Executive Engineer JPDCL ED Kathua
Office of the Executive Engineer JPDCL ED Kathua
Creation of 630KVA Sub Station at GMC Kathua on turnkey basis under the jurisdiction of OM Division, Kathua(JPDCL)
2021_PDD_151052_1
KED/36 of 2021-22 Dt.30.11.2021
Open Tender
Electrical Works
Turn-key
10 days
Kathua
Please refer Tender documents.
7 documents required · 7 mandatory
₹100
Executive Engineer JPDCL ED Kathua
Exempted
28 Dec 2021
1 Dec 2021
27 Dec 2021
1 Dec 2021
24 Dec 2021
1 Dec 2021
1 Dec 2021 - 7 Dec 2021
Amount
Creation of 630KVA Sub Station at GMC Kathua on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material:
11/0.433kV, 630 KVA, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Copper wound ), and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
630sqmm 3.5 Core LT XLPE cable
9 Mtr. Long PCC Pole( WL-300Kg)
Cement bottoming 1:2:4 mix as per REC standards 0.5 cum /pole
Transformer plateform of Size (L X B X H) 8' X 8' X 6' as per REC Standard of 1:2:4 mix
11 KV CT/PT unit,oil type(50/5 Amp) along with trivector energy meter with compatible meter box and PVC copper control cables(minimum size 2.5 mm2)
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45KN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps for L.A set/G.O set/Horn Gap
Galvinized Nuts and Bolts.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. ( 3 Nos for Sub Station, 01 no. for CT/PT Unit and 1No. for Distribution Box)
Fabrication,supplying ,testing and commissioning of LT panel (1600(W)X1050(H)X325(D)) made of 2mm thick M S sheet with main frame made of angle iron with provisions for fixing the following: 1. 1 No. incomer MCCB (1000Amp) 2. 2 No MCCB (630 Amp) outgoing 3. Aluminium Bus bar of suitable size for three phases and neutral. The LT distribution panel shall include removable cable gland plates and cable glands suitable for 400 mm2 incomer (double circuit) and outgoing cable fixed at the bottom of the panel. The LT panel should have two doors in the front and the doors should be hintched properly to the frame with locking arrangement. The roof of the distribution panel should be in the form of canopy.
MCCB 3 pole with thermal magnetic release with O/L & S/C protection of rating 1000 Amp,with rated ultimate short circuit breaking capacity 50 KA and rated service short circuit breaking capacity = 75%
MCCB 3 pole with thermal magnetic release with O/L & S/C protection of rating 630 Amp,with rated ultimate short circuit breaking capacity 50 KA and rated service short circuit breaking capacity = 75%
Aluminium Bus bar for 1000 Amp with current density >= 1amp per mm2, (10X100mm) or (2nosX10X50) and neutral bus bar should also be fixed to the LT distribution panel
Erection of Chain Link Mesh fencing of dimension 8'X8'X4' with angle supports and door(complete Job)
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Sundry items like aluminium lugs, Jumpers, binding Tape,
DIVY ELECTRICAL ENGINEERING
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .