| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.7 CrAccepted-AOC 309 10 SURESHWAR TECHNO IT PARK PREMISES CO OP SOC LTD NEW LINK ROAD BORIVALI WEST MUMBAI 400092 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400092 | ₹20.7 Cr Quoted ₹20.9 Cr | L1 | Accepted-AOC Qualified L1 AOC |
| 2 | L2₹21.4 CrRejected-Finance THIRD FLOOR AMIT CRYSTAL SENAPATI BAPAT ROAD PUNE 411 016 | PUNE | PUNE | MAHARASHTRA | 411016 | ₹21.4 Cr | L2 | Rejected-Finance Not L1 Hence Reject Tender |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹19.7 Cr
EMD Value
₹9.9 L
Closing Date
27 Jan 2023, 6:00 pmClosed
Executive Engineer, Public Works Division, Pune 1.
Executive Engineer, Public Works Division, Pune 1.
73-1 - Renovation of Main OPD, Surgical Store, Ward No.1, Ward No. 10,, Ward No. 16, Blood Bank at Sassoon General Hospital, Pune. (Including Electrical Work)
2023_PWDRP_866199_1
E-Tender Notice No. 73 for 2022-2023
Open Tender
Civil Works - Buildings
365 days
Sassoon General Hospital Pune
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
₹9.9 L
Chief Engineer, Public Works Region, Pune.
29 Mar 2023
13 Jan 2023
30 Jan 2023
13 Jan 2023
27 Jan 2023
13 Jan 2023
19 Jan 2023
Amount
Removing cement tiles, or marble or polished shahabad floor or dado without bed concrete including stacking the materials as directed with all leads, lifts etc. complete Ground Floor
First Floor
Second floor
Third Floor
Removing the existing cement plaster of any thickness without causing dust nuisance and stacking the debris upto a distance of 50 metres or spreading in the compound and cleaning the site etc. complete Ground Floor
First Floor
Second floor
Third Floor
Removing doors and windows with frames and stacking the materials as directed with all leads, lifts, complete. Ground Floor
First Floor
Second floor
Third Floor
Removing Water Closet pans including disconnecting the sanitary and water supply connections, removing and breaking flooring and bed con-crete around pan removing the same carefully and stacking the serviceable materials as adn where directed including throwing the unserviceable materiasls out side etc. carefully and throwing out the refusal outside etc. complete. Ground Floor
First Floor
Second floor
Third Floor
Removing urinal pans or wash hand basins with frame including disconnecting the sanitary and water supply connections, removing the same carefully and stacking the serviceable materials as and where directed including throwing the unserviceable materials outside etc complete. Ground Floor
First Floor
Second floor
Third Floor
Removing cast iron or wrought iron or Asbestos Cement pipe and stacking them as directed with all leads lifts, complete. Ground Floor
First Floor
Second Floor
Third Floor
Removing wooden or Asbestis Cement partition including frame work and stack-ing the materials as with all leads, lifts etc. complete. Ground Floor
First Floor
Dismantling brick masonry in lime or cement mortar and stacking the materils as directed with all leads, lifts etc Ground Floor
First Floor
Second floor
Dismantling the Reinforced cement concrete Work 1:2:4 and sorting out the materials such as steel etc. as directed and stacking them within the specified lead as directed etc. complete. Ground Floor
First Floor
Second floor
Lowering down the debris obtained from breaking and removing the cement plaster / burnt brick masonry of the Ground Floor by any means without causing dust nuisance and damage to structure, stacking the same as and where directed including cleaning the site complete. First floor
Second floor
Third Floor
Providing second class Burnt Brick masonry with conventional/ I.S. type bricks in cement mortar 1:6 in superstructure including striking joints, raking out joints, watering and scaffolding etc. Complete. Ground Floor
First Floor
Second Floor
Providing second class Burnt Brick masonry with conventional/ Indian Standard type bricks in cement mortar 1:4 in half brick thick wall including mild steel longitudinal reinforcement of 2 bars of 6 millimetre diaMetre / 2 hoop iron strips 25 millimetre X 1.6 millimetre placed at every third course, properly bent and bonded at ends scaffolding, racking out joints and watering etc. complete. Ground Floor
First Floor
Second floor
Providing and laying Cast in situ/Ready Mix cement concrete M-20 of trap metal for Reinforced cement concrete beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand Vertical shaft impact (VSI) Grade) Ground Floor
First Floor
Second Floor
Third Floor
Providing internal cement plaster 20 millimetre thick in Single coats in cement mortar 1:4 without neeru finish, to concrete, brick surface, in all positions including scaffolding and curing etc.complete Ground Floor
First Floor
Second Floor
Third Floor
Providing internal cement plaster 12 millimetre thick in single coat in cement mortar 1:4 without neeru finish to concrete or brick surfaces, in all positions including scaffolding and curing etc. complete. Ground Floor
First Floor
Providing sand faced plaster externally in cement mortar using approved screened sand, in all positions including base coat of 15 millimetre thick in cement mortar 1:4 using waterproofing compound at 1 kilogramme per cement bag curing the same for not less than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 6 to 8 millimetre thick in cement mortar 1:4 finishing the surface by taking out grains and curing for fourteen days scaffolding etc.complete. Ground Floor
First Floor
Second floor
Providing and laying Cast in situ/Ready Mix cement concrete in Mix-10 of trap metal for foundation and bedding including bailing outwater, Steel centering, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing if required and curing complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand Vertical shaft impact (VSI) Grade) Ground Floor
Providing and laying water proof treatment of terrace slab with Burnt Brick Coba in all position with an average thickness of 150 millimetre consisting specialised materials as per the manufactures specifications and covering 10 years guarantee on court fee stamp paperincluding all lead, lift, etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and applying water proofing treatment using acrylic polymer modified cement based water proofing coating with fibre glass mesh mixing at the rate of powder to liquid (2:1) by weight covering 9 to 10 Square Metre per kilogramme with two coat using approved chemicals for masonry and concrete surface by brush covering 7 years guarantee on Stamp Papers etc. complete. First Floor
Providing and applying gypsum plaster ( with Gypsum material ) with finishing with gypsum material in 10 to 13 millimetre thickness to previously plastered surface / or on newly brick surface ( Excluding rough cast plaster ) in all position including preparing and Finishing the surface scaffolding etc.complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and laying Vitrified MATT finish having decorative type of size 1000 millimetre x 1000 millimetre of 8 to 10 millimetre thickness (on a existing flooring) with bonding chemical and confirming to Indian Standard 15622-2006 (Group Bla) of approved make shade and pattern for flooring in required position laid on a bed of bonding chemical filling joints curing and cleaning etc .complete. Ground Floor
First Floor
Second floor
Providing and laying vitrified matt fininsh tiles having size 590 millimetre to 605 millimetre x to 605 millimetre of 8 to 10 millimetre thickness and confirming Indian Standard 15622-2006 (Group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement morar including neat cement float, filling joints, curing and cleaning etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and laying vitrified mirror / glossy finish tiles having size 590 millimetre to 605 millimetre x 590 millimetre to 605 millimetre of 8 to 10 millimetre thickness and confirming to Indian Standard 15622-2006 ( group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including neat cement float, filling joints, curing and clearing etc. complete Ground Floor
First Floor
Second Floor
Third Floor
Providing and laying in position flooring of telephone black / Amba White / Cat bary brown / Ruby red / Ocean Brown granite stone of approved shade and size 18 millimetre to 20 millimetre thick on bed 1:6 cement mortar including cement floats striking joints, pointing in cement mortar 1:3 curing and cleaning etc. complete. Ground Floor
First Floor
Second floor
Providing and laying telephone black / Amba White / Cadburybrown / Ruby red / Ocean Brown granite stone of 18 to 20 millimetre thick for door frame/ dado/ window boxing etc. On cement mortar 1:6 including filling joints with polymer base filler nosing/moulding the sharp edges wherever necessary, curing, etc. complete. Ground Floor
First Floor
Second floor
Third Floor
Providing 25 millimetre to 30 millimetre thick partition of polished black kadappa stone slab of approved quality including giving required size and shape etc. Fixing in cement mortar 1:3 curing and cement etc. complete. b) Both side polish Ground Floor
