| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Lump sum price worked out by the contrator for the work as listed against Sch "A" part I (Internal Electrification Works) | 1 | Lump Sum | - | - |
| 2 | Lump sum price worked out by the contrator for the work as listed against Sch "A" part II (External Electrification Works) | 1 | Lump Sum | - | - |
| 3 | Sch "A" PART III (MISC ITEMS OF B/R AND E/M ITEMS)
Excavation for cable trenches in soft soil, depth upto 1.5 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand after laying of cable in layers of 20 cm, ramming, watering and disposal of surplus excavated soil complete all as specified and as directed. | 400 | Cum | - | - |
| 4 | Automatic intelligent Power Factor Correction (APFC) System:-
Supply, Installation, testing and commissioning of 200 KVAR Automatic Power Factor Correction (APFC) panel, out door type floor mounted free standing totally enclosed, extendable, IP 65, of following capacity for 3 phase, 415 V + 10 %, 50 Hz AC System for Ambient temperature -5°C to +40°C, fabricated in compartmentalised designed made of CRCA sheet steel of 3.0mm thick for framework & covers, 3 mm thick for gland plate i/c cleaning & finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens Gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section capacitor and reactor, front and rear access, having suitable current carrying capacity, extensible TPN Aluminium alloy bus bar of high conductivity, DMC/SMC bus bar supports, bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 & 2) APFC Panel shall be in compliance with IS :16636 & SSR Part I Specifications etc. as per below details. (A) Incomers Suitable capacity MCCB Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED ndicating Lamp set along with required Instruments and accessories with | 1 | Each Job | - | - |
| 4.1 | extended rotary handle and door interlocking arrangement. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating. | - | - | - | - |
| 4.2 | (B) Instruments & Indications
i) 3-Phase current sensing APFC microprocessor relay/controller , advance 8/12 stages (8 stages for capacity below 100 KVAR and 12 stages 100 KVAR & above) with Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge and having display of Phase wise V, A, PF, Cos-Phi, Kw, KVA, KVAR, THD-V , THD-I, harmonics up to 31 level. 3 nos of dual core CT's accuracy class 1, 15VA at incomer of PCC Panel for APFC relay.
ii) Auto Manual Selector switch, auxiliary contactors with timer for delay in manual mode.
iii) Digital Multi function meter with LED Display for V, A, PF, KW, KVA, KVAR, THD-V & I, Frequency.
iv) Suitable rating control transformer shall be provided for control and indication circuit.
v) All components like control transformer, meter, relay and indicating lamp shall be protected by using suitable rating individual MCB's.
vi) Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS/HFFR 1100 V grade, PVC insulated multi stranded copper control wire.
(C) Bus Bars 1.3 Amp per Sq.mm,TPN, Electrolytic grade Aluminium bus bar of capacity 1.25 times of incomer rating as per SSR Part I | - | - | - | - |
| 4.3 | (D) Outgoings (APFC Section) Selection of the capacitors combinations shall be for continuous rating and each capacitor bank shall have suitable capacity Heavy Duty ISI Marked Capacitor, capacitor duty contactor,the capacitor shall be mounted on channel with base of perforated M S Powder coated sheet, connections inter connections etc. and other features as per SSR Part I Specifications and relevant IS Code having following:
(i) Capacitor bank ratings & stages shall be as per the technical specifications sheet of NIT.
(ii) Capacitor will be MPP self healing type with discharge resistor, pressure release mechanism.
(iii) Since Capacitor Voltage is 525 Volts, thus higher KVAR has to be considered to get rated output at 415 Volts.(iv) 14% Detuned Reactor of class H insulation & 150% linearity in series with Capacitor.
(Note: Technical specifications sheet for selection of the capacitors combinations shall be provided by the NIT Approving Authority with due consideration of number of capacitors i.e. 1 KVAR, 2 KVAR, 3 KVAR, 5 KVAR, 10 KVAR.....for smooth correction). | - | - | - | - |
| 5 | Supplying and fixing cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required complete all as specified and as directed. | 35 | EACH | - | - |
| 6 | Supplying and fixing indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 185 Sqmm 3 core, XLPE aluminium conductor cable of 11 KV grade as required complete all as specified and as directed. | 4 | Each | - | - |
| 7 | Supply, installation, testing and commissioning of following 500 KVA capacity Outdoor Type (continuous loading) BEE 3 Star rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV step down, 3 Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for out door applications with On Load Tap Changer (OLTC) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3x300 sq.mm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS Code including first filling of filtered dehydrated oil, including supplying and grouting of suitable M.S. Channel | 1 | Each Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.28 MB
BOQ_874909.xls
BOQ • 0.53 MB
tender_bldg_HVAC.pdf
Tender Documents • 1.58 MB
SLD_AnnxA.pdf
Additional Documents • 4.84 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].