos. 40A DP MCB (10 KA) 2 Nos. 32A DP MCB (10 KA)
UPS OUTPUT PANEL as described above
EXTERNAL LIGHTING FEEDER PILLER (Outdoor Type weather proof, double door with canopy and suitable MS Structure stand duly painted) A INCOMER 1 No. 40 amps 4P MCCB(25KA) 1 No. 40 amps 4P Astronomical timer for Automatic operation. B METERING & INDICATION i) 1 set of R,Y,B phase indicating lamps ii) 1 No.- AVF(Ameter,Voltmeter, Frequency) C BUS-BAR i) Electrolytic high conductivity Aluminium three phase and neutral busbars with earthing rated at 100 amps having a maximum current density of 1 amp per sq mm. The neutral busbar is to be of 50% capacity. D OUTGOINGS
10 Nos. 10A SP MCB (10 KA)
Supplying, installation, testing & commisioning of following capacity Plug In/ tap off box on the existing Air Insulated Compact Type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick sheet steel enclosure (IP54) duly powder coated with 4P MCCB complete etc. as required.
4 pole MCCB,630A, 50KA foe Existing End Feed Unit.
Supplying, installation, testing & commisioning of following capacity End Feed Unit for the existing Air Insulated Compact Type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure (IP54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required
630 A 50kA SC for 1 sec
Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required
630 A 50kA SC for 1 sec
EARTHING Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Supplying and laying 6 SWG G.I. wire at 0.50 meter below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
CABLE & END TERMINATIONS Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on cable tray as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1kV grade as required.
2 X 6 sq. mm (19mm)
3½ X 35 sq. mm (32mm)
3½ X 50 sq. mm (35mm)
3½ X 70 sq. mm (38mm)
3½ X 150 sq. mm (50mm)
3½ X 185 sq. mm (57mm)
3½ X 300 sq. mm (70mm)
4 X 10 sq. mm (25mm)
4 X 6 sq. mm (25mm)
4 X 16 sq. mm (28mm)
4 X 25 sq. mm (28mm)
HT CABLE END TERMINATION Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
Supply of HT cable Supplying of following sizes of XLPE aluminium conductor, corss linked polythylene, individual core screwed, flat steel strip armoured, PVC sheathed cable of 11KV grade (earthed) comforming to IS: 7098 (Part 2),with uptodate ammendment complete as required.
3 C x 240 Sq.mm XLPE HT cable (Earthed)
Supply of MV cable Supply, following sizes of PVC sheathed PVC/XLPE insulated Aluminium conductor/copper conductor power/ multicore control armoured cable of 1.1 KV grade.
3 ½ C - 300 sq mm Aluminium
3 ½ C - 185 sq mm Aluminium
3 ½ C - 150 sq mm Aluminium
3 ½ C - 120 sq mm Aluminium
3 ½ C - 50 sq mm Aluminium
3 ½ C - 35 sq mm Aluminium
4C- 16 sq mm Aluminium
4C- 10 sq mm Aluminium
4C- 6 sq mm Aluminium
2C- 6 sq mm Aluminium
4CX6 CU FLEX CABLE
3X4 CU FLEXIBLE WIRE
2CX4 CU FLEXIBLE WIRE
4CX4 CU FIRE SURVIVAL CABLE
4CX6 CU FIRE SURVIVAL CABLE
4CX10 CU FIRE SURVIVAL CABLE
4CX16 AL FIRE SURVIVAL CABLE
4CX25 AL FIRE SURVIVAL CABLE
3.5CX150 AL FIRE SURVIVAL CABLE
EXTERNAL LIGHTING WORK The rates for fixing of lighting fixtures shall include all fixing accessories that may be required to make the installation complete in all respects . Internal wiring between accessories connecting wires wherever required. Aesthetically designed 45W LED street light luminaire , housing shall be of corrosion free, pressure die cast aluminium, comprising of polycarbonate cover or better, LED chips,mounted on suitable designed aluminium heat sink with high thermal conductivity for better heat dissipation, fitted with integral drivers, stainless steel toggle clips & neoprene/ synthetic rubber gasket lining complying to IP 65/66 class of protection.
6-9 W LED Bollard Light .Pressure die cast aluminium painted housing with Diffuser made of Polycarbonate ,symmetrical wide light distribution Ingress Protection rating IP66. All luminaires shall be with associated driver , lamp and other connecting or mounting accessories to make it complete in all respect for operational purpose. The supplier shall submit the technical specification sheets alongwith LM reports for approval.
45W LED Post Top luminaire. Pressure die cast aluminium housing with Luminaire cover made of Polycarbonate/PMMA ,symmetrical wide light distribution & Ingress Protection rating IP66. All luminaires shall be with associated driver , lamp and other connecting or mounting accessories to make it complete in all respect for operational purpose. The supplier shall submit the technical specification sheets alongwith LM reports for approval.
7.0 meter high G.I octagonal pole (Above Ground Level) with single arm of suitable length with inbuilt junction box with 10A SP MCB, connectors for incoming/outgoing cable connection and 300mm x 300mm x 20 mm thick base plate complete in all respect including CC foundation minimum size 350mm x350mmx500mm with provision of PVC pipe for UG cable entry & termination of cable with gland/ thimble including 4 Nos. heavy duty foundation nut bolts with suitable length complete as required including erection of G.I. pole in 1:2:4 cement concrete (1 cement : 2 coarse sand : 4 graded stone aggregate 40mm nominal size) including excavation & refilling etc as required below ground complete as per requirement with all accessories.
45W Smart integrated solar street light with all in one Hybrid with system with built in Mono Crystalline panel, Lithium ferro phospate (Life PO 4) battery, MPPT charge controller and PIR Sensr with colour temperature 6000-6500K and with 7 mtr high pole.
40 KW GRID TIE SOLAR PV SYSTEM Supply, Installation, Testing and Commissioning of on grid Solar Photo voltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:- a) Solar Photo voltaic Module of capacity 330Wp or above, manufactured in India, conforming to IS 14286/ IEC 61215, IS/IEC 61730-Part-1,IS/IEC 61730-Part 2. Solar Photo voltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants /systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10years and 80% at the end of 25 years. b) Power Conditioning Unit (PCU) of 350800 VDC Input voltage range and 400V AC, three phase, 4wire,50Hz+/2.5Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. c) Data Monitoring System complete with accessories. d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection. f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/ conduit lugs and other accessories etc. as required.
Sub-Head - VIII- SAFETY EQUIPMENT Providing and fixing MV Danger Notice Plate of 200 mm x 150 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides and with inscription in single red colour on front side as required.
Providing and fixing HT Danger Notice Plate of 250 mm x 200 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides and with inscription in single red colour on front side as required.
Supply of fire buckets, 9 L (minimum capacity), 5 No. in each set duly filled with fine sand and fixed on an angle iron frame, red painted as per requirement of local authorities. Fire buckets shall be painted red from outside and white from inside with additional handle at the bottom and suitable for outdoor installation.
Supply and fixing on position the approved Single Line Diagram framed in 1000 x 800 mm size glass frame and installed in main switch room as directed by Engineer Incharge
Supply of First Aid box as directed by Engineer Incharge
Supply of tool kit with 1 pair 3.3 KV rubber hand gloves as directed by Engineer Incharge.
Supplying & fixing standard shock treatment charts in English & Hindi duly framed and covered with glass as directed by Engineer Incharge.
Providing Safety Mat made of elastomeric polymers Material (Class B) 1.2 M wide with thickness 2.5 mm to withstand 3.3 KV dielectric strength as per relevant IS Code
Providing a mat made of elastomeric polymers Material (Class A )1.2 M wide with 2 mm thickness to withstand 3.3 KV dielectric strength as per relevant IS Code
"FIRE SUPPRESSION SYSTEM FOR UPS & SERVER ROOM 34 Ltrs. Cylinder with Valve & Warning Sign Boards (42 Bar VDS Approved System)-1 Nos." Clean Agent-50 KG Master Cylinder Accessories: (Single Cylinder) * Pr. Guage + Low Pr. Supervisory Switch * Electromagnetic Actuator * Pneumatic Actuator * Flexible Discharge Hose * Flexible Actuation Hose * Manual Pneumatic Actuator * Union 7/16 JIC 1/8 Nozzles Supply of MS SCH 40 Seamless Pipes 2 Zone Fire Alarm Cum Gas Release Module with 7AH x 2 Batteries UL Listed FM Approved Listed Conventional Smoke Detectors with Base with 3 LED Color Indication Abort Switch Release Switch Hooter with Strobe 2 Core 1.5 Sqmm Armoured Cable
Medical Gas Pipeline System (MGPS) Equipments "Supply Installation, Testing & Commissioning of Medical Gas Pipeline System." Oxygen Supply System Fully Automatic control panel for Oxygen Having a constant flow out put of over 1500 LPM at 4.2 bar pressure.as per specification.
Oxygen Manifold (10+10) size of Primary manifold extendable type complete with middle frame with chain for individual cylinder (bulk cylinder D‐type) along with Non‐Return Valves for every cylinder and copper tail pipes.
Emergency Manifold Oxygen (6 + 6) with two stage High flow rate regulator with NRV for every cylinder and copper tail pipes.
Semi Automatic Control Panel for Emergency Mani‐Fold having a constant flow out put of over 1500 lpm at 4.2 bar pressure.
Nitrous Oxide (N2O) System Fully Automatic control panel for Nitrous Oxide Having a constant flow out put of over 500 LPM at 4.2 bar pressure.
Nitrous Oxide Manifold System, 1x2 No. size of Primary manifold extendable type complete with middle frame with chain for individual cylinder (bulk cylinder Dtype) along with Non‐Return Valves for every cylinder and copper tail pipes.
Emergency Nitrous Oxide Manifold System, 1 No: Emergency Manifold Nitrous Oxide ( 2 cylinders ) with two stage High flow rate regulator with NRV for every cylinder and copper tail pipes.
Carbon Dioxide (CO2) System Fully Automatic control panel for Carbon Dioxide Having a constant flow out put of over 500 LPM at 4.2 bar pressure..
Carbon Dioxide (CO2) Manifold System,1x2 No:. size of Primary manifold extendable type complete with middle frame with chain for individual cylinder (bulk cylinder Dtype) along with Non‐Return Valves for every cylinder and copper tail pipes.
Emergency Carbon Dioxide (CO2) Manifold System, 1 No: Emergency Manifold Nitrous Oxide ( 2 cylinders ) with two stage High flow rate regulator with NRV for every cylinder and copper tail pipes.
Vacuum System & Compressed System Duplex Vacuum Central System Complete with 02 nos. Vacuum Pump, each having minimum 40 cfm with Filter, interconnecting pipes, NRV, auto switch gear assy., exhaust silencer., Vacuum Receiver of 1000 Ltrs Capacity., Bacterial Filter
Duplex Compressed Air System including Vacuum Central System Complete with 02 nos. Vacuum Pump, each having minimum 40 cfm with Filter, interconnecting pipes, NRV, auto switch gear assy., exhaust silencer, Air Receiver of Capacity 500 & 1000 Ltrs, 4‐stage Air Filtration System, Pressure Reducing System
Gas Outlet Points/ Terminal Units with probe Oxygen Outlet
Nitrous Oxide Outlet
MA‐4 Outlet
MA‐7 Outlet
Vacuum Outlet
CO2 Outlet
Medical Grade Copper Tube/ Pipe: in accordance with BS EN 13348:2016 on Surface or Ceiling with hanging arrangement etc as required. 54 mm OD x 1.2 mm thick
42mm OD X 1.2mm thick
35mm OD X 1.2mm thick
28mm OD X 0.9 mm thick
22mm OD X 0.9 mm thick
15mm OD X 0.9 mm thick
12mm OD X 0.7 mm thick
Ward Vaccum Unit : Ward Vacuum unit Suction trap & Replaceable Bacteria filter with 600 ML all polycarbonate jar 63mm Guage Dial)
BPC Flowmeter with humidifier bottel Safety valve ) (0‐15 LPM) India with Certification
High Pressure tube
Low Pressure tube
Area Valve Box 2 Gas Services
3 Gas Services
4 Gas Services
5 Gas Services
6 Gas Services
Medical Gas Digital Alarm System 2 Gas Services
3 Gas Services
4 Gas Services
5 Gas Services
6 Gas Services
Master Alarm Panel Master Alarm for Medical Gas Manifold & Plant Room
Bed Head Panels ‐ Provision for 2 Gas Outlet(O2‐1+Vac‐I) with 5/15 Amp. Switch & Sockets and provision for Nurse call system. The size of the panel to be 1000 mm
Bed Head Panels ‐ Provision for 3 Gas Outlet(O2‐1+M.Air‐4‐14‐Vac‐ 1)with 5 Amp. 3 Nos.Switch & Sockets and provision for Nurse call system. The size of the panel to be 1500 mm.
Bed Head Panels ‐ Provision for 5 Gas Outlet(O2‐2+M.Air‐4‐1‐t Vae‐1) with 5 Amp. 3 Nos.Switch & Sockets and provision for Nurse call syste . The size of the panel to be 1800 mm
LINE ISOLATION VALVES WITH LOCKABLE: Supply, Installation, testing and commissioning of Line Isolation Valves 12 mm ball valve
15 mm ball valve
22 mm ball valve
28 mm ball valve
35 mm ball valve
42 mm ball valve
54 mm ball valve
MISCELLANEOUS ITEMS Combined Electrical Control Panel for Vacuum System, Compressed Air System (Cascading/seq.) and AGSS Plant complete with plant Room wiring.
Supply, Install, Testing and Commissioning of the Advanced Inventory Management System completed. Slim Storage System Door Automation Software
Description of Work / Item(s)
Amount
A' - Machinery Water Cooled Screw Chiller
Preference shall be given to HFO/GREEN refrigerant Chiller manufacturer shall be manufacturer of own compressor & shall have in house compressor related service support in Guwahati. Same capacity, same configuration, minimum 5 yrs old chiller shall be inspected to check the performance prior approval of submittals. 1 No. Suitable capacity squirrel cage IP 54 rated Suction Gas Cooled TERC (Totally Enclosed Refrigerant Cooled type) induction motor with class 'F' Insulation suitable for operation on 400+-10% volts, 50 HZ, A.C. Supply. 1 No. factory fitted Unit Mounted Star Delta Starter or VFD suitable for motor complete with ammeter with CTs, overload protection ,under voltage protection, protection against phase reversal & independent single phase preventers etc. complete as required. 1 Set- lubrication device consisting of automatic electric oil pump, oil cooler, oil strainer, automatic pressure regulating valve, oil heater, thermal switch etc. as required for the functioning of complete equipment 1 No - matching ASME 'U' stamped / BIS (Bureu of Indian Standard) shell and tube water cooled evaporator of Steel shell and integrally fined copper tubes with even pass configuration and max pressure drop up to 5 meters of Water Coloumn. Refrigerant sight glass shall be mandatorily provided in the condenser shell for checking moister content and refrigerant level. 1 No - matching ASME U stamped shell / BIS (Bureu of Indian Standard) and tube water cooled condenser of Steel shell and integrally fined copper tubes with even pass configuration and max pressure drop up to 5 meters. Refrigerant liquid level sensor shall be mandatorily provided in the condenser shell for checking moister content and refrigerant level. The condenser must be having hinged marine waterbox connection for ease of service. 1 Set - Microprocessor based control panel with colored touch screen display complete with accessories. The chiller controller shall be factory wired and unit mounted on the chiller machine. Separate mounting of chiller controller is not acceptable, so that any shifting of the chiller will not necessitate sensor field wiring.
Lot - Refrigerant line accessories comprising of safety valves, angle valves, liquid line indications, liquid level control etc. Liquid line isolation valve shall be provided to isolate refrigerant in condenser for maintenance purposes. Lot- Water Differential Pressure switches at inlet and outlet of condenser and chiller, water drain and air purge valves wherever required. Lot- Victaulic coupling/Flange Connection at the inlet and outlet piping connections of evaporator and condenser of chillers. Lot- Suction line and chiller insulation with minimum 19 mm thick polyvinyl nitrile rubber insulation duly insulated at manufacturer works/Site as manufacturer's standard Lot - Frame work for mounting the above condenser, chiller compressor and motor with base plate complete with ant vibration neoprene rubber pads or springs isolator Lot-Factory/Site Charged refrigerant gas and compressor oil. Lot-RCC/Cement concrete foundation for the chilling unit. The price quoted for supply, installation, testing & commissioning of Chilling Unit shall be inclusive of all duties & taxes, insurance, transportation / shipment cost from works to site, loading / unloading, port clearance charges etc. as required in Indian Rupees.
300 TR actual capacity. Water chilling machine as described above and at above mentioned operating conditions complete as required. (2 nos working + 1 no standby)
Air Cooled Heat Pump for Generating Hot Water with Inbuilt Pump
Control panel with display comprising of Controls. It shall also be equipped with protection and monitoring devices such as H/L Pressure switch/ Thermal and Current Overload Protector DP/ Flow switches at inlet and outlet of chiller, water drain & air purge valves, wherever required. Lot- suction line and chiller insulation Lot-frame work for mounting the above condenser, chiller, compressor and motor with base plate complete with antivibration pads/ springs. Lot- Initial/ first charge of refrigerant gas & compressor oil duly charged at factory. For pressure vessels i.e. evaporator & condenser ASME stamping is mandatory. Preference shall be given to HFO/GREEN refrigerant Chiller manufacturer shall be manufacturer of own compressor & shall have in house compressor related service support in Guwahati. Same capacity, same configuration, minimum 5 yrs old Heat Pump shall be inspected to check the performance prior approval of submittals. Lot- Initial/ first charge of refrigerant gas & compressor oil duly charged at factory.
Inbuilt Pump Details Supply, installation, testing and commissioning of PN16 rated primary chilled water pump with CI Casing, SS shaft & Impeller, CED Coating, Externally flushed Outside Type balanced Mechanical Seal(to be easily replaceable without disburing the pump and motor shaft), each pump capable of delivering the specified flow rate comprising the following and complete as per specifications. The external flush line must be used for the purpose of heat dissipation from the mechanical seal.Pumps shall be BMS compatible. i)Vertical Inline Axial Split Coupled centrifugal pump with motor mounted factory integrated IP55 VFD with sensorless/wireless control, capable to vary upto 60 Hz depending upon load requirement. The Pump VFD must display all the critical parameters like amps, volts, frequency, dynamic flow and head of each operating pump to omit the requirement of separate flowmeter. ii) Suitable HP, TEFC permanent magnet motor with Efficiency IE5, class `F' insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply. Hot Water Pump Motor upto 7.5kw shall be strictly of permanent magnet type. Note: Contractor must provide necessary vibration isolation arrangement, if required. Water flow rate : 25 USGPM (95 LPM Approx.) Head : 70 ft. Motor HP : 1.5HP(suggested) or as per OEM standard Pump Efficiency(Min) : 70 % or above Pumps as mentioned above (1W+1S)
Heating capacity of 30KW actual capacity Water heating machine (For Monsoon Reheating of OTs) as described above and at above mentioned operating conditions complete as required. (1 nos working + 1 no standby)
Primary Chilled Water Pumps
Supply, installation, testing and commissioning of PN16 rated primary chilled water variable speed vertical inline pump pump with CI Casing, Bronze Impeller, SS shaft,CED Coating, Externally flushed Outside Type balanced Mechanical Seal(to be easily replaceable without disburing the pump and motor shaft), each pump capable of delivering the specified flow rate comprising the following and complete as per specifications. The external flush line must be used for the purpose of heat dissipation from the mechanical seal.Pumps shall be BMS compatible. Pump efficiency shall be minimum 80%. ii) Suitable HP, TEFC Induction motor with Efficiency IE3, class `F' insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply. Note: Contractor must provide necessary vibration isolation arrangement, if required. Primary Chilled water pumps Water flow rate : 720 USGPM (2722 LPM Approx.) Head : 40 ft. Motor HP : 15.0 HP(suggested) or as per OEM standard Efficiency : 75 % or above RPM : 4P/2P as per better pump efficiency
Pumps as mentioned above (2W+1S)
Secondary Chilled Water Pumps with VFD
Supply, installation, testing and commissioning of PN16 rated primary chilled water variable speed vertical inline pump with CI Casing, Bronze Impeller, SS shaft, CED Coating, Externally flushed Outside Type balanced Mechanical Seal(to be easily replaceable without disburing the pump and motor shaft), each pump capable of delivering the specified flow rate comprising the following and complete as per specifications. The external flush line must be used for the purpose of heat dissipation from the mechanical seal.Pumps shall be BMS compatible. Pump efficiency shall be minimum 80%. i) Variable Speed Vertical Inline Axial Split Coupled centrifugal pump with motor mounted factory integrated IP55 VFD with sensorless/wireless control, capable to vary upto 60 Hz depending upon load requirement. The Pump VFD must display all the critical parameters like amps, volts, frequency, dynamic flow and head of each operating pump to omit the requirement of separate flowmeter. ii) Suitable HP, TEFC Induction motor with Efficiency IE3, class `F' insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply.
Water flow rate : 720 USGPM (2722 LPM Approx.) Head : 85 ft. Motor HP : 25.0 HP(suggested) or as per OEM standard Pump Efficiency(Min) : 75% or above RPM : 4P/2P as per better pump efficiency
Pumps as mentioned above (2W+1S)
Condenser Water Pumps
Supply, installation, testing and commissioning of PN16 rated Primary chilled water vertical inline pump with CI Casing, Bronze Impeller, SS shaft, CED Coating, Externally flushed Outside Type balanced Mechanical Seal(to be easily replaceable without disburing the pump and motor shaft), each pump capable of delivering the specified flow rate comprising the following and complete as per specifications. The external flush line must be used for the purpose of heat dissipation from the mechanical seal.Pumps shall be BMS compatible. Pump efficiency shall be minimum 80%. ii) Suitable HP, TEFC Induction motor with Efficiency IE3, class `F' insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply. Note: Contractor must provide necessary vibration isolation arrangement, if required. Water flow rate :1200 USGPM (4617 LPM Approx.) Head : 80 ft. Motor HP : 40.0 HP(suggested) or as per OEM standard Pump Efficiency(Min) : 75% or above RPM : 4P/2P as per better pump efficiency
Pumps as mentioned above (2W+1S)
Cooling Tower (CTI approved)
Supplying, installing, testing & commissioning of CTI certified induced draft vertical out-door type FRP cooling tower of stated heat rejection capacity with fiber glass reinforced water basin, PVC fillings with integral louvers and drift eliminators complete with hot water basin, spray system comprising of GI pipe & brass nozzle,either fitted with statically & dynamically balanced axial flow type fan-direct driven or driven through reduction gear box with VFD operated TEFC induction motor having IP-65 protection and IE-3 rated, suitable for operation at 415 ± 10% voltage, 50 Hz A/C 3 phase supply.The outdoor noise criterion for cooling towers, at a distance of 50 meters from the fan shall be NC-45.Therefore, noise level in open areas 50 meters away from towers in any direction shall not exceed 60 DB.The structure of the cooling towers shall be designed for wind and other loads as per IS: 875. The cooling tower shall be complete with powder coated suction screen, make up quick fill arrangement, overflow and drain connections with necessary valves, fan guard and suitable inspection ladder, access arrangement for cooling tower interior, cement concrete foundation, steel/ masonary supporting structure, anti-vibration/spring mountings etc. complete as per CPWD 2017 specifications and as required. Water Leaving Temperature : 90.0 Deg F Water Entering Temperature : 97.5 Deg F Ambient Monsoon Wet Bulb Temperature for Guwahati : 83.5 Deg F (28.6 Deg C) Water Flow Rate : 1200 USGPM
Cooling Tower as above (2 Working+1 Standby)
Make-Up Water Tank for Cooling Tower
Supplying, installing, testing & commissioning of sintex water tank for make up water for cooling tower at terrace.All valves acesessaries shall be complete as required.
Capacity - 5000 lts
Automatic Tube Cleaning System
Supply & Installation testing & commissioning of suitable of automatic condenser tube cleaning system equipped with soft/brush ball, ball re-circulation device, ball entrapment module, ball diverter module, ball injection module requiring cleaning balls for cleaning condenser tube system for chiller. The tube cleaning system shall be equipped with a master programmable logic controller with user definable features to adjust cleaning cycle timing to suit operational parameters of condenser, ball rejection module, ball retrieval module, and related piping configuration compromising the master mechanical components control system to be installed for each chiller condenser or a single system of multiple chiller condenser. The Automatic tube cleaning system shall utilize cleaning balls with soft/ spikes configuration to reach and clean grooves of enhanced tubes. A combined system to be provided for 300 TR x 3 nos chillers. The system shall include Injection Pump, Collection Pump, Ball Trap, Programmable Logic Controller (PLC) Panel, MultiColour HMI, Electrically Operated Control Valves, Necessary valves and fittings, electrical control wiring and power cableling, etc to make the syestem complete for 3 nos chillers. One set of skid containing 2 pumps, 2 nos ball traps and 2 nos ball collectors as per OEM standards complete as required.
Expansion Tank and Dirt Air Seperator (Chilled Line)
Supply, installation, testing & commissioning of PN 16 rated and ASME stamped Closed Loop Expansion tank and Dirt Air Separator with strainer, auto airvent, insulaton, necessary pneumatic devices and Pressurization unit with two pumps (1W+1S), pressure switch & other accessories, the control panel should also be included as per followings. ASME stamped expansion tank and dirt air separator must be sourced from pump manufacturer same as chilled water make for unit responsibility. The unit shall be housed in powder-painted canopy suitable for external installation, if required.
800 Litres ASME stamped Expansion Tank
AIR HANDLING UNIT (FOR OT'S)-SEPTIC PURPOSE-With VFD
Supply, Installation, testing and commissioning of Eurovent certified factory fabricated double skin(50mm Thick) type Air Handling Units (BMS compatible) for Operation Theatres as per specifications given below:-AHU Construction:- It shall be made out of 0.8 mm pre -coated Galvanized steel sheet outside & 0.8 mm Aluzinc Sheet inside with 50 mm Thick panel insulated with them Rockwool insulation (density not less than 96 kg/m³). Drain pan (made out of 1.2 mm stainless steel (SS Grade 304) sheet insulated with 19 mm think closed cell insulation nitrile rubber with thermal brake profile. The AHU casing shall comply to Eurovent standard EN 1886 for casing strength D1, Casing Air leakage L1, Thermal Brigding factor TB2, Thermal Transmittance T2 & Filter bypass leakage F9.AHUs Inner skin of panels & all parts which comes with air contact shall be minimum 22 G anodized aluminum.Necessary foundation required & anti vibration pads shall be provided & cost for the same shall be included in this item.Supply Air Stream:-
Terrace Floor
F/M OT 1, 3200CFM/12.8/2.75 KW TR F/M AHU WITH 125MMWG SP
F/M OT 2, 3200CFM/12.8/2.75 KW TR F/M AHU WITH 125MMWG SP
F/M OT 3, 3200CFM/12.8/2.75 KW TR F/M AHU WITH 125MMWG SP
F/M OT 4, 3200CFM/12.8/2.75 KW TR F/M AHU WITH 125MMWG SP
F/M Endoscopy-1, 3200CFM/12.8/2.75 KW TR F/M AHU WITH 125MMWG SP
F/M Endoscopy-2, 3200CFM/12.8/2.75 KW TR F/M AHU WITH 125MMWG SP
Double Skin Ceiling Suspended AHU With Pre Filters + Fine filters
11000 CFM / 28.0 TR / F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
7000 CFM / 17.0 TR/ F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
5500 CFM / 14.0 TR / C/S AHU / 45MM WG SP (2-LEVEL FILTERATION)
3200 CFM / 8.0 TR/ C/S AHU / 45MM WG SP (2-LEVEL FILTERATION)
First Floor
12000 CFM / 30.0 TR/ F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
11600 CFM / 29.0 TR / F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
Second Floor
15000 CFM / 37.5 TR / F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
11000 CFM /27.0TR / F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
Third Floor
11000 CFM / 27.5 TR/ F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
10500 CFM /26.0TR/ F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
Fourth Floor
14500 CFM / 36.0 TR / F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
11000 CFM /27.0 TR / F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
Fifth Floor
13000 CFM / 32.5 TR/ F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
11500 CFM /28.0 TR / F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
Sixth Floor
13500 CFM / 33.0 TR / F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
10500 CFM /26.0 TR/ F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
Seventh Floor
6500 CFM / 16.0 TR / F/M AHU / 65MM WG SP (2-LEVEL FILTERATION)
1000 CFM /2.5 TR / C/S AHU / 45MM WG SP (2-LEVEL FILTERATION)
1200 CFM/3.0 TR / C/S AHU / 45MM WG SP (2-LEVEL FILTERATION)
7500 CFM /18.0 TR / F/M AHU / 45MM WG SP (2-LEVEL FILTERATION)
HI WALL SPLIT UNITS Thermostat/Humidistat for AHU (Proportional type)
Supply, Installation, testing and commissioning of Air-cooled DX type Hi-wall split air conditioners each comprising an outdoor unit(s) consisting of hermetically sealed compressor,Inverter type suitable for operation on 230V, 50Hz, 1 Phase AC supply, air cooled condenser, condenser fan along with Cooling thermostats etc. with outer casing and indoor fan coil unit consisting of centrifugal fans, fan motor, DX cooling coil, outer casing, filter, control and power panel with remote etc. entire cabling and wiring from indoor to outdoor, insulation (as per the actual pipe length) and with full charge of refrigerant gas (including the increased pipe length, if any) and oil, supports, canvas connection etc. complete as per drawings. The indoor and outdoor units shall be with structural steel supports, angles, rods etc. The quoted price shall also include 24G soft copper refrigerant piping with 13 mm "O" class factory backed nitrile rubber with aluminum foil from outdoor unit to indoor unit complete with insulation (atleast 20mtrs), refrigerant charging, PVC drain piping with 6mm thick nitrile rubber insulation, supports, clamps, fittings, connections, sleeves, supports, MCB, stabilizer etc. from main panel to the unit. Machine shall run on automatic wall mounted relay that makes the units work under main system failure. Complete as required as per site conditions.The units should be controlled with a logic panel, when the AHU. will be conditioning the room temp, the Split units will be deactivated. When the HVAC unit is stopped the split units will be activated, one unit will run other will be in standby. After 12 hours the other split unit will run the first one which was running will now be in standby. In case one unit fails the unit will be disconnected from the circuit the other will be in continuous operation. Logic panel should give audio visual indication till it is deactivated manually.
1.5 TR Unit For ATM
2.0 TR Unit
Thermostat/Humidistat for AHU (Proportional type)
Supply, installation, testing and commissioning of latest generation digital display type BMS compatible thermostat / humidistat with controller for cool / heat application suitable for two/four pipe system & humidistat suitable for working with humidifier and hot water coil control valves for various air handling Units. The thermostat shall have provision of setting of space temperature and display of the same. The humidistat shall have provision of setting space RH and display of the same. The quoted price of thermostat / humidistat shall include the cost of 20mm MS conduits, control cabling, MS Box etc. as required. The cost quoted shall be excluding the control valves and humidifier. It shall include all accessories ,mountings, wiring between thermostat & unit, terminations etc.(BMS Compatibility to be provided).
Thermostat for AHU
Supply, installation, testing and commissioning of VARIABLE AIR VOLUME (VAV) BOXES complete with leakage proof damper, differential pressure sensor, ,motorized aluminium construction damper with actuator (UL approved), Rapid Average Pitot tube; Air Flow Straightner (Honey-Comb patterned). LCD touch screen type cooling & Heating thermostat with all the parameter control, differential pressure sensor,24 Volt power supply unit for each VAV box, controller capable of accepting analogue/digital signal from thermostat and output to damper actuator.The thermostat should have capacitive touch button with large display wired control port should be controlled by mobile app(optional).Complete as required as per site conditions.
First Floor 200CFM - 400CFM
Second Floor 200CFM - 400CFM
Third Floor 200CFM - 400CFM
Fourth Floor 200CFM - 400CFM
Fifth Floor 200CFM - 400CFM
Sixth Floor 200CFM - 400CFM
Supply, installation, testing and commissioning of controller Modulating motorised assembly for pressure independent volume control with programmable advanced application specific controller having digital differential pressure sensor, 4 UI & 4 UO, wired wall module port & communication should only be BACNET over IP for all VAV controllers; & necessary power supply circuit suitable for 220V. Mapping shall be required for monitoring individual room temperature, air flow and damper position for areas conditioned through VAV boxes.Quoted price shall be inclusive of wiring in GI conduit between Controler and individual VAV Boxes.Complete as required as per site conditions.
First Floor
Second Floor
Third Floor
Fourth Floor
Fifth Floor
Sixth Floor
Supply installation testing and commissiong of Ultrasonic Humidifier of suitable capacity , complete with stainless steel SS-304 tank with level switch, piezo transducers duly interlocked with level sensors, Solenoid operated RO water makeup, water over flow protection, overflow and drain connections. Supplying, installing, testing & commissioning of AMCA Certified INLINE FANS suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised stee 18 SWG. The inline fan shall be with backward/forward curve centrifugal impeller fitted with maintenance free external rotor motor, flexible connections at the discharge & inlet. high efficiency (efficiency-1 / IE-2) TEFC squirrel cage 3 phase 50 Hz, 415 Volt, Class H insulated with IP 54 protection fan motor, V- belt Drive package consisting of Motor Pulley, fan Pully, V- elt, belt Guard and other accessories. quoted price shall be inclusive of DOL starter panel with cabling between starter panel and fan. The incoming power supply to speed regulator / starter panel shall be provided by electrical contractor.The fan shall have low sound level exceeding not more than 40 DBA at three meter distance.The out let velocity shall not exceed 12mtr/sec.
Inline Fans cabinet type (accoustically lined)
Supplying, installing, testing & commissioning of AMCA Certified INLINE FANS suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised stee 18 SWG. The inline fan shall be with backward/forward curve centrifugal impeller fitted with maintenance free external rotor motor, flexible connections at the discharge & inlet. high efficiency (efficiency-1 / IE-2) TEFC squirrel cage 3 phase 50 Hz, 415 Volt, Class H insulated with IP 54 protection fan motor, V- belt Drive package consisting of Motor Pulley, fan Pully, V- elt, belt Guard and other accessories. quoted price shall be inclusive of DOL starter panel with cabling between starter panel and fan. The incoming power supply to speed regulator / starter panel shall be provided by electrical contractor.The fan shall have low sound level exceeding not more than 40 DBA at three meter distance.The out let velocity shall not exceed 12mtr/sec.
Air Quantity : 2100 CFM (Cabinet Type) Static Pressure : 15 mm wg Motor rating : As Required Duty : Toilet Exhaust
Air Quantity : 900 CFM (Cabinet Type) Static Pressure : 15 mm wg Motor rating : As Required Duty : Toilet Exhaust
Air Quantity : 650 CFM (Cabinet Type) Static Pressure : 15 mm wg Motor rating : As Required Duty : Toilet Exhaust
Air Quantity : 600 CFM (Cabinet Type) Static Pressure : 15 mm wg Motor rating : As Required Duty : Toilet Exhaust
Air Quantity : 500 CFM (Cabinet Type) Static Pressure : 15 mm wg Motor rating : As Required Duty : Toilet Exhaust
Air Quantity : 250 CFM (Cabinet Type) Static Pressure : 15 mm wg Motor rating : As Required Duty : Toilet Exhaust
Air Quantity : 200 CFM (Cabinet Type) Static Pressure : 15 mm wg Motor rating : As Required Duty : Toilet Exhaust
Air Quantity : 150 CFM (Cabinet Type) Static Pressure : 15 mm wg Motor rating : As Required Duty : Toilet Exhaust
Air Quantity : 100 CFM (Cabinet Type) Static Pressure : 15 mm wg Motor rating : As Required Duty : Toilet Exhaust
Propeller Fans
Air Quantity : Dia. 250 (300 CFM), 2.5 mm St. Pr., 900 RPM or as per OEM, fan suitable for 220 ± 5% volts 50 cycles, 1 phase AC supply. Power : As Required Duty : Toilets Exhaust
AXIAL FLOW FAN (AMCA Certified for Sound & Preformance):
Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung / floor mounted vane/tube axial flow fans of following capacity with GSS casing/ standard M.S. construction and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency IE2 for Emergency Supply, Pressurization and Smoke Exhaust Fans and IE3 for Normal Supply, and Exhaust Fans suitable for 3 Phase 50 Hz 415V ± 10 %. Motor shall be class 'F' insulation for Fresh Air and Pressurization Fans and class 'H' insulation for Exhaust Fans. Fire rated flexible connection etc. including all accessories complete as required and as per specifications. Motor of exhaust fans shall be of high temperature resistance "Class H Smoke Spill" 250° C for 2 hrs. Fan shall be EN 12101-3 Certified & CE/UL Listed for high temprature. Motor make shall be same as mentioned on the fire certificate. Fan total efficiency should not be less than 70%. All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. Suitable TP isolator within MS enclosure should be provided. Gravity louvers will be provided at the discharge of the fan so as to avoid reverse flow. Static pressure shall be checked/verified by contractor prior to order. Entire fan model & AMCA Seal shall appear in technical submittal of fan. Complete as required as per site conditions. The fans operating under normal modes shall have low sound level not exceeding more than 75 dB(A)at three meter distance at both ends when measured in hemispherical reverberant room conditions. To achieve specified dB(A) level sound attenuators shall be provided at inlet / outlet and included in the cost.The fans operating under emergency modes shall have sound level not exceeding more than 85 dB(A) at three meter distance at both ends when measured in hemispherical reverberant room conditions.
Air Quantity : 15000 CFM Static Pressure : 30 mm wg Motor Rating : 10.0 HP (Suggested) Insulation : Class F Duty : Lift well Pressurisation
Air Quantity :13000 CFM Static Pressure : 30 mm wg Motor Rating : 7.5 HP (Suggested) Insulation : Class F Duty : Lift Lobby Pressurisation
Air Quantity : 7000 CFM Static Pressure : 30 mm wg Motor Rating : 5.0 HP (Suggested) Insulation : Class F Duty : Make-up Air
Air Quantity : 6500 CFM Static Pressure : 30 mm wg Motor Rating : 3.0 HP (Suggested) Insulation : Class F Duty : Make-up Air
Air Quantity : 6000 CFM Static Pressure : 40 mm wg Motor Rating : 3.0 HP (Suggested) Insulation : Class F Duty : Make-up Air
Air Quantity : 5500 CFM Static Pressure : 30 mm wg Motor Rating : 3.0 HP (Suggested) Insulation : Class F Duty : Make-up Air
Air Quantity : 5000 CFM Static Pressure : 30 mm wg Motor Rating : 3.0 HP (Suggested) Insulation : Class F Duty : Make-up Air
Air Quantity : 4500 CFM Static Pressure : 30 mm wg Motor Rating : 3.0 HP (Suggested) Insulation : Class F Duty : Make-up Air
Air Quantity : 3000 CFM Static Pressure : 30 mm wg Motor Rating : 1.5 HP (Suggested) Insulation : Class F Duty : Make-up Air
Air Quantity : 7500 CFM Static Pressure : 30 mm wg Motor Rating : 5.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 7000 CFM Static Pressure : 30 mm wg Motor Rating : 5.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 6500 CFM Static Pressure : 30 mm wg Motor Rating : 3.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 6000 CFM Static Pressure : 30 mm wg Motor Rating : 3.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 5500 CFM Static Pressure : 30 mm wg Motor Rating : 3.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 5000 CFM Static Pressure : 30 mm wg Motor Rating : 3.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 4500 CFM Static Pressure : 30 mm wg Motor Rating : 3.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 3000 CFM Static Pressure : 30 mm wg Motor Rating :1.5HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 2000 CFM Static Pressure : 30 mm wg Motor Rating :1.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 1000 CFM Static Pressure : 30 mm wg Motor Rating :1.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
Air Quantity : 1000 CFM Static Pressure : 30 mm wg Motor Rating :1.0HP (Suggested) Insulation : Class H Duty : Smoke Exhaust
'B'- Chilled Water Piping,Fittings & Valves
INSULATED CHILLED / HOT WATER PIPING
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with closed cell elastometric nitrile rubber for external thermal insulation on pipes with approved sample of Class 'O' Glass Cloth 7 Mil (GC-Blue/Green/Red Color) faced closed cell nitrile rubber. Density of the material shall be 40-55 kg/metre cube. All joints shall be sealed with 50mm Glass cloth self adhesive tape.For pipe dia. 80nb up to 600nb : Class ‘O’ Nitrile Sheets with manufacturer bonded Treated Woven Glass Fibre Covering to be used. For Pipe Dia. Below 80nb : The tubes shall be fully factory (machine) slit along each length with two strips of double sided self adhesive tape pre-applied complete as per specifications and as required complete in all respect. 20- 100 mm nominal dia with 32 mm thick insulation.125-350 mm dia with 38 mm thick insulation (1st Layer 25 mm Plain Nitrile & 2nd layer 13 mm GC sheets) Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S.Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS
250 mm dia.
200 mm dia.
150 mm dia.
125 mm dia.
100 mm dia.
80 mm dia.
65 mm dia.
50 mm dia.
40 mm dia.
32 mm dia.
25 mm dia.
Condenser Water Pipe (non insulated)
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS ‘C’ class along with necessary clamps, vibration isolators and fittings such as bends,tees etc..but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:- The Pipes size 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
300 mm dia
200 mm dia
150 mm dia
50 mm dia
40 mm dia
Valve With insulation
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated as per below specifications as the connected piping and adequately supported as per specifications. SITC Cast iron Lugged Design butterfly valve complete with flanges etc., PN 16 class rating. Valve body is made of Cast iron to IS 210 Gr. FG 260 and disk is made of Ductile (SG) Iron to IS 1865 Gr. 450/10 with Nylon Coated, stem of 431 Stainless steel with upper and lower self-lubricating anti-friction bearings,seat of EDPM integrally moulded suitable for the fluid and temperature and 10 position lock levers with position for valve up to 150 mm.Worm gear (for size 200mm and above), with hand wheel. Standard flange shall be ASME B.16.5 and bolts can be used with no change in flange insulation method. Flange bolts shall be tightened directly on metal surface of flange and not on top of insulation.
200 mm dia
150 mm dia
80 mm dia
65 mm dia
50 mm dia
SITC Balancing Valve with built in measuring facility.The balancing valves of size 25mm to 50mm dia shall be of Gun Metal Construction with screwed ends. Whereas Valves of size 65mm and above shall be of Cast Iron to IS 210 Gr. FG 260 Flanged Construction. Valves shall be PN-16 rating and conforming to BS 7350 DRV standard. For Cast Iron Flanged Design Balancing Valves size 50mm and above in Cast Iron to IS 210 Gr. FG 260 Body and Bonnet, SS-410 Stem, SS-410 /EN-3 Disc and EPDM Sealing Disc.
200 mm dia
80 mm dia
40 mm dia
32 mm dia
25 mm dia
SITC The Y Strainer PN-16 MOC of the Body shall be Mild Steel & SS-304 Filter with 3mm perforation with flanged connection, gaskets permanent magnet.
200 mm dia
100 mm dia
80 mm dia
65 mm dia
Providing and fixing in position the following Ball Valves with Strainer duly insulated as per specifications and drawings. Ball valve shall be screwed type brass/bronze lever operated, quarter turn ball valve (screwed type) of full flow with bronze /forged brass hard chrome plated ball with setting & gland of superior quality of preferably PN 16 rating.
25 mm dia
20 mm dia
SITC DUAL PLATE TYPE CHECK VALVES For Cast Iron Lugged Design Check valves PN-16 , 50 mm and above it shall comply with API 594,silent,non slam type . Cast iron to IS 210 Gr. FG 260 Body, ASTM A 217 Gr. CA-15 (SS-410) Plates, SS-410 Hinge/Stop Pin, SS-316 Spring, EPDM Seal.
200 mm dia
Providing and fixing in position the following Ball Valves without strainer duly insulated as per specifications and drawings. Ball valve shall be screwed type brass/bronze lever operated, quarter turn ball valve (screwed type) of full flow with bronze /forged brass hard chrome plated ball with setting & gland of superior quality of preferably PN 16 rating.
40 mm dia
32 mm dia
25 mm dia
20 mm dia
Valves Without Insulation
Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications & as required. BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for condenser water circulation as specified
300 mm Dia
200 mm Dia
150 mm Dia
Balancing Valve with built in measuring facility with C I body flanged construction with EPDM coated disc with long pitch & PN 16 pressure rating for condenser water circulation as specified.
200 mm Dia
SITC The Y Strainer PN-16 MOC of the Body shall be Mild Steel & SS-304 Filter with 3mm perforation with flanged connection, gaskets permanent magnet.
200 mm dia
Providing and fixing in position the following Ball Valves for drain & makeup water line as per specifications and drawings. Ball valve shall be screwed type brass/bronze lever operated, quarter turn ball valve (screwed type) of full flow with bronze /forged brass hard chrome plated ball with setting & gland of superior quality of preferably PN 16 rating.
40 mm dia
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required.
Providing & Fixing in position the mercury in glass with industrial type thermometers.
PIBC VALVE for Chilled water coil Supply, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modualating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum,complete as required.
65 mm Dia
80 mm Dia
100 mm Dia
Three Way Control Valve for Hot water coil Supply, installation, testing and commissioning of Three Way Control Valve in a single body equipped with electronic modulating actuator working on 0-10 V DC, 4- 20 mA electric signal. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications of following sizes. The valve shall be complete with digital type modulating thermostat (with NTC sensors) which will have provision of setting room temperature.The valve system shall be complete with necessary control cabling between control transformer,valve and standalone thermostat.The valve shall be suitable for the following pipe sizes:
40 mm Dia pipe
32 mm Dia pipe
25 mm Dia pipe
Providing, fixing, testing & commissioning of resilient rubber lined double arch vibration eliminators suitable for raw water up to 45 deg. C temperature to provide relief from stresses at pipe flanges. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.(PN 16 rating)
200 mm dia
80 mm dia
Providing and fixing Auto air vents (Brass MOC) of following size
20 mm dia
Pot Strainer Supplying, installation, testing and commissioning of Pot strainer. Pot Strainers body shall be fabricated out of MS plate IS 226. Thickness of sheet shall be as per size of the strainer chamfered pipes with flanges shall be provided at inlet /outlet connections of the strainer. A powerful magnet shall be provided in the body to arrest MS particles. Filter element of Pot Strainer shall be of non magnetic 18 gauge SS sheet properly reinforced to avoid damage of the element.A set of MS flanges with tongue and groove arrangement and neoprene rubber gasket shall be provided on the top cover and Pot Strainer flange with sufficient bolts and nuts to make the joint water light. The Pot strainer body shall be properly de-rusted and epoxy coated from inside and outside.
Connection Size 300 mm dia (for condenser water line)
Connection Size 250 mm dia (for chilled water line)
Connection Size 80 mm dia (for hot water line)
Drain Pipings Providing and fixing in position the following GI medium class ISI marked, cut to required length and installed with screw joints including the necessary ISI marked fittings (bends, tees, unions, sockets etc) duly insulated with 6 mm thick nitrile rubber pre formed pipe section as per specifications.
25 mm dia
32 mm dia
40 mm dia
Flow switches Providing and fixing in position approved make pedal type flow switches complete with copper control wiring between inlet and outlet of each chiller & decoupler line. These shall be BMS compatible. 300mm dia
'C' - Air Distribution DUCTING: Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round 180GSM ducting complete with neoprene rubber gaskets,elbows,splitter,dampers,vanes,hangers,supports etc as per approved drawings and specifications of following sheet thickness complete as required.
Thickness 0.63 mm sheet (24 Guage)
Thickness 0.80 mm sheet (22 Guage)
Thickness 1.00 mm sheet (20 Guage)
Thickness 1.25 mm sheet (18 Guage)
Supply, fabrication, installation and testing of Factory Fabricated Aluminium ducts for OT's in accordance with the approved shop floor drawing complete with all accessories, bends, fittings, specials, chutes, vanes, necessary supports etc. as per specification. 20 gauge Aluminium Ducting
Supply, installation, testing and commissioning of opposed blade aluminium volume control dampers with black mat finish in supply air duct collars,Damper shall be with 16G GSS body and blades shall be with aluminium airfoil construction. complete with neoprene rubber gaskets,nuts, bolts, screws linkages, flanges etc. as per approved shop drawings and specifications.
Supply, fabrication, installation and testing of non-porous flexible connections constructed of fire resistance flexible, double canvas connection with resistoflex material as per the approved shop drawings.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers as per specifications.
Supplying, fixing testing commissioning of supply air diffusers (Flat face type) of powder coated & made from extruded aluminium section ,smudge proof with aluminium volume control dampers with anti smudge ring.All extruded aluminium diffusers shall be provided with removable central core and concealed key operation for volume control damper.Complete as required.
Supplying, fixing testing commissioning of return air diffusers (Flat face type) of powder coated & made from extruded aluminium section,smudge proof without aluminium volume control dampers with anti smudge ring.All extruded aluminium diffusers shall be provided with removable central core.Complete as required.
FIRE DAMPERS Supplying, Fixing,testing and commissioning of fire dampers of at least 1½ hour fire rating as per UL555/1995 tested by CBRI,in supply air duct/main branch and return air path as and where required of required sizes, i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal.Damper blades shall be airfoil shaped (equivalent to 2.3mm thickness strength) roll formed using 0.8mm thick single piece of galvanized sheet.Fire damper shall be equipped with a electric limit switch to indicate open and close position of the damper blades.The dampers shall meet the requirements of NFPA90A, 92A and 92B and shall be classified as Leakage Class 2 smoke damper in accordance with latest version of UL555S. Each fire/smoke damper shall be AMCA licensed and bear the AMCA seal for air Performance. Pressure drop shall not exceed 7.5Pa when tested at 300m/min face velocity on 600x600mm size damper. Actuator shall be UL listed complete as required and as per specifications.
Fire damper(150 mm deep)
Control Panel with actuator(10Nm Torque) & Wiring
Door Transfer Grill Supply, installatio, testing, balancing and commissioning of extruded aluminium powder coated door transfer grill mesh with matching flange at rear side as required.
600 mm X 150 mm Size
Louvers Supplying, installing, testing and commissioning of Fresh Air powder coated Anodized extruded aluminium construction fresh air louvers (50 mm deep) (Fresh air louver with VCD , bird screen & rattle-free) complete as per specification.
Supplying, installing, testing and commissioning of Exhaust Air powder coated Anodized extruded aluminium construction fresh air louvers (50 mm deep) air louver without VCD , bird screen & rattle-free)complete as per specification.
HEPA FILTER Supply, Fixing & Testing of hepa filter of 99.7% Eff down do 0.3 micron with laminar flow diffuser of size 600x600x150mm.
Laminar Air Flow Plenum for OT Supply of LAMINAR CABINET made out of SS 304 grade Stainless Steel Unit Qty Rated material as per dimensions mentioned below. Minipleated High Efficiency Particulate filters of H13 rating with a filtration efficiency of 99.997% down to 0.3 microns to be supplied. The filters shall be made of water resistant,fire-retardant microfine glass fibre media with Hotmelt Foil seperators. The maximum Pressure Drop of the HEPA filter should not exceed 25 mm WC in clean condition. The filteration ceiling system should have flow equalizer to achieve uniform and constant air distribution over the entire surface. It should have provision for the insertion of OT light pendent at the centre of the cabinet with necessary covering sheet at top and bottom surface in SS 304, 18 Gauge construction with thermal insulation as specified . The flow rate of Laminar Air Flow Ceiling should not be less than 5400 cum/hr at average velocity of 0.24 m/s (Face velocity should be minimum 0.21m/s and maximum 0.28m/s). The laminar shall have SS 304 perforated sheet with proper mounting arrangements. All hardwares to be in medical grade Stainless Steel construction only. MOC of filter resting frame shall be made of SS 304 and cleats provided for fixing arrangements also to be provided of same SS 304 material.. The filters shall be supplied with factory fitted leak-proof 18G SS 304 Plenum Box Joint shall be with neoprene rubber gasket to minimize leakage. The plenum box shall be common for multiple filters and MOC will be 1.2 mm thick ss 304 will have perforated 1.2 mm thk SS 304. Entire Laminar Cabinet to be [externally thermally insulated with Armaflex make antimicrobial 23 MM thick, min 50 kg/cum density ‚FM approved , thermal conductivity 0.033 w/mdegK, u value 10000, Closed cell Nitrile Insulation backed with Aluminium Foil. Proper provision for supporting arrangement to be provided lat all four corners and at the centre of sides. SIZE- 8 FEET x 6 FEET
Supply , Installation, Testing , Commissioning of RETURN AIR RISERS in Operation Theatre Complex made out of 18 Gauge SS 304 with Damper and Prefilter.
Supply , Installation, Testing , Commissioning of Perforated RETURN AIR GRILL in Operation Theatre Complex made out of 18 Gauge SS 304 .
Pressure Differential Sensor For OT & Isolation Rooms Supply, installation & testing of pressure differential Sensor/Magnehelic gauges For each OT & Isolation Rooms.
Digital Thermometer with digital display For OT & Isolation Rooms Supply, installation & testing of Digital Thermometer with Digital display For each OT & Isolation Rooms.
DUCT THERMAL & ACOUSTIC INSULATION Supply & installation of external thermal insulation on ducts with factory laminated aluminum of mat finish on closed cell nitrile rubber with density min 40 Kg/ Cum for nitrile rubber, FM approved class 'O',Maximum Thermal conductivity 0.034 K.cal/ hr. degree C/m at 10 Deg C mean temp. complete as per specifications. All longitudnal and transverse joints shall be sealed with 50mm wide and 3mm thick Nitrile rubber tape. The cost shall be inclusive of Low VOC adhesive.
13 mm thick (Return air ducts in Conditioned Space & Air Washer duct) with protective coating
19 mm thick (Supply air ducts in Conditioned Space) with protective coating
25 mm thick (Supply air ducts in Outdoor) with protective coating
Supply, installation testing and commissioning of duct acoustic insulation Inside the Duct with Engineered Nitrile Rubber open cell foam with Density 140 - 180 Kg/m3 passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test or 10,000 fpm air velocity as per ASTM C 1071-05 to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents.
'D' - HVAC ELECTRICAL HVAC Plant Room Panel (Panel Must Be Totally type tested TTA type & as per IS 61439 part 1 & 2)
BACK ACCESS PANELS WITH ACB's Design, fabrication, assembly, wiring and supply, erection , testing and commissioning of front operated dead front cubicle type compartmentalised as per Form 4B, rear access free standing, dust and vermin proof (IP 54 ingress protection) main switchboards conforming to IEC-61439 suitable for use at 415 volts, 3 phase 4 wire 50 Hz system suitable for short circuit withstand capacity of 31 MVA for 1 Sec (specified with the panel) at 433 volts, fabricated from 2 mm outer thick CRCA MS sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/T/flat sections including 3 mm thick gland plates on top and bottom and including lifting hooks and including entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos. earth stud and including complete with 7 tank process for powder coating in approved shade over metal surface cleaned and treated with seven tank process complete with interconnections etc. as per specifications, as required and as below. The incoming and outgoing feeders shall be accommodated in a modular arrangement, detachable gland plates, adequate size cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate, including PVC insulated copper FRLS wires of 2.5sq.mm for CT's etc. complete as required as per specifications and drawing attached. A fairly uniform coating of 80 or better microns shall be provided. Bottom base channel of MS section not less than 100mmx 50mm x 5mm thick, fabrication shall be done in transportable sections. 3 Nos. MCCB for Chiller (including 1 no spare) 3 Nos. MCCB, for cooling tower (including 1 nos spare) 3 Nos. MCCB, for condenser pump (including 1 no spare) 3 Nos. MCCB, for secondry pump (including 1 no spare) 3 Nos MCCB, for Primary pump (including 1 no spare) Note: The panel shall be provided with suitable potential free contact for connections to the Building Automation System and shall exchange signals from BMS system for ON/OFF/Trip/Fault signals.
Supplying, Receiving, Fixing, Testing & Commissioning of Outdoor type (IP-65) HVAC Plant Room Panel made out of 14 SWG sheet as described above
32A 4P MCB with 7.5 HP DOL Starter for Pressurization Fan
32A 4P MCCB with 7.5 HP DOL Starter for Pressurization Fan
32A 4P MCCB with 10.0 HP Star-Delta Starter for Pressurization Fan
32A 4P MCCB with 7.5 HP DOL Starter for Pressurization Fan
32A 4P MCCB with 7.5 HP DOL Starter for Smoke Exhaust
25A 4P MCCB with 3.0 HP DOL Starter for Smoke Exhaust
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU(Left Side-GF)
40A 4P MCB with 7.5 HP DOL Starter for CSU-01( Cafeteria-01)
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU(Right Side-GF)
40A 4P MCB with 7.5 HP DOL Starter for CSU-02( Cafeteria-01)
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU(Left Side-1F)
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU(Right Side-1F)
63A 4P MCCB with 10.0 HP Star-DeltaStarter for F/M AHU1(Left Side-2F)
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU1(Right Side-2F)
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU(Left Side-3F)
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU(Right Side-3F)
63A 4P MCCB with 10.0 HP Star-DeltaStarter for F/M AHU(Left Side-4F)
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU(Right Side-4F)
63A 4P MCCB with 10.0 HP Star-Delta Starter for F/M AHU(Left Side-5F)
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU(Right Side-5F)
63A 4P MCCB with 10.0 HP Star-Delta Starter for F/M AHU(Left Side-6F)
40A 4P MCB with 7.5 HP DOL Starter for F/M AHU(Right Side-6F)
32A 4P MCCB with 5.0 HP DOL Starter for F/M AHU(Left Side-7F)
32A 4P MCCB with 5.0 HP DOL Starter for F/M AHU(Right Side-7F)
Supplying,Receiving, fixing, testing & commissioning of AHU Panel-1 (Ground Floor-LH) as described above
MV Cable Supply, laying & fixing of following sizes of PVC sheathed PVC/XLPE insulated Aluminium conductor/copper conductor with end termination glands power/ multicore control armoured cable of 1.1 KV grade.(Cables exposed to sunlight and rain to be UV resistant or UV safe. Note:All Cables from panel to Axial Fans shall be fire survival cables.
3 ½ C - 300 sq mm Aluminium
3 ½ C - 240 sq mm Aluminium
4C- 70 sq mm Aluminium
4C- 35 sq mm Aluminium
4C- 16 sq mm Aluminium
4C- 10 sq mm Aluminium
4C- 6 sq mm Aluminium
4C- 4 sq mm Aluminium
4C- 2.5 sq mm Aluminium
4C- 1.5 sq mm Aluminium
2C- 1.5 sq mm Aluminium
SITC of G.I. strip/wire on wall/slab/column/beam alongwith saddles and clamps etc including end connections complete in all respect.
25 MM x 3 MM
8 SWG x 2 Nos
MS Cable Trays Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.Provider:Aditya Steel,Asawa,MEM.
300 mm width X 50 mm depth X 1.6 mm thickness
Description of Work / Item(s)
Amount
FIRE HYDRANT WORKS Fire Hose Cabinet Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Gunmetal
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :
Single headed Gunmetal
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :
Gun Metal
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :
Providing and fixing of standard short size GM branch pipe with nozzle of 20mm nomnal bor outlet with instaneous type 63 mm dia coupling complete IS marked & TAC approved.
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
SUBHEAD-I (A): PIPING FOR FIRE FIGHTING SYSTEM Providing and fixing C.I. double acting air valves of approved quality with bolts, nuts, rubber insertions etc. complete ( The tail pieces, tapers etc. if reqd. will be paid separately)
50 mm dia.
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS:5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
150 mm dia
200 mm dia
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
80 mm dia
150 mm dia
200 mm dia
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
150 mm nominal bore (class C)
100 mm nominal bore (class C)
80 mm nominal bore (class C)
65 mm nominal bore (class C)
50 mm nominal bore (class C)
40 mm nominal bore (class C)
32 mm nominal bore (class C)
25 mm nominal bore (class C)
Providing, fixing, testing & commissioning of 15mm dia uartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :
Pendent Sprinkler
Upright Sprinkler
Concealed sprinkler
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.
150mm dia
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.
Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required.
FIRE NON SCHEDULED ITEMS Providing and fixing carbon-di-oxide type fire extinguishers consisting of welded M.S. cylindrical body, internal discharge tube, discharge nozzle, suspension bracket, conforming to IS 15683, finished externally with red enamel paint and fixed to wall with brackets complete with internal charges.
Capacity 4.5 kg
Providing and fixing (ABC Dry Chemical Powder ) type Fire Extinguisher of Capacity 6 kg Confirms to IS 15683, bearing ISI mark complete with brass forged squeeze grip type valve fitted with pressure gauge , pressurize with dry Nitrogen gas filled, with discharge nozzle with wall mounting bracket complete with internal charges.
Capacity 6 Kg.
Providing and fixing angle iron (40 mm x 40 mm x 5 mm) MS door frame 900x2100 door capable of accommodating fire hose reel, landing valve, hose pipes, fittings & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) Cost of fire extinguishers not included in item rate. (Liasioing with civil contractor for making 900x600x2100 Recessed type mansoary box (by civil contractor).
Providing and fixing of TAC approved 1.6mm thick M.S. fire hose cabinet (750x600x250mm) made out of 16 gauge M.S. sheet capable of accommodating landing valve, hose pipes, fittings & accessories. The box shall have a front glass door with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) - for external and roof hydrant.
Providing and fixing of Fire Axe
Providing and fixing brass ball valve with SS 304 Stem and ball, teflon seat complete (PN-16).
Tribeni Constructions Limited
Shree Gautam Construction Co. Ltd.
Tribeni Constructions Limited
Tribeni Constructions Limited
Tribeni Constructions Limited
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.06 MB
BOQ_773967.xls
BOQ • 1.07 MB
Download all tender documents and submit your bid