First Floor
Second floor
Third Floor
Providing and preparing kitchen otta up to 75 centimetre width,made up from 30 millimetre thick and 75 centimetre high vertical support for kadppa at 1 metre centre to centre of 25 millimetre thick both side polished kadappa middle shelf and bottom of 20 millimetre thick one side polished kadappa with faciapatti of 20 x 50 millimetre kadappa including all material labour cutting fixing with cement mortar and araldite curing polished and cleaning etc. complete. Ground Floor
First Floor
Second floor
Third Floor
Providing and laying machine cut machine Polished Kota stone flooring 25 millimetre to 30 millimetre thick and required width in plain/ diamond pattern on bed of 1:6 cement mortar including cement float, filling joints with neat cement slurry, curing, polishing and cleaning etc. complete. Ground Floor
First Floor
Second floor
Providing and fixing in required position skirting or dado of polished Kotah Stone slab 25 millimetre to 30 millimetre thick fixed on base on plaster of cement mortar 1:4 including cement float, filling joints with cement slurry, curing rubbing, polishing and cleaning complete. Ground Floor
First Floor
Second floor
Providing Mirror polishing to Kota Stone including using all necessary stones and equipments cleaning, washing etc. complete. For Flooring. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing in position Thermo Mechanically Treated (TMT) - FE - 500 bar reinforcement of various diameter for Reinforced cement concrete pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches etc. as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fabricating structural steel work in rolled sections like joists, channels, angles, tees etc. as per detailed design and drawings or as directed including cutting, fabricating, hoisting, erecting, fixing in position making riveted / bolted /welded connections without connecting plates, braces etc. and including one coat of anticorrosive paint and over it two coats of oil painting of approved quality and shade etc. complete. Ground Floor
First Floor
Providing and fixing 15 millimetre thick eco-friendly densified edge calcium silicate false ceiling of approved texture of size 595 millimetre x 595 millimetre in true horizontal level, suspended on interlocking metal grid of hot dipped galvanized steel sections (galvanising at @12 gm square metre including both sides) consisting of main T runner suitably spaced at joints to get required length and size 24X38 millimetre made from 0.33 millimetre thick(minimum ) sheet, spaced 1200 millimetre center to center and cross T of size 24X28 millimetre made of 0.33 millimetre thick(minimum ) sheet to be interlocked at the middle of the 1200x600 millimetre panel to form the grid of size 600x600 millimetre resting on periphery walls/partitions on a periMetre wall angle precoated steel of size 24x24x3000 made of 0.4 millimetre thick (minimum) sheet with the help of all plugs at 450 millimetre and laying 15 millimetre thick densified edges calcium silicate ceiling tiles of approved texture (spintone/cosmos/hexa) in the grid, including light fittings , fixtures , smoke detectors etc., wherever required. Main T runners suspended from ceiling with using galvanised iron slotted cleats of size 25x35x1.6 millimetre fixed to ceiling using 12.5 millimetre diameter And 50 millimetre long dash fasteners, 4 millimetre galvanised iron adjustable rods with galvanized steel levels clips of size 85x30x0.8 millimetre , spaced at 1200 millimetre center to center along main T bottom exposed with 24 millimetre of all T-sections shall be prepainted with polyester baked paint, for all heights, as per specifications, drawings etc.complete. (currently this item should be used only for VIP cabins) Ground Floor
First Floor
Providing and fixing frame work of galvanised iron for suspended false ceiling which includes galvanised iron perimeter channels of size 27 millimetre and 0.5 millimetre thick having one flange of 20 millimetre and another of 30 millimetre along with periMetre of the ceiling, fixing in brick wall / partition with the help of rawal plugs and screws,suspending galvenised iron intermediate channels of size 45 millimetre and 0.9 millimetre thick with two flanges of 15 millimetre each from the soffit at 1200 millimetre centers with steel galvanised iron hanger of width 25 millimetre x 0.5 millimetre fasteners, ceiling section of 0.5 millimetre thickness having curved wedge of 51.5 millimetre and two flanges of 26 millimetre each with lips of 10.5 millimetre fixed to the intermediate channel with the help of connecting clips and in direction perpendicular to the intermediate channel at 450 millimetre centers, 12.5 millimetre dry walls screws at 230 millimetre centers; fixing screws mechanically either with screw driver or drilling machine with suitable attachment etc. complete. Ground Floor
First Floor
Providing and fixing false ceiling of 10 to 12 millimetre thick decorative boards of fibrous plaster of paris including scaffolding if necessary all architectural work like mouldings, cornices, coves, domes, cups as per detailed drawings and three coats of spray painting to boards etc. complete. (excluding frame work, runners and mild steel suspenders). Ground Floor
First Floor
Providing and fixing 30 millimetre thick Poly vinyl chloride FLUSH L DOOR SHUTTER consisting of panel of hollow Poly vinyl chloride profile of 20 millimetre thickness consisting frame made out of mild steel tubes of 19 gauge thickness and size of 19 millimetre x 19 millimetre inserted inside the hollow section of stiles rails top and bottom rails and two 19x 19 millimetre mild steel tubes inserted horizontally inside the hollow profile section using 4/5 millimetre sheet using screws hollow profile shall be lipped with 10 millimetre (5 millimetre x 2 millimetre) thick x 20 millimetre width on stiles and rails using solvent cement. The inner panel shall be laminated with 5 millimetre thick termite proof waterproof plain /prelam Poly vinyl chloride sheet using solvent cement on the both sides of the panel including stainless steel fixtures and fastening etc. Complete as per direction of Engineer incharge, manufacturers specification and drawing. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing 34 millimetre thick moulded door shutter consisting of solid core single leaf flush door of 30 millimetre thickness lipped with 15 millimetre ( 5 millimetre x 3 millimetre) thick x 30 millimetre width on one style and top rail and 10 millimetre (5 millimetre x 2 millimetre) thick x 30 millimetre width on other style and bottom rails. The inner panels laminated with 2 millimetre thick termite proof, water proof and fire resistant moulded Poly vinyl chloride sheet with 2,4,6 design in different plain and /or prelim colours on one side after routing the moulded design on flush doors and 2 millimetre plain and /or pre lam Poly vinyl chloride on other side using rubber adhesive on flush door and solvent cement adhesive on the Poly vinyl chloride lipping etc. as per direction of Engineer in charge and manufacturers specification and drawing etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing 44 millimetre. thick commercial pinewood flush door (single leaf or double lead) partly glazed with both sides 1.5 millimetre. thick laminate finish 50 millimetre.x10 millimetre. lipping for four edages over laped with laminate with or without vision panel with 8 millimetre. thick toughened glass with eatching with 50 millimetre.x10 millimetre. lipping patti with 2 coats of melamine polish finish door shall be fixed with 2 numbers of stainless steel aldrops. stainless steel ball bearing butt hinges 4"x1.1/4" x 1.1/4" (4hinges for single leaf door and 8 hinges for double leaf door). Stainless steel D handle 250 or 300 millimetre. long - 1pair (for single doors) and 2 pairs (for bouble doors), stainless steelDoor stopper with magnetic catcher - 1 no. (for single leaf doors) and 2 nos. (for double leaf doors) SS tower bolt 8" - 1 no. for single doors) and 2 nos. (for double doors) stainless steel 1.25 millimetre kick plate and push plate 2 number each(for single doors) and 4 numbers each (for double doors) and aldrops including necessary labour, hardware, etc. complete. as per design and drawing As directed by Engineer Incharge/ Interior Designer. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation including all leads and lifts at all levels and shall be as directed by Engineer in charge. Ground Floor
First Floor
Providing and fixing 12 millimetre thick Toughened Glass Door including ozone company patch ,Floor Spring door closer ss handle door lock with necessery Labour etc completed as per drawing and design of work as directed by Engineer Incharge. Ground Floor
Providing and fixing 12 millimetre thick Toughened Glass Partion including ozone company patch and Profile fitting with necessery Labour etc completed as per drawing and design of work as directed by Engineer Incharge . Ground Floor
Providing and fixing frame with / without ventilator of size as specified with Country cut teak wood for doors and windows including chamfering, rounding, rebating, iron holdfast of size 300 millimetre x 40 millimetre x 5 millimetre with oil painting, etc. complete Ground Floor
First floor
Providing and fixing Country cut teak wood double or single leaf panelled shutters, 35 millimetre thick style top and freze rail 95 x 35 thick with lock and bottam rail 195 x 25 millimetre thick and panels without ventilator as per detailed drawing excluding the door frame, stainless steel fixtures and fastening and finishing the wood work with oil painting 3 coats complete. Ground Floor
First floor
Providing and fixing in position aluminium openable window of any size as per detailed drawing and as directed by Engineerincharge with all necessary alluminium sections including necessary fixtures and fastening with 5 millimetre thick clear float glass etc. complete.b) Powder Coated. Ground Floor
First Floor
Providing and fixing in position aluminium fixed window fully glazed of any size as per detailed drawing and as directed by Engineerincharge with all necessary alluminium sections including necessary fixtures and fastening such as 5 millimetre thick clear float glass etc. complete.b) Powder Coated. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing in position powder coated aluminium louvered windows / ventilatorof various sizes with powder coating as per detailed drawing and specifications including aluminium frames 80 x 38 millimetre x 1.22 millimetre box type, 5 millimetre thick sheet glass louvers, of approved quality etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing chicken mesh of 22 gauge, with about 30 centimetre width at the junction of Reinforcement cement concrete members and brick work, of approved quality including fixing mesh in position by necessary drilling in concrete / Burnt Brick masonry and or tying by binding wire etc. complete. Ground Floor
First Floor
Second floor
Providing and fixing aluminium grill diamond mesh type DG202 of 7.5 millimetre thick including fixing in position anodised aluminium frame section of 80 x 38 millimetre x 1.22 millimetre size box, cutting to the required size with all wastage , labour, lead lift etc. complete. Ground Floor
First Floor
Second floor
Providing and fixing 75 millimetre diameter stabiliser pipe/ Poly vinyl chloride soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing 100 millimetre dia stabiliser pipe/ Poly vinyl chloride soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and constructing Brick Masonry Inspection Chamber 90 centimetre x 45 centimetre x 90 centimetre including 1:4:8 cement concrete foundation 1:2:4 cement concrete channels half round glazed stoneware pipes, Brick Masonry, plastering from inside and Cast Iron lid cover of 75 kilogramme with lid and frame fixed in cement concrete.
Providing and constructing Brick Masonry Inspection Chamber 60 centimetre x 45 centimetre x 90 centimetre including 1:4:8 cement concrete foundation 1:2:4 cement concrete channels half round glazed stoneware pipes, Brick Masonry, plastering from inside and with frame fixed in cement concrete with Reinforced cement concrete Cover medium duty 140 kilogramme with frame etc complete.
Providing and fixing screw down for 25 millimetre diameter wheeled stop tap of brass including necessary sockets/union nut complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing screw down for 32 millimetre diameter wheeled stop tap of brass including necessary sockets/union nut complete Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing screw down for 40 millimetre diameter wheeled stop tap of brass including necessary sockets/union nut complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing screw down for 50 millimetre diameter wheeled stop tap of brass including necessary sockets/ union nut complete Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing chromium plated BIB cock with wall flange of approved make including necessary sockets/ union nut etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing chromium plated Angular stop clock with wall flange of approved make continental including necessary sockets/union nut etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing European type wall-hung Ivory colour closet of approved make with push valve concealed type with cover plate 32 millimetre size of approved make including soil pipe, vent pipe up to outside face of wall ,100 millimetre diameter galvanised iron plug bend inlet pipe all fittings, cuttingand making good walls, floors etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing chromium plated Two way BIB cock of approved make continental including necessary sockets/union nut etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing Hand shower (health faucet) with 8 millimetre diameter 1 metre long flexible tube having wall hook with approved make including necessary sockets/ union nut etc. complete as directed by Engineer in charge. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing chromium plated wall mixer with provision for overhead shower with 115 millimetre long bend pipe and wall flange of approved make including necessary sockets/union nut etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing on walls/ ceiling/ floor 15 millimetre diameter Chlorinated Poly vinyl chloride pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in Public Works Department chowky or as directed etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing on walls/ ceiling/ floor 25 millimetre diameter Chlorinated Poly vinyl chloride pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in Public Works Department chowky or as directed etc. complete. Ground Floor
First Floor
Second floor
Third Floor
Providing and fixing on walls/ ceiling/ floor 32 millimetre diameter Chlorinated Poly vinyl chloride pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in Public Works Department chowky or as directed etc. complete. Ground Floor
First Floor
Second floor
Third Floor
Providing and fixing on walls /ceiling/ floor 40 millimetre diameter Chlorinated Poly vinyl chloride pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in Public Works Department chowky or as directed etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing on walls/ ceiling/ floor 50 millimetre diameter Chlorinated Poly vinyl chloride pipe with necessary fittings, remaking good the demolished portion etc. complete. Ground Floor
First Floor
Second floor
Providing and fixing 10 centimetre Cast Iron Nahani Trap including Cast Iron grating bend and piece of Cast Iron pipe upto the outside face of the wall complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing High Density Polythein container one piece moulded water tank made out of low density polythyler and built corrugation including of delivery up to destination hoisting and fixing of accessories such as inlet, outlet overflow of all tanks capacity above 1000 to 20,000 litres Ground Floor
First Floor
Second floor
Providing and fixing collapsible steel gate in one / two leaves with hot rolled vertical channels of 18 x 9 x 3 millimetre minimum size, crossings of M.S. flats of size 18 x 5 millimetre T or E section for runner of minimum 40 x 6 millimetre size for flange, mild steel flat for top runner of minimum size 40 x 12 millimetre with roller wheels confirming to grade F.G. 150 fitted with snap headed rivets of minimum size 6 millimetre maximum spacing of vertical channels be 100 millimetre enclosed gate position and clear space of 150 millimetre between two sets of crossings with hold fasts, stoppers, spaces, handles, locking arrangement and one coat of red lead primer and oil painting etc. complete. (Indian Standard 105211983). Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing Oval Type Under Counter Wash Hand Basin Ivory colour of 420 x 590 x 195 millimetre size with pillar cock, chromium plated Angular stop cock, long thread of approved make continental including stainless steel bottle trap of necessary pipe connection up to the outside face of the wall, having Telephonic Black / Colour Granite of 180 millimetre thick fixed on Black Kadappa Framework, etc. Complete as directed by Engineer in charge. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing stainless steel sink of size 600 x 510 x 200 millimetre incluidng coupling, outlet pipe, elbow and other necessary fitting, finishing etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and applying priming coat on concrete/ masonary/ Asbestos Cement plastered surfaces including scaffolding if necessary, preparing the surface by thoroughly cleaning oil, grease, dirt and other foreign matter and sand papering as required etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and applying plastic emulsion paint of approved quality, colour and shade to new surface in three coats including scaffolding, preparing the surface. (excluding primer coat) etc. complete. Ground Floor
First Floor
Conveying building rubbish and debris upto 30 kilometre from work site including loading and unloading etc complete.
Providing and fixing Curtains / Blinds MAC - BLACKOUT TORINO TR 5408 for windows including all necessary fixtures and fittings as per the smple approved by Architect etc complete. All samples must be approved by the project Architect and work must be done as derected by Engineer - In-Charge. Ground Floor
First Floor
Second Floor
Third Floor
Providing and Fixing 2 millimetre thick stainless steel Cladding of 304 Q. Grade sheet about 17 kilogramme per Square Metre with box frame of Mild Steel Rectangular Pipe of Size 40 millimetre X 25 millimetre X 4 millimetre thick 0.75x0.90 metre center to center graphics includes cutting, bending, fixing of column with drilling the hole,welding the frame fixing grinding finishing, polishing etc.complete. Ground Floor
First floor
Second floor
Supply and Installation of SHERA infill wall system with seamless finish using fibre cement lining board of SHERA make (External Grade) of dimension 1220 millimetre x 8 millimetre. with advanced recessed edge, density 1300 kilogramme per cubic metre (+50) and Thermal conductivity should be minimum 0.15W/m'k and PH value of 7-8, comply to ASTM C1185 and INDIAN STANDARD ORGANIZATION 8336 part(E) for confirming durability properties. galvanised iron frame section of size 134x34x0.6 millimetre with GSM 120 coating should be used to fix boards on either face of wall with spacing of 305 millimetre between two adjacent studs and Gl track of 134x34x0.6 millimetre should be used to fix ceiling and bottom with concrete fastener of Numbers 7. MS supports wherever required for shera walls to be paid seperately. SHERA boards should be fixed in staggered pattern on both sides using SHERA Screws W 20. SHERA Light weight concrete mortar should be prepared using of politerm, cement and crushed sand used in 1:1:3 ratio with density of 700Kgs./cum is to be filled in the cavity using light weight concrete pump as specified by SHERA. SHERA jointing compound along with self adhesive SHERA Fibre mesh tape should be used with SHERA jointing compoound to achieve xseamless finish at board to board joints as per procedure approved by authority. All the gaps between wall and existing structure is to be filled with PU sealant (paintable) as mentioned in approved drawing by the authority. All doors, windows and any other openings to be boxed/covered with shera board from all sides. Ready to paint wall shall be installed at site. All work to be carried out by SHERA trained applicator. Adequate strengthening with approved mild steel sections shall be done at door frame and window locations to bring more stability to structure which will be paid seperately. Ground Floor
First Floor
Providing and applying pearl/ luster finish paint of approved colour and shade to the existing plaster surface including scaffolding, preparing the surface, applying the acrylic wall putti etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and fixing in position (as per 1868 / 1982) Aluminium sliding window of three tracks with rectangular pipe 95 x 38.10 x 0.90 millimetre at weight 0.637 kilogramme per one Running Metre with window frame bottom track section 92 x 31.75 x 1.30 millimetre at weight 1.070 kilogramme per one Running Metre . Top and side track section 92 x 31.75 x 1.30 millimetre at weight 0.933 kilogramme per one Running metre. The shutter should be of bearing bottom 40 x 18 x 1.25 millimetre at weight 0.417 kilogramme per one Running Metre Inter locking section 40 x 18 x 1.10 millimetre at weight 0.469 kilogramme per Running metre. and handle and top section 40 x 18 x 1.25 millimetre at weight o.417 kilogramme per one Running metre. As per detailed drawings and as directed by Engineerincharge with all necessary Aluminium sections fixtures and fastenings such as roller bearing in nylon casting and self locking catch fitted in vertical section of shutter including 5 millimetre thick plain glass and aluminium mosquito net shutter with stainless steel jail with all required screws and nuts etc, complete. With powder coating without box. Ground Floor
First floor
Second Floor
Third Floor
Medium Height Steel Storage @ 750Lx450Dx1200HTProviding and fixing Openable Steel Storage of 750 x 450 x 1200Ht, with 2 adjustable shelves, Complete body and shutter made in 0.8 millimetre thick and Top in 2 millimetre thick CRCA, 2 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns. with 25 millimetre. thick as per drawing. Ground Floor
First floor
Second floor
Full Height Steel Storage @ 750Lx450Dx2100HTProviding and fixing Openable Steel Storage of 750 x 450 x 2100Ht, with 4 adjustable shelves, Complete body and shutter made in 0.8 millimetre thick and Top in 2 millimetre thick CRCA, 4 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns as as per drawing. Ground Floor
First floor
Second floor
Removing brick bat coba including stacking the spoils as directed with all leads, lifts etc, complete. First floor
Second floor
Third Floor
Providing water proof bedding for flooring of Bath and water closet 25 millimetre thick in cement mortar 1:3 including using approved water proofing compound in specified proportion as per manufacturers specifications for per bag of cement including leveling, curing and covering 10 years guarantee on court fee stamp paper of Rs.500/- including ponding test etc. complete. First floor
Second floor
Providing and laying Vitrified Glossy finish having decorative type of size 1000 millimetre x 1000 millimetre of 8 to 10 millimetre thickness (for Dado) with bonding chemical and confirming to Indian Standard 15622-2006 (Group Bla) of approved make shade and pattern for dado bonding chemical filling joints curing and cleaning etc .complete. Ground Floor
First floor
Second floor
Providing and fixing mild steel grill work for windows, ventilators etc. 20 kilogramme per square metre as per drawing including fixtures, necessary welding and painting with one coats of anticorrosive paint and two coats of oil painting complete. Ground Floor
First floor
Second floor
Providing and fixing 40 millimetre diameter and 1.5 millimetre thick Stainless steel hand railing in stainless 304 Grade including fabricating ,fixtures, errecting, necessary welding, grinding, finishing, buffing to stainless steel pipe etc. complete. Ground Floor
First floor
Second floor
Providing and fixing chromium plated towel rod 16 millimetre diameter and 75 centimetre In length including all accessories complete. Ground Floor
Second floor
First Floor
Third Floor
Providing and fixing 450 millimetre 550 millimetre size superior type Belgium mirror with 16 millimetre diameter nickel plated towel rod etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Providing and applying washable oil-bound distemper of approved colour and shade toold and new surfaces in two coats including scaffolding, preparing the surfaces.(excluding the primer coat.) etc. complete. Ground Floor
Providing and fixing 10 centimere Poly vinyl chloride nahani trap with grating etc. complete. Ground Floor
Providing Autoclaved areated concrete block masonry of approved manufacture confirming to Indian Standard 2185 Part III 1984 of size 600 millimetre x 200 millimetre and thickness 100,150, 200 or 250 millimetre using Ready to use BLOCK JOINT MORTAR1:6 in foundations and plinth of inner walls / external walls including bailing out water, striking joints on unexposed faces, racking out joints on exposed faces and watering complete. First floor
Providing and fixing colour coated Zincalume ( R ) AZ150 ( min 150 gram per square metre total on each side ) profiled sheets for roofing. The feed material is manufactured out of nominal 0.45 millimetre Base Metal Thickness ( BMT ) (0.5 millimetre TCT ), Hi-strength steel with min.550 MPa yield strength, metallic hot dip coated with Aluminium-Zinc alloy (55% aluminium 43.4% zinc 1.6% silicon) with COLORBOND ( R ) steel quality super durable polyester paint coat ( with inorganic pigment). The paint shall have a total coating thickness of nominal 35 um, comprising of nominal 25 um exterior coat on top surface and nominal 10 um reverse coat on back surface. Profile sheet shall have nom. 950-1050 millimetre effective cover width and nominal 25-30 millimetre deep ribs with subtle square fluting in the five pan at nominal 180-250 millimetre center- to-center. The end rib shall be designed for anti-capillary groove. and return leg. The feed material should have coil manufacturers product details marked a regular interval. Including fasteners with min. fastened with min. 25 um Zinc-Tin alloy coated, Hex head, self-drilling screw etc. complete. (weight of profile 4.52 kilogramme per square metre ) First floor
Providing and applying two coats Apex Ultima Puranature Anti-Pollution Or equivalent approved brand, paint should decomposes organic substances and inorganic gases(NOx, VOC’s, CO, SOx, formaldehydes, etc.) in presence of natural or artificial light. It contains Graphene and nanoparticles of titanium oxide. and Absorbs CO2 (4.8 kilogramme /15 l). plaster crack should be filled by Acrylic base Crack seal/Textured Crack filler, Paint has to applied on one coat of Apex Ultima Puranature Anti-Pollution Primer or Equivalent. Warranty Should be given by the Manufaturer The work should be done by the Manufacturer Recommended applicator and he should be able to furnish stage wise onsite technical reports from the concerned company technologist. Ground Floor
First Floor
Second Floor
MEDICAL GRADE COPPER PIPING Supplying, Installation,Testing and Commissioning of Copper Pipes of 42 milliMetre Outer Diametre x 1.2 millimetre thick Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge. Ground Floor
MEDICAL GRADE COPPER PIPING Supplying, Installation,Testing and Commissioning of Copper Pipes of 28 millimetre Outer millimetre x 0.9 millimetre thick Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge. Ground Floor
MEDICAL GRADE COPPER PIPING Supplying, Installation,Testing and Commissioning of Copper Pipes of 15 milliMetre Outer DiaMetre x 0.9 milliMetre thick Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge. Ground Floor
LOCKABLE LINE VALVESSupply, Installation,Testing and Commissioning of 15 millimetre lockable line valves. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge, howeever shall be excluding Goods and Service Tax Ground Floor
LOCKABLE LINE VALVES Supply, Installation,Testing and Commissioning of 28 milliMetre lockable line valves. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge, howeever shall be excluding Goods and Service Tax Ground Floor
LOCKABLE LINE VALVES Supply, Installation,Testing and Commissioning of 42 milliMetre lockable line valves. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge, howeever shall be excluding Goods and Service Tax Ground Floor
BED HEAD PANELS Supply, Installation,Testing and Commissioning of BED HEAD WALL PANEL EUROPEAN EU CERTIFIED 1500 millimetre AS PER TENDER TECHNICAL SPECICIFICATIONS. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge, howeever shall be excluding Goods and Service Tax Ground Floor
OXYGEN SYSTEMSupply, Installation, Testing and Commissioning of Fully Automatic oxygen control panel - 1500 Litres per Minutes capacity. Fully Complies and meets with HTM02-0/NFPA99/ISO 7396-1 refer to Specification for details The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge, however shall be excluding Goods and Service Tax Ground Floor
OXYGEN SYSTEM Supply, erection, Installation, Testing and Commissioning of 12+12 Size of Main oxygen manifold complete with 24 numbers pig tail pipes and 24 numbers of non return valves with middle frame complete in all aspect. Fully Complies and meets with Health Technical HTM02-0/NFPA99/ISO 7396-1 . Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge, however shall be excluding Goods and Service Tax Ground Floor
ZONE VALVE BOX - 2 Gas Services Supply, Installation,Testing and Commissioning of Zone Valve Box.Fully Complies and meets with Health Technical Memorandum02- 0/National Fire Protection Association99/ International Organization for Standardization 7396-1. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge, howeever shall be excluding Goods and Service Tax Ground Floor
AREA ALARM Supply, Installation,Testing and Commissioning of 2 Gases Service. Fully Complies and meets with Health Technical Memorandum02- 0/National Fire Protection Association 99/ International Organization for Standardization 7396-1.Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge, howeever shall be excluding Goods and Service Tax Ground Floor
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC [1-1-9]
Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC [1-1-10]
Supplying and erecting HMS PVC conduit FRLS grade 32 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC [1-1-11]
Supplying and laying HMS PVC conduit FRLS grade 32mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC [1-1-12]
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON. [1-2-7]
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 32 mm with accessories on wall/ceiling as per specification No: WG-MA/CON [1-2-8]
Supplying and erecting GI flexible Conduit 25 mm dia. conforming to I.S. with required number of couplings, bushes, check nuts etc. complete [1-2-20]
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW [1-3-2]
Supplying and erecting green colour earthing with 1x 2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW [1-3-2]
Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW [1-3-3]
Supplying and erecting green colour earthing with 1x 4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW [1-3-3]
Supplying and erecting green colour earthing with 1x 6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW [1-3-4]
Supplying and erecting mains with 4x 6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW [1-3-4]
Supplying and erecting green colour earthing with 1x 10 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW [1-3-5]
Supplying and erecting mains with 4x 10 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW [1-3-5]
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete. [1-6-1]
Supplying and erecting modular type switch 16 / 20 A with indicator, duly erected on provided plate and box with wiring connections complete. [1-6-6]
Supplying and erecting modular type D.P. switch 32A with indicator, duly erected on provided plate and box with wiring connections complete. [1-6-8]
Supplying and erecting modular type 3 pin 6A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete. [1-6-10]
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete. [1-6-11]
Supplying and erecting modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete. [1-6-23]
Supplying and erecting PVC Surface modular switch box with double mounting plate for 2 module duly erected. [1-6-27]
Supplying and erecting PVC Surface modular switch box with double mounting plate for 6 module duly erected. [1-6-30]
Supplying and erecting PVC Surface modular switch box with double mounting plate for 12 module duly erected. [1-6-32]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 6 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-38]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 12 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-40]
Point wiring for light/bell hybrid type (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/HW [1-7-15]
Point wiring for ceiling fan (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/HW [1-7-16]
Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG-PW/SW [1-7-19]
Point wiring for ceiling fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG-PW/SW [1-7-20]
Wiring for plug on board with Switch socket surface/concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW [1-7-26]
Dismantling the existing light, fan, bell, clock, independent plug point, wiring including circuit mains of all types along with accessories etc. complete as per specification No: WG-DM/PW [1-13-1]
Dismantling the existing aluminium/copper mains, sub-mains wiring upto 10 sq.mm. along with accessories etc. complete as per specification No: WG-DM/PW [1-13-3]
Supplying and erecting LED square / circular Max. 11 W down lighter/Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 1200 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. [2-1-3]
Supplying and erecting LED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 2000 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. [2-1-5]
Supplying and erecting LED Panel Light(600mm X 600mm) Max. 35 W having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min 4200 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50 including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. [2-1-8]
Supplying and erecting anodized aluminium corridor / passage light LED fitting (4 feet) Max. 22W with high transitivity diffuser with system lumens output of Min.2200 lumens , min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block / wooden board with 3 years warranty. [2-1-18]
Supplying and erecting luminous / modular type call bell indicator with plastic body, heavy duty coil and indicator lamp working on 230V A.C. supply with resetting arrangement complete erected on double wooden/ sunmica board. [2-3-14]
Supplying and erecting bracket fan 400 mm. sweep A. C. 230 volts 50 cycles 1350 RPM. Oscillating type, plastic or metal blades chrome plated guard with speed regulator and moisture proof treatment to winding and with ‘E’ class insulation. [2-10-4]
Supplying and erecting air circulator 450 mm. sweep oscillating type, wall mounting 1440 RPM with speed regulator, overheat protection unit, totally enclosed, flame proof motor suitable for 230/250 Volts single phase, 50 cycles A.C. supply, with one meter of 3 core lead wire and with moisture proof treatment to winding and with ‘E’ class insulation. [2-10-5]
Supplying pedestal type air circulator 450 mm. sweep oscillating type suitable to work on 230 Volts 50 cycles 1440 RPM with speed regulator, metallic blades, overhead protection unit, totally enclosed, flame proof motor with additional 3 core wire, 5 meter length and hand shield type 3 pin 5A. plug top complete with moisture proof treatment and ‘E’ class insulation. [2-10-8]
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete. [2-10-13]
Supplying and erecting energy saving ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF [2-10-21]
Supplying and erecting fan clamp of 30 x 5 mm. M.S. flat of required length and 10 mm. M.S. bolt and nuts erected with necessary hook of 10 mm. M.S. round bar and painted. [2-11-3]
Supplying and erecting ‘B’ class G.I .pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire. [2-11-6]
Dismantling existing fluorescent fittings of any type & size. [2-12-1]
Dismantling the existing ceiling fan /exhaust fan / cabin fan / bracket fan complete with accessories, G.I. down rod, frame etc. and making the site clear. [2-12-4]
Supplying and erecting storage type water heater 25 litres capacity having standing loss <0.511kWh/24hour/45°C, high impact resistance engineering plastic body with anti corrosive high grade steel inner tank, heating element having hard water & corrosion protection, with minimum 3 safety protections (i.e. thermostat & thermal function cut-out, valve) with total pressure 8 bar withstanding capacity duly tested and marking sr. no. and date of erection complete. specification no. AP-WH/STWH [3-1-2]
Providing fiber reinforced PVC flexible pipe upto 1m length with brass locking nuts and washers and clips at both ends suitable for hot water and cold water both (1 set of 2 nos.) complete. [3-1-11]
Supplying, installing, testing and commissioning of split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor, room air conditioning unit 1.0TR to 1.2TR capacity having ISEER minimum 5.00 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser, minimum 2.5PM filter, self diagnosis feature, stabilizer free operation & temperature display on indoor unit, noise level maximum 50dBA at position as per specification no. APAC/ WAC [3-2-9]
Supplying, installing, testing and commissioning of split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor, room air conditioning unit 1.3TR to 1.6TR capacity having ISEER minimum 5.00 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser, minimum 2.5PM filter, self diagnosis feature, stabilizer free operation & temperature display on indoor unit, noise level maximum 50dBA at position as per specification no. APAC/ WAC [3-2-11]
Supplying, installing, testing and commissioning of split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor. room air conditioning unit 1.7TR to 2.0TR capacity having ISEER minimum 5.0 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser, minimum 2.5PM filter, self diagnosis feature, stabilizer free operation & temperature display on indoor unit, noise level maximum 50dBA at position in provided recess with wooden frame complete specification no. AP-AC/WAC [3-2-13]
Supplying, installing, testing and commissioning of split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor, room air conditioning unit 2.1TR to 2.3TR capacity having ISEER minimum 3.8 to maximum 4.39 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser, minimum 2.5PM filter, self diagnosis feature, stabilizer free operation & temperature display on indoor unit, noise level maximum 50dBA at position as per specification no. APAC/ WAC [3-2-14]
Supplying, installing, testing and commissioning of cassette type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor room Air conditioning unit 2.5TR to 2.7TR capacity having ISEER minimum 5.00 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32/R410A having copper condenser, dust filter, self diagnosis feature, stabilizer free operation, noise level maximum 50dBA at position as per specification no. APAC/ WAC [3-2-19]
Supplying, installing, testing and commissioning of cassette type room Air conditioning unit 2.8TR to 3.3TR capacity with refrigerant R32/R410A 415V, 50 Hz, A.C. supply having 1 no of air handling unit (Mega split) mounting type complete with temperature display on indoor unit, dust filter, noise level maximum 50dBA at position as per specification no. APAC/ WAC [3-2-20]
Supplying and erecting seamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigerant having 22SWG thickness and inner dia/size 12mm complete. [3-2-26]
Supplying and erecting seamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigerant having 22SWG thickness and inner dia/size 16mm complete. [3-2-27]
Supplying and erecting seamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigerant having 22SWG thickness and inner dia/size 22mm complete. [3-2-28]
Supplying, erecting, testing and commissioning of self contained water cooler 230/250V 50Hz nominal cooling capacity of 80 litres per hour and storage capacity 120 litres with partially stainless steel body as per specification no. AP-WCR/WC22 [3-3-9]
Supplying and erecting ultra violet storage type water purifier (RO+UV+UF) with softener for safe drinking water consisting of UV germicidal tube of 8W capacity choke made of copper wire and two indicator lamps with output of purified water minimum 0.33 litre/min with activated carbon filter and softener operating on 230V, single phase A.C. supply with UV fail & filter change indication system .(for TDS more than 200) [3-5-1]
Supplying, installing, testing and commissioning of 20kVA capacity online pure sine wave, with backup time of 2 hrs. PWM & IGBT based UPS with 0.9 to unity output pf, 3 phase input and 3 phase output complete with all protections as per specification no. AP-UPS (Trauma ICU-2 no,blood bank-1no,office-1) [3-7-8]
Supplying and erecting 12V/100Ah SMF battery with battery terminal wire, duly charged with 24 months warranty complete. [3-8-12]
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. [3-11-77]
Dismantling the existing electric geyser or storage type water heater of any size along with plumbing connections and making the site clear. [3-12-1]
Dismantling the existing split type air conditioner of any type and capacity safely without any damages and making the site clear. [3-12-3]
Supplying and erecting elastomeric nitrile rubber / foam tube type sleeves for coating and insulating on provided PC / copper pipes having 9 mm thickness and inner diameter / sizes 12 mm for solar water heater/AC system. [4-2-9]
Supplying and erecting elastomeric nitrile rubber / foam tube type sleeves for coating and insulating on provided PC / copper pipes having 9 mm thickness and inner diameter / sizes 16 mm for solar water heater/AC system. [4-2-10]
Supplying and erecting elastomeric nitrile rubber / foam tube type sleeves for coating and insulating on provided PC / copper pipes having 9 mm thickness and inner diameter / sizes 22 mm for solar water heater/AC system. [4-2-12]
Supplying and erecting triple pole mini feeder pillar with 500V, 300A FPMCCB as incomer and 3 outgoing circuits with HRC fuse base and cartridge of 100A with aluminium bus bar erected in 14 SWG CRCA sheet box with supporting angles, self locks, gasket having IP54,IK10 protection and slanting top to be erected on provided foundation as per specification no. SW-SWR/MFP [5-2-2]
Supplying, erecting and marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-2]
Supplying, erecting and marking SPMCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-3]
Supplying, erecting and marking DPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-6]
Supplying, erecting and marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-11]
Supplying, erecting and marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-13]
Supplying and erecting triple pole and neutral distribution board (TPNDB), SPMCB of 4 ways/phase (12 poles), with door, 1.2mm thickness, surface/flush mounted, IP 43 protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB [5-4-1]
Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB [5-4-8]
Supplying and erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame. [5-4-13]
Supplying and erecting triple pole and neutral distribution board (TPNDB), 3 pole/ 4 pole MCCB as incomer & outgoing SP MCB (12 poles) or TP MCB of 4 ways (12 poles), with door, 1.2mm thickness, surface/flush mounted, on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1 [5-4-15]
Supplying and erecting triple pole and neutral distribution board (TPNDB), 3 pole/4 pole MCCB as incomer & outgoing SP MCB (24 poles) or TP MCB of 8 ways (24 poles), with door, 1.2mm thickness, surface/flush mounted, on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1 [5-4-16]
Providing and erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-1]
Providing and erecting 4 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-1]
Providing and erecting 3 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-2]
Providing and erecting 4 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-3]
Supplying, fixing, and commissioning 2 pole, RCBO 6/10/16/20/25A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO [5-6-9]
Supplying, fixing, and commissioning 2 pole RCBO 32/40A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO [5-6-10]
Supplying, fixing, and commissioning 4 pole RCBO 32/40A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO [5-6-13]
Providing and erecting floor/wall mounting, MCCB panel board, with door, suitable for four pole incoming 250A, 12 ways four pole outgoing, up to 100 A MCCBs on iron frame, as per specification no. SW-SWR/MCCBPB. (Excluding MCCBs) [5-7-5]
Providing and erecting incoming and outgoing cable alleys suitable for MCCB panel board with door, 250A incoming and 12 way outgoing or 400A incoming and 6/8 way outgoing made from CRCA sheet 1.6 mm thick duly powder coated and having vertical insulated partition for shielding between the shared face of cableway and DB. [5-7-15]
Providing and erecting prewired meter module suitable for MCCB panel board with CTs and emfs VIF meter. [5-7-17]
Supplying and erecting SS enclosure for MCCB suitable for up to 100A MCCB. [5-11-17]
Dismantling Dismantling the existing switchgears, DB, and bus bar of any size complete with/ without board or angle iron frame [5-12-1]
Dismantling Dismantling any type of unserviceable feeder pillar, switch gear panel, capacitor panel, metering panel, bus-bar panel, electronic equipment panel, etc. and making the site as required, Approx. size (up to 150 cm x 70 cm x 45 cm ) - Small Cupboard [5-12-4]
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. [6-1-19]
Supplying and erecting bus bar chamber triple pole with neutral with four aluminium bars, 500V 200A having 25mm (Width) X 5 mm (Thickness) , with 99.9 % aluminium purity as per E91E Grade & Current Density 0.8 A per sq. mm. compliance to IS 5082 and Enclosure fabricated with 16 SWG CRCA sheet and epoxy paint, with suitable number of ways and with SMC/DMC Insulators and accessories of suitable rating complete as per specification no. CP-BB [6-2-2]
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 25 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-15]
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-17]
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-19]
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-20]
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½core 240 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-23]
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 16 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-29]
Supplying and laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 250 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. [7-6-7]
Supplying and laying (including excavation) of suitable width & depth up to 90 cm) 160 mm outside dia, double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete. [7-6-14]
Providing and erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 100 mm height comprising all required standard accessories. [7-11-1]
Providing and erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 200 mm width & 100 mm height comprising all required standard accessories. [7-11-2]
Dismantling the existing cables of all types & size up to 10 sq mm. [7-12-1]
Dismantling the existing cables of all types & size above 10 sq mm up to 50 sq.mm. [7-12-2]
Dismantling the existing cables of all types & size above 50 sq mm. [7-12-3]
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials, testing & recording the results as per specification no. EA-EP [9-1-2]
Providing earthing with copper earth plate size 60 x 60 x 0.315 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover with minimum 25 kg Carbon based environment friendly back fill Ground Enhancing compound complete with all materials, testing & recording the results as per specification no ESE -LA [9-1-6]
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP.(25X3 mm strip 350 mtr x 0.670 kg/mtr) [9-2-2]
Excavating hard Rock or bituminous road by chiselling for preparing pit for pole / stay/earth plate / for laying cable/ pipe & clearing the site by removing debris & making the site as required complete.(0.5*0.5*72) [16-1-5]
second class Burnt Brick masonry with conventional /I.S. type bricks in cement mortar 1:6 in foundation sand plinth of inner walls /in plinth external walls including bailing out water manually, striking joints on unexposed faces, raking out joints on exposed faces and watering etc. Complete.(1.2*0.9*1)*12 nos [16-2-1]
Providing and fixing reinforced cement concrete cover of size 60 cm x 45 cm with frame over inspection chamber etc. complete of medium duty (100 Kilogram). [16-2-4]
Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing or any other purpose). [16-3-7]
Supplying and laying HMS PVC conduit FRLS grade 20 mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 40 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting PVC box trunking of size 75x50 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 1 module complete duly erected.
Supplying and erecting 2 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW
Supplying and erecting 20 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW
Supplying and erecting 50 pair, 0.5mm dia, jelly filled unarmoured telephone copper cable with poly-al laminate moisture barrier, laid in provided PVC casing capping/conduit as per specification No. WG-TW
Supplying and erecting 15m HDMI cord low voltage grade minimum 4k compliant to be laid in provided conduits with male/female 19 pin HDMI connectors complete.
Supplying, Erecting and Commissioning of MDF Box 200x200 pairs made from min. 1.5mm thick MS sheet as per specification no. WG-TW
Supplying, Erecting and Commissioning of 20 pairs FR junction box with moulded plastic enclosure as per specification no. WG-TW
Supplying, Erecting and Commissioning of 50 pairs FR junction box with moulded plastic enclosure as per specification no. WG-TW
Supplying, Erecting and Commissioning of 10 pair module for connection & disconnection of telephone cable as per specification no. WG-TW
Supplying, Erecting and Commissioning of push button telephone instrument desk top/wall mount with caller ID & Speaker unit as per specification complete.
Supplying, Erecting and Commissioning of IP telephone instrument as per specification complete.
Supplying and installing cat-6 cable suitable for networking as per specification no. WG-COC/NC
Supplying and erecting LSZH armoured multimode optical fibre cable with 6 fibres, core dia 50/125 µm (OM3), suitable upto 10 GBPS, ethernet distance at 850 nm of wavelength, on wall/ceiling or laid in provided pipe/trench as per specification no. WG-COC/OFC LSZH
Supplying and fixing 1 m UTP patch cord of Cat 6 type in position as per specification No. WG-COC/PC
Supplying and fixing 3 m UTP patch cord of Cat 6 type in position as per specification No. WG-COC/PC
Supplying and pluging 3 m fibre patch cord LC-SC MM (50) OM4 LSZH duplex complete as per specification no. WG-COC/FPC
Supplying, fixing, and configuring 8-ports managed gigabit, Layer-2 switch, 10/100/1000 base-T, POE smart switch plus 2 SFP erected in provided rack complete.
Supplying, fixing, and configuring 24 ports, POE switch in provided rack as per specification No. WG-NWC/ENS
Supplying, fixing, and configuring 24 ports with 4 (SFP+) port, ethernet managed switch with web view/CLI, 6KV surge protection on ethernet port and console port for management in provided rack as per specification no. WG-NWC/GBS
Supply Installation commissioning of 4 MP Full HD IP Dome /Bullet Camera Image Sensor 1/3" 4 megapixel progressivescan CMOS Effective Pixels 2304 (H) × 1296 (V) Electronic Shutter Speed Auto/Manual 1-1/100000 s Min. Illumination 0.5 lux F2.1 (Color); 0 lux (IR LEDs on IR Distance - nUp to 100 ft (30 m) Day/Night -auto (ICR)/Color/BW Backlight Compensation - BLC/HLC/DWDR White Balance - Auto/Manual Gain Control - Auto/Manual Noise Reduction - 3D Privacy Masking- Up to 4 areas Lens Focal Length- 2.8 mm Horizontal Angle of View 92° 86°-28 Compression H.265 (Main/High/Baseline Profile) /MJPEG Resolution 3 MP (2304×1296) 1080p Main Stream 4 MP 30 fps 16x Digital zoom 60 fps Resolution- Verifocal lens 320 db Corridor Mode Support Network Protocol IPv4/IPv6 HTTP HTTPS TCP/IP UDP UPnP ICMP IGMP RTSP RTP SMTP NTP DHCP DNS PPPoE DDNS FTP IP Filter QoS Compatibility -nONVIF Profile S CGI Max. User Access 20 users Mobile App - for iPhone iPad Android Phone and Tablet Power Supply PoE (802.3af) 12 V DC Working Environment -22°F to 140°F (-30°C to 60°C); 10% to 100% RH condensing Ingress Protection IP66 Vandal Resistance - IK10 Regulatory FCC Part 15B Class B (3 years warranty)
Supplying, fixing, and configuring 20 SFP ports + 4 Combo SFP 10/100/1000 Base-T erected in provided rack complete.
Supplying, fixing, and configuring 1-port mini-GBIC SX MM fibre transceiver (up to 550m, support 3.3V power) erected in provided rack complete.
Supplying, installing & testing UTP connector (RJ-45) as per specification No. WG-NAS/UTPC.
Supplying and erecting Supplying erecting testing & commissioning of NVR 32 Channel professional series 4K HD Network Video Recorder . Smart H.265+/H.265/Samrt H.264+. Max 320Mbps Incoming Bandwidth .Up to 12MP Resolution for Preview& Playback . Bit Rate 16Kbps~20Mbps per channel . 2HDMI/2VGA simultaneous video output to enhance the storage eliability when the network break down . Quad-Core embeded processor . 8 SATA III Ports Up to 6 TB for each HDD for 48TB Storage 2 RJ45 port (10/100/1000Mbps) Independent of Joint Networking. Analytical Features Like - ANPR People Count Face Detection Missing/Abondoned Objects Tripwire and Intrusion alarms Smart FAN to achive High Cooling Effect .Automatic Network the video data stored on the camera. (3 years warranty)
Supplying and fixing tool-less IO (Ethernet) flush/surface type in provided modular box as per specification no. WG-NAS/IO
Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no. WG-NAS/PP
Supplying and fixing 12 ports light guide unloaded interconnect unit, rack mounted type, with adapter panel for termination of optical fibre cables in provided U rack complete as per specification no. WG-NAS/LIU
Supplying and fixing 24 ports light guide unloaded interconnect unit, rack mounted type, with adapter panel for termination of optical fibre cables in provided U rack complete as per specification no. WG-NAS/LIU
Supply and Installation of 4 TB (7200 RPM) Surveillance hard disk 4 TB storage capacity with SATA support 6GB/s NCQ 64 MB cache 3.5 inches
Supplying and fixing 1 x 12 duplex adapter panel - SC complete
Supplying and fixing SC/LC type multimode duplex adapter to couple two connectors between OFC & Fibre switch/Fibre module as per specification no. WG-NAS/MMA
Supplying and fixing SC/LC type multimode pigtails (OM3) for LIU to terminate OFC in LIU as per specification No. WG-NAS/LIU2
Supplying and fixing 9U wall mount rack (Dimension-DxWxH – 500x600x500 mm) as per specification No. WG-NAS/RAK
Dismantling the existing Telephone / LAN / WAN / TV cables and wires of all sizes along with casing-capping / conduit complete as per specification No: WG-DM/PW
SSupply installation and commissioning of 42” Full HD Commercial LED Display /Monitor 42 inches or higher Full HD VGA DVI HDMI LAN USB RGB RS 232C IN/OUT AV IN COMPONENT IN AUDIO IN/OUT WIFI READY SPEAKERS
Supplying and erecting modular type telephone socket one gang with safety shutter, duly erected on provided plate and box with wiring connections complete.
ELECTRICAL CONTROL PANEL FOR MAIN PANEL ROOM Fabricating & Supply installing testing and commissioning of Main Electrical control panel( Size : 1.60 Mtr X 1.80 Mtr X 1.0 Mtr ). INCOMING 1 nos. 800A 4P ACB electrical draw out type (50 KA) 1 Sets of 800 Amps. Aluminium Bus bars with colour coded heat shrinkable PVC sleeves 1 Set of RYB indicating lamps with individual MCB 1 No. flush mounted panel meter suitable rated current transformers 1 No. 0-500V. All Incomer shall be with surge protection OUTGOING FEEDER FOR MAIN PANEL - 200 A FP MCCB ( 1 Nos. ), 250 A FP MCCB ( 2 Nos.) & 400 A FP MCCB (3nos.) All the components shall be housed in a common cubical made of 16 swg. M.S.sheet .The panel shall be powder coated of approved colour both inside & out side. The panel shall have both bottom & top cable entry provisions and panel shall be mounted on Pedestal of 300 mm height with necessary accessories etc completed.Panel shall be as per IS 61439 (Part- 3)
Dismantling Dismantling existing OCB, ACB, LBS, VCB complete from existing panel board in an approved manner.
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½core 400 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL ( 30 Mtr X 2 Run X 4 nos. of panel = 240 Mtr )
Providing and erecting epoxy outdoor / indoor end termination kit for LT XLPE armoured cable 400 sq mm., with necessary material as per specification No. CB-JT/LT
Providing and erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 500 mm width & 100 mm height comprising all required standard accessories.
Dismantling the existing cables of all types & size above 50 sq mm.
Supplying, installing & testing maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete, and recording the results Specification no. EA-MOBI
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP. ( 25 X 3mm = 0.67 X 50 Mtr = 33.50 Kg)
Shubham EPC Private Limited
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf