Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.1 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹22.7 L+₹41,260 (1.85%)Rejected-Finance 329 COD COLONY KOYLA NAGAR PO KIDWAI NAGAR KANPUR 208011 | KANPUR | KANPUR | UTTAR PRADESH | 208011 | L2 | Rejected-Finance HIGHER THAN L1 BIDDER | |
| 3 | L3₹25.6 L+₹3.3 L (14.6%)Rejected-Finance | L3 | Rejected-Finance HIGHER THAN L1 BIDDER | |
| 4 | L4₹27.2 L+₹4.9 L (21.8%)Rejected-Finance | L4 | Rejected-Finance HIGHER THAN L1 BIDDER | |
| 5 | L5₹27.4 L+₹5.1 L (22.7%)Rejected-Finance | L5 | Rejected-Finance HIGHER THAN L1 BIDDER |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
12 Sept 2024, 6:00 pmClosed
LT COL VISHAL BHURIA
GE I Kanpur Cariappa Road Cantt Kanpur 208004
REPAIR/MAINT OF LT CABLE DISTRIBUTION NETWORK DISTRIBUTION TRANSFORMER AND ALLIED WORKS IN OFFR QTRS, COD ESTATE, VRG LINE, ME LINE AND INSIDE COD AREA UNDER GE (I) KANPUR
2024_MES_665275_1
GE(I)/KAN/T-46 OF 2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KANPUR
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (I) KANPUR
₹78,000
Yes
7 Dec 2024
11 Jul 2024
19 Sept 2024
11 Jul 2024
12 Sept 2024
25 Jul 2024
Amount
Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables,foundation filling of poles or stays and for rerouting of cables complete all as specified and directed.
Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each complete all as specified and directed.
Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm, thick after laying, stretching and testing the cable complete all as specified and directed.
M&L for Sub class ‘B’ bricks old size. laid dry flat over the cable abutting each other, length of cable equal to width of brick complete all as specified and directed.
M&L for pre cast cement concrete (1:4:8) type D2 using 40mm graded stone aggregate for foundation filling of poles as mass concrete complete all as specified and directed.
M&L for pre cast cement concrete (1:3:6) type C2 using 40mm graded stone aggregate for foundation filling of stays complete all as specified and directed.
Supply and laying to wall or poles or fixing or passing through pipe, in replacement of 1100 volts grade heavy duty cable with XLPE insulated aluminium multistranded conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and overall PVC sheathed 16 sq. mm nominal cross section 2 core in service connections complete including taking out old unsv cable of any type, make & size all as required and directed. (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification)
All as per srl item No 8 above but cable of size 10 Sqmm 2 core complete all as specified and directed.
All as per srl item No 8 above but cable of size 25 Sqmm 2 core complete all as specified and directed.
Supply and laying in trenches or fixing to wall/pole or passing through pipe in replacement of XLPE insulated heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 25 Sqmm 3.5 core complete including taking out old unsv cable of any type, make & size complete all as specified and directed. (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification)
All as per srl item No 11 above but cable of size 35 Sqmm 3.5 core complete all as specified and directed.
All as per srl item No 11 above but cable of size 70 Sqmm 3.5 core complete all as specified and directed.
All as per srl item No 11 above but cable of size 95 Sqmm 3.5 core complete all as specified and directed.
All as per srl item No 11 above but cable of size 120 Sqmm 3.5 core complete all as specified and directed.
All as per srl item No 11 above but cable of size 150 Sqmm 3.5 core complete all as specified and directed.
All as per srl item No 11 above but cable of size 185 Sqmm 3.5 core complete all as specified and directed.
All as per srl item No 11 above but cable of size 240 Sqmm 3.5 core complete all as specified and directed.
S&F in replacement of Cable jointing kit for 1100 volt grade cable for outdoor/indoor termination end joint heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 16 to 35 Sqmm 3.5/4 core complete all as specified and directed.
All as per item No 19 above but for 50 to 95 Sqmm size complete all as specified and directed.
All as per item No 19 above but for 120 to 185 Sqmm size complete all as specified and directed.
All as per item No 19 above but for 225 to 300 Sqmm size complete all as specified and directed.
S&F in replacement of cable jointing kit for 1100 volt grade cable for straight through termination heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 10 to 16 Sqmm 4 core complete all as specified and directed.
All as per item No 23 above but for 25 to 50 Sqmm size complete all as specified and directed.
All as per item No 23 above but for 70 to 150 Sqmm size complete all as specified and directed.
All as per item No 23 above but for 185 to 240 Sqmm size complete all as specified and directed.
Disconnecting electrically and taking out old unserviceable HT UG cables any type of size 70 to 300 Sqmm 3 core complete all as specified and directed.
Supply, laying in trenches or passing through pipe/ducts, fixed to wall or poles XLPE insulated screened PVC sheathed galvanized steel strip or wire armoured electric power cable with alumn conductor of cross sectional area 95 Sqmm 3 core 11 kV rated suitable for earthed system including testing and commissioning all as specified and directed Note : (Excavation and earth work, sand cushioning brick covers and GI pipe etc shall be measured and paid separately.
All as per item No-28 above but HT 11 kV cable of size 120 Sqmm complete all as specified and directed.
Supply and fix in replacement of cable straight through jointing kit for 11 kV grade cable termination cold shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 to 120 Sqmm complete all as specified and directed.
Supply and fix in replacement cable end jointing kit for 11 kV grade cable for indoor termination cold shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 to 120 Sqmm complete all as specified and directed.
Supply and fix in replacement cable end jointing kit for 11 kV grade cable for outdoor termination cold shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 to 120 Sqmm complete all as specified and directed.
M & L for PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in floor / hard-standing, surface finished even and smooth without using extra cement to match with the existing surface complete all as specified and directed.
Boring of holes under road ,pavement hard standing by trenchless technology using ultra sound technique and necessary machine incl HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
Dismantling PCC/steel poles any type and any size including excavation for taking out pole, breaking of PCC block with due care and setting aside for reuse or depositing to MES stores yard complete all as specified and directed.
S & F in replacement of Power / Control Copper Cables, with solid copper conductor, XLPE insulated, 2.5 sqmm, 6 core cut to pieces including making all necessary connections as per site requirement and removing the old unsv control cables from ducts etc complete all as specified and directed.
Supply, errecting and installation of steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metres long) duly painted with two coat of black bituminous paint through out, internally and externally up to planning depth and painting remaining portion of pole with two coat of aluminium paint to the entire exposed surfaces over one coat of red oxide primer making/painting three Nos circular strips each of 30 cm wide with one yellow and 02 Nos black colour strip synthetic enamel paint and marking pole number with black paint all as spfd and directed. (Note : Excavation, earth work, PCC work shall be measured and paid separately under respective items)
Disconnecting electrically, dismantling from foundation with due care and setting aside LT/HT fedder pillar box any type any size with all accessories complete all as specified and directed.
S&F in replecement HT 11 kV bus bar outdoor type weather and vermin proof feeder pillar box factory fabricated CPRI approved duly painted with two coat of enamelled paint, pedestal type made out of mild steel sheet 3.15mm thick, factory made, using angle iron 40mm x 40mm x 6mm and 500mm high, front opening double shutter weather proof , rust proof, dust proof with provision of rubber gasket and locking arrangement including HT bush, insulator & bus bar color code - 03 Nos and making connection with suitable size of thimbles, nuts, bolts and washers etc incl necessary earth work complete all as specified and directed.
M&L for replacement of GI tubing light grade 80mm bore with fittings laid for protection of cable under road crossing fixed to walls or pole complete all as specified and as directed.(clamps for fixing pipe, nuts, bolts washers shall be measured separately )
All as per srl item No 40 above but 50mm bore complete all as specified and directed.
All as per srl item No 40 above but 40mm bore complete all as specified and directed.
S & F in replacement of in position retro reflective sign board size not less than 2.5 ft to 2 ft, cut to sizes/shape made out of 3 mm thick high density aluminium sheet fixed on wall with aluminium frame work with all weather effected duly riveted with vinyal sheet based of blue colour base by hot process including letter/number as directed fitted on wall with proper arrangement complete all as specified and directed. Note : The matter which is to be written shall be decided by Enge-in-charge
Repair of broken doors for LT panel and bus bars by welding and incl supply and fixing of new hinges and other material as required at site complete all as spfd and directed.
Removal of unwanted vegetation/bushes/small plants shrubs around the water/electric supply installations/ inside the valve pit and surface excavation not exceeding 15 cm depth leveling the ground and removing the excavated material to a distance exceeding 50 M complete all as specified and directed.
Supply and installation, connecting eclectically & commissioning in replacement of LT feeder pillar box outdoor type of suitable size,factory fabricated made out of MS sheet of thickness 3.15 mm front door openable with locking arrangement mounted on angle iron legs made out of angle iron of size 40x40x6mm, 1.5 mtr long, 1.0 mtr above ground level and 0.50 mtr embedded in PCC blocks of suitable size,duly painted with two coats of synthetic enamel paint over a coat of red oxide complete with 300 amps rated copper bus bar suitable for 3 phase 4 wire supply system duly drilled holes and making all cable connection with proper thimbles mounted on epoxy based post insulators and one MCCB 200 Amps 4 pole 415 Volt, 35/36 kA complete all as specified and required at site.
M & L for replacement of existing unserviceable LT panel, Installation, commissioning and testing of new LT panel cubical type suitable for outdoor installation factory made CPRI approved of suitable size,dust & vermin proof fabricated out of 3.15 mm thick CRCA sheet duly powder coated with cable entry & exit with suitable size of glands, terminals & thimbles all as specified , duly mounted on angle iron frame of sjuitable size fixed on RCC/PCC block fixed with grounded bolts & nuts and washers including rating copper bus bar not less than 40X10 mm suitable for 600 Amps for 3 phase 4 wire mounted on epoxy based post insulators with suitable size of CTs, LED indicator lamp set type RYB (indicator lamps should display colour of phase as well as phase volatge complete) of make AE/Legrand/L&T, complete internal wiring with suitable size of copper conductor PVC insulated and sheathed cable front and rear openable double door with locking arrangement, angle iron frame made out from suitable size and making good all disturbed surfaces of floor/wall using RCC/PCC work as required at site complete all as required at site or directed. Make : Make : Havells/L&T/C&S/Schnieder/Legrand (switchgears are of same manufacturing Note: All MCCBs should have adjustble thermal and fixed magnetic setting and Ics will not less than 75%Icu INCOMMER (i) MCCB 3 Phase, 4 Pole 400 Amps,35/36kA rupturing cap,415 volts 50 Hz AC supply - 01 Nos (ii) Digital voltmeter 0 to 500 volt - 01 Set (iii) Digital ameter 0 to 250 amp - 01 Set (iv) Phase indicating lamp RYB with indicating voltage in digital LED format ( set of three) - 01 Set OUTGOING (i) MCCB 3 Phase, 4 Pole,160 Amps,25 kA,415 volts 50 HZ AC supply - 02 Nos (ii) MCCB 3 Phase, 4 Pole,100 Amps,25 kA,415 volts 50 HZ AC supply - 01 Nos (iii) MCCB 3 Phase, 4 Pole,63 Amps,25 kA,415 volts 50 HZ AC supply - 02 Nos
S&F in replacement of MCCB 4 Pole 415 Volts 3 phase 400 Amps 35/36 kA, thermal magnetic release, Ics will not less than 75%Icu -01 No (incoming).
All as per item No 48 above but MCCB 250 Amps 35/36 kA complete all as specified and directed.
All as per item No 48 above but MCCB 100 Amps 16 kA complete all as specified and directed.
All as per item No 48 above but MCCB 160 Amps 25 kA complete all as specified and directed.
All as per item No 48 above but 63 Amps 16 kA complete all as specified and directed.
Detection of any type of fault in HT/LT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator with carring vehicle will be brought by the cable fault detection agencies. Span of faulty cable will be trace out by the agencies by meggering HT cable. Note : 1. Detection of fault in one span of length will be measured as one Job either machine placed from one side or both side of the cable. 2. Technicians will be employed by the working agencies. 3. Earth work and taking out will be included in quoted rates. 4. Material for repair and replacement measured and paid saperately. 5. One job shall be measured if the fault has successfully identified by the fault locator machine or removing moisture in the cable if required.
M&L in replacement of earthing complete with galvanised iron earth plate electrode of size 600x600x6 mm thick as earth electrode with top edge of the earth plate not less than 1.5mtr below ground level using GI wire 4mm dia as earth continuity conductor connected to earth plate by means of GI thimbles nuts bolts washers all as directed including providing earth wire protection pipe GI light grade15mm dia from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and RCC pit cover in PCC 1:3:6 adequate quantity of charcoal dust and salt all around the erth plate, earth work in any type of soil remaing surplus excavated material all as required at site and specified in EP No 5 of SSR part I 1991 or directed incl testing on competion.
All as per srl item No 54 above but connected to galvanised iron strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electric plate No 3 connected to earth test point complete all as specified and directed.
M & L for fixing earthing strip 32 x 6 mm GI strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, In Repair, complete all as specified & directed.
Supply and fix in replacement Gate light fitting LED type 25 W with CCT not less than 5700 K ,and IP 65 Protection ,230V recessed mounting mirror opticluminare complete with all accessories pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size, complete including wire and making connection complete with pole all as specified and directed by GE(I).
DEO Traders (BID ID -3085008)
M/S DARSHAN ENGINEERING WORKS (BID ID -3085085)
Kumar Electricals (BID ID -3076253)
NEW TECH ELCTRICALS (BID ID -3088022)
Bharat Sales Corporation (BID ID -3085527)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .