Executive Engineer Jal Shakti Divn Haroli
Executive Engineer Jal Shakti Divn Haroli
( SH Laying, Jointing and testing of GMS Pipe 80 mm dia (Medium Class) in Rising Main Supply and Errection of centrifugal Pumping Machinery ).
2024_HPIPH_94489_1
No. JSV/ Haroli/ TA/ tender/24- 4602-25 dt 18-10-24
Open Tender
Civil Works
Item Rate
90 days
WSS Badhera
as per NIT
11 documents required · 11 mandatory
₹400
Yes
Executive Engineer Jal Shakti Divn Haroli
₹34,755
Yes
5 Dec 2024
19 Oct 2024
30 Oct 2024
19 Oct 2024
29 Oct 2024
19 Oct 2024
19 Oct 2024 - 29 Oct 2024
Amount
Demolition below G.L upto 1.50 Meters depth and disposal of unserviceable materials within 20 metres lead in un-reinforced cement concrete up to 15 cm thickness and to the entire satisfaction of Engineer-in-Charge.
Providing and laying cement concrete 1:3:6 (1 cement: 3 sand: 6 graded stone aggregate 20 mm nominal size) and curing complete excluding cost of form work in Foundation and Plinth
Excavation in foundation and trenches etc.(in pipes and pits) in all kinds of soils such as pick work, jumper work, blasting in soft / hard rock, chiselling / wedging out of rock / where blasting prohibited) saturated soil stacking the excavated soil as directed by the Engineer-in-charge clear from the edge of excavation and then returning the stacked soil in 15 cm layers when required into plinth sides of foundation etc. consolidating each deposited layer by ramming and watering and then disposing of all surplus excavated earth as directed by the Engineer –in-charge in all leads and lifts.
Laying, jointing and testing in trenches Galvanized mild steel flanged/butt welded pipes below mentioned dia and grade conforming to IS:1239-2004 (with latest amendments). The MS Flanges are to be provided for 5% of total joints as per table below conforming to IS:6392-1971 (latest upto date amendments) and welding of MS flanges with pipe as per IS: 816-1969 with electrodes as per IS:814-1991 including required number and size of MS nuts and bolts as per IS 1369-1967 and compressed asbestos fibre jointing gaskets sheet not less than 3.00mm in thickness as per IS:27121-1965. The welding of flanges to be done on both faces in three layers in each face to make the joints leak proof including all kind of specials such as bends of all degrees to be made from parent tube, short pieces, tail pieces all made from parent tube and to the entire satisfaction of the Engineer-in-Charge. The pipes end should be bevelled suitable for butt welding. the circumferencial butt welded joints (95% of the total joints) by electrical arc welding to following dia & class pipes, welding of pipes to be done in three layers to make joints leak proof and to achieve the minimum effective throat thickness of welded conforming to IS 816-1969 specifications, by using welding electrode of 2.5mm to 6.3 mm of Advani oerlikon (Adore)-CITOJET/ESAB make conforming to IS 814-1991, at site of work complete in all respect .The laying of Pipes conform to IS 5822 (with latest ammendentments upto date) including all kind of specials such as bends of all degrees to made from parent tube, short pieces, tail pieces all amde from parent tube within all leads and lifts (Earth work in trenches, MS flanges and butt welded joints to be measured and paid for seperately)
80mm dia.(Medium grade)
Providing and welding M.S. flanges @ 5% of joints, conforming to following tables as per IS 6392-1971 (Latest with upto date amendments) with plain end GMS/MSERW pipe in requsite number of layers on both faces to make the joint leak proof (The cost of providing and laying of GMS/MSERW pipes to be measured and paid for seprately). The welding of flanges should conform to IS:816-1969 with electrodes as per IS: 814-1991 and required number of nuts and bolts conforming to IS 1364. including cost of gasket sheet nuts & bolts. The thickness of gasket sheet not less then 3.00mm conforming to IS 2712-1998. The work shall be done to the entire satifaction of engineer in charge with in all leads and lifts.
(80 mm dia T-17)
(80 mm dia T-5)
Providing circumferential butt welded joints @ 95% by electrical arc welding to GMS pipe, welded in requisite number of weld runs so as to achieve the minimum effective throat thickness of weld conforming to IS 816-1969 specifications, by using welding electrodes of 2.5mm to 6.3mm of Advani Oerilikon (Adore)-CITOJET/ES/ESAB make,conforming to IS 814-1991, include Die pentration test,at site of work complete in all respects, including manual/mechanical handling of pipes in all leads and lifts to the entire satisfaction of Engineer-in-Charge. 80 mm dia
Providing horizontal spindle, horizontal / radial split casing /end suction ( back pull out arrange-ment) Single /double /multi stage of Kirloskar / KSB Crupton KSB/Calama/BS/ Groundfos/ Hindustan/ Lubbi make as per BIS IS 1520-1980 with upto date ammendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron / cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitable for operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900 RPM.The power of electric motor/ motors should be at least +10% in excess of the maximum power required by the pump / pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325 IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements. (a) Pump :- Specifications i) Make ii) Model iii) No. of stages iv) Manfacurer's certificate to be attached. performance i) Discharge ii) head Make ii) Model iii) efficiency of pump a) duty Head b) (+) 10% duty head c). (-) 15% Duty Head d) performance curve to be attached b). Motors:- Specificions Make ii) Model iii) Rating iv). speed v) Insulation (C) Coupling (D) Base plate
Discharge (Q) = 5.95LPS.
Total Head (H) = 97.47 Mtrs.
a)LWL In Sump well = 109.74 mtr
b)R.L. of shaft = 109.75 Mtrs.
c)R.L. of discharge Pt. = 117.50 Mtrs.
d)Suction lift. +ve mtrs.
e)Discharge Head = 0.00 Mtrs.
f) Static Head = 7.75 Mtrs.
Rising main.
Length = 2310 Mtrs.
Diameter = 80mm. dia
Class GMS Tube(M)
Pumping hours. = 8 Hours.
Altitude of installations above M.S.L =500 mtrs.
Characteristic of Water
a)Temperature 20 Deg.Col.
b)Turbidity ________ JTU
c)Alloanity _________ mg/1 ca Co3
d)Size of solids __________ mm
e) Others.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 63 amp.
Providing MS Sheet, steel fabricated floor mounted closed (Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 Gauge comprising and capable of mounting the following acccessories with all internal connections.
ELCB of recommended make L&T / Havells make as per IS: 2516-1985 with upto date ammendments, and of suitable range which should have control box, operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. i) Make : ii) Type : iii) up to 63 Amp
iv )The voltage monitor Relay three Phase with all protection and usual indicator and electric siren against single phasing, low vaoltage, high voltage reverse phasing, overloading and phase voltage difference as per IS 3842 ( Latest Edition). i) Make : ii) Type : iii) Range:0-500
Power factor meter of standard make as per relevent IS code with upto date ammendments.i) Make : ii) Type : iii) Range: 0-500
Frequency meter of standard make as per relevent IS code with upto date ammendments..i) Make : ii) Type : iii) Range: 0-500
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three line phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments including.i) Make : ii) Type : iii) Rating
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 (P-I&II) with upto date ammendments. i) Make : ii) Type : iii) Capacity
Capacitor of BHEL / L&T make as per IS : 2834-1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevant ISI code (of Seimens / Clocter / IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date ammendments, Rating of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range 6 KVR
Providing suitable Starter of L&T / Havell's / BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag under voltage release, with or without 'initial oil filling as the case may be with single Phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. i) Type ii) Make
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 80 mm dia for the delivery line of the 80 mm dia for Suction line of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.0 (80mm dia sluice valve)
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 65 mm dia for the delivery line of the 65 mm dia for delivery line of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.0 (65 mm dia sluice valve)
Providing and fixing of Cast iron double flanged Swing type reflux valve of kirloskar/Leader / Kartar/Kilburn /BHEL /LP/RG Brand make IS 5312 Part 1 of 80 mm dia having by pass arrangement for the rising main of pump and capable of with standing the normal seat pressure as per BIS i)Make ii)Class PN 1.0 iii)Seat pressure(MPa) iv)Material Cast iron 80 mm dia
Providing 80 mm dia circular dial pressure gauge of Precision / Fiebig make complete with all accessories such as stop cock, Copper tubing etc. as per IS: 3624-1987 with upto date ammendments. i) Make : Range.
Installation of all above items appearing above as per the systematic drawing attached with the documents or as per the direction of Engineer-in-Charge. .`
Fixing double flanged GMS piping work ( Layout to be approved by Engineer-in-Charge). for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends, Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No.5.( GMS PIpe shall be issued by the department free of cost from Divisional store Samnal. The size of various components to be as under:-
i) Suction Pipe GMS Pipe 80 mm dia. (M)
ii) Delivery Pipe GMS 65 mm dia. (M)
and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 80 mm dia to be joined.
Providing and laying copper PVC Insulated 3 core armoured power cable (One cable carrying all the three phases) of suitable size and capacity to Motors and all other elelctrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Seimen / Gloster / IEC / ICC / EICO / National / Grandlay / finolex / Havell make ' including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable (A) Motor side (From Switch to Starter & Starter to motor) i) Size 6.00 mm2 ii) Make iii) Type - Armounred power cable iv) Capacity v) Core 3 (B) Supply Side (From meter of HPSEB to Bus Bar & Switch) i) Size 10.00 mm2 ii) Make iii)Type - Armounred power cable iv) Capacity v) Core 3
Providing and fixing double loop earthing with GI flat of suitable thickness electrode complete with material such as thimble, Nuts & Bolts, charcoal and common salt as per IS 3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the direction of the Engineer-in-Charge..i) GI wire 8 SWG up to 15 HP
Madan Lal Govt Contractor (BID ID -445924)
PANKAJ GOVT. CONTRACTOR (BID ID -445988)
HARBANS SINGH (BID ID -446065)
Asha Enterprises (BID ID -446000)
KESAR SINGH (BID ID -445975)
Om Parkash Govt Contrator (BID ID -446040)
HARDYAL SINGH GOVT. CONTRACTOR (BID ID -446046)
Narinder Kumar (BID ID -446081)
Harvinder Singh Maan (BID ID -446080)
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .