TECHNICAL
14 conditions · 3 needing a document upload
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. Annual Contractual Turnover Data for the Previous 3/4 Years should be submitted as per Annexure-IX.(AnnexureVIB of Tender Documents)
Technical Eligibility Criteria: (a)The tenderer must have successfully completed any of the following during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or One similar work each costing not less than the amount equal to 60% of advertised value of the tender. (b) (i)In case of tenders for composite works (e.g. works involving more than one distinct component, such as Civil Engineering works, S&T works, Electrical works, OHE works etc. and in the case of major bridges - substructure, superstructure etc.), tenderer must have successfully completed any of the following during last 07 seven) years, ending last day of month previous to the one in which tender is invited: Three similar works each costing not less than the amount equal to 30% of advertised value of each component of tender, or Two similar works each costing not less than the amount equal to 40% of advertised value of each component of tender, or One similar work each costing not less than the amount equal to 60% of advertised value of each component of tender. Note for b(i): Separate completed works of minimum required values for each component shall also be considered for fulfillment of technical eligibility criteria. ( c) Similar nature of Work is defined as "Similar nature of Work is defined as "Supply, installation, testing and commissioning of any LT/HT Electrical Work. ." Note: Work experience certificate from private individual shall not be considered. However, in addition to work experience certificates issued by any Govt. Organisation, work experience certificate issued by Public listed company having average annual turnover of Rs 500 crore and above in last 3 financial years excluding the current financial year, listed on National Stock Exchange or Bombay Stock Exchange, incorporated/registered at least 5 years prior to the date of opening of tender, shall also be considered provided the work experience certificate has been issued by a person authorized by the Public listed company to issue such certificates. In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order, bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final/last bill paid by company in support of above work experience certificate.
Similar nature of Work is defined as "Supply, installation, testing and commissioning of any LT/HT Electrical Work".
39 conditions · 9 needing a document upload
Check List: The tenderer(s) would fill up the check list, as per Annexure-XXIII to ensure that they are submitting the complete tender offer.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Electrical Works for (i)At TSK Division:- Provision of 01 no RUB at MD-2 at (KM13/9- 14/0) in KOWN-LPK section at TSK Division. (ii)Provision of 01 no RUB by elimination of L-Xing No ST-89 at Km 360/3-4 in TTB-MXN section at TSK Division. (iii)Provision of 01 no RUB at ST/99 at (KM 388/0-1) in NCH-SLX section at TSK Division. (iv)Provision of 2 nos. RUB at L-Xing no. ST/117 at Km 430/5-6 and ST/118 at Km 434/3-4 in SLGR- LXA section at TSK Division. (v)Provision of 2 nos. RUB at L-Xing no.ST/131 at Km 487/6-7 in NAM-BFD and ST/134 at Km 502/2-3 In NHK-DJG section at TSK Division.
LV-T-14-TSK-959-R~NFR
LV-T-14-TSK-959-R
Open
Works - General
12 Months
Tinsukia, Assam
₹0
₹2.5 L
24 Sept 2026
24 Sept 2026
2 Oct 2026
293 items across 5 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 18,41,785 | ||
| — | 5.00 | — | — | ||
| Supply, excavation, erection, testing and commissioning of 11-metre long GI tubular pole of type SP-53, having base diameter 165.1 mm, middle diameter 139.7 mm and top diameter 114.3 mm, with minimum thickness of 4.85 mm at base and middle and 4.50 mm at top, and approximate weight of 183 kg. The work includes supply of all foundation materials and erection of the pole in cement concrete foundation of mix 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate of 40 mm nominal size), including excavation of pit, centering and shuttering, proper alignment, concreting, curing, refilling and disposal of surplus earth, complete in all respects as per site conditions and directions of the Supervisor-in-Charge. | — | — | — | 1,82,390 | |
| — | 600.00 | — | — | ||
| Supply, drawing, strengthening and stringing of ACSR conductor 6/1/3.35 mm (Rabbit) on HT/LT overhead lines, including laying of conductor on ground, lifting and placing on poles, tensioning with approved tension clamps, binding on insulators, and providing jumpers as required.The work shall be carried out complete in all respects as per relevant specifications, safety norms and directions of the Supervisor-in-Charge. | — | — | — | 22,200 | |
| — | 4.00 | — | — | ||
| Supply, fitting and fixing of GI channel of size 100 x 50 x 6 mm, 2200 mm long, on tubular pole for pole structure, including provision of necessary MS/GI clamps of size 50 x 6 mm. The work includes drilling of required holes on pole/channel, supply and fixing of all associated accessories such as nuts, bolts, washers and hardware, proper alignment and secure fastening. The item is complete in all respects as per approved drawings, site conditions and directions of the Engineer-in-Charge. | — | — | — | 4,304 | |
| — | 6.00 | — | — | ||
| Supply, fitting and fixing of GI channel of size 100 x 50 x 6 mm, 2500 mm long, on tubular pole for pole structure, including provision of necessary MS/GI clamps of size 50 x 6 mm. The work includes drilling of required holes on pole/channel, supply and fixing of all associated accessories such as nuts, bolts, washers and hardware, proper alignment and secure fastening. The item is complete in all respects as per approved drawings, site conditions and directions of the Engineer-in-Charge. | — | — | — | 7,338 | |
| — | 6.00 | — | — | ||
| Supply and binding of 11 kV polymeric disc insulator of 70 kN rating, including supply and fixing of complete hardware fittings such as ball and socket arrangement, clevis, arcing horn (where required), shackles, pins, nuts, bolts and washers. The insulator shall be made of high-quality polymer with FRP core and silicone rubber housing, suitable for outdoor overhead line application. The work includes proper binding of conductor, ensuring correct alignment and electrical clearances, complete in all respects as per relevant IS/IEC standards, approved drawings and directions of the Engineer-in-Charge. | — | — | — | 4,452 | |
| — | 9.00 | — | — | ||
| Supply, fitting and fixing of 11 kV polymeric type pin insulator 5KN , including supply and fixing of galvanized pin, nuts, bolts, washers and all necessary hardware fittings. The insulator shall be of high-quality polymer with FRP core and silicone rubber housing, suitable for outdoor overhead line application. The work includes proper mounting, alignment and binding of conductor, complete in all respects as per relevant IS/IEC standards, approved drawings and directions of the Engineer-in-Charge. | — | — | — | 3,114 | |
| — | 4.00 | — | — | ||
| Supplying and erection of galvanised stay set for 11 kV overhead lines, complete with 19/20 mm diameter x 1.8 metre long GI stay rod, anchor plate of size 450 mm x 450 mm x 7.5 mm thick, thimble, stay clamps, turn buckle of size 20 mm x 600 mm, 7/4.00 mm diameter GI stay wire, and 11 kV strain insulator, including all necessary fittings and accessories. The work also includes providing cement concrete foundation in CC 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate of 40 mm nominal size), excavation of pit, placing of anchor plate, proper alignment, concreting, curing, refilling and disposal of surplus earth. The item is complete in all respects as per approved drawings, site conditions, relevant standards and directions of the Engineer-in-Charge. | — | — | — | 20,240 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of 11 kV, 3-phase GO-DO switch of 400 Amps capacity, including dismantling/removal of existing GO-DO fuse wherever required and replacement with new unit. The work includes supply and fixing of MS channel cross-arm of size 100 x 50 x 6 mm, operating handle/operating pipe, insulators, fuse carriers, contacts. The item is complete with all necessary hardware fittings, alignment, electrical connections, testing for proper operation and commissioning, complete in all respects as per relevant IS/IEC standards, approved drawings and directions of the Engineer-in-Charge. | — | — | — | 36,594 | |
| — | 1.00 | — | — | ||
| Supply, installation, and fixing of 11KV Lightning Arrester (LA) set, rated 9kV (RMS) with 10kA discharge capacity, zinc-oxide type, suitable for outdoor mounting, complete with all accessories, clamps, connectors, earthing provisions, and tested for satisfactory operation as per IS 1881/IEC 60099. | — | — | — | 2,967 | |
| — | 150.00 | — | — | ||
| Supply, laying , connection , testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable size 95 mm.sq. 4 core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988.For laying of above cable digging of trench and excavation of earth/concrete to depth 0.75 Mtrs. and breadth 0.5 Mtrs. below the ground level and a layer of sand of 0.075 Mtrs. thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of sand of 0.075 Mtrs. thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. The cable route markers should be provided along the route of cables to indicate their presence so that damage/accident are Not caused by inadvertent digging.All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024. | — | — | — | 1,68,750 | |
| — | 250.00 | — | — | ||
| Supply, laying , connection , testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable size 50 mm.sq. 4 core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988.For laying of above cable digging of trench and excavation of earth/concrete to depth 0.75 Mtrs. and breadth 0.5 Mtrs. below the ground level and a layer of sand of 0.075 Mtrs. thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of sand of 0.075 Mtrs. thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. The cable route markers should be provided along the route of cables to indicate their presence so that damage/accident are Not caused by inadvertent digging.All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024. | — | — | — | 1,82,500 | |
| — | 300.00 | — | — | ||
| Supply, laying , connection , testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable size 16 mm.sq. 2 core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988.For laying of above cable digging of trench and excavation of earth/concrete to depth 0.75 Mtrs. and breadth 0.5 Mtrs. below the ground level and a layer of sand of 0.075 Mtrs. thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of sand of 0.075 Mtrs. thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. The cable route markers should be provided along the route of cables to indicate their presence so that damage/accident are Not caused by inadvertent digging.All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024. | — | — | — | 90,900 | |
| — | 6.00 | — | — | ||
| a) Supply and erection of Single Arm type Hot Dip Galvanized in single deep to average 65 micron DFT 7 mtr. long octagonal pole with sectional dia 130x70 mm, overall sectional thickness 3 mm complete with base plate size 220x220x12 mm, 4 Nos. 700 mm long foundation bolt of 20 mm dia with all other accessories as per direction of Engineer in charge at site. b) Supply and erection of PCC/RCC/shallow foundation of size and depth as per recommendation and drawing of the manufacturer (approx. 1.6 mtr.x 0.6 mtr.x0.6 mtr.) with excavation of earth for foundation of all depth and all places, nature and condition of soil including de-watering, shoring, shuttering, batching, mixing, placing, leveling, carrying etc and re-filling the pit after completion of foundation work from excavated earth or borrowed pit by contractor's own arrangement for octagonal poles. | — | — | — | 1,38,390 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of 63 kVA, 11/0.433 kV, 3-phase, 50 Hz, outdoor type, aluminium wound, oil-immersed distribution transformer, BIS Energy Efficiency Level-I, suitable for ONAN cooling, vector group Dyn11, complete with first filling of transformer oil, silica gel breather,drain valve and all standard accessories conforming to the latest IS:1180 (Part-1) and other relevant IS specifications. Complete in all respects as per manufacturer's recommendations and as directed by the Engineer-in-Charge. | — | — | — | 2,20,660 | |
| — | 9.00 | — | — | ||
| Supply & erection of earth by 80 mm dia 3 Mtrs. long (4.5 mm thickness) GI pipe ,8 SWG GI wire, GI nuts, bolts including masonry materials for earthing pit, salt, charcoal etc. and construction of earth pit covered with cement concrete plate having locking arrangement and watering pipe. | — | — | — | 28,134 | |
| — | 2.00 | — | — | ||
| Supply, fitting, fixing of 200 Amps outdoor type cable junction box, angle frame mounted, dust & vermin proof, complete with rain cap, aluminium basbar of suitable size for TPN, 200 Amps, 415 V made out of 16 SWG CRCA sheet duly painted, Cable Junction Box Size: (lxbxh=450x 450x600 mm). The base of the fedder pillar junction box to be provided with CC foundation of propotion 1:1.5:3( cement, sang,Chips) after connection of Ug cables. | — | — | — | 17,878 | |
| — | 240.00 | — | — | ||
| Supply, laying and fixing of 2 x 2.5 sq.mm FRLHS single-core copper cable (phase & neutral) through 25 mm dia PVC conduit concealed in walls, complete as required. | — | — | — | 29,760 | |
| — | 30.00 | — | — | ||
| Supply, laying and fixing of 2 x 1.5 sq.mm FRLHS single-core copper cable (phase & neutral) through 25 mm dia PVC conduit concealed in walls, complete as required. | — | — | — | 2,610 | |
| — | 240.00 | — | — | ||
| Supply, laying and fixing of 1.0 sq.mm FRLHS single-core copper cable through same 25 mm dia PVC conduit concealed in walls for earth continuity, complete as required. | — | — | — | 5,040 | |
| — | 1.00 | — | — | ||
| Supply, fitting, fixing of Floor Mounted LT panel board having TPN AL bus bars capacity: 400 Amps. to be mounted in a sheet steel cubical panel made of CRCA steel with the following provision:(i)250 Amps MCCB, 4 Pole, 25KA BC, Ics=100% Icu,=1 Nos (ii)125 Amps MCCB, 4 Pole, 25KA BC, Ics=100% Icu,=2 Nos (iii)MCB 63 Amps TPN "C" series=1 No (iv)Three Phase LED Ammeter CL 1 with selectror switch inbuilt for main feeder= 1Nos (v)Three Phase LED Voltmeter CL 1 with selectror switch inbuilt for main Volt measurement range= 50-550 VAC= 1Nos (vi)LED RYB indicator pilot lamp for indication of incoming = 3 Nos | — | — | — | 58,510 | |
| — | 1.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of 8 way Double Door SPN MCB DB with IP-43 protection, Door earthing,Neutral Bar,earth bar and bus bar provided with the following MCBS:- (i) MCB 16 A DP C Series, 10KABC= 4Nos | — | — | — | 6,360 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of Single Phase Street Light Panel/Time Light Distribution Board (DB) in CRCA sheet steel enclosure of minimum 1.6 mm thickness, suitable for wall mounting with IP-54 degree of protection, complete with 40 A TPN MCB conforming to IS/IEC 60898-1, 10 kA breaking capacity, C-curve, 240/415 V AC, 50 Hz; 32 A, 3 Pole AC-3 rated power contactor conforming to IS/IEC 60947-4-1, suitable for switching inductive lighting loads, coil voltage 230 V AC; Astronomical Digital Timer Switch with battery provision having minimum 30 programme , inbuilt Real Time Clock (RTC), manual override (Auto/ON/OFF), LCD display, operating supply 230 V AC, 50 Hz, contact rating 16 A,complete with Auto/Manual selector switch, ON/OFF push buttons, LED indication lamps, neutral link, earth terminal, FRLS copper internal wiring with ferruled conductors, with mounting components, terminal blocks, cable glands, gland plate, earthing stud, labels and all necessary accessories, suitable for 230 V, single-phase, 50 Hz supply with maximum connected load of 6 kW, complete in all respects including testing and commissioning as directed by the Engineer-in-Charge | — | — | — | 62,590 | |
| — | 2.00 | — | — | ||
| — | — | — | 3,39,744 | ||
| — | 2.00 | — | — | ||
| — | — | — | 34,940 | ||
| — | 230.00 | — | — | ||
| Supply of Flat Three Core 10 SQ mm PVC Insulated & PVC Sheathed Industrial Cable for Submersible Pump Motors 1100 Volt, conforming to IS 694 | — | — | — | 1,31,100 | |
| — | — | — | 16,59,348.52 | ||
| — | 10.00 | — | — | ||
| Supply, excavation, erection, testing and commissioning of 11-metre long GI tubular pole of type SP-53, having base diameter 165.1 mm, middle diameter 139.7 mm and top diameter 114.3 mm, with minimum thickness of 4.85 mm at base and middle and 4.50 mm at top, and approximate weight of 183 kg. The work includes supply of all foundation materials and erection of the pole in cement concrete foundation of mix 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate of 40 mm nominal size), including excavation of pit, centering and shuttering, proper alignment, concreting, curing, refilling and disposal of surplus earth, complete in all respects as per site conditions and directions of the Supervisor-in-Charge. | — | — | — | 3,73,290 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocumentTSK959R.pdf
ATTACHMENT
GCCAPRIL2022WITHALLACS.pdf GCC 2022 WITH ACS
ATTACHMENT
AnnexuresSectionVII.pdf
ATTACHMENT
GCCAPRIL2022WITHALLACS.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .