TECHNICAL
15 conditions · 4 needing a document upload
Clause Regarding GST: (a) All the Bidders/tenderers should ensure that they are GST Compliant and their quoted tax Structure are as per GST LAW.(b) Tenderer Should Furnish their GSTIN numbers representing the States in Which they are registered GST, along with address of Registered Office.(c)The Contract is under GST Act and rules as applicable time to time.
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. Annual Contractual Turnover Data for the Previous 3/4 Years should be submitted as per Annexure-IX.(Annexure- VIB of Tender Documents)
40 conditions · 11 needing a document upload
Check List: The tenderer(s) would fill up the check list, as per Annexure-XXIII to ensure that they are submitting the complete tender offer.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Provision and augmentation of 750 Volt Supply arrangement for maintenance of HOG coaches in washing/sick lines at DBRG Coaching depot.
LV-T-14-TSK-921-R-1
LV-T-14-TSK-921-R-1
Open
Works - General
12 Months
Tinsukia, Assam
₹0
₹1.9 L
20 Apr 2026
27 Mar 2026
6 Apr 2026
45 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 92,47,546.92 | ||
| — | 1.00 | — | — | ||
| Supply, installation, testing & Commissioning of Step Down Transformer, Copper Wound, 11/0.750KV, Capacity: 800KVA, 50 C/s, Naturally Cooled(ONAN),Vector Group Dyn11,BIS- Level-II, first filling of Transformer oil as per IS 335 and with all standard accessories . The stardard accesories includes: Name and Diagram Plate, 2 Nos of Lifting Lugs, Oil filling hole with lug, Radiator, Conservator tank, 2 Nos of earthing terminal,Drain Valve, Silica Gel Beather, Arching Horn, Air- release plug. Detaild Techical specification attached.Current density should not exceeding 2.4 A/sq.mm under all operating conditions. | — | — | — | 20,60,000 | |
| — | 1.00 | — | — | ||
| "Supply, fitting, fixing, testing and commissioning of of Outdoor type LT cubical panel board having shed cover above panel. The panel shall be metal-enclosed, free-standing compartmentalized, modular type suitable for outdoor installation. The panel shall be dust and vermin proof and the enclosure shall provide a degree of protection of not less than IP-65. Panel shall be fabricated out of 14 SWG cold rolled steel plates & properly supported using angles & channels. The whole panel shall be mounted on a base frame made out of suitable structural, preferably ISMC Channels. Joints of any kind in sheet shall be seam welded, all welding slag grounded off and welding pitwiped smooth with plumber metal. All panels and covers shall be properly fitted and square with the frames and holes in the panel correctly positioned. The Panel shall be fully compartmentalised with front and back opening doors.. When compartment door is opened, busbar and cable alley shall be shrouded by barrier plates. All panels shall be provided with suitable cable alley and vertical bus bar alley.Each cable chamber shall have cable entry from bottom and suitable removable gland plates shall be provided for this purpose. The cable chamber shall be provided with suitable supporting arrangement between the gland plate and terminals, in the middle. The cable chamber shall have a minimum width of 300 mm depending upon the outgoing cables. Each chamber shall be provided with a hinged type door opening away from the cable alley and shall be provided with black flowertype thumb screw which shall ensure tight closing. The edges of the door shall be provided with a neoprene rubber gasket to make the compartment dust proof.. The panel shall consists of the following Switchgears: Incoming: (i) MCCB, 4 pole, 1250 Amps(Micoprocessor Release range 500-1250 A), 50 KA Breaking capacity,suitable for 750V AC operating voltage= 1 Nos as Incomer. (ii) Aluminium Busbar ,1200A, TPN for 750V AC Outgoing: (i) MCCB, 4 pole, 500Amps(Micoprocessor Release range 320-800A), 70KA Breaking capacity,suitable for 750V AC operating voltage= 4 Nos (ii) Digital Voltmeter LED indication with inbuilt selector switch (0-1000 V)= 5 Nos (iii) Digital Ammeter LED indication with inbuilt selector switch (40-400 Amps)=8 Nos( 2 Nos of Main incomig of ACB and 6 Nos for outgoing of MCCB)" | — | — | — | 7,02,625 | |
| — | 1.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of of Outdoor type LT cubical panel board having shed cover above panel. The panel shall be metal-enclosed, free-standing compartmentalized, modular type suitable for outdoor installation. The panel shall be dust and vermin proof and the enclosure shall provide a degree of protection of not less than IP-65. Panel shall be fabricated out of 14 SWG cold rolled steel plates & properly supported using angles & channels. The whole panel shall be mounted on a base frame made out of suitable structural, preferably ISMC Channels. Joints of any kind in sheet shall be seam welded, all welding slag grounded off and welding pitwiped smooth with plumber metal. All panels and covers shall be properly fitted and square with the frames and holes in the panel correctly positioned. The Panel shall be front and back opening doors.When compartment door is opened, busbar and cable alley shall be shrouded by barrier plates. All panels shall be provided with suitable cable alley and vertical bus bar alley.Each cable chamber shall have cable entry from bottom and suitable removable gland plates shall be provided for this purpose. The cable chamber shall be provided with suitable supporting arrangement between the gland plate and terminals, in the middle. The cable chamber shall have a minimum width of 300 mm depending upon the outgoing cables. Each chamber shall be provided with a hinged type door opening away from the cable alley and shall be provided with black flowertype thumb screw which shall ensure tight closing. The edges of the door shall be provided with a neoprene rubber gasket to make the compartment dust proof.. The panel shall consists of the following Switchgears: Incoming: (i) Air Ciuruit Breaker, Mechanical Drawout type, 1250 Amps, 4 Pole,50KA,Icu=Ics=Icw,LSIG Protection,Fault Indication, Microprocessor based trip unit operating voltage: 750V AC= 1 Nos with interlocking arrangement provision. | — | — | — | 3,71,426 | |
| — | 6.00 | — | — | ||
| "Supply, installation, testing & commissioning of outdoor type feeder pillar LT panel Board, having TPN copper Busbar 1000A, Free standing with provision of Danger Board and shed cover above the panel with the following Switchgears. The panel Shall be manufactured using 16SWG CRCA steel sheet epoxy powder coated with protection IP 65. The Interconnection of the panel shall be be done using suitable size copper cables. (i) 500 A 4 Pole 16KA MCCB with O/L S/C thermal magnetic release for operating voltage 750V =1 No (ii) 500A MCCB Spreader= 1 No (iii) R,Y,B Indication Lamp=3Nos (iv) 2A SP 10KA MCB=3 Nos (v) 3 phase power plug socket 400 Amps, 750 volt suitable for LHB coaches or as per RDSO spec No.RDSO/PE/SPEC/D/AC/0177(Rev.0)-2013 for supplying 3 phase 750 volt power to LHB coaches=1 set" | — | — | — | 21,53,112 | |
| — | 750.00 | — | — | ||
| Supply, connection, testing and commissioning of L T XLPE Insulated aluminium armoured cable 1.1KV Grade, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor/Solid Aluminium Conductor cable having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988 o f size: 630 SQ MM Single Core. Cable laying by excavation of earth depth 0.75 Mtrs. into breadth 0.508 Mtrs. below the ground level and a layer of course sand of 7.5 CM thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of course sand of 7.5 CM thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. Above the Layer of Course Sand 3 inch Size Brick is to be provided for protection of cable. Cable route markers to be provided at an interval not less than 50 Mtrs. All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024. | — | — | — | 9,61,500 | |
| — | Breakup | for details. | — | ||
| Supply, connection, testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor/Solid Aluminium Conductor cable having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988 . Cable laying by excavation of earth depth 0.75 Mtrs. into breadth 0.508 Mtrs. below the ground level and a layer of course sand of 7.5 CM thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of course sand of 7.5 CM thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. Above the Layer of Course Sand 3 inch Size Brick is to be provided for protection of cable. Cable route markers to be provided at an interval not less than 50 Mtrs. All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024. | — | — | — | 15,31,200 | |
| — | 160.00 | — | — | ||
| Boring of 2.6 mtr. underneth Road/Railway track and laying of 150 mm dia HDPE pipe PN 8 for passing underground cable using HDD machine Boring. Supply of the HDPE pipe is included in the scope of this work.The work to be executed as per direction of Engineer Incharge at site.(2 Nos of Boring 80Mtrs Each) | — | — | — | 5,69,600 | |
| — | 300.00 | — | — | ||
| Supplying and laying of size 120 mm dia (OD-120 mm & ID-103 mm nominal) DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. | — | — | — | 1,10,400 | |
| — | 4.00 | — | — | ||
| Supply, fitting, fixing of 400 Amps outdoor type cable junction box, angle frame mounted, dust & vermin proof, complete with rain cap, aluminium basbar of suitable size for TPN, 400 Amps, 750 V made out of 16 SWG CRCA sheet duly painted, Cable Junction Box Size: (lxbxh=450x 450x600 mm). The base of the fedder pillar junction box to be provided with CC foundation of propotion 1:1.5:3( cement, sang,Chips) after connection of Ug cables. | — | — | — | 36,688 | |
| — | 12.00 | — | — | ||
| Construction of CC work for outdoor type panel foundation of transformer in Concrete 1:1.5:3 (1 cement : 1.5 sand : 3 graded stone aggregate 20mm nominal size: 2.0x3.0x1.0=6 CUM=2 Nos. Total CUM=12 CUM | — | — | — | 1,12,152 | |
| — | 24.00 | — | — | ||
| Earthwork in filling in embankment, guide bunds, around buried type abutments, bridge gaps, trolley refuges, platforms etc. with contractor's own earth conforming t o Soil Quality Class SQ1 after preparation o f foundations a s applicable, benching in existing banks wherever required, spreading in layers with motor grader, bringing the moisture content t o OMC, mechanical compaction to specified density and dressing of bank to final profile as p e r RDSO Specifications: RDSO/2020/GE: IRS-0004 with latest correction slips. | — | — | — | 9,397.92 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of Polymeric 11 KV, 3 phase GO DO Switch,400 Amps complete with operating handle & one set spare bare fuse . | — | — | — | 36,594 | |
| — | 2.00 | — | — | ||
| Supply, fitting, fixing of 11 KV LA set 9 KV (RMS) , discharge capacity 10 KA | — | — | — | 5,934 | |
| — | 10.00 | — | — | ||
| Supply, digging & erection of GI tubular pole 11 Mtr. long SP 53(Pole Dia : Base-165.1 mm, Middle-139.7 mm, Top- 114.3 mm), Thickness: Base-5.4 mm, Middle-4.5 mm, Top-3.65mm, weight of pole : 194 KG approx) . Supply of foundation materials & erection of pole in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required & as per advice of Supervisor Incharge at site., | — | — | — | 3,73,290 | |
| — | Breakup | for details. | — | ||
| Supply, fitting, fixing of GI channel size 110x50x6 mm including clamp size 50x6 mm | — | — | — | 30,152 | |
| — | Breakup | for details. | — | ||
| Supply , fitting , fixing of GI angle size 50x50x6 mm with drilling of holes and necessary Clamps and brackets of the following size: | — | — | — | 10,576 | |
| — | 500.00 | — | — | ||
| Supply , drawing, strengthening and stringing of ACSR conductor 6/1/3.35(Rabit)) in H T lines with laying conductor on ground, lifting on poles, tensioning with tension clamps, binding on insulator, jumpering with P.G. clamp including supply & fittings of tension clamps, nuts & bolts with standard sagging in each and every span. | — | — | — | 18,500 | |
| — | 12.00 | — | — | ||
| Supply, fitting, fixing of polymeric type 11 KV disc insulator, 70KN with hardware fitting. | — | — | — | 8,904 | |
| — | 18.00 | — | — | ||
| Supply & fitting, fixing & binding of 11 KV Polymeric Pin insulator 5KN, complete with large steel head GI pin, nut , washer etc. as required. | — | — | — | 6,228 | |
| — | 100.00 | — | — | ||
| Supply, drawing, straining & binding of GI guard wire on pole structure by GI bearer wire of 6 SWG & 8 SWG cross wire(1 route length consist of 2 mtrs. 6 SWG & 1 mtr.8 SWG GI wire). | — | — | — | 2,000 | |
| — | 16.00 | — | — | ||
| Erection of earth by 50 mm dia 3 Mtrs. long (3.6 mm thickness) GI pipe , GI Strip 32x6mm-5 Mtrs long for connection,GI nuts, bolts including masonry materials for earthing pit, salt, charcoal etc. and construction of earth pit covered with RCC cover slab 12.7 mm thickness and watering pipe per Drawing No PCEE/ELG/DRG/2024/1 Dtd 30.09.2024 | — | — | — | 84,288 | |
| — | 1.00 | — | — | ||
| Supply of All-in One Computer, Processor: 12th Gen Intel Core™ i5-1235U (up to 4.4 GHz with Intel Turbo Boost Technology, 12 MB L3 cache, 10 cores, 12 threads, OS: Windows 11 Home, Graphics: Intel Iris Xe graphics, Memory: 8 GB RAM DDR4 3200MHz, Storage: 512 GB M.2, Pcle NVMe, SSD(Solid State Drive), Wireless Keyboard & Mouse,Display@58<46@5 cm (23.8 inch) diagonal, FHD (1920 x 1080), VA, three-sided micro-edge, anti-glare . For Use of Data Monitoring at DBRG Coaching Depot. | — | — | — | 52,980 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
AnexxuresSectionVIINew.pdf
ATTACHMENT
techspecificationtransformer.pdf Technical Spec of Transformer
ATTACHMENT
Tender Document
ATTACHMENT
GCCACS11.pdf
ATTACHMENT
techspecificationtransformer.pdf
ATTACHMENT
TenderDocumentTSK-921-R-1.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .