Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.9 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹14.4 L+₹51,787 (3.72%)Rejected-Finance 5 B MOTIMANDIR 736 KASBA PETH PUNE 411011 | PUNE | PUNE | MAHARASHTRA | 411011 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹14.9 L+₹96,033 (6.90%)Rejected-Finance | L3 | Rejected-Finance Not Lowest |
Tender Value
₹14.4 L
EMD Value
₹28,900
Closing Date
11 Jun 2020, 6:00 pmClosed
CWE Pune
HEADQUARTERS COMMANDER WORKS ENGINEERS GEN CARIAPPA MARG, PUNE-411 001
81687SPECIAL REPAIR / REPLACEMENT OF 750 KGS COLD ROOM AGAINST BER AT CADET MESS NDA KHADAKWASLA.
2020_MES_340968_2
81687SPLREPOFCDRMATNDAKWASLA
Open Tender
Electrical and Maintenance Works
Item Rate
123 days
GE NDA Khadakwasla
As per Tender
9 documents required · 9 mandatory
₹500
GE NDA Khadakwasla
₹28,900
Yes
17 Jul 2020
29 May 2020
13 Jun 2020
29 May 2020
11 Jun 2020
30 May 2020
Amount
Design basis of frezer room for frozen chicken Supply installation, testing and commissioning of PUF Panel and refrigeration system for freezer room size 5.2 m x 2.8 m x 2.45 m, suitable for daily loading capacity 750 Kg to 1500 Kgs, room temperature maintinted upto (-) 20 Degree centrigrade, refrigeration load 4KW x 2 (01 X working and 01 x stand by) unit three phase compressore
(a) (i) Evaporatiors of ceiling suspended type-02 Set of single phase 3/5 blower fan assembly, (ii) aircoled condensing unit for cold room (iii) Refigeratoion capacity - 4 KW, 3 phase-2 Nos (iv) type of refigeration -R 404a, 410,134a (v) evaporation temp maintained upto (-25degree Centigrade) (vi) Display digital temperature meter incuding suitable difforst temp setting device-02 Nos (b) Insulation material -freezer room PUF Panel/slab insulation PUF Panel cladded with 0.45mm thick SS Sheet both side, 40kg/cum PUF density (i) Wall 120mm thick panel -40 sqm (ii) Ceiling 120mm thick panel-16sqm (iii) Floor slab 100 mm thick PUF with all accessories and 20 mm to 25 mm thick kota stone flooring with 20 mm thick screed bed in CM (1:4) over 100 mm thick PCC (1:3:6) type C2 - 16 sqm (c) PUF panel accessories : flashing silicon, liquid PUF, rivets etc - 56 sqm (d) Swing type insulated door-900(W)x2000(H)x120 mm thick, PUF insulated panel cladded with both side SS sheet, complete with frame, kick plate and all accessories like locks and hinges -01 Job
Refrigeration system accessories consisting of refrigeration control valves,Copper pipe (suitable length from indoor to outdoor unit) insulated with 13 mm thick closed cell nitrile rubber insulation complete with fittings elbow, bend, supporting arrangement on wall , condensate drain UPVC medium grade Pipe, refrigeration gas R 404a, 410,134a , oil etc -02 Nos
(a) Supply installation, termination , testing and commissioning control wiring required for outdoor unit and indoor unit upto requried length - 01 Job (b) Supply, installation, testing and commissioning of Additional top up- referigerant- 01 Job (c) UPVC medium grade (as per site condition) drain piping for the units 25 mm dia - 25 m
MS stand for outdoor units zinc cromium primer duly epoxy coated - 02 Nos
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) connected to galvanized iron strip 25 mm x 4 mm, 7.5 m long by means of bolts, nuts and washers of galvanized iron or steel, GI light grade protection pipe 15 mm dia, GI medium grade water pipe 20 mm dia with funnel all as shown in electric plate No 3 of SSR-2009 pt-I and testing complete including earth work excavation in any type of earth strata PCC 1:2:4 as in earthing pit, 50 mm PCC pit cover with 6mm iron handle attached , common salt charcoal all as specified including testing on complete. Note GI strip beyond 7.5 m shall be measured and paid for seprately.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required with 25 mm x 4 mm GI strip.
Supply install commissioning and testing of commerial air curtain unit for prevention of dust and conditioned air losses, single phase, 220V, 50HZ, made out of MS/CRCA sheet of minimum thickness 18 gauge finished with two coats of red oxide primer and final coat of synthetic enameld paint (over backed) with MS CRV 18 gauge suare perorated suction grills, aluminium alloy fans, and single phase electric motor, nozzles etc, complete with fittings and acessories so as produce 1-15 m/sec air velocity at floor level for door opening size 40"x78" complete all as specified and as directed.
S & F sheet metal MCB DB 4 Way (double door) TPN with 200 Amps rateded copper bus bar horizontal type complete all as specified and as directed.
S&F MCB TP 32A, 50 Hz 'C' series 10 KA complete all as specified and as directed.
S&F MCB SP 20A, 50 Hz 'C' series 10 KA complete all as specified and as directed.
S&F MCCB 415 V 16 KA, FP 100A, 50HZ complete all as specified and as directed.
M&L for sub main wiring 5x4 sqmm ( phase , neutral and earth) PVC insulated (heavy duty) 1100 volts grade, FRLS, with stranded copper conductor in & including PVC casing caping/conduit of suitable size not less than 25 mm ( 5 run of 4 sqmm cable and one run of PVC casing caping will be measured as one unit) complete all as specified and as directed.
M&L for sub main wiring 3 x 2.5 sqmm ( phase , neutral and earth) PVC insulated (heavy duty) 1100 volts grade, FRLS, with stranded copper conductor in & including PVC casing caping of suitable size not less than 25 mm ( 3 run of 2.5 sqmm cable and one run of PVC casing caping will be measured as one unit) complete all as specified and directed .
Dismantling and taking out all electric and walk in freezer airconditioning machine carefully complete with outdoor unit, indoor unit, copper pipes, cables etc and depositing AC unit to MES store complete all as specified and as directed.
Re-fixing of all existing cabling work main XLPE cable, power cable etc complete all as specified and directed.
Supply and fix surface/suspended water proof industrial luminiare with polycarbonate housing and diffuse included suitable for twin T8 LED tube (shall be operated from door opening and closing with push connect unit) complete all as specified and as directed.
M & L for brickwork with subclass 'B' Bricks straight or curved on plan exc 6m means radius buit in CM 1:6 complete all as specified and as directed.
M & L for Cement concrete 1:3:6 type C2 using 40 mm stone aggregate foundation /resting platform in foundation filling and mass concrete complete all as specified and as directed.
M & L for mild steel rolled section connected with each other with welding (angle, tee, channel, beam, hollow sections etc) as in main and cross beams, hip verticle hollow sections and jack rafters, purlins where connected to common rafters and running rils where verticle suctions and fixed in welded in wallsin wall surface with plates and other verticle sections are fixed in ground level embedded in concrete fixed and horizontal sections fixed in wall with bolt completly, fixed with angle, cleats or other connecting plates conforming to Gde Fe -410-W (Gde E-250) quality-B complete all as specified and directed by Engr-in-charge.
S&F pre-painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50 mm thick fixed in any position where directed of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws with one corrugation side lap, bent to shape complete all as specified and as directed.
M & L painting to steel surface over 10 cm width or girth with two coats of syntetic enamalled paint over and red oxide primer complete all as specified and as directed.
M/s Green Leaf Electricals
Sneha Aircool
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .