| Sl No | Description | Qty | Unit | Pacific Enterprises L2 | RRK PROJECTS L1 |
|---|---|---|---|---|---|
| 1.00 | Taking down old unserviceable split air conditioner of any make/capacity complete incl indoor/outdoor unit with accessories etc complete from the existing wall/surface and depositing to MES E/M store complete all as specified and directed | 39 | Each Job | 2,000 ₹78,000 | 500 ₹19,500 Lowest |
| 2.00 | Taking down of old /unserviceable /faulty submain wiring any size with PVC conduit copper wires complete all as specified and directed | 195 | RM | 20 ₹3,900 | 10 ₹1,950 Lowest |
| 3.00 | Taking down of old/ /unserviceable /faulty sheet metal enclosure with socket plug top and neutral enclosure complete all as specified and directed | 39 | Each | 50 ₹1,950 | 20 ₹780 Lowest |
| 4.00 | Supply, installation, testing and commissioning of hi wall mounting air cooled inverter split type Air conditioner units complete with cordless LCD remote control unit and with turbo cool, stabilizer free operation,energy saver,anti corrosive blue fins for protection in built air ioniser and plasma filter for better indoor air quality with 5 star rating and the out door unit will be fixed in open space with proper foundation or on wall with proper fixing/supporting stand arrangements including 3 mtr suction & discharge refrigerant copper pipe line with high EER complete all as specified and directed (Make BLUE STAR Model no-DNU or techno commercially equivalent model in Voltas/Carrier/Hitachi) of following capacity :- | - | - | - | - |
| 5.00 | 1.5 TR capacity | 20 | Each | 60,000 ₹12,00,000 | 55,000 ₹11,00,000 Lowest |
| 6.00 | 2 TR capacity | 17 | Each | 72,000 ₹12,24,000 | 70,000 ₹11,90,000 Lowest |
| 7.00 | 3 TR capacity | 2 | Each | 90,000 ₹1,80,000 Lowest | 95,000 ₹1,90,000 |
| 8.00 | M&L for sub main wiring with 4.00 Sqmm nominal cross sectional area, two single core, 1100 volts grade, multi-stranded, PVC insulated, unsheathed, FRLSH copper conductor cable with and including continuous earth wire of size 4 Sqmm nominal cross sectional area, single core, 1100 volts grade, multi-stranded, PVC insulated, unsheathed, FRLSH copper conductor cable drawing into and including rigid non-metallic PVC concealed conduit 25mm dia, medium grade with all conduit accessories and connected to common earth dolly with suitable copper lugs including all cutting / chases etc in stone/ brick masonary/ walls and making good to the disturbed surfaces to match the existing complete all specified & directed.
(Note : One run of earth continuity conductor, one run of PVC Conduit and two runs of copper conductor shall be together taken as one length for measuring unit length) | 175 | RM | 430 ₹75,250 | 270 ₹47,250 Lowest |
| 9.00 | All as per item No 8.00 but for 2 x 6.0 Sqmm for phase & neutral and 1 x 6.0 Sqmm for continuous earth wire in 20 mm PVC conduit complete all specified & directed. | 20 | RM | 550 ₹11,000 | 380 ₹7,600 Lowest |
| 10.00 | S&F sheet metal enclosure with socket plug top and neutral enclosure with a two pin and earh plug and socket complete with one SPN MCB 20 Amps 'C' curve type, complete all as specified and directed | 39 | Each | 1,200 ₹46,800 Lowest | 1,500 ₹58,500 |
Tender Value
Refer Docs
EMD Value
₹80,591
Closing Date
9 Mar 2026, 6:00 pmClosed
GE (AF) BANGALORE
GE (AF) BANGALORE, HQ TC AIR FORCE , BANGALORE - 560006
SPL REPAIRS TO VARIOUS COOLING/HEATING APPLIANCES AGAINST BER AND PROVN OF SMOKE DETECTOR, FIRE ALARM AND MISC AT EDP SECTION AT CHAFB
2026_MES_752942_1
8454/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) BANGALORE
AS PER NIT
5 documents required · 5 mandatory
₹500
GE (AF) BANGALORE
₹80,591
6 Apr 2026
16 Feb 2026
11 Mar 2026
16 Feb 2026
9 Mar 2026
2 Mar 2026
17 Feb 2026 - 24 Feb 2026
Taking down old unserviceable split air conditioner of any make/capacity complete incl indoor/outdoor unit with accessories etc complete from the existing wall/surface and depositing to MES E/M store complete all as specified and directed
Taking down of old /unserviceable /faulty submain wiring any size with PVC conduit copper wires complete all as specified and directed
Taking down of old/ /unserviceable /faulty sheet metal enclosure with socket plug top and neutral enclosure complete all as specified and directed
Supply, installation, testing and commissioning of hi wall mounting air cooled inverter split type Air conditioner units complete with cordless LCD remote control unit and with turbo cool, stabilizer free operation,energy saver,anti corrosive blue fins for protection in built air ioniser and plasma filter for better indoor air quality with 5 star rating and the out door unit will be fixed in open space with proper foundation or on wall with proper fixing/supporting stand arrangements including 3 mtr suction & discharge refrigerant copper pipe line with high EER complete all as specified and directed (Make BLUE STAR Model no-DNU or techno commercially equivalent model in Voltas/Carrier/Hitachi) of following capacity :-
1.5 TR capacity
2 TR capacity
3 TR capacity
M&L for sub main wiring with 4.00 Sqmm nominal cross sectional area, two single core, 1100 volts grade, multi-stranded, PVC insulated, unsheathed, FRLSH copper conductor cable with and including continuous earth wire of size 4 Sqmm nominal cross sectional area, single core, 1100 volts grade, multi-stranded, PVC insulated, unsheathed, FRLSH copper conductor cable drawing into and including rigid non-metallic PVC concealed conduit 25mm dia, medium grade with all conduit accessories and connected to common earth dolly with suitable copper lugs including all cutting / chases etc in stone/ brick masonary/ walls and making good to the disturbed surfaces to match the existing complete all specified & directed. (Note : One run of earth continuity conductor, one run of PVC Conduit and two runs of copper conductor shall be together taken as one length for measuring unit length)
All as per item No 8.00 but for 2 x 6.0 Sqmm for phase & neutral and 1 x 6.0 Sqmm for continuous earth wire in 20 mm PVC conduit complete all specified & directed.
S&F sheet metal enclosure with socket plug top and neutral enclosure with a two pin and earh plug and socket complete with one SPN MCB 20 Amps 'C' curve type, complete all as specified and directed
M&L for cutting of existing stone masonry wall for crossing the suction, discharge pipe line and electric line connection of split type Air conditioner and after the connection necessary cement work will be provided for making the surface as good complete all as specified and directed.
S&F Copper tubing for refrigerant suction line of split AC of size 19.05 mm drawn through pipes/ fixed to walls/ laid on floor or roof in all respects, complete all as specified and directed
S&F Copper tubing for refrigerant suction line of split AC of size 9.5 mm drawn through pipes/ fixed to walls/ laid on floor or roof in all respects, complete all as specified and directed
S&F Heat insulation superior quality nitrile rubber of 9 mm thickness, ISI marked for copper tubing of any size of refrigerant line including necessary clamps, PVC tape knots etc complete all as specified and directed
S&F AC drain hose outlet PVC pipe of standard size 20 mm complete all as specified and directed.
S&F PVC insulated FRLSH copper conductor control cables of size 2.5 sq mm 5 core for outdoor to indoor unit connection for split AC complete all as specified and directed
S&F GI bracket of suitable size for outdoor unit of air conditioning complete all as specified and directed
Disconnection and taking down old/faulty geyser of any capacity after disconnecting the wire, nut bolts etc from existing location / wall and depositing to MES Store complete all as specified and directed
S&F water heater storage type (Geyser), capacity 25 litres, 230 volt, AC, BEE 5 star rated, including all accessories complete, geyser to be fixed on wall with suitable size of nut/ bolt / heavy fasteners and washers incl making good the disturbed surfaces of wall and making necessary cold and hot water pipe connection with suitable 02 Nos heavy duty connection pipe of SS rope threaded type with brass unions at both ends, 45 cm long, 15mm bore complete including electric connection complete all as specified and directed. (Make - Havells Model Monza Nu or techno commercially equivalent in Racold / V Guard / Venus)
S&F water heater storage type (Geyser), capacity 50 litres, 230 volt, AC, BEE 5 star rated, including all accessories complete, geyser to be fixed on wall with suitable size of nut/ bolt / heavy fasteners and washers incl making good the disturbed surfaces of wall and making necessary cold and hot water pipe connection with suitable 02 Nos heavy duty connection pipe of SS rope threaded type with brass unions at both ends, 45 cm long, 15mm bore complete including electric connection complete all as specified and directed. (Make - Havells Model Monza Nu or techno commercially equivalent in Racold / V Guard / Venus)
Supply, Installation, testing and commissioning of Microprocessor based 1 loop, net workable, analogue addressable type fire alarm control panel with LCD display. The loop capacity shall be able to take 50 analogue addressable devices in one loop. The fire alarm panel shall have sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilations fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 220 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 14 hours normal working and then be capable of operating the sytem for 2 hours during an emergency condition as required complete all as specified and directed.
Supply, installation, testing and commissioning of Fire detectors complying with and type certified to EN 45 addressable type multisensor detector with heat and smoke combination photoelectric / optical base with self built intelligence as per IS:2175 complete all as specified and directed.
S&F Fault Isolator Modules for isolating shorted, dewired & loose circuit fault isolators with automatic resetting arrangement complete all as specified and directed.
S&F Sounder complete with Sounder Relay Modules of capacity 90 DB output at 1 meter distance; strobe lights with 110 cd. The strobes shall be synchorized for better evacuation as per specification complete as required duly UL listed including sound relay module complete all as specified & directed
S&F Addressable Control Relay Module for AHU as required as per specification complete all as specified and directed.
S&F Addressable Manual call point/pull station single action type with gold plated SPST contacts, complete as required and as per specifications complete all as specified and directed.
Supply and laying of 2 Core x 1.5 Sqmm Twisted Copper FRLS Armoured Cable fixed concealed in medium duty PVC Conduit on the wall of the building structure complete with termination and testing as per requirement complete all as specified and directed.
Supply, installation, testing and commissioning of Response Indicator (RI) complete all as specified and directed.
Supply, installation, testing and commissioning of UPS of capacity 1 KVA with batteries& all accessories to maintain reliability of supply system to fire alarm complete all as specified & directed.
M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised iron wire 4 mm dia by means of bolts, nuts and washers of galvanised iron or steel connected to transformer, DG set, LT panel / DB/ earthing test point including PCC chamber, RCC cover 50mm thick with 8 mm dia bars, protection pipe, watering pipe 20 mm GI, funnel etc including excavation, earth work, disposal of surplus soil and earth strip protection pipe of GI 15 mm bore light grade upto 7.5 metre including testing on complete all as specified and directed. Note :- The rate shall be deemed to be inclusive of the cost of earth work, excavation on any type soil and removal of surplus soil to a distance of 50 m, earth lead protection GI pipe medium grade of mentioned size from earth plate electrode to main switch & GI wire of 4 mm dia length up to 7.50 m including taking down of old unserviceable exisitng earthing .
M&L for Point wiring complete with 1100 volts grade single core, PVC insulated FRLS cable with multi-stranded copper conductor of size 4.00 sq mm nominal area, passing through heavy grade PVC casing and capping of suitable size, with all necessary fittings on wall/ roof surfaces, duly earthed with one run of single core PVC insulated FRLS cable with multi stranded copper conductor of size 4.00 sqmm for earthing wire connected to common earth dolly including 1.6 mm thick fabricated CI/MS sheet terminal box concealed mounting in the wall , covered with 3 mm thick electroplated bakelite sheet top cover for housing 15 A switches & sockets for One switch socket point 15 Amps controlled by one switch complete all as specified and as directed
Supply and laying of 25 mm Steel rigid Conduit for surface area including Bends, Junction boxes, coupling Base, saddles screws etc complete all as specified and directed
M&L for Removing and refixing of any type of false ceiling,roof cutting including all necessary items and civil works complete all as specified and directed.
Supply, installation, testing and commissioning of Repeater Fire Alarm Panel, Active Repeater, Silence, Mute, Reset, Accept, Evacuate and Test Controls, DX control panels require 24 Vdc supply, ZX control panels require 24 V, DC supply and an RS485 card of size 165 x 254 x 50mm (H x W x D) complete all as specified and directed.
Supply, installation and testing of Beam Master detector with transmitter and receiver Bayblend FR110 Trim, Lexan Lens Cover, Noryl Blackbox, 1.77kg, 2mA @ 24 V, DC, 200 x 230 mm reflector complete all as specified and directed
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.22 MB
Tender_8454.pdf
Tender Documents • 0.45 MB
BOQ_843336.xls
BOQ • 0.87 MB
SOC_8454.pdf
Additional Documents • 0.01 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .