| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹2.9 CrAccepted-AOC | ₹2.9 Cr Quoted ₹3.0 Cr | L-1 | Accepted-AOC L-1 Bidder |
| 2 | L-2₹3.0 Cr+₹3.7 L (1.23%)Rejected-Finance 71 GOLA MAHAL SADAR BAZAR BARRACKPORE KOLKATA 700120 | 24 PARAGANAS NORTH | WEST BENGAL | 700120 | ₹3.0 Cr+₹3.7 L (1.23%) | L-2 | Rejected-Finance Other than L-1 Bidder |
| 3 | L-3₹3.9 Cr+₹91.5 L (30.7%)Rejected-Finance | ₹3.9 Cr+₹91.5 L (30.7%) | L-3 | Rejected-Finance Other than L-1 Bidder |
Tender Value
₹3 Cr
EMD Value
₹3.8 L
Closing Date
10 Nov 2022, 6:00 pmClosed
HQ CE SILIGURI ZONE
HQ CE SILIGURI ZONE, MES, SEVOKE ROAD, PO SALUGARA, DIST JALPAIGURI, PIN 734008 (WB)
PROVN OF RCC OVERHEAD WATER STORAGE TANK AT A ZONE OF BENGDUBI MIL STN UNDER GE BENGDUBI
2022_MES_555152_1
98742/BENG/SZ/E8 (CA No.CESZ/BENG/08 OF 2022-23)
Open Tender
Civil Works
Lump-sum
540 days
BENGDUBI
Please refer Tender documents.
8 documents required · 8 mandatory
₹2,000
GE BENGDUBI
₹3.8 L
Yes
HQ CE SILIGURI ZONE
6 Dec 2022
29 Sept 2022
17 Nov 2022
29 Sept 2022
10 Nov 2022
27 Oct 2022
29 Sept 2022 - 13 Oct 2022
14 Oct 2022
Amount
BUILDINGS / INFRASTRUCTURE WORKS (SCH 'A' PART-I)
Lump sum price worked out by the Contractor for “(BUILDINGS / INFRASTRUCTURE WORKS)” as listed in Schedule ‘A’ Part-I. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 2,49,39,600.00 inserted by the MES in Schedule ‘A’ Part-I.
SITE CLEARANCE AND SITE DEVELOPMENT INCLUDING EARTHWORK AND EXCAVATION (SCH 'A' PART-II)
Lump sum price worked out by the Contractor for “(SITE CLEARANCE AND SITE DEVELOPMENT INCLUDING EARTHWORK AND EXCAVATION)” as listed in Schedule ‘A’ Part-II. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 98,003.58 inserted by the MES in Schedule ‘A’ Part-II.
INTERNAL WATER SUPPLY (SCH 'A' PART-III)
Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part-III. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 14,841.02 inserted by the MES in Schedule ‘A’ Part-III.
INTERNAL ELECTRIFICATION (SCH 'A' PART-IV)
Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part-IV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 67,237.10 inserted by the MES in Schedule ‘A’ Part-IV.
ROAD, PATH & CULVET (SCH 'A' PART-V)
Lump sum price worked out by the Contractor for “ROAD, PATH & CULVERT” as listed in Schedule ‘A’ Part-V. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 2,55,296.34 inserted by the MES in Schedule ‘A’ Part-III.
SEWAGE DISPOSAL (SCH 'A' PART-VI)
Lump sum price worked out by the Contractor for “(SEWAGE DISPOSAL)” as listed in Schedule ‘A’ Part-VI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 31,086.14 inserted by the MES in Schedule ‘A’ Part-VI.
DEMOLITION & DISMANTLING (SCH 'A' PART-VII)
Lump sum price worked out by the Contractor for “DEMOLITION & DISMANTLING” as listed in Schedule ‘A’ Part-VII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 6,27,020.34 inserted by the MES in Schedule ‘A’ Part-VII.
EXTERNAL WATER SUPPLY (SCH 'A' PART-VIII)
Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part-VIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,78,968.07 inserted by the MES in Schedule ‘A’ Part-VIII.
EXTERNAL ELECTRIC SUPPLY (SCH 'A' PART-IX)
Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIC SUPPLY” as listed in Schedule ‘A’ Part-IX. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 2,74,071.23 inserted by the MES in Schedule ‘A’ Part-IX.
MISCELLANEOUS ITEMS REQUIRED FOR B/R & E/M SERVICES (Sch 'A' Part-X)
INTERNAL ELECTRIFICATION S&F LED light 1X 10 W (or nearest next higher wattage) (4 feet), 5700 K, wall / surface mounted, integrated type with aluminium housing and caps with integrated high efficiency electronic driver and surge suppressor of 2 KV or more, luminare efficiency > 95 lumes / watt, power factor > 0.90, operating range - 140 to 270 V, 50 Hz fixed with 02 Nos. of PVC round / square blocks, screws etc complete with all accessories internally prewired and connecting up complete all as specified and directed.
S&F energy saving and environmental friendly long life LED 20 Watt building security light made up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having TOP opening with driver compartment, IP66 protection with other accessories and necessary electric connection complete all as specified and directed.
S&F BLDC ceiling fan 1200 mm sweep, 350 RPM single phase 220-240 Volts, AC 50 Hz, 26 Watts, p-f 0.99, Air delivert 220 CMM with down rod, canopy, remote control and provision of cable 3 core of size 0.5 Sqmm (16/0.2 mm) from ceiling rose to fan including writing of MES No. 2 cm height with synthetic enamel paint complete all as specified and directed. MAKE : Havells Efficiencia Neo 1200 mm or equivalent as approved by GE.
S&F exhaust fan PVC body with louvers 150 mm sweep, 1200 RPM single phase 230 Volts, AC 50 Hz, with Air delivery 280 m3/min, gravity open / close shutter including provision of cable 3 core of size 0.5 Sqmm (16/0.2 mm) from ceiling rose to fan including writing of "Consumer No." 2 cm height with synthetic enamel paint complete all as specified and directed.
S&F wall fan 400 mm sweep, 1350 RPM, single phase 240 Volts, AC 50 Hz, 55 Watts, Air delivert > 65CMM and connecting up complete all as specified and directed. MAKE : Havells madel - Aindrila premium or equivalent model of Bajaj / Crompton.
SEWAGE DISPOSAL On site Hume pipe septic tank conventional designed to carry sewage and sullage water, excavation in in any type of soil, PCC (1:4:8) below foundation, vent shaft, connection etc, complete for 10 user complete all as specified and directed.
M&L construction of 10 users soakage well all as specified and shown on drawing.
EXTERNAL WATER SUPPLY M&L for grouting in concrete bolts with nuts and washers of size 300 mm long 12 mm dia and anti vibration pad for pumping set and pump motor foundation all as directed.
Installation only existing centrifugal pumping set of capacity 15 HP to 20 HP to the position complete with anti vibration pad as directed, connecting all electrical cables, pipes and complete testing including necessary two coats of synthetic enamelled paints after preparation of surface over a coat of red oxide primer and including taking down from its existing position existing complete all a specified and directed.
S&F foot valve conforming to IS-4038 (ISI marked) 100 mm size complete all as specified and directed.
Supply, installation, testing & commissionig of Cl Non-Return (Reflux) Valve 100 mm bore, both end flanged, class PN 1.6 (ISI marked) conforming to IS 5312 (Part I & ll) including making new flanged joints with 3 mm thick rubber gasket with necessary bolts, nuts, washer etc of Suitable size complete all as speciied and as directed.
S&F for sluice valve cast iron body class PN-1.6 grade with SS spindale both end flanged and GM valve sheet and iron wheel conforming to IS: 14846 including all materials required such as 3 mm thick rubber gusket, bolts, nuts washers drilled of size 250mm bore, (ISI marked) complete all as specified and as directed.
Supply, Jointing and laying in trenches in standard length , centrifugally cast (spun) ductile iron (DI) pressure pipes,with inside cement mortar lining and black bitumen external coating, nominal daimeter, class K-9 classification, confirming to IS-8329 (ISI marked), including pushon and rubber gasket joints and jointing necessary DI specials etc including testing, complete all as specified for the ind and laying pipe ductile Iron ,S/S including specials class K9 of 100 mm dia complete all as specfied and directed. NOTE : DI specials/ fittings will be measured and paid separately under relevent items of Schedule
Supply, Jointing and laying in trenches in standard length , centrifugally cast (spun) ductile iron (DI) pressure pipes,with inside cement mortar lining and black bitumen external coating, nominal daimeter, class K-9 classification, confirming to IS-8329 (ISI marked), including pushon and rubber gasket joints and jointing necessary DI specials etc including testing, complete all as specified for the ind and laying pipe ductile Iron ,S/S including specials class K9 of 150 mm dia complete all as specfied and directed. NOTE : DI specials/ fittings will be measured and paid separately under relevent items of Schedule
Supply, Jointing and laying in trenches in standard length , centrifugally cast (spun) ductile iron (DI) pressure pipes,with inside cement mortar lining and black bitumen external coating, nominal daimeter, class K-9 classification, confirming to IS-8329 (ISI marked), including pushon and rubber gasket joints and jointing necessary DI specials etc including testing, complete all as specified for the ind and laying pipe ductile Iron ,S/S including specials class K9 of 250 mm dia complete all as specfied and directed. NOTE : DI specials/ fittings will be measured and paid separately under relevent items of Schedule
S & F of DI pipe fittings class K-12 bends (any type, radius and angel) tapers any type (straight, bend, increasing, decreasing or double socket etc) tee pieces single brancehs 'Y' junction double branch, cross (all socket or socket and spigot) collars, caps and plugs for DI pipe upto 150 mm bore of pipes complete all as specified and directed.
S & F of DI pipe fittings class K-12 bends (any type, radius and angel) tapers any type (straight, bend, increasing, decreasing or double socket etc) tee pieces single brancehs 'Y' junction double branch, cross (all socket or socket and spigot) collars, caps and plugs for DI pipe upto 200 to 300 mm bore of pipes complete all as specified and directed.
M&L for construction of brick masonry valve pit of size 1200x1200x1200mm (internal dimension) one brick thick wall in CM 1:4 on 100mm thick PCC 1:4:8 type D-2 (40mm graded aggregate) as in foundation, and 15mm thick rendering in cement mortor (1:4) internally, externally up to 15cm below GL, providing valve pit cover made of 5 mm thick MS sheet/plate, welded with 50 X 50 X 6mm angle iron frame fixed on top of valve pit by means of hold fast 150mm long, embeded in PCC 1:2:4 type B-1 (20mm graded aggregate) block of size 230 x 200 x 100mm and provision of hinges, handle and locking arrangement including two coats of anti-corrosive paint over a coat of red oxide zinc chrome primer and necessary excavation and earth work in soft/loose soil including dismantling of existing valve pit complete all as specified & directed.
Supply, installation, testing and commissioning 3 phase and neutral, 415 volts indoor type LT Panel Board, IP-43, CPRI approved, factory fabricated & factroy assembled , waterproof,dust and vermin proof cubical type with locking arrangement , LT Penal made out of suitable size angle iron, channel and fabricated from 3.15 mm thick (minimum) CRCA sheet with anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032), independently housing for each control switch gear and indicating lamps with & including busbars made of copper duly insulated with heat retardent fire proof (HRFR) heat shrinkable sleeves of relevant colours. Bus bar shell be properly supported/mounted on epoxy insulators. All live parts and joints shall be insulated with (HRFR) shrouds, conforming to IS, including provn for cable gland and lugs for incoming and out going cable and connecting suitable earth strips. Suitable openable doors shall be provided of all operational switchgear and MCCBs and detchable cover shall be provided on all other accessories. Grouting the pillar box in ground with & including suitable size foundation & plinth of PCC 1:3:6(type C-1 using 20 mm grade stone aggregate) complete. Penal shall be manufactured suitable for housing and including the following duly control wiring with multistranded copper condutor FRLS with colour coding incl connection with copper lugs complete for 3 phase 50 Hz electric supply. Item Continued as 10.20
Supply, commissioning, erecting and testing complete of manufacturer or OEM manufactured, static silent with eccoustic enclosure Diesel Engine Driven Generating Set of capacity 30 KVA Liquied coolant cooled, 415 Volts (AC three phase, 4 Wire system of supply) 50 Hz at power factor 0.8 minimum. The DG Set shall consists of diesel engine coupled to a matching alternator, through flexible coupling and mounted on common base frame and complete with control panel standardized by manufacturer, fuel tank with mounting arrangements and inlet, outlet return inlet oil arrangement, exhaust pipe complete and suitable for conditions prevalent at Bengdubi mil stn including PCC foundation (of suitable size leaving at least 0.5 m all around for ease of movement and 0.5 M height), anti-vibration pads complete all as specified and directed, including all features to comply with latest CPCB guidelines and comprising of followings:- (i) ENGINE (Prime Mover): Diesel Engine 1500 RPM, direct injection, multi cylinders, four stroke, confirming to IS:10000/ISO3046/BS:649/BS:5514 amended up to date, for continuous running capable of taking 10% overload for one hour in 12 hour, water cooled, naturally turbo charged, capable of giving adequate BHP to drive Alternator capable of delivering 30 KVA or next higher capacity at outdoor atmospheric conditions at Bengdubi, fitted with following accessories:- (a) Dynamically balanced fly wheel with starter ring (b) Air cleaned oil bath type. (c) Electronic governer (d) Dry exhaust manifold with suitable exhaust residential grade silencer to reduce the noice level. (e) Radiator Assembly. Item Continued as 10.22
(f) Radiator fan with guard. (g)Vaccum indicator. (h) Fuel filter and fuel hoses. (j) Fuel injection pump (FIP) (k) Lubricating oil filter and pump. (l) Electrical starting system with battery charging alternator and axial type starter motor including adquate number of high capacity maintenance free lead acid battery, 12 Volts DC as per manufacturer recommendation including interconnecting cable/ leads with terminal complete with start/ stop switch. (m) Engine safety shut down system against low oil pressure and high water pressure. (n) Exhaust gas driven turbo charger. (o) Oil filter. (p) Lube oil cooler. (q) Engine maintenance manual with spare parts list. (r) Suitably designed acoustic enclosure as per CPCB regulation. (s) Any other item not included/ specified but is a standard design of the manufacturer. (ii) ENGINE INSTRUMENT ELECTRONIC PANEL:- Engine instrument panel shall compriding of the following control : (a) Starting on/ off switch. (b) Water tempreture display. (c) Hour meter cum RPM display. (d) Lub oil pressure display. (e) Lub oil tempreture display. Item Continued as 10.23
(f) Battery charging display. (g) Safety alarm against high water tempreture and low oil pressure. (h) Automatic on/off of engine facility with GCU. (j) Any other item not included/ specified but is a standard design of the manufacturer. (iii) ALTERNATOR:- Alternator shall be self excited, self regulated, brushless for 30 KVA continuous operation at the speed of 1500 RPM at 415 Volts, 50 Hz, Three Phase, 4 Wire system with advance electronic voltage regulator to ensure high voltage accuracy with + / -1% with class H insulation and SPDP enclosure directly coupled with engine through flexible coupling and confirming to IS-4722 complete-01 No Note:- Alternator should be able to deliver output rating at actual site conditions. (iv) Common fabricated base frame for engine and alternator made from structural channel, leak proof PCC 1:2:4 mix, type B1 foundation including adequate number of suitable anti vibration pad all as per the recommendation of the manufacturer-01 Number (v) Bottom mounted (or as per manufacturer design) steel fuel tank fabricated out of 14 SWG MS sheet of capacity not less than 8 Hour continous operation inside canopy with fuel level gauge, drain plug, locking arrangement etc with and including GI pipe connection duly laid as per Engineering practice complete. (vi) AMF CONTROL PANEL: Supply, fabricating and testing of factory made,3.15 mm thickness outdoor type, floor mounted cubical automatic main failure panel with degree of protection IP-42 confirming to IS 2147, suitable for 30 KVA capacity DG set, fabricated using 14 Gauge CRCA sheet, powder coated comprsing of suitable rated bus bar, internal wiring with control MCB, provn of connecting incomming and outgoing leads/ bus bar as approved with and including following accessories:- Item Continued as 10.24
Supply, fixing and jointing flat submersible cable of size 10 sqmm 3 core 80/0.4 PVC insulated and sheathed stranded copper conductor cable including testing and taking out old and unserviceable cable complete all as specified and directed.
EXTERNAL ELECTRIC SUPPLY S&F Junction Box made of thermoplastic of size 155 x 210 x 92 mm with knockouts for cable entry including connecting terminals, IP-66 protection complete all as specified and directed. MAKE : Hensal Cat No. KF 1610 B or equivalent as approved by GE.
M&L for drawing PVC insulated, PVC sheathed round multicore flexible cable with copper conductor three core (Red, Black, Breed) 1.5 Sqmm complete all as specified and directed.
M&L for Advance Maintenance Free Zinc & Alloy coated G.I. safe earthing electrode with pipe in pipe technology of not less than 76.30 mm outer dia (thickness not less than - 2.5 mm) and 42.40 mm inner dia (thickness not less than 3.2 mm) and two meter length, the electrode should be of galvinised with Zinc (80 -100 micron) and Alloy ( 250 - 300 micron) coated. The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM) . The GI electrode shall be surrounded with 50 kg BackFill compound to provide maximum contact between the electrode and Back Fill Compound. Backfill compound should be eco-frendly and having RoHs certification. GI Electrode Shall be tested from CPRI. The earting pit should be cover with pcc(1:2:4) B1 cover of 450 x 450 mm complete all as specified and directed and as per sketch "A" Zinc and Alloy coated safe earthing electrode should be Make : ASHLOK, Model : ASEEL-39-ZC&AC or equivalent (Earth Resistance should be less than 1 Ohm ) NOTE : (i) For each earth electrode excavation to be done of size not less than 3m x 0.75m and excavated soil to be replace with good quality / highly conductive soil, rate deemed to be include in the quoted rate. (ii) All earth connection to be done using special nut bolt.
Sub total
SCHEDULE OF CREDIT (SCH 'A' PART-XI)
DEDUCT Credit Amount B/F from Serial Page No. 69 against Sch ‘A’ Part-XI.
Shree Mahabir Builders
FRIENDS CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .