Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.2 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹44.9 L+₹3.5 L (8.50%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN L1 | |
| 3 | L3₹45.7 L+₹4.3 L (10.3%)Rejected-Finance 6 RAILWAY STATION ROAD ONKAR INDUSTRIES GULAMALI PURA BAHRAICH UTTAR PRADESH 271801 | BAHRAICH | UTTAR PRADESH | 271801 | L3 | Rejected-Finance OTHER THAN L1 | |
| 4 | L4₹55.7 L+₹14.3 L (34.5%)Rejected-Finance R O WARD NO 08 H NO 108 DHAR ROAD UDHAMPUR TEHSIL DISTT UDHAMPUR 182101 | UDHAMPUR | UDHAMPUR | JAMMU KASHMIR | 182101 | L4 | Rejected-Finance OTHER THAN L1 |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
29 Aug 2022, 6:00 pmClosed
GE (UTILITIES) UDHAMPUR
GE (UTILITIES) UDHAMPUR, PO-GARHI, PIN-182121
Repair/Maintenance of external Electric Supply, Water Supply and DG Sets alongwith connected works at certain different locations under GE (Utilities) Udhampur.
2022_MES_542484_1
GE/U-39/2022-23
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (UTILITIES) UDHAMPUR
Please refer Tender documents
8 documents required · 8 mandatory
₹500
GE (UTILITIES) UDHAMPUR
₹90,000
Yes
20 Sept 2022
1 Aug 2022
31 Aug 2022
1 Aug 2022
29 Aug 2022
15 Aug 2022
Amount
Dehydration including filtration and cleaning of Voltage stabilizer oil by dehydrating machine including testing of sample before and after dehydration and filtration and replacement of silica gel complete all as specified and directed by Engr-in-Charge. Note:- Dehydration machine and testing kit will be provided by the Deptt. but transpotation of machine is the responsibility of Contractor without any extra cost to the Deptt. Sample testing will be carried out in the presence of Engr-in-Charge on site.
Pouring of up to the appropriate level Voltage stabilizer oil of low viscosity having dielectric strength not less than 60 KV complete all as specified and as directed by Engr-in-Charge. Note:- Dielectric strength test shall be carried out at site before poring/filling in transformers in the presence of Engr-in-Charge on the site.
Defect rectification of LT 1.1 KV cable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pules, ECHO fault locator with high frequency distance calculator for cable of any size XLPE 11 KV / 1.1 KV complete all as specified and directed by Engr-in-Charge.
Supply, jointing and testing Straight through cable joint heat shrinkable including all material and accessories suitable for 4 core X 25-95 Sqmm XLPE cable of 1100 volts (E)grade complete all as specified and directed by Engr-in-Charge. Make / Model :- Birla 3 M Ltd, raychem rpg. Note : Cost of Prepration of existing end deemed to be included in unit rate.
Comprehensive maintainance of oil cooled servo voltage stablizer capacity 200 KVA by isolating ,disconnecting of input/output ,supply cable,opening of top of voltage stablizer,detecting of fault ,u/s component in control panel /dimmerstat /PCB etc,cleaning of serviceable parts/ component ,including preparation of old painted steel surface by brushing /cleaning strain grease /oily spots with thinner and two coats of spray painting with spray machine & replacement of worn out spare parts etc, complete all as specified and directed by Engr-in-Charge.
Lightening arrestors(in replacement) expulsion type complete with all fittings, suitable for 11000 Volts grade transmission class, discharge capacity 65KA including brackets, clamps, nuts, washers and connecting to 4mm dia GI earth wire complete all as specified and directed by Engr-in-Charge.
11000 volts grade disc type insulator (in replacement) porcelain vitreous 145mm hight, 255mm dia ball and socket type white or brown or green with tension clamps complete all as specified and directed by Engr-in-Charge.
Pin type porcelain vitreous white or brown or green insulator (in replacement) including one galvanized mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000 volts grade complete all as specified and directed by Engr-in-Charge.
MS Channel/angle iron/flat iron (in replacement) of required size and bend to shape as in cross arms, bracing and support including, MS clamps back plates with bolts, nuts, and washers drilled for insulators including painting with two coats of synthetic enemel paint (Aluminium shade) over a coat of red oxide primer complete all as specified and directed by Engr-in-Charge.
Supply, fixing and erecting steel tubular swaged poles erected to truly vertical or planted as strut complete with 6mm thick mild steel base plate(300mmx300mm), welded to pole, finial taper plug, bolts, nuts, and screws poles made out of ERW MS tubing conforming to IS-2713 Part-II Type 410 SP-55, 11.0 mtr long including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bitumenous paint internally and portion embedded in concrete, making five black & white bands at lower portion of pole, each 300mm wide alternately upto the height and marking pole No. with black paint at suitable height including making two nos holes of suitable size in steel tubular pole by gas welding for passing PVC cable connection from junction box to security lights through pole where junction box to be fitted in pole, complete all as specified and directed by Engr-in-Charge. Note: Cost of Excavation, Earth Work and PCC in foundation are deemed to be included in quoted rate.
MCCB 4 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA complete all as specified and directed by Engr-in-Charge.
MCCB 4 Pole, 415 V, fixed type, 125 Amps with breaking capacity 16 KA complete all as specified and directed by Engr-in-Charge.
MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge.
MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge.
Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed by Engr-in-Charge.
Earthing complete with Galvanized earth plate electrode 600 mm x 600mm x3.15mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level ) with top edge plate not less than 1.5 metre below normal ground level and covered with alternate compact layer of common salt and charcol dust, connected to Galvanized earth strip of size 20x3mm as earthing lead by means of bolts, nuts, chuck nuts and washers of Copper earth lead including PCC pit in PCC 1:2:4, type B-1, CI pit cover of size 30cm x 30cm x 10mm with angle iron frame and handle, GI medium grade watering pipe 20mm bore and funnel with wire mesh, light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and connected to earthing test point complete all as specified and directed by Engr-in-Charge. Note 1: On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engr-in-Charge. Note 2:- Cost of following items are deemed to be included in unit rate. a.Earth strip & protection GI pipe upto 7.5 mtr of size 40 mm. b.20 mm nominal bore light grade GI pipe for provision of watering. c. Requisite quantity of common salt and charcoal. d. Testing of earthing.
Copper strip 20 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and directed by Engr-in-Charge.
Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled, screwed including 3 nos. 8mm dia 25mm long hexagonal head screw & brezing all joints complete all as specified and directed by Engr-in-Charge.
Disconnecting the bindings of loose overhead conductor of LT/HT lines from insulators and restringing the same for proper sag and rewinding with new aluminium winding wires at insulators, making all jumpers and inter connections of conductors at cut points as well as turnings using PG clamps of suitable size as per size of conductor for any type of conductor including restringing of continuous GI earth wire complete all as specified and directed by Engr-in-Charge. Note :- (i) Trimming of tree branches upto 3 m all around the conductors is deemed to be included in the rates quoted. (ii) Three ACSR conductors and two GI earth wire will be measured as one unit length for payment. (iii) Cost of PG clamps, aluminium winding wire and eye hook for GI earth wire are included in the rates quoted for restringing.
Multi function meter input 3 Phase 4 Wire, Voltage Range 415V AC (L-N)/520V AC(P-P), Display Parameter : Voltage (p-p) (P-L), Amp (R,Y,B) Current : 0-5A , CT 05-6000A insttalled on LT panel including necessory wiring, CT of required size complete all as specified and directed by Engr-in-Charge. Make: Multispan Cat Pat No AVF-19N or equivalent in Schneider, L&T.
Supply, laying, jointing and testing of XLPE insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5 core X 185Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed by Engr-in-Charge.
All as per serial item No 22.00 here-in-before but of size 3.5 core X 95 sqmm.
All as per serial item No 22.00 here-in-before but of size 3.5 core X 70 sqmm.
All as per serial item No 22.00 here-in-before but of size 3.5 core X 35 sqmm.
All as per serial item No 22.00 here-in-before but of size 4 core X 25 sqmm.
All as per serial item No 22.00 here-in-before but of size 4 core X 16 sqmm.
All as per serial item No 22.00 here-in-before but of size 2 core X 10 sqmm.
Excavation in trenches not exceeding 1.5 m wide and and not exceeding 1.5 m depth in Hard/dense soil and getting out complete all as specified and directed by Engr-in-Charge.
Returning, filling in, with excavated soil including spreading, levelling, watering and well ramming in layers not exceeding 25 cm, complete all as specified and directed by Engr-in-Charge.
Removal of surplus soil to distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed by Engr-in-Charge.
Cutting of existing road width not excecding 0.60 m and depth n-exc 1.5m and M&L for repair of road as per existing cross section of road complete all as specified and directed by Engr-in-Charge.
DWC ( Double wall corruated ) pipe 120 x 103 mm conforming to IS 14930/ IS 16205 for protection of LT / HTCable of size 95 sqmm including neccesory Snap-Fit cupler required for fixing complete all as specified and directed by Engr-in-Charge.
All as per serial item No 16.00 here-in-before but of size 90/76 mm for XLPE cable 3.5 core X 95 sqmm.
All as per serial item No 16.00 here-in-before but of size 77/63 mm for XLPE cable 3.5 core X 70 sqmm-10 smmm.
Supply ,installation ,testing and commissioning (in replacement) of feeder pillar box Kiosk type ,LT(415 Volts, 50 Hz , 3-phase, 4 wire supply) floor mounted , factory assembled, outdoor type weather and vermin proof (Protection Class IP-54) made out of 40m x 40mm x 6mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet with front hinged opening, rubber lining, locking arrangement ,powder coated externally and internally after seven tanks treatment and lifting channel, fully compartmentalized design complete Bus Bar chamber comprising incomer MCCB 315 Amp, 4 Nos aluminium strip bus bars air insulated and PVC sheathed capacity 400 Amps with colour coding complete all as specified and directed by Engr-in-Charge.
On load change over switch 200 Amps, front handle, 415 Volt, 4 pole 50 Hz, including neccesory addition / alteration in panel for mounting and providing Busbar, Nut bolts & Washers complete all as specified and directed by Engr-in-Charge. Make : Havells Cat part No IHCNFO0200 or equivalent in L&T/HPL.
On load change over switch 125/100 Amps, front handle, 415 Volt, 4 pole 50 Hz, including neccesory addition / altration in panel for mounting and providing Busbar, Nut bolts & Washers complete all as specified and directed by Engr-in-Charge. Make : Havells Cat part No IHCNFO0125 or equivalent in L&T/HPL.
On load change over switch 63 Amps, front handle, 415 Volt, 4 pole 50 Hz, including neccesory addition / altration in panel for mounting and providing Busbar, Nut bolts & Washers complete all as specified and directed by Engr-in-Charge. Make : Havells Cat part No IHCNFO0063 or equivalent in L&T/HPL.
Weather proof street light junction box of size 300 x 200 x 105mm including MCB SP 6 Amps and connecting terminals 4 way and fixing with street light poles using necessary MS clamps, nuts, bolts washers, lugs for incoming and out going cables gland for cable etc of suitable size complete all as specified and as directed by Engr-in-Charge. Make : Hensel/Sintex/Universal Switch Gear control. Note : The rates quoted are inclusive of provision and fixing of suitable lugs and glands for cable connection.
Cleaning the existing exposed surfaces of steel tubular pole of 9.0 mtr long including cross arms, brackets, clamps etc and painting with two coats of aluminium paint marking five black & white bands at lower portion of pole, Each 300 mm wide alternately and marking pole No. with yellow paint on black base at suitable height complete all as specified and directed by Engr-in-Charge.
120 Watt LED Flood light (in replacement) with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 110 lumen/Watt (Minimum lumen output of luminarie should be 16500 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engr-in-Charge.
60 Watt LED street light fittings (in replacement) with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 6000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engr-in-Charge.
All as per serial item No 43.00 here-in-before but for LED street light fittings of size 90 watt capacity.
Bracket for street light fitting made of 40mm bore light grade GI tube bent to shape required, suitable for fixing on pole including fixed with bolts, nuts, washers duly painting the bracket with two coats of aluminium paint over a coat of zinc chrome primer complete including taking down the existing bracket and refixing and connecting up the light fitting etc complete all as specified and directed by Engr-in-Charge.
Automatic timer switch (in replacement) pole mounted enclosure consisting of ON/OFF switch, Digital Timer Device, power contactor 40 Amps, 4 pole, MCB 40 Amps, TP - 03 Nos, enclosure made of rust proof, shock proof, conforming to IP -54 complete all as specified and directed by Engr-in-Charge. Make : Kakatiya/Healer/Bajaj. Note: (i) Inlet/outlet connecting cable PVC insulated aluminium stranded conductor 6 Sqmm, 4 single core for incoming & outgoing up to 8 Mtr deemed to be included in the unit rate. (ii) Provn of glands and lugs shall be deemed to be included in the quoted rate.
PCC M-10(1:3:6), type C-1 (using 20 mm graded stone aggregate) as in coping etc including necessary form work and finishing the surface of PCC above ground level with cement mortar 1:4, 5mm thick complete all as specified and directed by Engr-in-Charge.
PCC M-7.5 (1:4:8), type D-2 (using 40 mm graded stone aggregrate in foundation, mass concrete) as in foundation of poles & stay etc complete all as specified and directed by Engr-in-Charge.
Gun Metal globe or Gate valve iron wheel head screwed both ends for iron pipes of size 50mm dia bore complete all as specified and directed by Engr-in-Charge.
All as per serial item No 49.00 here-in-before but of size 25 mm bore.
All as per serial item No 51.00 here-in-before but of size 20 mm bore.
All as per serial item No 51.00 here-in-before but of size15 mm bore.
Taking down carefully old GI pipe of size 20/15 mm bore and setting aside for reuse if found serviceable complete all as specified and directed by Engr-in-Charge.
All as per serial item No 53.00 here-in-before but of size 25 mm bore.
All as per serial item No 53.00 here-in-before but of size 40 mm bore.
All as per serial item No 53.00 here-in-before but of size 50 mm bore.
Supply, laying, testing GI tubing 15 mm dia bore medium grade conforming to IS : 1239 with all fittings laid in trenches complete all as specified and directed by Engr-in-Charge.
All as per serial item No 57.00 here-in-before but of size 20 mm bore.
All as per serial item No 57.00 here-in-before but of size 25 mm bore.
All as per serial item No 57.00 here-in-before but of size 40 mm bore.
All as per serial item No 57.00 here-in-before but of size 50 mm bore.
Supply and laying CI pipe line with spigot and socket ends and centrifugaly cast class A in any length laid in trenches of size 80 mm dia complete all as specified and directed by Engr-in-Charge.
All as per serial item No 62.00 here-in-before but of size 100 mm bore.
All as per serial item No 62.00 here-in-before but of size 150 mm bore.
Cast iron flanged drilled heavy duty (in replacement) sluice valve with ISI mark with stainless steel spindle and check nut and plan PN-1.6 complete with rubber insertion nuts and bolts with washers of size 100 mm bore etc complete all as specified and directed by Engr-in-Charge.
Brick masonry valve pit chamber of size 900x900x900mm internal size complete with excavation, earth work and brick work in CM 1:6, 15mm thick plastering in CM 1:4 internally including 5mm thick MS Sheet cover and angle iron frame of suitable size and two coats of synthetic enamel paint over one coat of red oxide primer complete with locking arrangement including demolition of old existing unserviceable valve pit chamber complete all as specified and directed by Engr-in-Charge.
Drilling and tapping cast iron water mains (in position) for branch connections of the internal dia 15 mm complete all as specified and directed by Engr-in-Charge.
Drilling and tapping cast iron water mains (in position) for branch connections of the internal dia 20 mm complete all as specified and directed by Engr-in-Charge.
Rectification of defective run lead joint by burning out lead joint in position including recovering lead and making new lead joint for 150 mm bore including bailing out water coming from defective joints by means of electric/diesel driven pump set, testing of the joint under full working pressure for the following CI Pipe lines complete all as specified and directed by Engr-in-Charge.
All as per serial item No 69.00 but of size100mm dia.
Supply, installation, testing and commissioning in repair of outdoor type,weather proof, LT Panel made out of 3.15 mm thick CRCA steel sheet mounted on 60 cm long legs made out of 50 x 50 x 6 mm equal angle,embedded in PCC 1:2:4 type B-1 blocks of size 15 x 15 x 20 cm, front and back openable,double door openable up to minimum 150 deg. & removable type having magnetic catche system, lockable / openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable for 3 phase 4 wire 415 volts 50 Hz, factory febricated with suitable foamed-in PU gasket to make it dust/vermin proof , IP 54 protection, Powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliest for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produce to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels.complete, suitable cable glands for cable entry. The panel shall be suitable to accomodate the following equipments: - (a) Aluminium bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 600 amps for Phases neutral - 01 set.
Febrication of MS sheet of 3.15 thick, for making provision of cable entry at bottom of panel including taking down LT cable from the existing panel and refixing the same after inserting the cable gland, necessory cutting, welding painting included in the quoted rate complete all as specified and directed by Engr-in-Charge.
Supply, jointing and testing End Termination cable joint heat shrinkable including all material and accessories suitable for XLPE cable of 1100 volts (E)grade size upto 50 Sqmm X 4 core/ 3.5 core complete all as specified and directed by Engr-in-Charge. Make / Model :- Birla 3 M Ltd, raychem rpg. Note : Cost of Prepration of existing end and new thimble deemed to be included in unit rate.
All as per serial item No 73.00 here-in-before but for 70 sqmm 3.5 core to 150sqmm 3.5 core XLPE cable.
All as per serial item No 73.00 here-in-before but for 185 sqmm 3.5 core to 300 sqmm 3.5 core XLPE cable.
Dismantling /opening of alternator of DG Set by disconnection of cable connections and flexible coupling, nuts/bolts and alternator foundation nut, bolts including strip opening of alternator and checking out burnt out parts of DG Sets of capacity 100KVA to 200 KVA and taken back in temporary platform complete all as specified and directed by Engr-in-Charge.
All as per Sr item No. 76 here-in-before but for DG Sets of capacity 40KVA to 75 KVA.
All as per Sr item No. 76 here-in-before but for DG Sets of capacity 10KVA to 31.25 KVA.
Taking out burnt armature, winding wire and rewinding of armature with super enameled copper winding wire of existing gauge for 10KVA to 200 KVA set wire DG sets complete all as specified and directed by Engr-in-Charge. Make: Atlas/Devi Dayal.
Taking out burnt field coil and rewinding of field coil with super enameled copper winding wire of existing gauge for 10KVA to 200 KVA sets complete all as specified and directed by Engr-in-Charge. Make: Atlas/Devi Dayal.
Insulation of armature with Class ‘B’ insulation and Varnishing of armature winding and drying up to desired temperature for 100 KVA to 200 KVA DG Sets complete all as specified and directed by Engr-in-Charge.
All as per Sr item No. 81 here-in-before but for DG Sets of capacity 40KVA to 75 KVA.
All as per Sr item No. 81 here-in-before but for DG Sets of capacity 10KVA to 31.25 KVA.
Insulation of field coils with Class ‘B’ insulation and varnishing of field coils and drying up to desired temperature for 100KVA to 200 KVA Alternator of DG Sets.
All as per Sr item No. 84 here-in-before but for DG Sets of capacity 40KVA to 75 KVA.
All as per Sr item No. 84 here-in-before but for DG Sets of capacity 10KVA to 31.25 KVA.
Burnt rectifier of size 2” x 2” x 24 plate (In replacement) set of three complete all as specified and directed by Engr-in-Charge.
Re-assembling of rotor and stator after rewinding and re-fixing of Alternator with Engine by assembling flexible coupling with alternator mounting with nuts, bolts including making cable connection complete including testing and commissioning at desire load of DG Set of capacity 100KVA to 200KVA complete all as specified and directed by Engr-in-Charge.
All as per Sr item No. 88 here-in-before but for DG Sets of capacity 40KVA to 75KVA.
All as per Sr item No. 88 here-in-before but for DG Sets of capacity 10KVA to 31.25 KVA.
Dismantling of radiator and repair by welding/soldering of radiator and re-fixing the same after cleaning of radiator with soda and acid including replacement of radiator foundation nuts, bolts (where ever required) complete all as specified and directed by Engr-in-Charge.
Fuel Injector Pump ( in replacement) complete all as specified and directed by Engr-in-Charge. Make : Cat Part No.03.247.10.0.00 Kirloskar or as approved by GE.
Wiring harness assembly ( in replacement) suitable for silent complete all as specified and directed by Engr-in-Charge. Make: Cat Part No,02.946.10.0.00 Kirloskar or as approved by GE.
Controller/ PCB ( in replacement) with (± / - 15VDC) out put for hall effect sensor complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.02.732.13.0.00 of Kirloskar or as approved by GE.
Actuator ( in replacement) with spring (sedemac make) complete all as specified and directed by Engr-in-Charge. Make: Cat Part No. 4H .1720.01.0.00 of Kirloskar or as approved by GE.
V belt A46 (in replacement), complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.02.071.01.0.00 of Kirloskar or as approved by GE.
V belt (AX 50) (in replacement), complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.06.337.01.0.00 of Kirloskar or as approved by GE.
V belt (AX 48) (in replacement), complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.06.338.01.0.00 of Kirloskar or as approved by GE.
V belt Belt (AX 52) (in replacement) complete all as specified and directed by Engr-in-Charge. Make: Rawedge cog Cat Part No.06.353.01.0.00 of Kirloskar or as approved by GE.
V belt (A46) (in replacement) complete all as specified and directed by Engr-in-Charge. Make: Rawedge cog Cat Part No.06.354.01.0.00 of Kirloskar or as approved by GE.
V belt A-47 (in replacement) complete all as specified and directed by Engr-in-Charge. Make: Rawedge cog Cat Part No.04.140.01.0.00 of Kirloskar or as approved by GE.
V belt AX 51 (in replacement) complete all as specified and directed by Engr-in-Charge. Make: Rawedge cogCat Part No.04.249.01.0.00of Kirloskar or as approved by GE.
V belt AX 49 (in replacement) complete all as specified and directed by Engr-in-Charge. Make: Rawedge cog Cat Part No.04.249.02.0.00 of Kirloskaror as approved by GE.
V belt AX 43 (in replacement) complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.04.250.01.0.00 of Kirloskar or as approved by GE.
V belt (AvX 10 -1265L) (in replacement) Blower Pulley complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.04.668.01.0.00 of Kirloskar or as approved by GE.
V belt (AvX 10 -1136L) (in replacement) for alternator Pulley complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.04.669.01.0.00 of Kirloskar or as approved by GE.
Belt guard ( in replacement) complete all as specified and directed by Engr-in-Charge. Make:Cat Part No.04.141.01.0.00 of Kirloskar or as approved by GE.
Filter Header ( in replacement) (For L.O & Fuel filter) complete all as specified and directed by Engr-in-Charge . Make: - Cat part No.04.268.01.0.00 of Kirloskar or as approved by GE.
Cyl.Head Subassly ( in replacement) with valves complete all as specified and directed by Engr-in-Charge. Make: - Cat part No.04.291.30.0.00 of Kirloskar or as approved by GE.
Lub oil filter mounting assembly ( in replacement) complete all as specified and directed by Engr-in-Charge. Make: - Cat part No.03.041.10.0.00 of Kirloskar or as approved by GE.
Battery terminal ( in replacement) batteries of capacity upto 12 Volt 180 AH.inculding nuts and bolts of DG set capacity 10KVA to 200KVA complete all as specified and directed by Engr-in-Charge.
Leak OFF pipe assly (in replacement) complete all as specified and directed by Engr-in-Charge. Make: Cat part No.03.721.10.0.00 of Kirloskar or as approved by GE.
Set of high pressure pipes (in replacement) complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or as approved by GE.
Lub pipe ( in replacement ) complete all as specified and directed by Engr-in-Charge. Make: Cat part No.02.074.02.0.00 of Kirloskar or as approved by GE.
Start Stop card RB electronics (in replacement ) complete all as specified and directed by Engr-in-Charge. Make: Cat part No.03.963.48.0.00 of Kirloskar or as approved by GE.
Nozzle Leak OFF pipe assly (in replacement) complete all as specified and directed by Engr-in-Charge. Make: Cat part No.04.815.20.0.00 of Kirloskar or as approved by GE.
Realy board (in replacement)8ch ,2c/o,12DC complete all as specified and directed by Engr-in-Charge. Make: Cat part No.04.931.11.0.00 of Kirloskar or as approved by GE.
Fuel Pipe (in replacement) for filter (pre- filter to take unit) complete all as specified and directed by Engr-in-Charge. Make: Cat Part NO.03.635.16.0.00 of Kirloskar or as approved by GE.
Fuel return pipe (in replacement) complete all as specified and directed by Engr-in-Charge. Make : Cat Part NO.03.635.17.0.00 of Kirloskar or as approved by GE.
1.1 Ltr Duel Fuel filter (in replacement) w/o over flow valve complete all as specified and directed by Engr-in-Charge. Make: Cat Part NO.03.656.20.0.00 of Kirloskar or as approved by GE.
Air cleaner assembly (Air cleaner + Strap) ( ( in replacement)) suitable DG Set for capacity 10KVA to 200KVA complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.04.587.10..0.00 of kirloskar or as approved by GE.
Residential Slienicer (in replacement) suitable DG Set for capacity 10KVA to 200KVA complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.02.538.10.0.00 of Kirloskar or as approved by GE.
Injector (in replacement ) with nozzle complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.02.481.01.0.00 of Kirloskar or as approved by GE.
Servicing of DG Set, draining out used Engine oil of DG Set and cleaning sump completely with re-filling of engine oil 15 W 40 in sealed drum after taking out un-serviceable engine oil from oil sump complete all as specified and directed by Engr-in-Charge. Note :- Oil 15W40 shall be measured and paid separetely under relevant item as supply only.
Fuel filter (primary and secondary) (in replacement) of DG Set of capacity 100KVA to 200KVA complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or as approved by GE.
Fuel filter (primary and secondary) ( in replacement) of DG Set of capacity 40KVA to 75KVA complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or as approved by GE.
Fuel filter (primary and secondary) (in replacement) of DG Set of capacity 10KVA to 31.25KVA complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or as approved by GE.
Oil filling body(in replacement) for DG Set capacity of 100KVA to 200KVA complete all as specified and directed by Engr-in-Charge. Make :- Kirlolskar or as approved by GE.
Oil filling body ( in replacement) for DG Set capacity of 40KVA to 75KVA complete all as specified and directed by Engr-in-Charge. Make:- Kirlolskar or as approved by GE.
Oil filling body (in replacement ) for DG Set capacity of 10KVA to 31.25KVA complete all as specified and directed by Engr-in-Charge. Make - Kirlolskar or as approved by GE.
Hose (H.Exchanger to W.Pump) ( in replacement) complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.6H.1145.03.0.00 of Kirloskar or as approved by GE.
Turbo charger ( in replacement) for HA 494TC Stage III complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.04.750.01.0.00 of Kirloskar or as approved by GE.
Engine start push button ( in replacement ) Green colour 'NO' contact( vasihno make,cat no.2xvaf,flush type) complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.03.918.17.0.00 of Kirloskar or as approved by GE.
Engine stop push button (in replacement) Red colour 'NO' contact( vasihno make,cat no.2xvaf,flush type) complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.03.918.18.0.00 of Kirloskar or as approved by GE.
Cylinder Head assly (in replacement ) complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.04.684.70.0.00 of Kirloskar or as approved by GE.
Combine leak off pipe ( in replacement) (Injector to fuel filter) complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.04.755.03.0.00 of Kirloskar or as approved by GE.
Alternator starter 12 Volts(in replacement) of DG Sets complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.06.033.01.0.00 of Kirlskar or as approved by GE.
Alternator starter 24volts (in replacement) of DG Sets complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.06.034.06.0.00 of Kirlskar (Lucas) or as approved by GE.
Governer Assembly ( in replacement ) 100KVA to 200KVA complete all as specified and directed by Engr-in-Charge. Make: Kirlskar (Lucas) or as approved by GE.
Governer Assembly (in replacement ) 10KVA to 75KVA complete all as specified and directed by Engr-in-Charge. Make: Kirlskar (Lucas) or as approved by GE.
Stop solenoid assembly 12V DC(in replacement) for micro pump (two coil) heavy duty electrical control make energise to stop of DG Sets complete all as specified and directed by Engr-in-Charge. Make : Cat Part No.04.770.10.0.00 of Kirloskar or as approved by GE.
Battery cable assembly ( in replacement) ( -ve & +ve ) 4 length suitable complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.02.950.10.0.00 of Kirloskar or as approved by GE.
Variable speed DC genset controller(in replacement) complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.02.735.01.0.00 of Kirloskar or as approved by GE.
Battery cable assembly(in replacement) complete all as specified and directed by Engr-in-Charge.
Inter connection battery cable lead (copper) (in replacement ) with terminal size 35 sq mm (30 cm long) complete all as specified and directed by Engr-in-Charge.
Supply and filling coolent for radiators. K Cool super Plus -50-50 premix.Cat part No.82.020.35.1.25. 25ltrs Packing complete all as specified and directed by Engr-in-Charge. Make : Super Plus or as approved by GE.
AVR S/F variable speed DCDG (in replacement ) suitabler for DG Sets of capacity 100KVA to 200KVA complete all as specified and directed by Engr-in-Charge. Make :- Kirloskar or as approved by GE.
AVR S/F variable speed DCDG ( in replacement) suitabler for DG Sets of capacity 10KVA to 75KVA complete all as specified and directed by Engr-in-Charge. Make :- Kirloskar or as approved by GE.
Disttled water for battery complete all as specified and directed by Engr-in-Charge.
Flexible pipe of M30 X 1.5 union (replacement) both side,1400mm long complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or as approved by GE.
Supply only Engine Oil 15W 40 in sealed drum complete all as specified and directed by Engr-in-Charge.
Drain Pipe of DG Sets (in replacement) of capacity 10KVA to 200KVA complete all as specified and directed by Engr-in-Charge. Make:- Cat Part No.6H.1187.02.0.00 of Kirloskar or as approved by GE.
Over hauling of Fuel injector pump of DG set by taking down carefully, transprotation of the same to civil work-shop for repair & complete service of FIP pump and calibration on automatic setting machine, shifting of FIP pump from civil work-shop to worksite and re-fixing the same to DG set and testing 100KVA to 200KVA complete all as specified and directed by Engr-in-Charge.
Over hauling of Fuel injector pump of DG set by taking down carefully, transprotation of the same to civil work-shop for repair & complete service of FIP pump and calibration on automatic setting machine, shifting of FIP pump from civil work-shop to worksite and re-fixing the same to DG set and testing 10KVA to 63KVA complete all as specified and directed by Engr-in-Charge.
Dismantling / Taking down the 31.25KVA DG Set (Engine and Alternator ) assembly / parts for carrying out / replacement of following spare parts at site and re-assembling the DG Set after repair and testing complete. Note: Spare parts replaced shall be measured and paid as supply only under following items :-
Supply only Piston Ring set complete all as specified and directed by Engr-in-Charge. Make: Cat Part No..2H.009.10.0.00 of Kirloskar/Cummins
Supply only Cylinder liner with joints rings complete all as specified and directed by Engr-in-Charge. Make: Cat Part No2H.008.10.0.00 of Kirloskar/Cummins
Supply only valve cylinder head assly complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.4H.007.40.0.00 of Kirloskar/Cummins
Supply only valve seat insert (inlet) complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.4H.007.03.0.00 of Kirloskar/Cummins
Supply only valve Guide Cyl head complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.4H.007.02.0.00 of Kirloskar/Cummins
Supply only Valve collet (3-grove)lock complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.02.022.28.0.00 of Kirloskar/Cummins
Supply only Cylinder head gasket complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.3H.009.06.0.00 of Kirloskar or as approved by GE.
Supply only Sets of Jointst(Engine Gasket set complete) complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.3H.074.20.0.00 of Kirloskar/Cummins.
Supply only Crank oil seal front complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.03.013.06.0.00 of Kirloskar/Cummins.
Supply only Crank oil seal rear complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.03.007.06.0.00 of Kirloskar/Cummins
Supply only Thrust washer complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.4H.003.02.0.00 of Kirloskar/Cummins
Supply only connecting rod bearing(cell) complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.H.073.4.10.013 of Kirloskar/Cummins
Supply only Main general bearing(cell) complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.M..073.4.00.013 of Kirloskar or as approved by GE.
Supply only Fuel Filter Element complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.3H.132.01.0.00. &Cat Part No.3H.132.02.0.00 of Kirloskar/Cummins
Supply only Oil Filter Element complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.3H.078.02.0.00 of Kirloskar/Cummins
Supply and filling of Engine oil 15/30 complete all as specified and directed by Engr-in-Charge. Make :- Castrol or as approved by GE.
Supply only Connecting rod bush complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.C.073.6.00.003 of Kirloskar/Cummins.
Supply only wiring harness assembly (LOP,ELECTRICAL,LOT,START,WITHOUT ALTERNATOR) complete all as specified and directed by Engr-in-Charge. Make:- Cat Part No.02.567.10.0.00 of Kirloskar/Cummins
Supply only Oil pump assly complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.03.010.50.0.00 of Kirloskar/Cummins
Supply only Piston assembly complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.0185-5914 of Kirloskar/Cummins
Supply only Harness,wiring engine KTA -38 complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.AX1013031 of Kirloskar/Cummins
Supply only Fan Belt complete all as specified and directed by Engr-in-Charge. Make :- Cat Part No.02.637.01.0.00 of Kirloskar/Cummins
Supply only Copper Washer complete all as specified and directed by Engr-in-Charge. Make :- Cat part No 4H.087.30.0.00 of Kirloskar/Cummins
Supply only Fuel pipe set complete all as specified and directed by Engr-in-Charge. Make :- Cat part No 03.052.03.0.00. and 03.052.07.0.00 of Kirloskar/Cummins
Supply only Air Cleaner Element complete all as specified and directed by Engr-in-Charge. Make :- Cat part No .4H.1810.01.0.00 of Kirloskar/Cummins
Supply and filling of K Oil Super One liters Can of coolent complete all as specified and directed by Engr-in-Charge.
Supply only of Expansion below from 3R - valve genset complete all as specified and directed by Engr-in-Charge. Make :- Cat part No .4H.1810.01.0.00 of Kirloskar/Cummins
Supply only variable speed DC Gen Set controller complete all as specified and directed by Engr-in-Charge. Make:- Cat part No .Cat Part No. 02.735.01.0.00 of Kirloskar/Cummins.
Supply only AVR Make:-Kirloskar complete all as specified and directed by Engr-in-Charge.
Supply only Residential Slienicer complete all as specified and directed by Engr-in-Charge. Make: Cat Part No.02.538.10.0.00 of Kirloskar or as approved by GE.
Repair /Turner job of Cylinder head assly (valve set fitting,valve guide fitting,valve grinding and fitting (turner job) by taking out from DG set carefully, transportation of the same to civil work-shop for repair & complete service and calibration on automatic setting machine and civil work-shop to worksite complete all as specified and directed by Engr-in-Charge.
Repair /Turner job of Self starter 12 volt by taking out from DG set carefully, transportation of the same to civil work-shop for repair bearing/bush,rewinding of armature solenied switch & complete service on automatic setting machine and civil work-shop to worksite complete all as specified and directed by Engr-in-Charge.
Repair /Turner job of Crank shaft by taking out from DG set carefully, transportation of the same to civil work-shop for repair & complete service and calibration on automatic setting machine and civil work-shop to worksite complete all as specified and directed by Engr-in-Charge.
Repair /Turner job of Alternator assly 12volt,taking out from DG set carefully, transportation of the same to civil work-shop for repair rewinding , replacae bearing & complete service and calibration on automatic setting machine and civil work-shop to worksite complete all as specified and directed by Engr-in-Charge.
Repair /Turner job of Fuel injector pump(FIP),Injector assly,Pump element,delivery valve,and i nozzel,taking out from DG set carefully, transportation of the same to civil work-shop for repair & complete service and calibration on automatic setting machine and civil work-shop to worksite complete all as specified and directed by Engr-in-Charge.
Dismantling of radiator and repair by welding/soldering of radiator and re-fixing the same after cleaning of radiator with soda and acid including replacement of radiator foundation nuts, bolts complete all as specified and directed by Engr-in-Charge.
Repair/Replacement of s96 Voltmeter 0-500v AC AE/Rish complete all as specified and directed by Engr-in-Charge. Make:- Cat Part No. 02 856 31 0 00 of AE/Rish.
Repair/Replacement of s96 Ammeter AC AE/Rish complete all as specified and directed by Engr-in-Charge. Make:- Cat Part No. 02 856 32 0 00 of AE/Rish.
Rubbing the uneven as well as open surface of DG set of capacity ranging from 10 KVA to 100 KVA with emery paper, cleaning all the grease and oil substances over the area. applying two coats of synthetic enamelled paint as per existing colour code or complete all as specified and directed by Engr-in-Charge.
Battery 12volt 180Ah (in replacement) complete all as specified and directed by Engr-in-Charge.
Indicator lamp (LED type) fitting ( in replacement) with neon lamp in three colour (Red/Green/Yellow) complete all as specified and directed by Engr-in-Charge.
Set of Joints ( in replacement) complete all as specified and directed by Engr-in-Charge. Make: Cat Part No. 4H 087.05.0.00 of Kirloskar or as approved by GE.
12V,DC Relay Card ,1CH,Ic/o (in replacement ) with complete all as specified and directed by Engr-in-Charge. Make: Conform Cat Part No. 006025753H91 of Mahindra or as approved by GE.
Start stop card (in replacement) RB electronics complete all as specified and directed by Engr-in-Charge. Make: Cat Part No. 03.963.48.0.00 of Kirloskar or as approved by GE.
Water pump ( in replacement) assembly complete all as specified and directed by Engr-in-Charge. Make:- Cat Part No. 03.963.48.0.00 of Kirloskar or as approved by GE.
Oil pump (in replacement) assembly 10KVA to 45 KVA complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or as approved by GE.
Oil pump (in replacement ) assembly 62.5KVA to 200 KVA complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or as approved by GE.
Rocker (in replacement) assembly complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or as approved by GE.
GI strip of size 32mmx6mm with suitable nuts & bolts complete all as specified and directed by the Engr-in-Charge.
Dismantling the broken door of sound proof canopy of the DG set ranging from 10 KVA to 100 KVA and taking it to nearest workshop for repair. Repairing the door with new hinges & nut bolts etc and re-assembling the same at existing position & testing for proper opening & closing of the doors, including repair of the locking system, if required complete all as specified and directed by Engr-in-Charge. Note: The rate quoted deemed to include the cutting/ drilling/welding work.
Carbon Bush of DG Sets of Capacity 10 KVA to 200KVA (Set of three) complete all as specified and directed by Engr-in-Charge.
Radiator Baco with Fan complete all as specified and directed by Engr-in-Charge. Make:- Cat Part No.4H. 1205.92.0.00 of Kirloskar or as approved by GE.
Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 metre below normal ground level) connected to and including galvanized iron earth strip 32x6 mm dia by means of bolts nuts check nuts and washers of galvanized iron or steel including PCC pit in PCC 1:2:4 type B-1, CI pit cover of size 30cm x 30cm x 10mm with angle iron frame and handle, GI medium grade watering pipe 20mm bore and funnel with wire mesh light grade protection pipe 40 mm bore upto main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by Engr-in-Charge. Note: On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge
Gasket (For cyl head) 1.22 thick( replacement) complete all as specified and directed by Engr-in-Charge. Make: Cat Part Nol 4h. 007.24.0.00 of Kirloskar or as approved by GE.
Opening / taking out of injector with nozzle of DG set of any type / make capacity 15KVA to 320KVA disconnection and opening of fuel injector assembly, carrying complete overhauling /servicing fuel injection system with including replacemant of injector repair kit including cailbration of injector, checking of pressure complete for each injector and re-assembling the same, fitted with DG set properly in original location checking the alignment making proper fuel connection, testing for smooth operation complete all as directed by Engr-in-Charge.
Oil pressure Sensor(in replacement) complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or as approved by GE.
Water temperature Sensor ( in replacement) complete all as specified and directed by Engr-in-Charge. Make:- Kirloskar or as approved by GE.
Hooter (in replacement) ,12v DC,IOTA/DSS/EQUIV complete all as specified and directed by Engr-in-Charge. Make: Cat Part No. 02. 944.13.0.00 of of Kirloskar or as approved by GE.
proach associates
MOHAN LAL AND SONS
slathia construction works
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .