Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.1 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹24.1 L+₹870 (0.04%)Rejected-Finance | L2 | Rejected-Finance Rejected due to L2 | |
| 3 | L3₹27.3 L+₹3.1 L (13.1%)Rejected-Finance | L3 | Rejected-Finance Rejected due to L3 | |
| 4 | L4₹28.3 L+₹4.2 L (17.5%)Rejected-Finance | L4 | Rejected-Finance Rejected due to L4 | |
| 5 | L5₹28.8 L+₹4.7 L (19.3%)Rejected-Finance NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L5 | Rejected-Finance Rejected due to L5 |
Tender Value
₹43 L
EMD Value
₹86,000
Closing Date
29 Nov 2023, 6:00 pmClosed
Garrison Engineer (Army) No 2 Jodhpur
MILITARY ENGINEER SERVICES, GARRISON ENGINEER (ARMY) NO 2, MULTAN LINES, JODHPUR - 342010
PROVISION OF WATER METER AT RATANADA PUMP HOUSE (PH), AJMER LINE PH , LANCER LINE PH, MULTAN LINE PH, SHIKARGARH PH AND OLD SHIKARGARH OHT UNDER GE (ARMY) NO 02 AT ARMY AREA JODHPUR
2023_MES_626156_1
8800/23-24/58/05/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer (Army) No 2 Jodhpur
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Garrison Engineer (Army) No 2
₹86,000
Yes
9 Jan 2024
1 Nov 2023
1 Dec 2023
1 Nov 2023
29 Nov 2023
15 Nov 2023
Amount
Supply, Installing,Testing and Commissioning of Full Bore Electromagnetic Flow Meter with 4-20 mA output, convertor and digital display along with flow totaliser suitable for line size of 300 mm dia : Make -Endress hauser / Krohne Marshall / ABB / Yokogawa ( NOTE- The meter must be compatible with PLC panel and gateway modem for real time info.)
Supply, Installing,Testing and Commissioning of Full Bore Electromagnetic Flow Meter with 4-20 mA output, convertor and digital display along with flow totaliser suitable for line size of 250 mm dia : Make -Endress hauser / Krohne Marshall / ABB / Yokogawa NOTE- (The meter must be compatible with PLC panel and gateway modem for real time info.)
Supply, Installing,Testing and Commissioning of Full Bore Electromagnetic Flow Meter with 4-20 mA output, convertor and digital display along with flow totaliser suitable for line size of 200 mm dia : Make -Endress hauser / Krohne Marshall / ABB / Yokogawa NOTE- (The meter must be compatible with PLC panel and gateway modem for real time info.)
Provision of 4G sim card connection in the name of the GE/AGE E/M or as required by the Engineer in charge with 1 year data subscription charges from the date of commissioning of system..
Supply, Installation, Testing & Commissioning of Indoor type Programmable Logic Controller based Automation Panel. The panel shall be floor mounted of Size 600x600x200mm, fabricated from 1.6 mm thick CRCA sheet properly powder coated with angle iron support frame of size 40x40x6mm. The Panel shall be suitable for control and Monitoring of 01 no Flow Meter,. The Panel shall consist of (i) PLC with CPU, Power Supply, suitable no. of digital inputs / outputs and analog inputs / outputs, expansion modules, RTC and 02 nos. Communication Ports (ii) HMI - 4 line LCD display with 15 sealed membrane keys & 1 No. Communication Ports, (iii) SMPS of 5 A rating, (v) MCB - 2P, 10 A, (vi) 0.5 sqmm multistarnded internal wiring with ferruling and suitable lugs. (vii) GPRS enabled wirless modem, Omni directional antenna and PLC to modem communication cord etc. (viii) Suitable no. of interposing relays 24 V D.C. and 230 V A.C. coil rating and 6 A contact rating The PLC and Panel shall perform the follwing function (a) GPRS based on line realtime wieless communicaion with the Central SCADA Station
Cutting existing DI line of size 200 mm and inserting Elctromagnetic flow meter with fitting and flange work, including earth work and bailing out line water complete. Note- Flow meter shall be measured & paid under respective items. Ii) Rate inclusive for DI / CI fitting up to 300mm.
Cutting existing DI line of size 250 mm and inserting Elctromagnetic flow meter with fitting and flange work, including earth work and bailing out line water complete. Note- Flow meter shall be measured & paid under respective items. Ii) Rate inclusive for DI / CI fitting up to 300mm.
Cutting existing DI line of size 300 mm and inserting Elctromagnetic flow meter with fitting and flange work, including earth work and bailing out line water complete. Note- Flow meter shall be measured & paid under respective items. Ii) Rate inclusive for DI / CI fitting up to 300mm.
Excavating in trenches for manually soft/loose soil, n exc 1.5 m wide and n exc 1.5 m in depth; for taking out anytype of water tubing, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out
Returning, filling in any type of soil including spreading, levelling, watering and well ramming in layers not exc 25 cm.
Removing excavated surplus soil to a distance not exceeding 50M where directed and at a level not exceeding 1.5 M above the starting point.
Suppy & Fixing on wall including suitable saddle and spacers 6 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, Copper cable .
Suppy & Fixing on wall including suitable saddle and spacers 2 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, Copper cable .
Supplying and laying of Un-reinforced precast concrete cable cover class LV, type 1, flat size 250mmx150mmx40mm and abutting each other with gap between adjacent precast concrete cable cover not exceeding 10mm over underground cable for protection.
Material and labour for sand cushioning to underground cable screened un-washed river sand and punning for cushioning as per technical data to the cable all as specified and as directed by EIC.
Supplying and laying GI pipe light B Class of size 40mm to protect underground cable for road and footpath crosing.
Material and labour for cutting the road for laying of pipe and repair the same with road repair material (Patch mat) all as directed as site width of road cutting would be 0.3 to 1.0 Metre.
M&L for replacement in earthing complete with galvanized steel earth plate electrode, 60Cm X60 Cm X 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 Mtr deep below ground level) with top edge of the earth plate not less than 1.5 Mtr below normal ground level, connected to galvanized earth strip 32x6 mm by means of galvanised iron or steel with 40mm dia GI pipe light grade for protection of earth strip and all as shown in electrical plate No. 3 connected to elelctrical equipments all as specified or indicated including Exc & earth work, constn of PCC pit with RCC cover, watering pipe 20mm dia light grade with funnel & wire mesh & testing on completion all as directed. cost of earth strip of size 32x6mm up to 7.5 mtr deemed to be included in the rate quoted by contactor
Integrate modification of the program and creation of additional screen and soft keys to faciliate remote monitoring and operation of the PLC base slave panels incorporated.Work includes modification of the existing SCADA system and its formats so as to include the status of the said automation slave panels in the reporting software
S.G.ENGINEERING COMPANY
RISING ELECTRICALS
Siddharth Constructions
Anil Builders
Harsh Enterprises
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .