PROVN OF RING MAIN SYSTEM FOR ELECTRIC SUPPLY FOR NAPIER LINE AND BI LINE AT NEW CANTT ALLAHABAD UNDER GE (WEST) ALLAHABAD
2021_MES_435958_1
81596/W/E8
Open Tender
Civil Works
Item Rate
180 days
Allahabad
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (West) Allahabad
₹28,780
Yes
11 Jun 2021
12 Apr 2021
20 May 2021
13 Apr 2021
18 May 2021
4 May 2021
60 days
Amount
Supply, installation and commissioning of 11KV, 630A, non extensible outdoor,fixed type (IP 54) RMU (Ring main Unit) 3-Way comprising of 2 Nos 630 Amps, vaccum circuit breaker (comprising two No Incomers & 1 No Vaccum circuit breaker as outgoing) inside robotically welded stainless steel 304 (Non ferrite Non magnetic grade) tank havin min, thickness 3+0.5mm & IP67 Degree protection. RMU should be provided with internal busbars as well as earthing busbar should be of cooper, one number fault passage indicator per unit padiock provision & complete with accessories. The RMU shall be type tested for internal arc test of 20 KV/1 Sec as per IEC 62271-220. The earthing of cable sheilds. The outer enclosure main door should cover entire part of the switchgear including front cover and cable doors for providing complete IP54 protection. The unit shall include the following with all necessary standard fitting as required at site - (a) 2 Nos Incoming 630 Amp motorised Vaccum circuit breaker, triple pole single break 3 position (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted high fixed type voltage indicator device as per IEC 61958-1 fully rated with earth switch, spring assisted mechanism with built in operating handle, arc proof hinged type cable cover air insulated cable boxes and boots suitable for bottom front entry termination of 3 core cable 95/120/185 sqmm. (b) 01 No Outgoing 630 Amp motorised Vaccum circuit breaker, triple pole single break 3 position (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted high fixed type voltage indicator device as per IEC 61958-1 fully rated with earth switch, spring assisted mechanism with built in operating handle, arc proof hinged type cable cover air insulated cable boxes and boots suitable for bottom front entry termination of 3 core cable 95/120/185 sqmm.
(C) Bus Connected PT Unit-01 No for metering consisting of following :- (i) Type M : Air insulated metering module 12 KV, 630A 20 KA for 3 sec. (ii) 3 Voltage transformers of the ratio 11 KV/1.732/110 V/1.732.25 VA Class 1.0 with HT fuses on primary side and MCB on secondary side. (iii) 3 Digital MFM with 485 port to measure Amps, Volts, Frequency, PF, KWH, KVRA (iv) 1 CFL illumination. (v) 1 Space heater with thermostate. (vi) 1 RYB phase indicator (vii) 1 Cable support busbar, stand for 3 way unit, 1 manometer & 1 perating handle. (viii) 1 Set bushing for external bushbar connection along with bushbar cover & sleeved bushbars for coupling. (ix) 2x12 V Battery with battery charger of suitable burden for motor operation. Input 230 V AC & output 24 V DC. (d) Capacitive voltage indicator fixed type VPIS 9-15KV. (e) necessary interlocking arrangement for sefty and operation. (f) One No operating handle for manual operation. (g) One No Mono meter. (h) Safety interlock shall be provided as per relevant IEC/IS standard and manufactures directions. (j) Safety interlocks shall be provided as relevand IEC/IS standard and manufactures directions. (k) Above switchgear shall confirm to all relevant IEC/IS standard. (l) Manual operation of vaccum circuit breaker should be possible without dismantling the motor from RMU. the motor should be fitted in such a way that it should not be outside from covers of RMU.
(m) Coupling of RMU and metering module should be with the help of bolted type arrangement so thsat the coupling at site shall be easy. Pulg in type bushing shall not be acceptable. (n) Minimum 3 module should accommodate in one tank to avoid multiple coupling at site. (o) The switchgear shall have built in progamming logic using reputed make PLC (ACS500/Equip) for automatic change over between two motorized incomer VCB and shall derive voltage reference from incoming supply in respective incomer. PLC shall also be wired to all VCB's to monitor open/close 3+0.5 status. PLC should have communication facility over MODBUS protocol. (p) Three set of remote operation & control kits for motorisation & operation of PLC. (q) Three set of signal converter for PLC operation. (r) The autochangeover for incoming feeders shall be done within 10-15 second. (s) The PLC shall programmable at factory as well as dite for accoummodating future requirements as per manufacturers instruction for autochangeover for feeders. (t) PCC 1:2:4 type B1 using 20 mm graded aggregate for foundation of RMU as per recommendation of manufacturers & as directed by Engr-in-charge. Note :- Any other parts/items not specified above but have been considered essential for smooth and safe functioning of the RMU system shall be included in the items and are covered against the quoted rate.
Supply and fix cable jointing kit for 11 KV grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
M&L earthing complete with Gl electrode 600x600x6.00mm thick buried directly in ground vertically in pit of depth not less than 2.25 meter below normal ground level with top edge of the earth plate not less than 2.50 meter below normal ground level connected to Gl strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of brass connected including gun metal or phosphorus bronze of size 75x75x25 mm drilled and screwed including 3 Nos 8 mm dia 25 mm long hexagonal head screwed all as specified including excavation and earth work and disposal of surplus soil including 40 mm Gl tubing light grade and necessary fitting for protection of Gl strip including laying of charcoal, dust and common salt, PPC (1:2:3) type Cl using 20graded stone aggregate earth pit with 40x40x6mm MS angle iron grame RCC cover 40mm thick (1:2:4) type B20 using 12.5mm graded stone aggregate reinforced with 8mm dia round bar @ 75mm C/C both way with MS handle 20mm dia plastering 15mm thick CM (1:6:) internally and up to 150mm below ground level externally. PGL funnel with wire mesh 20mm dia Gl pipe for watering complete all as shown on electrical plate No.3 of SSR Part -1 2009 and connected in earth test point including testing completed all specified and directed.
Supply and laying XLPE insulated, screened ,pvc bedded galvanised steel strip or wire armoured electric power cable (heavy duty) with alluminium conductor 11000 volt grade having cross section area of 95 Sq mm 3 core "E" grade complete all as specified and directed.
Excavation in trenches in soft/ loose soil n.exc 1.5 m wide and n.exc. 1.5 mtr deep and getting out and laying HT UG Cable complete all as specified and directed .
Returning filling in with the soil obtained from item above here-in-before includiing spreading , leveling and well ramming in layers n.exc 25 cm thick complete all as specified and directed.
Removal of surplus excavated soil to a distance n.exc 50 mtr and depositing where directed at a level n.exc.1.5 mtr above starting point complete all as specified and directed
Supply and laying sub class 'B' brick old size laid flat in trenches across the length for protection of cable as cable cover complete all as specified and directed .
M&L for sand cushioning in trenches for protection of under ground cable provided in layers of sand as 8 cm before laying the cable and 15 cm deep after laying cable complete all as specified and directed.
M&L cable jointing kit for 11 KV cable for end termination heat shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, outdoor type complete all as specified and directed.
M/S Akash Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .