Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹6.0 L
EMD Value
₹6,500
Closing Date
11 Oct 2021, 6:00 pmClosed
SE EDC SAMBHAL
132 KV COMPOUND HYDEL COLONY CHANDAUSI
Change of damage wire of 11 KV Line in Town Sambhal and Installation of 250 KVA Transformers for Increasing Capacity 100 KVA to 250 KVA Transformer Under Electricity Distribution Division, Sambhal
2021_PVVNL_622692_2
28/2021-22/EDC SAMBHAL
Open Tender
Civil Works - Others
Lump-sum
30 days
CHANDAUSI
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
SE EDC SAMBHAL
₹6,500
Yes
13 Oct 2021
5 Oct 2021
12 Oct 2021
5 Oct 2021
11 Oct 2021
5 Oct 2021
Amount
Safe carriage of the following material from Store Centre JE's store to work site including loading and unloading at both ends.
13 Mtr./11 Mtr./9 Mtr./8.5 Mtr. Long PCC/ST Poles.
LT ABC Cable (3 x 120 + 1 x 95 + 1 x 16), (3 x 50 + 1 x 95 + 1 x 16), (3 x 95 + 1 x 70 + 1 x 16) Sq. mm
ACSR Dog Conductor
11/0.4 KV 250 KVA Transformers.
Line material such as Stone Pad, Earthing Complete, Piercing Clamp, Suspention Clamp with I Huk, Distribution Box Single & Three Phase with Clamp etc.
Constructed for LT Line, Single support 13/11/9/8.5 Mtr. long ST/PCC Poles Excavation of foundation pit in size of 75x45 cm. having depth of 1/6th of the full length of the support (pole), providing and laying of stone pad (300x300x75mm.) in the bottom of the pit. Erection of support (pole) complete with fixing all other accessories by providing nuts & bolts etc. as per RESPO Norms.
Single support LT lines Excavation of foundation pit in size of 75x45 cm. between long Spans having depth of 1/6th of the full length of the support (pole), Erection of support (pole) complete with fixing all other accessories by providing nuts & bolts etc. as per RESPO Norms.
Earthing of support with MS Earth Rod of (20x2500)mm. long including excavation of pit and driving MS Rod 3.0 M apart from support and 0.5M below the ground level and connecting below the earth electrodes with the help of G.I. Wire No.6 SWG tightening with nuts and bolts.
Removing of LT lines old/damage LT ABC Cable (3 x 120 + 1 x 95 + 1 x 16), (3 x 95 + 1 x 70 + 1 x 16) Sq mm and ACSR Dog Conductor & making bundle and stacking at a safe place, including loading and unloading at both ends
Removing of 11/0.4 KV 100 KVA Transformer from work site including loading and stacking at a safe place, including loading and unloading at both ends
Making of wire maseh fencing of size 2 x 2 x 1.5 mm for 250 KVA Transformer with plinth all accessories as per RESPO Norms.
Earthing of Water Lever Neutral and body with G.I. Pipe High Quality for 250 KVA Transformer
Mounting and fixing of 250 KVA transformer on plinth including making proper connections.
Laying, sagging, stringing and binding of ACSR Dog Conductor with all other accessories on pole as per RESPO Norms.
Laying, sagging, stringing and binding of LT ABC Cable (3 x 120 + 1 x 95 + 1 x 16), (3 x 50 + 1 x 95 + 1 x 16), (3 x 95 + 1 x 70 + 1 x 16) Sq. mm with all other accessories on pole as per RESPO Norms.
Making All HT/LT Connections and releasing of proper supply
NAVITECH ENGINEERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .