Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 513 514 MR3 MAHALAXMI NAGAR SUNCITY ROAD NEAR BOMBAY HOSPITAL INDORE MADHYA PRADESH 452010 | INDORE | MADHYA PRADESH | 452010 | Admitted-Finance |
| 2 | Admitted-Finance 119 1ST FLOOR SURAJDEVI SHUKLA COMPLEX GANJBANS TALL RAIPUR 492009 | RAIPUR | RAIPUR | CHHATTISGARH | 492009 | Admitted-Finance |
| 3 | Admitted-Finance BEHIND MPSEB HOSPITAL MPN 2 BIRSINGHPUR 484552 | BIRSINGHPUR | UMARIA | MADHYA PRADESH | 484552 | Admitted-Finance |
Tender Value
₹17.9 L
EMD Value
₹35,800
Closing Date
21 May 2024, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE PNW, SARNI
STPS, MPPGCL, SARNI
Procurement of Pressure Transmitters of various ranges and applications for IMD-4, STPS, Sarni.
2024_MPPGC_345112_1
PE-1532
Limited
Electronics Equipment
Item Wise
60 days
STPS, MPPGCL, SARNI
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹35,800
Yes
18 Oct 2025
15 Mar 2024
24 May 2024
15 Mar 2024
21 May 2024
15 Mar 2024
Pressure Transmitters of various ranges and applications
FLOW TRANSMITTER FOR SECONDFARY AIR FLOW MEASUREMENT SENSOR TYPE--> FT OPERATING RANGE--> 0 TO 360 t/hrMCRP --> 120 PR UNIT -->mmWCMCRT--> 319 DES TEMP --> 325 DP --> 0 to 90 mmWC Max Range of Model --> 100 mmWC Max Static Press --> 0.5 Kg/Cm2 NOTE:- RETROFIT TO EXISTING INSTALLED YOKOGAWA MODEL NO. --> EJA 120A-EES4A-92EA / HAC or REPLACEMENT MODEL --> EJA120E-JES4J-912EB MEDIUM-SEC AIR
PRESSURE TRANSMITTER FOR FLUE GAS PRESSURE MEASUREMENT AT PSH SENSOR TYPE --> PT OPERATINGRANGE--> -20 TO +20 mmWCMCRP --> -6 DES PR--> -7 PR UNIT -->mmWCMCRT-->1006 DES TEMP --> 1100 Max Range of Model - 100 mmWCMax Static Press - 0.5 Kg/Cm2 NOTE:- RETROFIT TO EXISTING INSTALLED YOKOGAWA MODEL NO. --> EJA 120A-EES4A-92EA / HAC or REPLACEMENT MODEL :- EJA120E-JES4J-912EB MEDIUM-FLUE GAS
PRESSURE TRANSMITTER FOR FLUE GAS PRESSURE MEASUREMENT AT RH O/L SENSOR TYPE --> PT OPERATINGRANGE--> -30 TO +25 mmWCMCRP --> -13 DES PR--> -15 PR UNIT -->mmWCMCRT-->773 DES TEMP --> 900 Max Range of Model - 100 mmWCMax Static Press - 0.5 Kg/Cm2 NOTE:-RETROFIT TO EXISTING INSTALLED YOKOGAWA MODEL NO. --> EJA 120A-EES4A-92EA / HAC or REPLACEMENT MODEL :-EJA120E-JES4J-912EB MEDIUM-FLUE GAS
PRESSURE TRANSMITTER FOR FLUE GAS PRESSURE MEASUREMENT AT FSH O/L SENSOR TYPE --> PT OPERATINGRANGE--> -60 TO +20 mmWCMCRP --> -23 DES PR--> -26 PR UNIT -->mmWCMCRT-->685 DES TEMP --> 800 Max Range of Model - 100 mmWCMax Static Press - 0.5 Kg/Cm2 NOTE:- RETROFIT TO EXISTING INSTALLED MODEL NO. --> EJA 120A-EES4A-92EA / HAC REPLACEMENT MODEL :-EJA120E-JES4J-912EB MEDIUM-FLUE GAS
PRESSURE TRANSMITTER FOR FLUE GAS PRESSURE MEASUREMENT AT LTSH O/L SENSOR TYPE --> PT OPERATINGRANGE--> -75 TO 0 mmWCMCRP --> -53 DES PR--> -58 PR UNIT -->mmWCMCRT-->464 DES TEMP --> 600 Max Range of Model - 100 mmWCMax Static Press - 0.5 Kg/Cm2 NOTE:- RETROFIT TO EXISTING INSTALLED YOKOGAWA MODEL NO. --> EJA 120A-EES4A-92EA / HAC REPLACEMENT MODEL :-EJA120E-JES4J-912EB MEDIUM-FLUE GAS
LEVEL TRANSMITTER FOR BOILER DRUM LEVEL MEASUREMENT SENSOR TYPE--> LT OPERATING RANGE--> -425 to 726 mm MCRP --> 169.7 DES PR--> 182.5 PR UNIT--kG/CM2(g) MCRT--> 351 DES TEMP --> 351 NWL --> 250mm BCL of Drum Max Range of Model --> 10000 mmWCMax Static Press --> 320 Kg/Cm2 NOTE:-RETROFIT TO EXISTING INSTALLED YOKOGAWA MODEL NO. -->EJA 120A-EES4A-92EA / HAC or REPLACEMENT MODEL :-EJA120E-JES4J-912EB MEDIUM-Water & Steam(Drum Level)
PRESSURE TRANSMITTER FOR LDO PRESSURE MEASUREMENT AHTER LOTV SENSOR TYPE --> PT OPERATING RANGE--> 0 TO 20 kg/cm2 MCRP --> 11 to 5 PR UNIT --> kg/cm2 Max Range of Model --> 30 kg/cm2 As per ANSI STD 300# NOTE:- RETROFIT TO EXISTING INSTALLED YOKOGAWA MODEL NO. --> EJA 438W - EASA2EA - AA10 - 92EA/Z/KU2 or REPLACEMENT MODEL:- EJA438E - JASCJ -912EB- WA23A1SW00-AA2A/KU2 MEDIUM-LDO
PRESSURE TRANSMITTER FOR PRESSURE MEASUREMENT AT BOILER SENSOR TYPE -->PT OPERATING RANGE-->0 TO 20 kg/cm2 MCRP -->11 PR UNIT -->kg/cm2 MCRT-->302 DES TEMP --> 320 Max Range of Model --> 30 kg/cm2 Max Static Press --> 30 Kg/Cm2 NOTE:- RETROFIT TO EXISTING INSTALLED YOKOGAWA MODEL NO. --> EJA 430A -EAS4A- 92EA or REPLACEMENT MODEL:- EJA 430E-JAS4J-912EB MEDIUM-ATOMISATION STEAM/STEAM/CONDENSATE/DMCW/CW
PRESSURE TRANSMITTER FOR HFO HEADER PRESSURE MEASUREMENT SENSOR TYPE--> PT OPERATING RANGE--> 0 TO 30 kg/cm2 MCRP --> 15 TO 4.5 PR UNIT --> kg/cm2 Max Range of Model --> 140 kg/cm2 As per ANSI STD 300# NOTE:- RETROFIT TO EXISTING INSTALLED YOKOGAWA MODEL NO. -->EJA 438W - EBSA2EA- AA08 - 92EA/Z/KU2 REPLACEMENT MODEL :- EJA 438E - JBSCJ-912EB-WA23A1SW00-AA28/KU2 MEDIUM-HFO
PRESSURE TRANSMITTER FOR LDO PRESSURE MEASUREMENT AT LDO PUMP O/L SENSOR TYPE--> PT OPERATING RANGE--> 0 TO 30 kg/cm2 MCRP --> 20 PR UNIT --> kg/cm2 Max Range of Model --> 140 kg/cm2 As per ANSI STD 300# NOTE:- RETROFIT TO EXISTING INSTALLED YOKOGAWA MODEL NO. -->EJA 438W - EBSA2EA- AA08 - 92EA/Z/KU2 OR REPLACEMENT MODEL :- EJA 438E - JBSCJ-912EB-WA23A1SW00-AA28/KU2 MEDIUM-LDO
DEL CONTROLS (BID ID -1034567)
INDIAN INDUSTRIAL EQUIPMENTS (BID ID -1030881)
stage.html
html • 0.04 MB
technical_406183.pdf
techsummary_406183.pdf
finance_406183.pdf
BOQ Comparative Chart
xlsx
cancelled_1.pdf
pdf • 0.24 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.41 MB
CHECKLIST.pdf
Tender Documents • 0.25 MB
SBD_Amendment.pdf
Tender Documents • 0.25 MB
SBD_SUPPLY.pdf
Tender Documents • 3.45 MB
NIT-Schedule1.pdf
Tender Documents • 0.12 MB
BOQ_406183.xls
BOQ • 0.30 MB
Technical_Bid.xls
Additional Documents • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .